Low Voltage Compact NSX High performance Moulded-case circuit breakers from 100 to 630 A - up to 690 V Catalogue 2012 2 Intelligent outlook Compact NSX Next-generation circuit breakers The Compact™ range of circuit breakers set tomorrow’s standards today and help exacting organisations achieve more from their LV infrastructure. An extended breaking capacity, the highest in its class, is available across the entire Compact NSX range. A power monitoring unit also enhances their outstanding protective functions. For the first time, users can monitor both energy and power, offering new performance in a remarkably compact device. III IV Combine safety and performance The Compact NSX range is innovative - it incorporates monitoring and communication functions, from 40 A upward, combined with impeccable protection. Expert technology 23 A roto-active contact breaking principle provides better limitation and endurance performance: new patents pending confirm the innovative character of Compact NSX >> Very high breaking capacity in a very small device. >> Exceptional fault current limitation for extended system life. Reduced installation costs Achieve up to 30 % savings: >> Total discrimination is ensured particulary in the case of miniature circuit breakers for considerable savings at the time of installation. >> Smaller devices mean more economical switchboards for a significant impact on overall cost of installation - no need for over-calibration. New breaking capacities New performance levels improve application targeting: >> 25 kA - Standard low short-circuit level applications, e.g., in service businesses. >> 36-50 kA - Standard applications (industrial plants, buildings, Breaking performance at 690 V and hospitals). >> 70-100 kA - High performance at controlled cost. NSX 100 NSX 250 NSX 400 NSX 630 HB2100 kA >> 150 kA - Marine ready, with an Ics rating meeting IACS requirements for emergency, essential, and MCC loads. HB1 75 kA >> 200 kA at up to 440 V - Industry-leading breaking capacity for high-density applications in oil and gas extraction and processing, mining operations, metals and minerals production, and data centres. Breaking performance at 415 V NSX 100 R 200 kA L 150 kA S 100 kA Enhanced protection for motors H 70 kA The Compact NSX range meets the requirements of IEC 60947-4-1 standards for protection of motors: N 50 kA F 36 kA B 25 kA >> 100 kA from 500 to 690 V - The world’s highest rated breaking capacity for the most demanding electrical environments, and ideal for high-efficiency, cost-effective 690 V systems. >> Well adapted to motor-starting solutions up to 315 kW at 400 V, providing protection against short circuits, overloads, phase unbalance, and phase loss. NSX 160 NSX 250 NSX 400 NSX 630 >> Set up additional protection systems for starting and braking with the motor running, reverse braking, jogging, or reversing in complete safety. >> Used in conjunction with a Schneider Electric contactor, the Compact NSX provides Type II coordination for motor applications. V VI Measure the difference Compact NSX circuit breakers provide outstanding protection as well as an integrated measurement unit to help you monitor power conditions and manage energy consumption. Integrated monitoring A Micrologic electronic tripping device with next-generation sensors: >> An ‘iron’ sensor for the power supply to the electronics >> An ‘air’ sensor (Rogowski coils) for the measurement part The originality lies in how Compact NSX measures, processes, and displays data, either directly on screen, on the switchboard front panel, or via a monitoring system. -10% Monitoring consumption can help reduce energy costs by as much as 10% Accessibility of information To keep costs under control and ensure service continuity, relevant information must be available in real time: >> A kilowatt-hour meter helps optimise costs and their allocation. >> Harmonic distortion rate shows the quality of electrical supply. >> Alarm notification secures operational control and maintenance planning. >> Event logs and tables, activated continuously, ensure the installed equipment base operates correctly, so energy efficiency is maximized. Installation supervision Used in conjunction with software, Compact NSX provides users with a set of parameters and tools to make it easy to monitor installations. ASIC Electronics (ASIC), independent of measurement, manage protection functions. The high degree of integration in electronics guarantees protection against conducted or radiated interference VII VIII Opt for service continuity The Compact NSX range provides exceptional discrimination that minimizes the impact of short circuits and ensures maximum service continuity. Direct access to maintenance indicators Discrimination Schneider Electric leverages over 30 years of experience and expertise in discrimination to ensure customers of maximum service continuity: >> The downstream circuit breaker trips as close as possible to the fault, so that the upstream circuit breaker is not overloaded. 100% service continuity Total service continuity The Compact NSX range offers innovative capabilities to ensure maximum continuity and uptime for your facilities: >> R, HB1, and HB2 high breaking capacity levels enable the circuit breakers to withstand demanding fault conditions, staying reliably in service after 3 faults. After a fault is cleared, remote control reclosing functionality puts circuits back into operation quickly. >> SDTAM module allows remote indication of motor overloads and actuation of a contact switch. The SDTAM switches the contact instead of tripping the circuit breaker. The module allows for machine restart directly from the contact switch without having to operate circuit breakers. Preventive maintenance Maintenance indicators provide information on the number of operations, level of wear on contacts, and total load rates. Maintenance is now preventive, avoiding faults. IX Added simplicity The Compact NSX range incorporates the same principles of easy installation and use that made its predecessor so successful, and takes these to a higher level. 65% time savings in installation compared with a classic monitoring solution The green ‘Ready’ LED flashes to show that all is well Simple in design >> Installers mount and wire Compact NSX in the same way as Compact NS, which makes engineering for a retrofit or extension simple. >> Design is simplified using support software that helps you with parameter settings and planning switchboard installation. LTS installation system Simple to install >> A Limited Torque Screw (LTS) system ensures proper installation of the tripping device for added flexibility. >> A transparent sealed flap protects access to tripping device switches and prevents settings from being changed. >> New electrical control adjustment also has a transparent sealable cover to prevent it from being operated accidentally. >> Pre-wired connectivity and plug-and-play interface modules allow for easy integration with communication networking. Simple to use >> Users customize alarms for all parameters, assign them to indicator lights, choose display priorities, and configure time delay thresholds and modes. >> A wealth of information, including continuously-activated event logs and tables, helps you ensure that the installed equipment base is operating correctly and that settings are optimized. X Transparent protective cover Choose the expertise of Schneider Electric Whether in buildings, factories or mission-critical infrastructures, Schneider Electric commits to helping you reduce energy costs and CO2 emissions. We offer products, solutions, and services that integrate with all levels of the energy value chain. Solutions adapted to all needs Through flexible solutions for commercial and industrial buildings, Schneider Electric commits to help customers gradually move towards an active approach to their energy efficiency. We help you get more return from investments and future design solutions. up to 30% savings in energy costs Energy performance contracts Schneider Electric offers innovative service to modernise technical installations. Our objective is: to dramatically reduce energy costs, whilst improving comfort and safety, all in an environmentally friendly way. 4 steps > Diagnosis > Proposals > Implementation > Follow-up Energy Audit & Measure building, industrial process Fix the basics Low consumption devices, Insulation material, Power factor correction... Optimize through Automation and regulation HVAC control, lighting control, variable speed drives... Passive Energy Efficiency Monitor, maintain, improve Meters installation, Monitoring services, EE analysis software Control Improve Active Energy Efficiency Environmentally responsible Compact NSX circuit breakers are part and parcel of the Schneider Electric energy efficiency approach. Designed for easy disassembly and recycling at end of life, Compact NSX complies with environmental directives RoHS* and WEEE**, and with ISO 14001 standards, thanks to non-polluting factories. * RoHS = Restriction of Hazardous Substances ** WEEE = Waste Electrical and Electronic Equipment XI XII Compact NSX100 to 630 A up to 690 V Contents Introduction2 Overview of applications Characteristics and performance of Compact NSX circuit breakers from 100 to 630 A up to 690 V Protection of 440 - 690 V Network Compact NSX trip units Functions and characteristics Characteristics and performance of Compact NSX circuit breakers from 100 to 630 A Accessories and auxiliaries Overview of Compact NSX100 to 630 fixed version Overview of Compact NSX100 to 630 plug-in and withdrawable versions Installation recommendations Installation in switchboards Safety clearances and minimum distances Installation example Additional characteristics Current and energy limiting curves How to use the discrimination table Catalogue numbers 2 2 3 4 6 6 8 8 10 12 12 12 13 14 14 16 29 NSX100/250R: complete fixed/FC device 30 NSX100/250HB1: complete fixed/FC device 32 Compact NSX100/250R (200 kA 380/415 V - 45 kA 690 V) Compact NSX100/250HB1 (85 kA 500 V - 75 kA 690 V) Compact NSX100/250HB1 (85 kA 500 V - 75 kA 690 V) NSX100/250HB2: complete fixed/FC device Compact NSX100/250HB2 (100 kA 500 V - 100 kA 690 V) Compact NSX100/250HB2 (100 kA 500 V - 100 kA 690 V) 30 32 33 34 34 35 NSX400/630R: complete fixed/FC device 36 NSX400/630HB1: complete fixed/FC device 37 NSX400/630HB2: complete fixed/FC device 38 Compact NSX400/630R (200 kA 380/415 V - 45 kA 690 V) Compact NSX400/630HB1 (85 kA 500 V - 75 kA 690 V) Compact NSX400/630HB2 (100 kA 500 V - 100 kA 690 V) Order form Compact NSX100 to NSX630 Circuit breakers and switch-disconnectors 36 37 38 39 39 39 1 Overview of applications Introduction Characteristics and performance of Compact NSX circuit breakers from 100 to 630 A up to 690 V Applications Protection of distribution systems (AC 440/690 V) DB112087.eps G DB112089.eps DB413431.eps Compact NSX devices are equipped with MA or TM thermal-magnetic trip units or Micrologic 2 / 5 / 6 electronic trip units to provide protection against short-circuits and overloads for: bb distribution systems supplied by transformers bb distribution systems supplied by engine generator sets bb long cables in IT and TN systems. They can be easily installed at all levels in distribution systems, from the main LV switchboard to the subdistribution boards and enclosures. Protection of motors (AC 440/690 V) The Compact NSX range includes a number of versions to protect motor applications: bb basic short-circuit protection with MA magnetic trip units or the electronic Micrologic 1-M version, combined with an external relay to provide thermal protection bb protection against overloads, short-circuits and phase unbalance or loss with Micrologic 2-M trip units bb more complete protection against overloads and short-circuits with additional motor-specific protection (phase unbalance, locked rotor, underload and long start) with Micrologic 6 E-M trip units. These versions also offer communication, metering and operating assistance. The exceptional limiting capacity of Compact NSX circuit breakers automatically provides type-2 coordination with the motor starter, in compliance with standard IEC 60947-4-1. Offer structure The Compact NSX HB offer has some differences compared to the standard NSX offer. bb 100 A frame and 250 A frame, there is no 160 A frame. The 125 - 160 A trip units are used in a 250 A frame. bb All R, HB1, and HB2 circuit breakers are restricted for use as line-load connection. They can not have power fed into the bottom of the circuit breaker. They will be marked with Line and Load markings. bb All trip units will be installed at the factory. Type of protection Distribution protection TMD Micrologic Motor protection MA Compact NSX100 40-100 2.2: 40-100 5.2 E: 40-100 6.2 E: 40-100 12.5-100 2.2 M: 25, 50, 100 6.2 E-M: 25, 50, 100 Compact NSX250 125-250 2.2: 100, 160, 250 5.2 E: 100, 160, 250 6.2 E: 100, 160, 250 150, 220 2.2 M: 150, 220 6.2 E-M: 150, 220 Compact NSX400 - 2.3: 250, 400 5.3 E: 250, 400 6.3 E: 250, 400 - 1.3 M: 320 2.3 M: 320 6.3 M: 320 Compact NSX630 2 2.3: 630 5.3 E: 630 6.3 E: 630 Micrologic 1.3 M: 500 2.3 M: 500 6.3 M: 500 Protection of 440 - 690 V Network DB413275.eps Compact NSX HB circuit breaker is designed specifically for the needs of systems operating at 440 to 690 V. Compact NSX250 HB2 Ui 800 V Uimp 8 kV Ue (V) Icu (kA) Ics 500 525 660/690 ~ ~ ~ 100 100 100 100 100 100 50/60Hz cat A IEC / EN 60947-2 HIC (kA) NEMA AB1 480V 100 600V 100 1 2 3 4 5 6 7 8 9 10 440-690 V applications There are three new breaking capacities: R, HB1, and HB2. Markets bb Marine. bb Oil and gas. bb Data centers. bb Other markets pursuing energy efficiency (water, industrial, etc.). Ability to service high power densities bb Upgrade voltage from ~415-440 to 690 V system allows: vv smaller cables can be used -- reduced cost and space -- reduced energy loss in transmission vv motors are more efficient at 690 V. bb Consider 690 V as an alternative MV system: vv lower cost, smaller footprint, and improved maintenance. Safety bb IACS (International Association of Classification Societies) change, requires Ics rating for emergency systems: vv key influence on Marine systems of high Ics ratings vv continuity of service after 3 faults. DB413276.eps Technology 1 Compact NSX630 HB2 Ui 800 V Uimp Ue (V) Icu(kA) Ir 225 - 500A 500 ~ 100 525 ~ 100 660/690 ~ 100 Ir 501 - 630A 500 ~ 100 525 ~ 100 660/690 ~ 100 50/60Hz 8 kV Ics 100 100 100 100 25 25 cat A 2 3 4 5 6 7 NEMA AB1 480V 600V 60947-2 HIC (kA) 100 100 Enhancing solutions bb Using smaller frames for 440-690 V high performance circuits: vv space and cost benefit vv NSX family consistency with same NSX accessories. bb 200 kA breaking capacity on R rating will be mainly used for: vv high power factor applications : around 2.8 instead of 2.2 vv selectivity with Masterpact UR. Type I & II coordination for motor applications 9 bb Type I & II coordination with Tesys contactors is available up to 690 V. bb Coordination tables are prepared with external overload relays and protection integrated into the Micrologic trip units. bb See complimentary bulletin for ratings. 10 Compliance with standards 8 IEC / EN bb Best in class technology and performance: vv high breaking capacity vv NSX family consistency of energy metering, alarming and diagnosis. bb Provides alternative to fuse protection at 440 - 690 V applications. Standardised characteristics indicated on the rating plate: 1 Type of device: frame size and breaking capacity class. 2 Ui: rated insulation voltage. 3 Uimp: rated impulse withstand voltage. 4 Ics: service breaking capacity. 5 Icu: ultimate breaking capacity for various values of the rated operational voltage Ue. 6 Ue: operational voltage. 7 Circuit breaker-disconnector symbol. 8 Colour label indicating the breaking capacity class. 9 Reference standard. 10 Main standards with which the device complies. Compact NSX circuit breakers and auxiliaries comply with the following: bb international recommendations: vv IEC 60947-1: general rules vv IEC 60947-2: circuit breakers vv IEC 60947-3: switch-disconnectors vv IEC 60947-4: contactors and motor starters vv IEC 60947-5.1 and following: control circuit devices and switching elements; automatic control components bb European (EN 60947-1 and EN 60947-2) and corresponding national standards: vv France NF vv Germany VDE vv United Kingdom BS vv Australia AS vv Italy CEI bb the specifications of the marine classification companies (Veritas, Lloyd's Register of Shipping, Det Norske Veritas, etc.), standard NF C 79-130 and recommendations issued by the CNOMO organisation for the protection of machine tools. For U.S. UL, Canadian CSA, Mexican NOM and Japanese JIS standards, please consult us. 3 Introduction Compact NSX trip units With Micrologic electronic trip units, Compact NSX stands out from the crowd. Thanks to the new generation of sensors and its processing capability, protection is enhanced even further. It also provides measurements and operating information. Thermal-magnetic or electronic trip unit? Thermal-magnetic trip units protect against overcurrents and short-circuits using tried and true techniques. But today, installation optimisation and energy efficiency have become decisive factors and electronic trip units offering more advanced protection functions combined with measurements are better suited to these needs. Micrologic electronic trip units combine reflex tripping and intelligent operation. Thanks to digital electronics, trip units have become faster as well as more accurate and reliable. Wide setting ranges make installation upgrades easier. Designed with processing capabilities, Micrologic trip units can provide measurement information and device operating assistance. With this information, users can avoid or deal more effectively with disturbances and can play a more active role in system operation. They can manage the installation, anticipate on events and plan any necessary servicing. Accurate measurements for complete protection Compact NSX devices take advantage of the vast experience acquired since the launch of Masterpact NW circuit breakers equipped with Micrologic trip units. From 40 amperes on up to the short-circuit currents, they offer excellent measurement accuracy. This is made possible by a new generation of current transformers combining "iron-core" sensors for self-powered electronics and "aircore" sensors (Rogowski toroids) for measurements. The protection functions are managed by an ASIC component that is independent of the measurement functions. This independence ensures immunity to conducted and radiated disturbances and a high level of reliability. Numerous security functions Torque-limiting screws The screws secure the trip unit to the circuit breaker. When the correct tightening torque is reached, the screw heads break off. Optimum tightening avoids any risk of temperature rise. A torque wrench is no longer required. "Ready" LED for a continuous self-test The LED on the front of the electronic trip units indicates the result of the self-test runs continuously on the measurement system and the tripping release. As long as the green LED is flashing, the links between the CTs, the processing electronics and the Mitop release are operational. The circuit breaker is ready to protect. No need for a test kit. A minimum current of 15 to 50 A, depending on the device, is required for this indication function. A patented dual adjustment system for protection functions. Available on Micrologic 5 / 6, the system consists of: bb an adjustment using dials sets the maximum value bb an adjustment, made via the keypad or remotly, fine-tunes the setting. This setting may not exceed the first one. It can be read directly on the Micrologic screen, to within one ampere and a fraction of a second. Coordinated tripping systems Compact NSX detects faults even faster and its tripping time is reduced. It protects the installation better and limits contact wear. DB413407.eps Time delay Protection function 100 A L 1 - 200 s Overload: Slow trip inversely proportional to the current level Ii Isd 1000 A z Currents Ir S or S0 20 - 500 ms Short time: Impedant short-circuit, instantaneous trip with adjustable S or fixed S0 time delay 1500 A I 10 - 50 ms Instantaneous: Ultra-fast detection with micro delay for discrimination (1) This tripping system is completely independent of the trip unit. Because it directly actuates the mechanism, it precedes the trip unit by a few milliseconds. 4 Reflex threshold z E.g. NSX100R 2400 A < 5 ms Reflex: Energy-based ultra-fast detection with major current limiting (1) Icu 36000 A New performance offers same level of discrimination at 440 V as NSX range. For 690 V see tables. Unmatched discrimination Discrimination Compact NSX provides maximum continuity of service and savings through an unmatched level of discrimination: bb given the high accuracy of measurements, overload discrimination is ensured even between very close ratings bb for major faults, the fast processing of the Micrologic trip units means the upstream device can anticipate the reaction of the downstream device. The upstream breaker adjusts its tripping delay to provide discrimination bb for very high faults, the energy of the arc dissipated by the short-circuit in the downstream breaker causes reflex tripping. The current seen by the upstream device is significantly limited. The energy is not sufficient to cause tripping, so discrimination is maintained whatever the short-circuit current. Understanding the names of Micrologic electronic trip units Protection 1: I Frame 2: NSX160/250 Measurements A: Ammeter I: Instantaneous L: Long time S0: Short time (1) (fixed delay) Short time Ground fault 3: NSX400/630 DB112120.eps DB112155.eps 6: LSIG M: Motors E: Energy DB112156.eps DB112094.eps 5: LSI G: Distribution, otherwise G: Generator 2: LS0I S: Applications Examples Micrologic 1.3 Instantaneous only 400 or 630 A Micrologic 2.3 LS0I 400 or 630 A Micrologic 5.2 A LSI 100, 160 or 250 A Ammeter Distribution Micrologic 6.3 E-M LSIG 400 or 630 A Energy Motor Distribution Distribution (1) LS0I protection is standard on Micrologic 2. To ensure discrimination, it offers short-time protection S0 with a non-adjustable delay and instantaneous protection. 5 Functions and characteristics Characteristics and performance of Compact NSX circuit breakers from 100 to 630 A PB110406_40.eps Common characteristics Rated voltages Insulation voltage (V) Ui 800 Impulse withstand voltage (kV) Uimp 8 Operational voltage (V) Ue Suitability for isolation AC 50/60 Hz 690 IEC/EN 60947-2 yes Utilisation category A Pollution degree IEC 60664-1 3 Circuit breakers PB110420_40.eps Compact NSX250 R. Breaking capacity levels Electrical characteristics as per IEC 60947-2 Rated current (A) Number of poles Breaking capacity (kA rms) In 40 °C lcu AC 50/60 Hz 220/240 V 380/415 V 440 V 500 V 525 V 660/690 V lcs AC 50/60 Hz 220/240 V 380/415 V 440 V 500 V 525 V 660/690 V Mechanical Electrical 440 V Service breaking capacity (kA rms) PB111001_44.eps Compact NSX250 HB2. Durability (C-O cycles) 690 V Characteristics as per Nema AB1 Breaking capacity (kA rms) AC 50/60 Hz 240 V 480 V 600 V Characteristics as per UL 508 Breaking capacity (kA rms) Compact NSX630 R. In/2 In In/2 In AC 50/60 Hz 240 V 480 V 600 V Protection and measurements Magnetic only Thermal magnetic Electronic with neutral protection (Off-0.5-1-OSN) (2) with ground-fault protection with zone selective interlocking (ZSI) (3) Display / I, U, f, P, E, THD measurements / interrupted-current measurement Options Power Meter display on door Operating assistance Counters Histories and alarms Metering Com Device status/control Com Earth-leakage protection By Vigi module (5) By Vigirex relay PB111013_44.eps Short-circuit protection Overload / short-circuit protection Compact NSX630 HB2. (1) There is no 160 A frame, use the 250 A frame with lower amperage trip units. (2) OSN: Over Sized Neutral protection for neutrals carrying high currents (e.g. 3rd harmonics). (3) ZSI: Zone Selective Interlocking using pilot wires. (4) 2P circuit breaker in 3P case for B and F types, only with thermal-magnetic trip unit. (5) Vigi module is not available for breaking capacity levels HB1 and HB2. 6 Installation / connections Dimensions and weights Dimensions (mm) WxHxD Fixed, front connections Weight (kg) Fixed, front connections Connections 3P 4P 3P 4P Connection terminals Pitch With/without spreaders Large Cu or Al cables Cross-section mm² Common characteristics Control Manual Electrical With toggle b With direct or extended rotary handle b With remote control b Versions Fixed b Withdrawable NSX100-250 (1) R HB1 Plug-in base b Chassis b NSX400 HB2 R NSX630 HB1 HB2 Ir = 225 - 500 A R HB1 100-250 400 630 2 (4), 3, 4 3, 4 3, 4 HB2 Ir = 501 - 630 A R HB1 HB2 200 200 200 80 65 45 85 80 75 100 100 100 200 200 200 80 65 45 85 80 75 100 100 100 200 200 200 80 65 45 85 80 75 100 100 100 200 200 200 80 65 45 85 80 75 100 100 100 200 200 200 80 65 45 20000 20000 10000 10000 5000 85 80 75 100 100 100 200 200 200 80 65 45 15000 12000 6000 6000 3000 85 80 75 100 100 100 200 200 200 80 65 45 15000 8000 4000 6000 2000 85 80 75 100 100 100 200 200 200 80 16 12 85 20 19 100 25 25 200 150 50 85 75 100 100 200 150 50 85 75 100 100 200 150 50 85 75 100 100 200 150 50 85 75 100 100 - - - b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b 105 x 161 x 86 140 x 161 x 86 2.4 2.8 105 x 161 x 86 140 x 161 x 86 6.05 7.90 140 x 255 x 110 185 x 255 x 110 6.2 8.13 35/45 mm 45/52.5 mm 45/70 mm 4 x 240 45/52.5 mm 45/70 mm 4 x 240 300 7 Accessories and auxiliaries Functions and characteristics Overview of Compact NSX100 to 630 fixed version DB413406.eps Insulation accessories Interphase barriers Sealable terminal shields Electrical auxiliaries Indication contact Voltage release SDTAM module SDx module Protection and measurements Micrologic 2 trip unit Micrologic 5 / 6 trip unit TM-D trip unit 8 Connection One-piece spreader Cable connectors Rear connectors Terminal extensions Cable connectors Communication and display BSCM module NSX cord Modbus interface FDM121 Control accessories Direct rotary handle Extended rotary handle Motor mechanism 9 Accessories and auxiliaries Functions and characteristics Overview of Compact NSX100 to 630 plug-in and withdrawable versions DB115888.eps Insulation accessories Interphase barriers Sealable long terminal shields for plug-in base Electrical accessories Automatic withdrawable auxiliary connector Manual auxiliary connector Mechanical accessories Circuit-breaker side plate Chassis side plate 10 Connection Cable connectors Rear connectors Lugs Rear connectors Adapter Cable connectors Terminal extensions Circuit breaker Plug-in base Power connection accessories Power connections Power connections for Vigicompact 11 Installation in switchboards Installation recommendations Safety clearances and minimum distances General rules When installing a circuit breaker, minimum distances (safety clearances) must be maintained between the device and panels, bars and other protection devices installed nearby. These distances, which depend on the ultimate breaking capacity, are defined by tests carried out in accordance with standard IEC 60947-2. If installation conformity is not checked by type tests, it is also necessary to: bb use insulated bars for circuit-breaker connections bb segregate the busbars using insulating screens. For Compact NSX100 to 630 devices, terminal shields and interphase barriers are recommended and may be mandatory depending on the operating voltage of the device and type of installation (fixed, withdrawable, etc.). Power connections The table below indicates the rules to be respected for Compact NSX100 to 630 devices to ensure insulation of live parts for the various types of connection. bb fixed devices with front connection (FC) or rear connection (RC) bb plug-in or withdrawable devices. Connection accessories such as crimp lugs, bare-cable connectors, terminal extensions (straight, right-angle, double-L and 45°) and spreaders are supplied with interphase barriers. Long terminal shields provide a degree of protection of IP40 (ingress) and IK07 (mechanical impact). Compact NSX100 to 630: rules to be respected to ensure insulation of live parts Fixed, rear connection Plug-in or withdrawable operating voltage DB115057.eps DB115061 DB115061 Short terminal shields Short terminal shields type of conductor Bare cables + connectors Possible Possible Possible Recommended Recommended Mandatory No Mandatory (supplied) Possible (instead of ph. Recommended Recommended barriers) Mandatory Possible for cable connectors NSX100 to 250 Possible for cable connectors NSX100 to 250 Mandatory No Mandatory (1) (supplied) Possible for cable connectors NSX100 to 250 Recommended Recommended Possible (1) (instead of ph. barriers) Mandatory Mandatory Insulated bars Extension terminals Cables + crimp lugs Bare cables + connectors No No Mandatory (use of short Mandatory terminal shield possible) No No Mandatory Mandatory Mandatory Mandatory No No Mandatory Mandatory Mandatory Mandatory (1) Long terminal shields, mandatory if the device is fixed through the door, whatever the voltage. 12 Short terminal shields Through panel Insulated bars Extension terminals Cables + crimp lugs u 500 V Long terminal shields DB115060 With: < 500 V Interphase barriers DB115059 Possible, recommended or mandatory accessories: No insulating accessory DB115056.eps DB115055.eps On backplate DB115058.eps Fixed, front connection DB115061 Type of connection Installation example Safety clearance Minimum distance between circuit breaker and front or rear panels DB115697.eps DB115046.eps Minimum distance between two adjacent circuit breakers A1 Bare or painted sheetmetal F Front panel B=0 F Note: if F < 8 mm: an insulating screen or long terminal shield is mandatory. D2 D1 D1 DB413246.eps D1 DB413245.eps DB413244.eps DB413243.eps Minimum distance between circuit breaker and top, bottom or side panels D1 C1 Devices without accessories. Devices with interphase barriers or long or short terminal shields. Minimum safety clearances for Compact NSX100 to 630 Operating voltage Clearance (mm) Between Between device and sheetmetal devices Painted sheet metal Bare sheet metal DB115698.eps Spacing y 60 mm Spacing > 60 mm Bars F1 F1 U y 440 V for devices equipped with: b no accessories b short terminal shields b interphase barriers b long terminal shields 440 V < U y 600 V for devices equipped with: b short terminal shields b interphase barriers (1) b long terminal shields (2) U > 600 V for devices equipped with: b short terminal shields b long terminal shields (1) Only for NSX100 to 250. (2) For all cases. A1 C1 D1 D2 C1 D1 D2 0 0 0 0 0 0 0 0 30 30 0 0 30 30 0 0 5 5 5 0 40 40 0 0 40 40 0 0 0 0 0 0 0 0 30 0 0 30 0 0 10 20 10 40 10 10 40 10 10 0 0 10 10 50 30 50 30 20 20 100 40 100 40 Clearances with respect to live bare busbars Minimum clearances for Compact NSX100 to 630 Operating voltage Clearances with respect to live bare busbars spacing y 60 mm spacing > 60 mm F2 F2 Bars Live busbars. F1 F2 F1 F2 350 350 80 80 350 350 120 120 prohibited: insulating screen required between device and busbars These clearances can be reduced for special installations as long as the configuration is checked by tests. U < 440 V 440 V y U y 600 V U > 600 V 13 Additional characteristics Current and energy limiting curves The limiting capacity of a circuit breaker is its aptitude to let through a current, during a short-circuit, that is less than the prospective short-circuit current. Ics = 100 % Icu DB115719.eps (Isc) Prospective Isc peak Prospective current Prospective Isc Limited Isc peak Actual current Limited Isc (t) The exceptional limiting capacity of the Compact NSX range is due to the rotating double-break technique (very rapid natural repulsion of contacts and the appearance of two arc voltages in-series with a very steep wave front). The exceptional limiting capacity of the Compact NSX range greatly reduces the forces created by fault currents in devices. The result is a major increase in breaking performance. In particular, the service breaking capacity Ics is equal to 100 % of Icu. The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising the following steps: bb break three times consecutively a fault current equal to 100 % of Icu bb check that the device continues to function normally, that is: vv it conducts the rated current without abnormal temperature rise vv protection functions perform within the limits specified by the standard vv suitability for isolation is not impaired. Longer service life of electrical installations Current-limiting circuit breakers greatly reduce the negative effects of short-circuits on installations. Thermal effects Less temperature rise in conductors, therefore longer service life for cables. Mechanical effects Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars being deformed or broken. Electromagnetic effects Fewer disturbances for measuring devices located near electrical circuits. Economy by means of cascading Cascading is a technique directly derived from current limiting. Circuit breakers with breaking capacities less than the prospective short-circuit current may be installed downstream of a limiting circuit breaker. The breaking capacity is reinforced by the limiting capacity of the upstream device. It follows that substantial savings can be made on downstream equipment and enclosures. Current and energy limiting curves The limiting capacity of a circuit breaker is expressed by two curves which are a function of the prospective short-circuit current (the current which would flow if no protection devices were installed): bb the actual peak current (limited current) bb thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor with a resistance of 1 Ω. Example What is the real value of a 150 kA rms prospective short-circuit (i.e. 330 kA peak) limited by an NSX250L upstream ? The answer is 30 kA peak. Maximum permissible cable stresses The table below indicates the maximum permissible thermal stresses for cables depending on their insulation, conductor (Cu or Al) and their cross-sectional area (CSA). CSA values are given in mm² and thermal stresses in A2s. CSA PVC Cu 1.5 mm² 2.97x104 2.5 mm² 8.26x104 4 mm² 2.12x105 6 mm² 4.76x105 4.10x10 1.39x10 2.92x10 6.56x10 Al PRC Cu 5.41x105 4 5 5 5 Al CSA PVC PRC 10 mm² 1.32x106 1.82x106 7.52x105 16 mm² 25 mm² 35 mm² 50 mm² Cu 3.4x106 8.26x106 1.62x107 3.31x107 Al 1.39x106 3.38x106 6.64x106 1.35x107 Cu 4.69x10 6 1.39x10 7 2.23x10 7 4.56x107 Al 1.93x10 6 4.70x10 6 9.23x10 6 1.88x107 Example Is a Cu/PVC cable with a CSA of 10 mm² adequately protected by an NSX160F? The table above indicates that the permissible stress is 1.32x106 A2s. All short-circuit currents at the point where an NSX160F (Icu = 35 kA) is installed are limited with a thermal stress less than 6x105 A2s. Cable protection is therefore ensured up to the limit of the breaking capacity of the circuit breaker. 14 Current-limiting curves Voltage 400/440 V AC Voltage 660/690 V AC Limited short-circuit current (k peak) Limited short-circuit current (k peak) 300 DB413433.eps DB413432.eps 300 200 200 146 146 100 80 70 60 50 100 80 70 60 50 40 k peak 30 F 20 F B 10 8 7 6 5 4 2 3 4 6 10 20 N N 30 40 H H 60 65 kA rms S S L L 100 R NSX630 NSX400 R NSX250 NSX100 NSX160 HB1 HB2 NSX630 40 k peak 30 H 20 L F, N 10 8 7 6 5 4 2 200 300 F 3 4 6 S L S R NSX400 R HB1 HB2 NSX250 NSX100 NSX160 N, H 10 20 30 40 kA rms 60 65 100 200 300 Energy-limiting curves Voltage 400/440 V AC Voltage 660/690 V AC Limited energy 9 5 3 2 1.41 8 10 2 9 5 3 2 1.41 8 10 5 5 3 2 3 2 10 As 10 DB413435.eps DB413434.eps 10 Limited energy 7 10 5 F 3 2 10 6 F B 5 N N H H S S L L R R NSX630 NSX400 NSX250 NSX100 NSX160 3 2 10 5 H 3 2 10 L S F, N 6 F 5 N, H S L R HB1 HB2 R HB1 HB2 NSX250 NSX630 NSX400 NSX100 NSX160 3 2 5 10 5 3 2 2 As 7 5 5 2 3 4 6 10 20 30 40 50 70 100 150 200 300 kA rms 3 2 2 3 4 6 10 20 30 40 50 70 100 150 200 300 kA rms 15 Additional characteristics How to use the discrimination table Combinaisons providing full discrimination are indicated by the symbol T. In that case the discrimination is ensured up to downstream breaker breaking capacity. If discrimination is partial, the table indicates the maximum fault current value (kA) until which discrimination is ensured. Requisite conditions The value indicated in the tables are valid for operational rated voltage 550 V, 660 V, 690 V 50-60 Hz. Following ratios shall be respected in order to avoid overlapping of tripping curves. Upstream Micrologic TM Downstream Ir up / Ir down Im up / Im down TM u 1.6 u 1.5 Micrologic u 1.3 u 1.5 MA + OL relay u3 u2 TM u 1.6 u2 Micrologic u 1.6 u 1.5 MA + OL relay u3 u2 DB413430.eps Additional settings conditions according to trip unit type CB1 bb Short time pick up (Isd) Tables indicate selectivity limits assuming Isd = 10 x Ir. In many cases when discrimination is total lower thresholds could be used if ratio condition between two magnetic protections is fulfilled. When selectivity limit indicated in the tables is equal to 10 x Ir, the selectivity limit is upstream circuit breaker short time pick up (Isd). bb Instantaneous pick up (Ii) Tables indicate selectivity limits assuming instantaneous pick up is set at the maximum value and when it is inhibited (Type B circuit breaker only). With Masterpact, when selectivity limit indicated in the tables is equal to 15 x In, the selectivity limit is upstream circuit breaker instantaneous pick up (Ii). When upstream circuit breaker is A type, and downstream circuit breaker is B type upstream instantaneous setting can be set lower than 15 In as far as it stay higher than downstream circuit breaker reflex tripping limit. When a Micrologic 5.x is used downstream a Micrologic 2.x Tsd shall be set at 0 and Ii shall be set at Isd. bb Short time delay (Tsd) When upstream and downstream breaker are equipped with Micrologic 5.x, 6.x, 7.x: the minimum non tripping-time of the upstream device must be greater than the maximum tripping time of the downstream device. Tsd CB1 > Tsd CB2 (One Step) CB2 16 bb I²t Off / On Tables indicate selectivity limits assuming I²t Function is Off. If I²t function is ON user shall check curves. Protection discrimination 690 V Additional characteristics Upstream: Compact NSX100-250 TM-D Downstream: TeSys GV2, GV3, TeSys U Upstream NSX100L NSX100L/R/HB1/HB2 NSX160L NSX250L/R/HB1/ HB2 Trip unit TM-D TM-D TM-D TM-D Downstream Icu O/L Rating (A) 16 25 32 40 50 63 80 100 80 100 125 160 160 200 250 Ir range Discrimination limit (kA) GV2 L03 100 kA LRD 03 0.25/0.40 T T T T T T T T T T T T T T T GV2 L04 100 kA LRD 04 0.40/0.63 T T T T T T T T T T T T T T T GV2 L05 100 kA LRD 05 0.63/1 T T T T T T T T T T T T T T T GV2 L06 100 kA LRD 06 1/1.6 T T T T T T T T T T T T T T T GV2 L07 + LA9 LB920 50 kA LRD 07 1.6/2.5 0.19 0.25 0.4 1 5 6 10 10 10 10 T T T T T GV2 L08 + LA9 LB920 50 kA LRD 08 2.5/4 0.19 0.25 0.4 0.5 0.5 0.5 1 1.5 1 1.5 T T 36 T T GV2 L10 + LA9 LB920 50 kA LRD 10 4/6.3 0.25 0.4 0.5 0.5 0.5 0.63 0.8 0.63 0.8 1.25 1.6 1.6 T T GV2 L14 + LA9 LB920 50 kA LRD 14 7/10 0.4 0.5 0.5 0.5 0.63 0.8 0.63 0.8 1.25 1.6 1.6 T T GV2 L16 + LA9 LB920 50 kA LRD 16 9/13 0.5 0.5 0.63 0.8 0.63 0.8 1.25 1.6 1.6 T T GV2 L20 + LA9 LB920 50 kA LRD 21 12/18 0.63 0.8 0.63 0.8 1.25 1.6 1.6 T T GV2 L22 + LA9 LB920 50 kA LRD 22 17/25 0.63 0.8 0.63 0.8 1.25 1.6 1.6 T T GV2 L32 + LA9 LB920 50 kA LRD 32 23/32 0.8 0.8 1.25 1.6 1.6 T T GV3 P13 6 kA Integrated 9/13 GV3 P18 6 kA Integrated 12/18 GV3 P25 6 kA Integrated 17/25 GV3 P32 6 kA Integrated 23/32 0.8 GV3 P40 6 kA Integrated 30/40 GV3 P50 6 kA Integrated 37/50 GV3 P65 6 kA Integrated 48/65 GV3 L25 6 kA LRD 22 20/25 0.63 0.8 GV3 L32 6 kA LRD 32 23/32 0.8 GV3 L40 6 kA LRD 340 30/40 GV3 L50 6 kA LRD 350 37/50 GV3 L65 6 kA LRD 365 48/65 LUB12 + LA9 LB20 35 kA LUC*X6 0.15…0.6 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*1X 0.35…1.4 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*05 1.25…5 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*12 3…12 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*X6 0.15…0.6 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*1X 0.35…1.4 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*05 1.25…5 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*12 3…12 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*18 4.5…18 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*32 8…32 0.8 1 1.6 1.6 T T LUC*X6 0.15…0.6 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*1X 0.35…1.4 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*05 1.25…5 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*12 3…12 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*X6 0.15…0.6 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*1X 0.35…1.4 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*05 1.25…5 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*12 3…12 0.5 0.5 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*18 4.5…18 0.5 0.63 0.8 0.7 0.8 1 1.6 1.6 T T LUC*32 8…32 0.8 1 1.6 1.6 T T LUB32 + LA9 LB20 LUB12 + LUA LB1 LUB32 + LUA LB1 35 kA 70 kA 70 kA 0.5 0.5 0.63 0.8 0.63 0.8 1 1.25 1.25 T T 0.5 0.63 0.8 0.63 0.8 1 1.25 1.25 T T 0.63 0.8 0.63 0.8 1 1.25 1.25 T T 0.8 1 1.25 1.25 T T 1.25 1.25 T T T T T 0.63 0.8 1 1.25 1.25 T T 0.8 1 1.25 1.25 T T 1 1.25 1.25 T T T T T 0.8 T Total discrimination, up to the breaking capacity of the downstream circuit breaker. 4 Discrimination limit = 4 kA. 0.8 No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 17 Protection discrimination 690 V Additional characteristics Upstream: Compact NSX100-250 Micrologic Downstream: TeSys GV2, GV3, TeSys U Upstream NSX100L/R/HB1/HB2 NSX160L NSX250L/R/HB1/ HB2 Trip unit Micrologic Micrologic Micrologic Downstream Icu O/L Rating (A) 40 Setting Ir 16 100 25 32 40 40 160 63 80 100 80 250 100 125 160 160 200 250 Discrimination limit (kA) GV2 L03 100 kA LRD 03 0.25/0.40 T T T T T T T T T T T T T T T GV2 L04 100 kA LRD 04 0.40/0.63 T T T T T T T T T T T T T T T GV2 L05 100 kA LRD 05 0.63/1 T T T T T T T T T T T T T T T GV2 L06 100 kA LRD 06 1/1.6 T T T T T T T T T T T T T T T GV2 L07 + LA9 LB920 50 kA LRD 07 1.6/2.5 T T T T T T T T T T T T T T T GV2 L08 + LA9 LB920 50 kA LRD 08 2.5/4 T T T T T T T T T T T T T T T T T GV2 L10 + LA9 LB920 50 kA LRD 10 4/6.3 GV2 L14 + LA9 LB920 50 kA LRD 14 7/10 T T T T T T T T T T T T T T T T T T T T T T T T GV2 L16 + LA9 LB920 50 kA LRD 16 9/13 T T T T T T T T T GV2 L20 + LA9 LB920 50 kA LRD 21 12/18 T T T T T T T T T T GV2 L22 + LA9 LB920 50 kA LRD 22 17/25 GV2 L32 + LA9 LB920 50 kA LRD 32 23/32 GV3 P13 6 kA Integrated 9/13 GV3 P18 6 kA Integrated 12/18 GV3 P25 6 kA Integrated 17/25 GV3 P32 6 kA Integrated 23/32 GV3 P40 6 kA Integrated 30/40 GV3 P50 6 kA Integrated 37/50 GV3 P65 6 kA Integrated 48/65 GV3 L25 6 kA LRD 22 20/25 GV3 L32 6 kA LRD 32 23/32 GV3 L40 6 kA LRD 340 30/40 GV3 L50 6 kA LRD 350 37/50 GV3 L65 6 kA LRD 365 48/65 LUB12 + LA9 LB20 35 kA LUB32 + LA9 LB20 LUB12 + LUA LB1 LUB32 + LUA LB1 35 kA 70 kA 70 kA T 0.6 1.5 T T T T T T T T T T T T T T T T 1.5 1.5 1.5 4 4 4 4 T T T 1.5 1.5 1.5 3.5 3.5 3.5 3.5 T T T 1.5 3 T 1.5 1.5 3 3 T T 3 3 T T T 2.4 2.4 T T T 2.4 1.5 1.5 3 1.5 3 3 3 T T T 3 3 3 T T T 2.4 2.4 T T T 2.4 LUC*X6 0.15…0.6 T T T T T T T T T T T T T T T LUC*1X 0.35…1.4 T T T T T T T T T T T T T T T LUC*05 1.25…5 T T T LUC*12 3…12 T T T T T T T T T T T T T T T T T T T T T T T T LUC*X6 0.15…0.6 T T T T T T T T T T T T T T T LUC*1X 0.35…1.4 T T T T T T T T T T T T T T T LUC*05 1.25…5 T T T LUC*12 3…12 LUC*18 4.5…18 LUC*32 8…32 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T LUC*X6 0.15…0.6 T T T T T T T T T T T T T T T LUC*1X 0.35…1.4 T T T T T T T T T T T T T T T LUC*05 1.25…5 T T T LUC*12 3…12 T T T T T T T T T T T T T T T T T T T T T T T T LUC*X6 0.15…0.6 T T T T T T T T T T T T T T T LUC*1X 0.35…1.4 T T T T T T T T T T T T T T T LUC*05 1.25…5 T T T LUC*12 3…12 LUC*18 4.5…18 LUC*32 8…32 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Total discrimination, up to the breaking capacity of the downstream circuit breaker. 4 Discrimination limit = 4 kA. T No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 18 3 3 T T T T T T T T T T T T Protection discrimination 690 V Additional characteristics Upstream: Compact NSX100-250 TM-D Downstream: Compact NSX100-250 TM-D Micrologic - MA + LRD Upstream NSX100L NSX100L/R/HB1/HB2 NSX160L NSX250L/R/HB1/ HB2 Trip unit TM-D TM-D TM-D TM-D Downstream O/L Rating (A) 16 25 32 40 50 63 80 100 80 100 125 160 160 200 250 Ir range Discrimination limit (kA) NSX100 L TM-D 16 0.5 25 0.5 0.5 0.63 0.8 0.63 0.8 1.25 1.25 1.25 2 2.5 0.5 0.5 0.63 0.8 0.63 0.8 1.25 1.25 1.25 2 2.5 32 NSX100 L/R/HB1/HB2 0.63 0.8 0.63 0.8 1.25 1.25 1.25 2 2.5 40 0.5 0.63 0.8 0.63 0.8 1.25 1.25 1.25 2 2.5 50 0.63 0.8 0.63 0.8 1.25 1.25 1.25 2 2.5 63 0.8 0.8 1.25 1.25 1.25 2 2.5 1.25 1.25 1.25 2 2.5 1.25 1.25 2 2.5 80 100 NSX160 L TM-D y 63 1.25 1.25 1.25 2 2.5 80 1.25 1.25 1.25 2 2.5 1.25 1.25 2 2.5 1.25 2 2.5 2 2.5 100 160 NSX250 L/R/HB1/HB2 TM-D 2.5 y 100 125 160 2.5 200 NSX100 L/R/HB1/HB2 Micrologic 40 NSX160 L Micrologic 40 0.5 0.63 0.8 0.63 0.8 1.25 100 0.5 0.63 0.8 0.63 0.8 1.25 100 1.25 1.25 2 2.5 1.25 1.25 2 2.5 1.25 1.25 2 2.5 1.25 1.25 2 2.5 1.25 2 160 NSX250 L/R/HB1/HB2 Micrologic 2.5 y 100 160 2.5 2.5 250 NSX100 L MA 2.5 LRD 06 1/1.6 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.63 0.8 1 1 1 20 20 NSX100 L MA 2.5 LRD 07 1.6/2.5 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.63 0.8 1 1 1 20 20 NSX100 L MA 6.3 LRD 08 2.5/4 0.19 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.63 0.8 1 1 1 20 20 NSX100 L MA 6.3 LRD 10 4/6.3 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.63 0.8 1 1 1 20 20 NSX100 L/R/HB1/HB2 MA 12.5 LRD 12 5.5/8 0.3 0.4 0.5 0.5 0.5 0.63 0.8 0.63 0.8 1 1 1 6 6 NSX100 L/R/HB1/HB2 MA 12.5 LRD 14 7/10 0.4 0.5 0.5 0.5 0.63 0.8 0.63 0.8 1 1 1 6 6 0.5 0.5 0.5 0.63 0.8 0.63 0.8 1 1 1 6 6 0.5 0.63 0.8 0.63 0.8 1 1 1 5 5 0.63 0.8 1 1 1 5 5 NSX100 L/R/HB1/HB2 MA 12.5 LRD 16 9/13 NSX100 L/R/HB1/HB2 MA 25 LRD 21 12/18 NSX100 L/R/HB1/HB2 MA 25 LRD 22 17/25 0.63 0.8 0.8 NSX100 L/R/HB1/HB2 MA 50 LRD 32 23/32 NSX100 L/R/HB1/HB2 MA 50 LRD 33 55 30/40 NSX100 L/R/HB1/HB2 MA 50 LRD 33 57 37/50 NSX100 L/R/HB1/HB2 MA 100 LRD 33 59 48/65 NSX100 L/R/HB1/HB2 MA 100 LRD 33 63 63/80 NSX100 L/R/HB1/HB2 MA 100 LRD 33 65 or 43 65 80/100 NSX100 L/R/HB1/HB2 Micrologic 25/50 2.2 M or 6.2 E-M 100 4 0.8 1 1 1 5 5 1 1 1 5 5 1 1 5 5 4 4 4 0.8 1 1 1 2 2.5 2.5 Discrimination limit = 4 kA. No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 19 Protection discrimination 690 V Additional characteristics Upstream: Compact NSX100-250 Micrologic Downstream: Compact NSX100-250 TM-D Micrologic - MA Upstream NSX100L/R/HB1/HB2 NSX160L NSX250L/R/HB1/ HB2 Trip unit Micrologic Micrologic Micrologic Downstream O/L Rating (A) 40 Setting Ir 16 100 25 32 40 160 250 40 63 80 100 80 100 125 160 160 200 250 16 1.5 1.5 1.5 1.5 2.4 2.4 2.4 2.4 3 3 3 25 1.5 1.5 1.5 1.5 2.4 2.4 2.4 2.4 3 3 3 1.5 1.5 1.5 2.4 2.4 2.4 2.4 3 3 3 1.5 1.5 2.4 2.4 2.4 2.4 3 3 3 1.5 2.4 2.4 2.4 2.4 3 3 3 2.4 2.4 2.4 3 3 3 2.4 2.4 3 3 3 2.4 3 3 3 2.4 2.4 3 3 3 2.4 2.4 3 3 3 2.4 3 3 3 3 3 3 3 3 Discrimination limit (kA) NSX100 L TM-D 32 NSX100 L/R/HB1/HB2 40 50 63 80 100 NSX160 L TM-D y 63 2.4 80 100 160 NSX250 L/R/HB1/HB2 TM-D 3 y 100 125 160 3 200 NSX100 L/R/HB1/HB2 Micrologic 40 NSX160 L Micrologic 40 1.5 1.5 1.5 1.5 2.4 2.4 2.4 100 2.4 2.4 2.4 100 2.4 3 3 3 2.4 3 3 3 2.4 3 3 3 2.4 3 3 3 3 3 160 NSX250 L/R/HB1/HB2 Micrologic 3 y 100 160 3 3 250 NSX100 L MA 2.5 LRD 06 1/1.6 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 NSX100 L MA 2.5 LRD 07 1.6/2.5 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 NSX100 L MA 6.3 LRD 08 2.5/4 4 4 4 4 4 4 4 4 8 8 8 8 20 20 20 NSX100 L MA 6.3 LRD 10 4/6.3 4 4 4 4 4 4 4 4 8 8 8 8 20 20 20 2 2 2 2 2 2 2 2.4 2.4 2.4 2.4 20 20 20 2 2 2 2 2 2 2.4 2.4 2.4 2.4 20 20 20 2 2 2 2 2 2.4 2.4 2.4 2.4 20 20 20 2 2 2 2.4 2.4 2.4 2.4 13 13 13 2 2 2.4 2.4 2.4 2.4 13 13 13 2.4 2.4 2.4 11 11 11 2.4 2.4 11 11 11 2.4 11 11 11 NSX100 L/R/HB1/HB2 MA 12.5 LRD 12 5.5/8 NSX100 L/R/HB1/HB2 MA 12.5 LRD 14 7/10 NSX100 L/R/HB1/HB2 MA 12.5 LRD 16 9/13 NSX100 L/R/HB1/HB2 MA 25 LRD 21 12/18 NSX100 L/R/HB1/HB2 MA 25 LRD 22 17/25 NSX100 L/R/HB1/HB2 MA 50 LRD 32 23/32 NSX100 L/R/HB1/HB2 MA 50 LRD 33 55 30/40 NSX100 L/R/HB1/HB2 MA 50 LRD 33 57 37/50 NSX100 L/R/HB1/HB2 MA 100 LRD 33 59 48/65 10 10 NSX100 L/R/HB1/HB2 MA 100 LRD 33 63 63/80 10 10 NSX100 L/R/HB1/HB2 MA 100 LRD 33 65 or 43 65 80/100 NSX100 L/R/HB1/HB2 Micrologic 25/50 2.2 M or 6.2 E-M 100 4 1 10 1.5 Discrimination limit = 4 kA. No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 20 2.4 2.4 2.4 2.4 3 3 3 3 Protection discrimination 690 V Additional characteristics Upstream: Compact NSX400-630 Downstream: TeSys GV2, GV3, TeSys U Upstream NSX400L/R/HB1/HB2 NSX630L/R/HB1/HB2 Trip unit Micrologic Micrologic Downstream Icu O/L Rating (A) 400 Ir range 160 200 250 320 400 630 250 320 400 500 630 T Discrimination limit (kA) GV2 L03 100 kA LRD 03 0.25/0.40 T T T T T T T T T GV2 L04 100 kA LRD 04 0.40/0.63 T T T T T T T T T T GV2 L05 100 kA LRD 05 0.63/1 T T T T T T T T T T T GV2 L06 100 kA LRD 06 1/1.6 T T T T T T T T T GV2 L07 + LA9 LB920 50 kA LRD 07 1.6/2.5 T T T T T T T T T T GV2 L08 + LA9 LB920 50 kA LRD 08 2.5/4 T T T T T T T T T T T GV2 L10 + LA9 LB920 50 kA LRD 10 4/6.3 T T T T T T T T T GV2 L14 + LA9 LB920 50 kA LRD 14 7/10 T T T T T T T T T T GV2 L16 + LA9 LB920 50 kA LRD 16 9/13 T T T T T T T T T T GV2 L20 + LA9 LB920 50 kA LRD 21 12/18 T T T T T T T T T T GV2 L22 + LA9 LB920 50 kA LRD 22 17/25 T T T T T T T T T T T GV2 L32 + LA9 LB920 50 kA LRD 32 23/32 T T T T T T T T T GV3 P13 6 kA Integrated 9/13 T T T T T T T T T T GV3 P18 6 kA Integrated 12/18 T T T T T T T T T T GV3 P25 6 kA Integrated 17/25 T T T T T T T T T T GV3 P32 6 kA Integrated 23/32 T T T T T T T T T T GV3 P40 6 kA Integrated 30/40 T T T T T T T T T T GV3 P50 6 kA Integrated 37/50 T T T T T T T T T T GV3 P65 6 kA Integrated 48/65 T T T T T T T T T T T GV3 L25 6 kA LRD 22 20/25 T T T T T T T T T GV3 L32 6 kA LRD 32 23/32 T T T T T T T T T T GV3 L40 6 kA LRD 340 30/40 T T T T T T T T T T GV3 L50 6 kA LRD 350 37/50 T T T T T T T T T T GV3 L65 6 kA LRD 365 48/65 T T T T T T T T T T LUB12 + LA9 LB20 35 kA LUC*X6 0.15…0.6 T T T T T T T T T T LUC*1X 0.35…1.4 T T T T T T T T T T LUC*05 1.25…5 T T T T T T T T T T LUC*12 3…12 T T T T T T T T T T LUC*X6 0.15…0.6 T T T T T T T T T T LUC*1X 0.35…1.4 T T T T T T T T T T LUC*05 1.25…5 T T T T T T T T T T LUC*12 3…12 T T T T T T T T T T LUC*18 4.5…18 T T T T T T T T T T LUC*32 8…32 T T T T T T T T T T LUC*X6 0.15…0.6 T T T T T T T T T T LUC*1X 0.35…1.4 T T T T T T T T T T LUC*05 1.25…5 T T T T T T T T T T LUC*12 3…12 T T T T T T T T T T LUC*X6 0.15…0.6 T T T T T T T T T T LUC*1X 0.35…1.4 T T T T T T T T T T LUC*05 1.25…5 T T T T T T T T T T LUC*12 3…12 T T T T T T T T T T LUC*18 4.5…18 T T T T T T T T T T LUC*32 8…32 T T T T T T T T T T LUB32 + LA9 LB20 LUB12 + LUA LB1 LUB32 + LUA LB1 T 35 kA 70 kA 70 kA Total discrimination, up to the breaking capacity of the downstream circuit breaker. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 21 Protection discrimination 690 V Additional characteristics Upstream: Compact NSX400-630 Downstream: Compact NSX100-250 TM-D Micrologic - MA + LRD Upstream NSX400L/R/HB1/HB2 NSX630L/R/HB1/HB2 Trip unit Micrologic Micrologic Downstream O/L Discrimination limit (kA) NSX100 L TM-D NSX100 L/R/HB1/HB2 NSX160 L TM-D NSX250 L/R/HB1/HB2 TM-D NSX100 L/R/HB1/HB2 Micrologic NSX160 L Micrologic NSX250 L/R/HB1/HB2 Micrologic NSX400 L/R/HB1/HB2 Micrologic NSX100 L MA 2.5 NSX100 L MA 2.5 NSX100 L MA 6.3 NSX100 L MA 6.3 NSX100 L/R/HB1/HB2 MA 12.5 NSX100 L/R/HB1/HB2 MA 12.5 NSX100 L/R/HB1/HB2 MA 12.5 NSX100 L/R/HB1/HB2 MA 25 NSX100 L/R/HB1/HB2 MA 25 NSX100 L/R/HB1/HB2 MA 50 NSX100 L/R/HB1/HB2 MA 50 NSX100 L/R/HB1/HB2 MA 50 NSX100 L/R/HB1/HB2 MA 100 NSX100 L/R/HB1/HB2 MA 100 NSX100 L/R/HB1/HB2 MA 100 NSX160 L MA 150 NSX250 L/R/HB1/HB2 MA 220 NSX100 L/R/HB1/HB2 NSX160 L NSX250 L/R/HB1/HB2 LRD 06 LRD 07 LRD 08 LRD 10 LRD 12 LRD 14 LRD 16 LRD 21 LRD 22 LRD 32 LRD 33 55 LRD 33 57 LRD 33 59 LRD 33 63 LRD 33 65 or 43 65 LRD 43 67 LR9 F5371 Micrologic 2.2 M or 6.2 E-M Rating (A) 400 Ir range 160 200 250 320 400 250 320 400 500 630 16 25 32 40 50 63 80 100 y 100 125 160 y 100 125 160 200 250 40 100 40 100 160 y 100 160 250 160 200 250 320 400 1/1.6 1.6/2.5 2.5/4 4/6.3 5.5/8 7/10 9/13 12/18 17/25 23/32 30/40 37/50 48/65 63/80 80/100 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 12 12 12 12 12 12 12 12 10 10 10 6.9 6.9 6.9 12 12 12 12 12 12 12 12 10 10 10 6.9 6.9 6.9 6.9 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 12 12 10 10 10 6.9 6.9 12 12 10 10 10 6.9 6.9 6.9 6.9 6.9 12 12 12 12 12 12 12 12 10 10 10 6.9 6.9 6.9 6.9 6.9 12 12 10 10 10 6.9 6.9 6.9 6.9 6.9 6.9 12 12 12 12 12 12 12 12 10 10 10 6.9 6.9 6.9 6.9 6.9 12 12 10 10 10 6.9 6.9 6.9 6.9 6.9 6.9 6.9 T T T T T T T T T 12 12 12 10 T T T T T T T T T 12 12 12 10 10 10 T T T T T T T T T 12 12 12 10 10 10 T T T T T T T T T 12 12 12 10 10 10 12 12 12 12 12 12 12 12 10 10 10 6.9 6.9 6.9 6.9 6.9 12 12 10 10 10 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 T T T T T T T T T 12 12 12 10 10 10 8 8 12 12 10 10 10 6.9 6.9 12 12 10 10 10 6.9 6.9 95/150 132/220 25/50 100 Micrologic 25/50 2.2 M or 6.2 E-M 100 150 Micrologic y 100 2.2 M or 6.2 E-M 150 220 T T T T T T T 13 13 11 11 11 630 T T T T T T T 13 13 11 11 11 4.8 T T T T T T T 13 13 11 11 11 4.8 4.8 4.8 T T T T T T T 13 13 11 11 11 4.8 4.8 4.8 T T T T T T T 13 13 11 11 11 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 T Total discrimination, up to the breaking capacity of the downstream circuit breaker. 4 Discrimination limit = 4 kA. 4.8 4.8 4.8 4.8 4.8 4.8 4.8 No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 22 12 12 10 10 12 12 10 10 6.9 6.9 8 8 12 12 10 10 10 6.9 6.9 6.9 Protection discrimination 690 V Additional characteristics Upstream: Compact NS630b-1600N/H Downstream: TeSys GV2, GV3, TeSys U, Compact NSX100-630 Upstream NS630b-1600N (30 kA) / H (40 kA) NS630b-1600N (30 kA) / H (40 kA) NS630b-1600N (30 kA) / H (40 kA) Trip unit Micrologic 2.0 Micrologic 5.0 - 6.0 - 7.0 Inst OFF Downstream Rating (A) 630 Setting Ir Micrologic 5.0 - 6.0 - 7.0 Inst 15 In 800 1000 1250 1600 630 800 1000 1250 1600 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600 Discrimination limit (kA) GV2 L03 - L06 T T T T T T T T T T T T T T T T T T T T T GV2 L07 - L32 + LA9 LB920 T T T T T T T T T T T T T T T T T T T T T LUB12 + LA9 LB20 T T T T T T T T T T T T T T T T T T T T T LUB32 + LA9 LB20 T T T T T T T T T T T T T T T T T T T T T LUB12 + LUA LB1 T T T T T T T T T T T T T T T T T T T T T LUB32 + LUA LB1 T T T T T T T T T T T T T T T T T T T T T GV3 32-65 T T T T T T T T T T T T T T T T T T T T T NSX100 L/R/HB1/HB2 MA < 100 y 100 T T T T T T T T T T T T T T T T T T T T T NSX160 L MA < 150 y 150 T T T T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 MA < 220 y 220 T T T T T T T T T T T T T T T T T T T T T NSX100 y 100 L/R/HB1/HB2 TM-D T T T T T T T T T T T T T T T T T T T T T NSX160 L TM-D y 160 T T T T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 TM-D y 125 T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 200 T T T T T T T T T T T T T T T T T T NSX100 L/R/HB1/HB2 Micrologic 250 40 T T T T T T T T T T T T T T T T T T T T T 100 T T T T T T T T T T T T T T T T T T T T T NSX160 L Micrologic 40 T T T T T T T T T T T T T T T T T T T T T 100 T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T y 100 2.5 4 T T T T T T T T T T T T T T T T T T T 160 2.5 4 T T T T T T T T T T T T T T T T T T T 4 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 Micrologic 250 NSX400 320 S/L/R/HB1/HB2 1.3 M NSX400 S/L/R/HB1/HB2 Micrologic 160 4 T T T T T T T T T T T T T T T T T 200 4 T T T T T T T T T T T T T T T T T 250 4 T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2.5 NSX630 500 S/L/R/HB1/HB2 1.3 M NSX630 S/L/R/HB1/HB2 Micrologic 250 T 6.3 T T T T T T T T T T T T T 320 6.3 T T T T T T T T T T T T T T 400 6.3 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 630 4 T T T Total discrimination, up to the breaking capacity of the downstream circuit breaker. 4 Discrimination limit = 4 kA. T No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 23 Protection discrimination 690 V Additional characteristics Upstream: Compact NS1600b-3200N Downstream: TeSys GV2, GV3, TeSys U, Compact NSX100-630, Compact NS630b-3200 Upstream NS1600-3200N (65 kA) NS1600-3200N (65 kA) NS1600-3200N (65 kA) Trip unit Micrologic 2.0 Micrologic 5.0 - 6.0 - 7.0 Inst 15 In Micrologic 5.0 - 6.0 - 7.0 Inst OFF Downstream Rating (A) 1600 2000 2500 3200 1600 2000 2500 3200 1600 2000 2500 3200 GV2 L03 - L06 T T T T T T T T T T T T GV2 L07 - L32 + LA9 LB920 T T T T T T T T T T T T LUB12 + LA9 LB20 T T T T T T T T T T T T LUB32 + LA9 LB20 T T T T T T T T T T T T LUB12 + LUA LB1 T T T T T T T T T T T T LUB32 + LUA LB1 T T T T T T T T T T T T GV3 32-65 T T T T T T T T T T T T Discrimination limit (kA) Compact NSX L/R/HB1/HB2 TM-D / MA NSX100 T T T T T T T T T T T T NSX250 T T T T T T T T T T T T Compact NSX L TM-D / MA NSX160 T T T T T T T T T T T T Compact NSX L/R/HB1/HB2 Micrologic NSX100 T T T T T T T T T T T T NSX250 T T T T T T T T T T T T Compact NSX L Micrologic NSX160 T T T T T T T T T T T T Compact NSX L/R/HB1/HB2 NSX400 T T T T T T T T T T T T NSX630 T T T T T T T T T T T T NS630b 16 20 25 T 24 T T T T T T T NS800 16 20 25 T 24 T T T T T T T NS1000 16 20 25 T 24 T T T T T T T 20 25 T T T T T T T 25 T T T T T Compact NS N NS1250 NS1600 Compact NS H NS630b 16 20 25 32 24 30 37.5 T T T T T NS800 16 20 25 32 24 30 37.5 T T T T T NS1000 16 20 25 32 24 30 37.5 T T T T T 20 25 32 30 37.5 T T T T NS1600 25 32 37.5 T T T NS1600b 25 32 37.5 T 60 60 NS1250 Compact NS N NS2000 T 32 60 NS2500 NS3200 Compact NS LB NS630b LB T T T T T T T T T T T T NS800LB T T T T T T T T T T T T T Total discrimination, up to the breaking capacity of the downstream circuit breaker. 4 Discrimination limit = 4 kA. No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 24 Protection discrimination 690 V Additional characteristics Upstream: NS630b-800LB Downstream: TeSys GV2, GV3, TeSys U, Compact NSX100-630, Compact NS630b-800 Upstream NS630b-800LB (75 kA) NS630b-800LB (75 kA) NS630b-800LB (75 kA) Trip unit Micrologic 2.0 Micrologic 5.0 - 6.0 - 7.0 Inst 15 In Micrologic 5.0 - 6.0 - 7.0 Inst OFF Downstream Discrimination limit (kA) GV2 L03 - L06 GV2 L07 - L32 + LA9 LB920 LUB12 + LA9 LB20 LUB32 + LA9 LB20 LUB12 + LUA LB1 LUB32 + LUA LB1 NSX100 L/R/HB1/HB2 MA NSX160 L MA NSX250 L/R/HB1/HB2 MA NSX100 L TM-D NSX100 R/HB1/HB2 TM-D NSX160 L TM-D NSX100 R/HB1/HB2 TM-D NSX250 L TM-D NSX100 L Micrologic NSX100 R/HB1/HB2 Micrologic NSX160 L Micrologic NSX250 L/R/HB1/HB2 Micrologic NSX400 S/L Micrologic NSX630 S/L Micrologic NS630b N/H Micrologic NS800 N/H Micrologic NS630b LB Micrologic NS800 LB Micrologic Rating (A) 630 Setting Ir 250 400 630 630 800 250 400 630 630 800 250 400 630 630 800 T T T T T T 15 10 10 15 15 10 10 10 T T T T T T 15 10 10 15 15 10 10 10 10 10 15 15 15 15 10 10 4 4 4 4 4 4 T T T T T T 15 10 10 15 15 10 10 10 10 10 15 15 15 15 10 10 10 10 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 T T T T T T 30 30 10 T 30 T 30 10 10 10 T T 30 30 T T 15 15 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 T T T T T T 30 30 10 T 30 T 30 10 10 10 T T 30 30 T T 15 15 8 8 8 8 8 8 8 8 8 T T T T T T 15 10 10 15 15 10 10 10 T T T T T T 15 10 10 15 15 10 10 10 10 10 15 15 15 15 10 10 10 10 6.3 6.3 6.3 6.3 T T T T T T 15 10 10 15 15 10 10 10 10 10 15 15 15 15 10 10 10 10 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 T T T T T T 30 30 10 T 30 T 30 10 10 10 T T 30 30 T T 15 15 8 8 8 8 8 8 8 8 T T T T T T 30 30 10 T 30 T 30 10 10 10 T T 30 30 T T 15 15 8 8 8 8 8 8 8 8 8 T T T T T T 15 10 10 15 15 10 10 10 T T T T T T 15 10 10 15 15 10 10 10 10 10 15 15 15 15 10 10 10 10 6.3 6.3 6.3 6.3 T T T T T T 15 10 10 15 15 10 10 10 10 10 15 15 15 15 10 10 10 10 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 T T T T T T 30 30 10 T 30 T 30 10 10 10 T T 30 30 T T 15 15 8 8 8 8 8 8 8 8 T T T T T T 30 30 10 T 30 T 30 10 10 10 T T 30 30 T T 15 15 8 8 8 8 8 8 8 8 8 6.3 6.3 6.3 6.3 6.3 6.3 8 8 8 8 6.3 6.3 6.3 8 8 8 8 8 8 8 6.3 6.3 6.3 8 8 8 8 8 8 8 6.3 6.3 8 8 8 8 8 6.3 6.3 8 8 8 8 8 6.3 6.3 8 8 8 8 8 6.3 6.3 6.3 6.3 6.3 6.3 8 8 8 8 6.3 6.3 6.3 8 8 8 8 8 8 8 6.3 6.3 6.3 8 8 8 8 8 8 8 6.3 6.3 6.3 6.3 8 8 8 6.3 6.3 8 8 8 8 8 6.3 6.3 8 8 8 8 8 y 100 y 150 y 220 y 100 y 100 y 160 y 160 y 160 200 250 40 100 40 100 40-100 160 y 160 250 160 200 250 320 400 250 320 400 500 630 250 320 400 500 630 320 400 500 u 630 250 320 400 500 630 320 400 500 u 630 15 15 15 15 2.5 2.5 2.5 2.5 800 4 4 4 630 15 15 15 15 10 10 10 6.3 T Total discrimination, up to the breaking capacity of the downstream circuit breaker. 4 Discrimination limit = 4 kA. 800 6.3 6.3 6.3 630 15 15 15 15 10 10 10 6.3 800 6.3 6.3 6.3 No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 25 Protection discrimination 690 V Additional characteristics Upstream: Masterpact NT06-16H1/H2 Downstream: TeSys GV2, GV3, TeSys U, Compact NSX100-630 Upstream Masterpact NT06-16H1/2 (42 kA) Masterpact NT06-16H1/2 (42 kA) Masterpact NT06-16H1/2 (42 kA) Trip unit Micrologic 2.0 Micrologic 5.0 - 6.0 - 7.0 Inst OFF Downstream Rating (A) 630 Setting Ir Micrologic 5.0 - 6.0 - 7.0 Inst 15 In 800 1000 1250 1600 630 800 1000 1250 1600 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600 Discrimination limit (kA) GV2 L03 - L06 T T T T T T T T T T T T T T T T T T T T T GV2 L07 - L32 + LA9 LB920 T T T T T T T T T T T T T T T T T T T T T LUB12 + LA9 LB20 T T T T T T T T T T T T T T T T T T T T T LUB32 + LA9 LB20 T T T T T T T T T T T T T T T T T T T T T LUB12 + LUA LB1 T T T T T T T T T T T T T T T T T T T T T LUB32 + LUA LB1 T T T T T T T T T T T T T T T T T T T T T GV3 32-65 T T T T T T T T T T T T T T T T T T T T T NSX100 L/R/HB1/HB2 MA y 100 T T T T T T T T T T T T T T T T T T T T T NSX160 L MA y 150 T T T T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 MA y 220 T T T T T T T T T T T T T T T T T T T T T NSX100 L/R/HB1/HB2 TM-D T T T T T T T T T T T T T T T T T T T T T NSX160 L TM-D T T T T T T T T T T T T T T T T T T T T T y 125 T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 TM-D 200 T T T T T T T T T T T T T T T T T T NSX100 L/R/HB1/HB2 Micrologic 250 40 T T T T T T T T T T T T T T T T T T T T T 100 T T T T T T T T T T T T T T T T T T T T T NSX160 L Micrologic 40 T T T T T T T T T T T T T T T T T T T T T 100 T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T y 100 2.5 4 T T T T T T T T T T T T T T T T T T T 160 2.5 4 T T T T T T T T T T T T T T T T T T T 4 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 Micrologic 250 NSX400 320 S/L/R/HB1/HB2 1.3 M NSX400 S/L/R/HB1/HB2 Micrologic 160 4 T T T T T T T T T T T T T T T T T 200 4 T T T T T T T T T T T T T T T T T 250 4 T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 2.5 NSX630 500 S/L/R/HB1/HB2 1.3 M NSX630 S/L/R/HB1/HB2 Micrologic 250 T 6.3 T T T T T T T T T T T T T 320 6.3 T T T T T T T T T T T T T T 400 6.3 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 500 630 4 T T Total discrimination, up to the breaking capacity of the downstream circuit breaker. 4 Discrimination limit = 4 kA. No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 26 T T Protection discrimination 690 V Additional characteristics Upstream: Masterpact NW08-20N1/H1/H2/L1 Downstream: TeSys GV2, GV3, TeSys U, Compact NSX100-630 Upstream Masterpact NW08-20N1 (42 kA) / H1 (65 kA) / H2 (85 kA) / L1 (100 kA) Masterpact NW08-20N1 (42 kA) / H1 (65 kA) / H2 (85 kA) / L1 (100 kA) Masterpact NW08-20N1 (42 kA) / H1 (65 kA) / H2 (85 kA) / L1 (100 kA) Trip unit Micrologic 2.0 Micrologic 5.0 - 6.0 - 7.0 Inst 15 In Micrologic 5.0 - 6.0 - 7.0 Inst OFF Downstream Rating (A) 800 1000 1250 1600 2000 800 1000 1250 1600 2000 800 1000 1250 1600 2000 Setting Ir 320 630 800 1000 1250 1600 2000 320 630 800 1000 1250 1600 2000 320 630 800 1000 1250 1600 2000 Discrimination limit (kA) GV2 L03 - L06 T T T T T T T T T T T T T T T T T T T T T GV2 L07 - L32 + LA9 LB920 T T T T T T T T T T T T T T T T T T T T T LUB12 + LA9 LB20 T T T T T T T T T T T T T T T T T T T T T LUB32 + LA9 LB20 T T T T T T T T T T T T T T T T T T T T T LUB12 + LUA LB1 T T T T T T T T T T T T T T T T T T T T T LUB32 + LUA LB1 T T T T T T T T T T T T T T T T T T T T T GV3 32-65 T T T T T T T T T T T T T T T T T T T T T NSX100 L/R/HB1/HB2 y 100 MA < 100 T T T T T T T T T T T T T T T T T T T T T NSX160 L MA < 150 y 150 T T T T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 y 220 MA < 220 T T T T T T T T T T T T T T T T T T T T T NSX100 L/R/HB1/HB2 TM-D T T T T T T T T T T T T T T T T T T T T T NSX160 L TM-D T T T T T T T T T T T T T T T T T T T T T y 125 T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T 200 3.2 T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 TM-D T T T T T T T T T T T T T T T T T T NSX100 L/R/HB1/HB2 Micrologic 250 40 T T T T T T T T T T T T T T T T T T T T T 100 T T T T T T T T T T T T T T T T T T T T T NSX160 L Micrologic 40 T T T T T T T T T T T T T T T T T T T T T 100 T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T y 100 T T T T T T T T T T T T T T T T T T T T T 160 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 Micrologic 250 NSX400 320 S/L/R/HB1/HB2 1.3 M NSX400 S/L/R/HB1/HB2 Micrologic 160 3.2 T T T T T T T T T T T T T T T T T T T T 200 3.2 T T T T T T T T T T T T T T T T T T T T 250 3.2 T T T T T T T T T T T T T T T T T T T T 320 T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T NSX630 500 S/L/R/HB1/HB2 1.3 M NSX630 S/L/R/HB1/HB2 Micrologic 250 3.2 6.3 T T T T T T T T T T T T T T T T T 320 6.3 T T T T T T T T T T T T T T T T T 400 6.3 T T T T T T T T T T T T T T T T T 500 T T T T T T T T T T T T T T T T T T T T T T T T T T T 630 T T Total discrimination, up to the breaking capacity of the downstream circuit breaker. 4 Discrimination limit = 4 kA. T No discrimination. Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves. 27 Protection discrimination 690 V Additional characteristics Upstream: Masterpact NW25-40H1/H2/H3, NW40b-63H1/H2 Downstream: TeSys GV2, GV3, TeSys U, Compact NSX100-630, Compact NS630b-3200 Upstream NW25-40 H1/H2/H3 Trip unit Micrologic 2.0 Downstream NW40b-63 H1/H2 NW25-40 H1/H2/H3 NW40b-63 H1/H2 NW25-40 H1/H2/H3 Micrologic 5.0 - 6.0 - 7.0 Inst 15 In NW40b-63 H1/H2 Micrologic 5.0 - 6.0 - 7.0 Inst OFF Rating (A) 2500 3200 4000 4000 5000 6300 2500 3200 4000 4000 5000 6300 2500 3200 4000 4000 5000 6300 Discrimination limit (kA) GV2 L03 - L06 T T T T T T T T T T T T T T T T T T GV2 L07 - L32 + LA9 LB920 T T T T T T T T T T T T T T T T T T LUB12 + LA9 LB20 T T T T T T T T T T T T T T T T T T LUB32 + LA9 LB20 T T T T T T T T T T T T T T T T T T LUB12 + LUA LB1 T T T T T T T T T T T T T T T T T T LUB32 + LUA LB1 T T T T T T T T T T T T T T T T T T NSX100 L/R/HB1/HB2 MA y 100 T T T T T T T T T T T T T T T T T T NSX160 L MA y 150 T T T T T T T T T T T T T T T T T T NSX250 L/R/HB1/HB2 MA y 220 T T T T T T T T T T T T T T T T T T Compact NSX L/R/HB1/HB2 NSX100 TM-D NSX250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Compact NSX L TM-D NSX160 T T T T T T T T T T T T T T T T T T Compact NSX L/R/HB1/HB2 NSX100 Micrologic NSX250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T Compact NSX L Micrologic NSX160 T T T T T T T T T T T T T T T T T T Compact NSX S/L/R/HB1/HB2 NSX400 T T T T T T T T T T T T T T T T T T NSX630 T T T T T T T T T T T T T T T T T T Compact NS N Micrologic NS630b 25 T T T T T T T T T T T T T T T T T NS800 25 T T T T T T T T T T T T T T T T T NS1000 25 T T T T T T T T T T T T T T T T T NS1250 25 T T T T T T T T T T T T T T T T T NS1600 25 T T T 25 32 40 40 T T T NS630b T T T T T T T T T T T T T T T T T T T T T T NS800 25 32 40 40 T T T 37.5 T 37.5 T T T T T T T T T T T NS1000 25 32 40 40 T T T T T T T T T T T T NS1250 25 32 40 40 T T 37.5 T 37.5 T T T T T T T T T T T NS1600 25 32 40 40 T T 37.5 T T T T T T T T T T T NS1600b 25 32 40 40 50 63 37.5 48 60 60 T T T T T T T T NS2000 25 32 40 40 50 63 37.5 48 60 60 T T T T T T T T 32 40 40 50 63 48 60 60 T T T T T T T T 40 T 50 T 63 T T T T T T T T T 60 T T T 60 T T T T T T T T T T T T T T T T T T T T T T T T Compact NS H Micrologic Compact NS N Micrologic NS2500 NS3200 Compact NS LB Micrologic NS630b T T 40 T NS800 T T T T Total discrimination, up to the breaking capacity of the downstream circuit breaker. 4 Discrimination limit = 4 kA. No discrimination. 28 Catalogue numbers Contents NSX100/250R: complete fixed/FC device Compact NSX100/250R (200 kA 380/415 V - 45 kA 690 V) NSX100/250HB1: complete fixed/FC device Compact NSX100/250HB1 (85 kA 500 V - 75 kA 690 V) Compact NSX100/250HB1 (85 kA 500 V - 75 kA 690 V) NSX100/250HB2: complete fixed/FC device Compact NSX100/250HB2 (100 kA 500 V - 100 kA 690 V) Compact NSX100/250HB2 (100 kA 500 V - 100 kA 690 V) NSX400/630R: complete fixed/FC device Compact NSX400/630R (200 kA 380/415 V - 45 kA 690 V) NSX400/630HB1: complete fixed/FC device Compact NSX400/630HB1 (85 kA 500 V - 75 kA 690 V) NSX400/630HB2: complete fixed/FC device Compact NSX400/630HB2 (100 kA 500 V - 100 kA 690 V) Order form Compact NSX100 to NSX630 Circuit breakers and switch-disconnectors 30 30 32 32 33 34 34 35 36 36 37 37 38 38 39 39 39 29 Catalogue numbers NSX100/250R: complete fixed/FC device Compact NSX100/250R (200 kA 380/415 V - 45 kA 690 V) Compact NSX100/250R With thermal-magnetic trip unit TM-D DB112222.eps Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d TM40D LV433200 TM50D LV433202 TM63D LV433204 TM80D LV433206 TM100D LV433208 Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d TM125D LV433470 TM160D LV433472 TM200D LV433474 TM250D LV433476 With electronic trip unit Micrologic 2.2 (LSOI protection) DB112223.eps Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 40 LV433270 100 LV433272 Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 100 LV433510 160 LV433512 250 LV433514 DB112224.eps With electronic trip unit Micrologic 5.2 E (LSI protection, energy meter) OK Mode Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 40 LV433277 100 LV433279 Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 100 LV433518 160 LV433520 250 LV433522 DB112224.eps With electronic trip unit Micrologic 6.2 E (LSIG protection, energy meter) OK Mode 30 Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 40 LV433281 100 LV433283 Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 100 LV433524 160 LV433526 250 LV433528 4P 4d LV433201 LV433203 LV433205 LV433207 LV433209 4P 4d LV433471 LV433473 LV433475 LV433477 4P 3d, 4d, 3d + N/2 LV433271 LV433273 4P 3d, 4d, 3d + N/2 LV433511 LV433513 LV433515 4P 3d, 4d, 3d + N/2, OSN LV433278 LV433280 4P 3d, 4d, 3d + N/2, OSN LV433519 LV433521 LV433523 4P 3d, 4d, 3d + N/2, OSN LV433282 LV433284 4P 3d, 4d, 3d + N/2, OSN LV433525 LV433527 LV433529 Catalogue numbers NSX100/250R: complete fixed/FC device Compact NSX100/250R (200 kA 380/415 V - 45 kA 690 V) Compact NSX100/250R DB115664.eps With magnetic trip unit MA Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d MA12.5 LV433242 MA25 LV433243 MA50 LV433244 MA100 LV433245 Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d MA150 LV433500 MA220 LV433501 DB112223.eps With electronic trip unit Micrologic 2.2 M (LSOI motor protection) Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 25 LV433274 50 LV433275 100 LV433276 Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 150 LV433516 220 LV433517 DB112223.eps With electronic trip unit Micrologic 6.2 E-M (LSIG motor protection, energy meter) Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 25 LV433285 50 LV433286 100 LV433287 Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V) Rating 3P 3d 150 LV433530 220 LV433531 31 Catalogue numbers NSX100/250HB1: complete fixed/FC device Compact NSX100/250HB1 (85 kA 500 V - 75 kA 690 V) Compact NSX100/250HB1 With thermal-magnetic trip unit TM-D DB112222.eps Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d TM40D LV433210 TM50D LV433212 TM63D LV433214 TM80D LV433216 TM100D LV433218 Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d TM125D LV433478 TM160D LV433480 TM200D LV433482 TM250D LV433484 With electronic trip unit Micrologic 2.2 (LSOI protection) DB112223.eps Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 40 LV433300 100 LV433302 Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 100 LV433540 160 LV433542 250 LV433544 DB112224.eps With electronic trip unit Micrologic 5.2 E (LSI protection, energy meter) OK Mode Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 40 LV433307 100 LV433309 Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 100 LV433548 160 LV433550 250 LV433552 DB112224.eps With electronic trip unit Micrologic 6.2 E (LSIG protection, energy meter) OK Mode 32 Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 40 LV433311 100 LV433313 Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 100 LV433554 160 LV433556 250 LV433558 4P 4d LV433211 LV433213 LV433215 LV433217 LV433219 4P 4d LV433479 LV433481 LV433483 LV433485 4P 3d, 4d, 3d + N/2 LV433301 LV433303 4P 3d, 4d, 3d + N/2 LV433541 LV433543 LV433545 4P 3d, 4d, 3d + N/2,OSN LV433308 LV433310 4P 3d, 4d, 3d + N/2, OSN LV433549 LV433551 LV433553 4P 3d, 4d, 3d + N/2, OSN LV433312 LV433314 4P 3d, 4d, 3d + N/2, OSN LV433555 LV433557 LV433559 Catalogue numbers NSX100/250HB1: complete fixed/FC device Compact NSX100/250HB1 (85 kA 500 V - 75 kA 690 V) Compact NSX100/250HB1 DB115664.eps With magnetic trip unit MA Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d MA12.5 LV433248 MA25 LV433249 MA50 LV433250 MA100 LV433251 Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d MA150 LV433502 MA220 LV433503 DB112223.eps With electronic trip unit Micrologic 2.2 M (LSOI motor protection) Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 25 LV433304 50 LV433305 100 LV433306 Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 150 LV433546 220 LV433547 DB112223.eps With electronic trip unit Micrologic 6.2 E-M (LSIG motor protection, energy meter) Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 25 LV433315 50 LV433316 100 LV433317 Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V) Rating 3P 3d 150 LV433560 220 LV433561 33 Catalogue numbers NSX100/250HB2: complete fixed/FC device Compact NSX100/250HB2 (100 kA 500 V - 100 kA 690 V) Compact NSX100/250HB2 With thermal-magnetic trip unit TM-D DB112222.eps Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d TM40D LV433220 TM50D LV433222 TM63D LV433224 TM80D LV433226 TM100D LV433228 Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d TM125D LV433486 TM160D LV433488 TM200D LV433490 TM250D LV433492 With electronic trip unit Micrologic 2.2 (LSOI protection) DB112223.eps Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 40 LV433330 100 LV433332 Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 100 LV433570 160 LV433572 250 LV433574 DB112224.eps With electronic trip unit Micrologic 5.2 E (LSI protection, energy meter) OK Mode Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 40 LV433337 100 LV433339 Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 100 LV433578 160 LV433580 250 LV433582 DB112224.eps With electronic trip unit Micrologic 6.2 E (LSIG protection, energy meter) OK Mode 34 Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 40 LV433341 100 LV433343 Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 100 LV433584 160 LV433586 250 LV433588 4P 4d LV433221 LV433223 LV433225 LV433227 LV433229 4P 4d LV433487 LV433489 LV433491 LV433493 4P 3d, 4d, 3d + N/2 LV433331 LV433333 4P 3d, 4d, 3d + N/2 LV433571 LV433573 LV433575 4P 3d, 4d, 3d + N/2, OSN LV433338 LV433340 4P 3d, 4d, 3d + N/2, OSN LV433579 LV433581 LV433583 4P 3d, 4d, 3d + N/2, OSN LV433342 LV433344 4P 3d, 4d, 3d + N/2, OSN LV433585 LV433587 LV433589 Catalogue numbers NSX100/250HB2: complete fixed/FC device Compact NSX100/250HB2 (100 kA 500 V - 100 kA 690 V) Compact NSX100/250HB2 DB115664.eps With magnetic trip unit MA Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d MA12.5 LV433254 MA25 LV433255 MA50 LV433256 MA100 LV433257 Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d MA150 LV433504 MA220 LV433505 DB112223.eps With electronic trip unit Micrologic 2.2 M (LSOI motor protection) Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 25 LV433334 50 LV433335 100 LV433336 Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 150 LV433576 220 LV433577 DB112223.eps With electronic trip unit Micrologic 6.2 E-M (LSIG motor protection, energy meter) Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 25 LV433345 50 LV433346 100 LV433347 Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V) Rating 3P 3d 150 LV433590 220 LV433591 35 Catalogue numbers NSX400/630R: complete fixed/FC device Compact NSX400/630R (200 kA 380/415 V - 45 kA 690 V) Compact NSX400/630R Electronic trip unit Micrologic 2.3 (LSOI protection) DB111455.eps NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 250 A 400 A NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 630 A Electronic trip unit Micrologic 5.3 E (LSI protection, ammeter) DB111456.eps NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 400 A NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 630 A 3P 3d LV433600 LV433602 LV433700 4P 3d, 4d, 3d + N/2 LV433601 LV433603 LV433701 3P 3d LV433606 LV433704 4P 3d, 4d, 3d + N/2, 3d + OSN LV433607 LV433705 3P 3d LV433608 LV433706 4P 3d, 4d, 3d + N/2, 3d + OSN LV433609 LV433707 OK Mode Electronic trip unit Micrologic 6.3 E (LSIG protection, energy meter) DB111456.eps NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 400 A NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 630 A OK Mode Electronic trip unit Micrologic 1.3 M-A (I motor protection) DB111457.eps NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 320 A NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 500 A Electronic trip unit Micrologic 2.3 M (LSOI motor protection) DB111457.eps NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 320 A NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 500 A 3P 3d LV433604 LV433702 3P 3d LV433605 LV433703 With electronic trip unit Micrologic 6.3 E-M (LSIG motor protection, energy meter) DB111457.eps NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 320 A NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 500 A 36 3P 3d LV433610 LV433708 Catalogue numbers NSX400/630HB1: complete fixed/FC device Compact NSX400/630HB1 (85 kA 500 V - 75 kA 690 V) Compact NSX400/630HB1 Electronic trip unit Micrologic 2.3 (LSOI protection) DB111455.eps NSX400HB1 (85 kA at 500 V - 75 kA at 690 V) NSX630HB1 (85 kA at 500 V - 75 kA at 690 V) 250 A 400 A 630 A 3P 3d LV433620 LV433622 LV433720 4P 3d, 4d, 3d + N/2 LV433621 LV433623 LV433721 400 A 630 A 3P 3d LV433626 LV433724 4P 3d, 4d, 3d + N/2, 3d + OSN LV433627 LV433725 400 A 630 A 3P 3d LV433628 LV433726 4P 3d, 4d, 3d + N/2, 3d + OSN LV433629 LV433727 320 A 500 A 3P 3d LV433624 LV433722 320 A 500 A 3P 3d LV433625 LV433723 Electronic trip unit Micrologic 5.3 E (LSI protection, ammeter) DB111456.eps NSX400HB1 (85 kA at 500 V - 75 kA at 690 V) NSX630HB1 (85 kA at 500 V - 75 kA at 690 V) OK Mode Electronic trip unit Micrologic 6.3 E (LSIG protection, energy meter) DB111456.eps NSX400HB1 (85 kA at 500 V - 75 kA at 690 V) NSX630HB1 (85 kA at 500 V - 75 kA at 690 V) OK Mode DB111457.eps Electronic trip unit Micrologic 1.3 M-A (I motor protection) NSX400HB1 (85 kA at 500 V - 75 kA at 690 V) NSX630HB1 (85 kA at 500 V - 75 kA at 690 V) DB111457.eps Electronic trip unit Micrologic 2.3 M (LSOI motor protection) NSX400HB1 (85 kA at 500 V - 75 kA at 690 V) NSX630HB1 (85 kA at 500 V - 75 kA at 690 V) DB111457.eps With electronic trip unit Micrologic 6.3 E-M (LSIG motor protection, energy meter) NSX400HB1 (85 kA at 500 V - 75 kA at 690 V) NSX630HB1 (85 kA at 500 V - 75 kA at 690 V) 320 A 500 A 3P 3d LV433630 LV433728 37 Catalogue numbers NSX400/630HB2: complete fixed/FC device Compact NSX400/630HB2 (100 kA 500 V - 100 kA 690 V) Compact NSX400/630HB2 Electronic trip unit Micrologic 2.3 (LSOI protection) DB111455.eps NSX400HB2 (100 kA at 500 V - 100 kA at 690 V) NSX630HB2 (100 kA at 500 V - 100 kA at 690 V) 250 A 400 A 630 A 3P 3d LV433640 LV433642 LV433740 4P 3d, 4d, 3d + N/2 LV433641 LV433643 LV433741 400 A 630 A 3P 3d LV433646 LV433744 4P 3d, 4d, 3d + N/2, 3d + OSN LV433647 LV433745 400 A 630 A 3P 3d LV433648 LV433746 4P 3d, 4d, 3d + N/2, 3d + OSN LV433649 LV433747 320 A 500 A 3P 3d LV433644 LV433742 320 A 500 A 3P 3d LV433645 LV433743 Electronic trip unit Micrologic 5.3 E (LSI protection, ammeter) DB111456.eps NSX400HB2 (100 kA at 500 V - 100 kA at 690 V) NSX630HB2 (100 kA at 500 V - 100 kA at 690 V) OK Mode Electronic trip unit Micrologic 6.3 E (LSIG protection, energy meter) DB111456.eps NSX400HB2 (100 kA at 500 V - 100 kA at 690 V) NSX630HB2 (100 kA at 500 V - 100 kA at 690 V) OK Mode Electronic trip unit Micrologic 1.3 M-A (I motor protection) DB111457.eps NSX400HB2 (100 kA at 500 V - 100 kA at 690 V) NSX630HB2 (100 kA at 500 V - 100 kA at 690 V) Electronic trip unit Micrologic 2.3 M (LSOI motor protection) DB111457.eps NSX400HB2 (100 kA at 500 V - 100 kA at 690 V) NSX630HB2 (100 kA at 500 V - 100 kA at 690 V) With electronic trip unit Micrologic 6.3 E-M (LSIG motor protection, energy meter) DB111457.eps NSX400HB2 (100 kA at 500 V - 100 kA at 690 V) NSX630HB2 (100 kA at 500 V - 100 kA at 690 V) 38 320 A 500 A 3P 3d LV433650 LV433748 Compact NSX100 to NSX630 Order form Circuit breakers and switch-disconnectors Name of customer: ..................................................................................... Address for delivery: .................................................................................. .................................................................................................................... Requested delivery date:............................................................................ Customer order no.:.................................................................................... To indicate your choices, check the applicable square boxes or note the quantity and enter the appropriate information in the rectangles Circuit breaker or switch-disconnector NSX100/160/250 - 160A not available with R, HB1or HB2 NSX400/630 Rating A Circuit breaker B, F, N, H, S, L, R, HB1, HB2 Switch-disconnector NA Number of poles 2, 3 or 4 Number of poles 2d, 3d or 4d tripped Fixed device Front connections Plug-in/withdr. Plug-in Withdrawable Earth-leakage ME, MH, MB - not available with R, protection HB1or HB2 Vigi module Voltage not available with HB1 or HB2 V 4P option on 3P NSX Compact type Trip unit Thermal-mag. TMD rating (16 ... 250 A) (40 ….250 A) with R, HB1 and HB2 TMG rating (16 ... 63 A) - not available with R, HB1or HB2 MA rating (2.5 ... 220 A) (12.5 ….220 A) with R, HB1 and HB2 Micrologic 2.2 Micrologic 2.3 Electronic * Not available with Micrologic 2.2 G* Micrologic 2.3 AB* R, HB1 or HB2 Micrologic 2.2 AB* Micrologic 5.3 A* Micrologic 5.2 A* Micrologic 5.3 E Micrologic 5.2 E Micrologic 5.3 A-Z* Micrologic 5.2 A-Z* Micrologic 6.3 A* Micrologic 6.2 A* Micrologic 6.3 E Micrologic 6.2 E Micrologic 1.3 M Micrologic 2.2 M Micrologic 2.3 M Micrologic 6.2 E-M Micrologic 6.3 E-M SDTAM Module External neutral CT 24 V DC power supply connector ZSI wiring accessory for NS630b NW/NT External power supply module 24 V DC 24-30 V DC 48-60 V DC 100-125 V AC 110-130 V AC 200-240 V AC 380-415 V AC Battery module Connection Rear-connection kit NSX100/250 connectors NSX400/630 connectors Right-angle terminal extensions Straight extensions Edgewise extensions Spreader Short Long Mixed Snap-on 1.5v to 95v (< 160 A) Snap-on 25v to 95v (< 250 A) Snap-on 120v to 185v (< 250 A) Distribution 6 x 1.5v to 35v Aluminium 2 cables 50v to 120v 1 cable 35v to 300v 2 cables 35v to 240v NSX100/250 45° terminal extension Double-L terminal extensions NSX100/250 (one piece) (45 mm) NSX400/630 (52.5 mm) (70 mm) Cu cable lugs NSX100/250 120v 150v 185v NSX400/630 240v 300v AI cable lugs NSX100/250 150v 185v NSX400/630 240v 300v Voltage measurement For lugs NSX100/250 y 185v Input for connector For lugs NSX400/630 Terminal shields NSX100/250 Short Long NSX400/630 Short Long Long for 52.5 mm spreaders Interphase barriers Set of 6 2 insulating screens:NSX100/250 NSX400/630 70 pitch Indication and measurement Ammeter module standard I max 3P 3P 3P 3P 3P Current-transformer module Current-transformer module + TCU Insulation-monitoring module - not available with HB1 or HB2 Voltage-presence indicator - not available with HB1 or HB2 Auxiliary contact OF, SD, SDE or SDV SDE adapter (TM, MA or Micrologic 2 trip units) SDX module Remote operation Electrical operation Voltage releases Rotary handles Direct Extended Indication auxiliary Locking Toggle (1 to 3 padlocks) Rotary handle Motor mechanism Interlocking Mechanical By key (2 keylocks, 1 key) for rotary handle Motor mechanism Instantaneous MX MN Fixed time delay MN Adjust. time delay MN 4P 4P 4P Standard AC AC AC AC AC Black MCC conversion access. Black Telescopic handle for withdrawable device 1 early-break switch Removable Keylock adapter (keylock not included) Keylocks Ronis 1351B.500 Keylock adapter + keylock Ronis (special) Keylock adapter (keylock not included) Keylocks Ronis 1351B.500 Toggle operated Locking kit without locks Keylocks Ronis 1351B.500 Installation accessories 4P Low level DC DC DC DC DC V V V V V Red and yellow front CNOMO conversion access. Red and yellow front 2 early-make switches Fixed Profalux KS5 B24 D4Z NSX100/250 NSX400/630 Profalux KS5 B24 D4Z Rotary Handle Profalux KS5 B24 D4Z IP30 escutcheon for all types (toggle/rotary handle/motor mechanism) IP30 escutcheon (with access to toggle + trip unit) IP30 escutcheon for Vigi module IP40 escutcheon for all types (toggle/rotary handle/motor mechanism) IP40 escutcheon for Vigi module IP40 escutcheon for Vigi or ammeter module Toggle cover Sealing accessories DIN rail adapter NSX100/250 3P 60 mm busbar adapter Plug-in / withdrawable configuration accessories Auxiliary connections 1 automatic connector fixed part with 9 wires (for base) 1 automatic connector moving part with 9 wires (for circuit breaker) 1 support for 3 automatic connector 1 support for 2 moving parts automatic connector 9-wire manual auxiliary connector (fixed + moving) Plug-in base accessories Long insulated terminals Set of 2 2 IP4 shutters for base Chassis accessories Escutcheon collar Toggle Vigi Locking kit (keylock not included) 2 carriage switches (conn./disconnected position indication) Parts or plug-in Plug-in base FC/RC 2P 3P 4P Withdrawable kits Set of two power connections Standard Vigi Safety trip for advanced opening For 3P/4P chassis Moving part Fixed part Adapter for plug-in base (for terminal shield or interphase barriers) Communication NSX Cord L = 0.35 m NSX Cord U > 480 V AC L = 0.35 m BSCM Communicating motor mechanism 220-240V Switchboard front display module FDM121 FDM mounting accessory Modbus interface Stacking accessory ULP line termination RJ45 connectors female/female Wire length RJ45 L = 0.3 m Wire length RJ45 L=1m Wire length RJ45 L=3m NSX Cord L = 1.3 m NSX Cord L = 3 m Wire length RJ45 L = 0.6 m Wire length RJ45 L=2m Wire length RJ45 L=5m Test tool Pocket battery for Micrologic Maintenance case USB maintenance interface Power supply 110-240 V AC Spare Micrologic cord 39 35, rue Joseph Monier CS 30323 F- 92506 Rueil Malmaison Cedex France As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. RCS Nanterre 954 503 439 Capital social 896 313 776 € www.schneider-electric.com Design: Schneider Electric Photos: Schneider Electric Edition: COM-POWER-NSX up to 690 V This document has been printed on ecological paper 06-2012 © 2012 - Schneider Electric - All rights reserved. Schneider Electric Industries SAS