Electronic Control Manual Auxiliary Devices Section Product Bulletin Issue Date 216 Q GQ-4000 0695 GQ-4000 Indication Systems The GQ-4000 Indication System provides accurate, centralized indication of selected remote variables. These variables may be temperature, relative humidity, position, and/or humidity or temperature setpoint value. All system components are individually selected to perform a variety of functions in accordance with exact job specification requirements. Each GQ-4000 system is composed of a regulated 24 VDC power supply, a DC measuring bridge unit, a variable resistance input source, and a signal readout device. A precision (±0.25% tolerance) nickel wire temperature sensing element, a CAB (cellulose acetate butyrate) humidity sensing element, or a feedback potentiometer provides the input to the DC measuring bridge unit. The bridge output, linearly proportional to the measured variable, is applied directly to the readout device without additional amplification. The GQ-4000 system design includes overload protection for indicating meters. Specifications The output of several DC bridge units, with the same range, may be switched into a single receiver utilizing appropriate switching devices. Components Power Supply Power for the DC measuring bridge unit(s) in the GQ-4000 system is provided by a VQ-6100-1 or VQ-6500-1 Regulated DC Power Supply. The VQ-6100 can supply 200 milliamperes, and the VQ-6500 can supply 70 miliamperes (both at 24 VDC). © 1995 Johnson Controls, Inc. Part No. 24-4146, Rev. B Code No. LIT-216134P The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. 1 Measuring Bridge The DC measuring bridge is the GQ-4100, a DC Wheatstone bridge circuit whose output results from a varying resistance in one or more of its legs. GQ-4100 units are available in several different ranges; refer to Table 1. All units have separate zero and span adjustments enabling individual calibration of each point in the system. Variable Resistance Input Sources For temperature indication, any TE-6000 precision (±0.25% tolerance) nickel wire element may be used as an input to a bridge. For position indication applications, use a PQ-1001 Damper Position Indicator. An AQ-4102 Remote Reset Control provides the input for remote temperature and humidity reset indication. It has a position indication potentiometer ganged to its remote reset potentiometer for accurate indication of the amount of reset. The position indication potentiometers in the PQ-1001 and AQ-4102 are 5000 ohms. Signal Readout Devices MZ-7000 series meters are used as indicators for the GQ-4000 system. These basic readout devices have a fixed internal resistance of 2000 ohms to accept a linear 0 to 100 microampere signal from any GQ-4100 bridge. Meter scale ranges are listed in Table 1; the meter scale must match the range of its associated bridge unit. To record measured variables, the output of a bridge (0 to 100 microamperes across 2000 ohms) is applied to a precision recorder. When a GQ-4100 bridge is used with a high impedance receiver, a 2000-ohm resistor must be placed across the receiver input or bridge output. 2 GQ-4000 Product Bulletin Mounting Assemblies Table 2 lists the various GQ-4000 mounting assemblies available for GQ-4100 bridges. Bridges are ordered separately (see Table 1) as are resistance input sources and readout devices. Enclosures are surface mounted, heavy-gauge steel cabinets with knockouts to facilitate wiring. Assemblies can be combined if necessary. See Bulletin GQ-4000-A for mounting, wiring, and calibrating instructions. Application and Drawing Identification HQTQ- Black Red ZQ- 5 6 1 2 8 3 4 Black Red TQ- 5 6 2 7 3 4 8 g q4 0 0 gq4000_ i GQ-4100-2 thru 7 GQ-4100-1 HQ- Black Red 5 6 1 2 8 4 gq4 00 0 _k GQ-4100-11 Two 5/16 inch (8m m ) D IA.M TG Holes C om bination Knockout for 1/2 and 3/4 inch (13 and 1 9 mm ) C onduit Near Side, and 3/4 and 1 inch (19 and 25 m m ) C onduit Far Side 4-3/8 112 2-3/16 56 9-1/4 236 1-9/16 40 2-1/4 57 1-1/2 38 3-1/16 78 13-3/4 350 6-7/8 175 1-9/16 40 1-1/2 38 D im ensions in mm C om bination Knockout for 3/4 and 1 inch (19 and 25 m m ) C onduit Near Side, and 1/2 and 3/4 inch (13 and 19 mm ) C onduit Far Side gq 40 00 _c GQ-4000-1 GQ-4000 Product Bulletin 3 1-5/8 41 13/32 10 1/4 6 3.5 89 2-1/4 57 (Distance Between Studs) 25 /32 20 3 76 3-1/32 77 1/4 6 (4 ) Places 19 483 D imensio ns in mm gq 40 00 _d GQ-4000-2 3 76 F ou r 5/1 6 in ch (8m m ) M T G H o le s 1 -1 /2 38 2 -1 /2 64 5 127 10 255 2-1/2 64 C om b in a tio n K n o ck ou t for 3 /4 a n d 1 in ch (19 a n d 2 5 m m ) C o nd uit N e a r S id e O n ly 2-1/2 64 C o m bin atio n K n o cko ut for 1 a n d 1 -1 /4 in ch (25 a n d 3 2 m m ) C o nd uit B o th S ide s 2-1/2 64 C om b in a tio n K n o ck ou t fo r 1/2 a n d 3 /4 inc h (13 a n d 1 9 m m ) C on du it F a r S id e O nly 2 -1 /2 64 4 102 12 305 4 102 20 50 9 5 -1 /2 1 40 9 229 5 -1/2 14 0 1-9/16 40 1-7/16 36 C o m b in a tio n K n oc ko u t fo r 3/4 a n d 1 in ch (1 9 a nd 2 5 m m ) C on d u it O n e E a ch S id e D im e n sio ns in mm C o m bin a tio n K n o cko ut fo r 1 /2 a nd 3 /4 in ch (1 3 a nd 1 9 m m ) C o n d u it O n e E a ch S id e GQ-4000-4 4 GQ-4000 Product Bulletin gq 40 0 0 _ e 1-1/2 38 1-1/2 38 1-3/4 49 3-3/8 86 Knockouts (2) For 1/2" Conduit (Top Only) Knockouts For 3/4" Conduit (Top Only) 2-5/8 67 7/32 5.5 1-5/16 33 Dia. MTG. Holes (8) 1-5/16 33 5-1/8 130 1-5/16 33 4-5/8 117 15/16 24 1-1/16 27 1-5/16 33 2-5/16 59 1-11/16 43 1-11/16 43 2-1/16 52 2-1/16 52 4-5/8 117 Dim ensions in mm gq4000_a GQ-4000-5 GQ-4000 Product Bulletin 5 Notes 6 GQ-4000 Product Bulletin Notes GQ-4000 Product Bulletin 7 Notes Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53202 8 GQ-4000 Product Bulletin Printed in U.S.A.