Compact NSX

advertisement
Low Voltage
Compact NSX
High performance
Moulded-case circuit breakers
from 100 to 630 A - up to 690 V
Catalogue
2012
2
Intelligent
outlook
Compact NSX
Next-generation circuit breakers
The Compact™ range of circuit breakers set tomorrow’s standards today
and help exacting organisations achieve more from their LV infrastructure.
An extended breaking capacity, the highest in its class, is available across
the entire Compact NSX range.
A power monitoring unit also enhances their outstanding protective
functions. For the first time, users can monitor both energy and power,
offering new performance in a remarkably compact device.
III
IV
Combine safety
and performance
The Compact NSX range is innovative - it incorporates monitoring and
communication functions, from 40 A upward, combined with impeccable protection.
Expert technology
23
A roto-active contact breaking principle provides better limitation and
endurance performance:
new patents pending confirm
the innovative character of
Compact NSX
>> Very high breaking capacity in a very small device.
>> Exceptional fault current limitation for extended system life.
Reduced installation costs
Achieve up to 30 % savings:
>> Total discrimination is ensured particulary in the case of miniature
circuit breakers for considerable savings at the time of installation.
>> Smaller devices mean more economical switchboards for a
significant impact on overall cost of installation - no need for
over-calibration.
New breaking capacities
New performance levels improve application targeting:
>> 25 kA - Standard low short-circuit level applications,
e.g., in service businesses.
>> 36-50 kA - Standard applications (industrial plants, buildings,
Breaking performance at 690 V
and hospitals).
>> 70-100 kA - High performance at controlled cost.
NSX 100 NSX 250 NSX 400
NSX 630
HB2100 kA
>> 150 kA - Marine ready, with an Ics rating meeting IACS
requirements for emergency, essential, and MCC loads.
HB1 75 kA
>> 200 kA at up to 440 V - Industry-leading breaking capacity for
high-density applications in oil and gas extraction and processing,
mining operations, metals and minerals production, and data
centres.
Breaking performance at 415 V
NSX 100 R
200 kA
L
150 kA
S
100 kA
Enhanced protection for motors
H
70 kA
The Compact NSX range meets the requirements of IEC 60947-4-1
standards for protection of motors:
N
50 kA
F
36 kA
B
25 kA
>> 100 kA from 500 to 690 V - The world’s highest rated breaking
capacity for the most demanding electrical environments, and
ideal for high-efficiency, cost-effective 690 V systems.
>> Well adapted to motor-starting solutions up to 315 kW at 400 V,
providing protection against short circuits, overloads, phase
unbalance, and phase loss.
NSX 160
NSX 250 NSX 400
NSX 630
>> Set up additional protection systems for starting and braking
with the motor running, reverse braking, jogging, or reversing in
complete safety.
>> Used in conjunction with a Schneider Electric contactor, the
Compact NSX provides Type II coordination for motor applications.
V
VI
Measure the difference
Compact NSX circuit breakers provide outstanding protection as well as an
integrated measurement unit to help you monitor power conditions and manage
energy consumption.
Integrated monitoring
A Micrologic electronic tripping device with next-generation sensors:
>> An ‘iron’ sensor for the power supply to the electronics
>> An ‘air’ sensor (Rogowski coils) for the measurement part
The originality lies in how Compact NSX measures, processes, and
displays data, either directly on screen, on the switchboard front panel,
or via a monitoring system.
-10%
Monitoring consumption
can help reduce energy
costs by as much as 10%
Accessibility of information
To keep costs under control and ensure service continuity,
relevant information must be available in real time:
>> A kilowatt-hour meter helps optimise costs and their allocation.
>> Harmonic distortion rate shows the quality of electrical supply.
>> Alarm notification secures operational control and maintenance
planning.
>> Event logs and tables, activated continuously, ensure the installed
equipment base operates correctly, so energy efficiency is
maximized.
Installation supervision
Used in conjunction with software, Compact NSX provides users with
a set of parameters and tools to make it easy to monitor installations.
ASIC
Electronics (ASIC),
independent of
measurement, manage
protection functions.
The high degree of
integration in electronics
guarantees protection
against conducted or
radiated interference
VII
VIII
Opt for service continuity
The Compact NSX range provides exceptional discrimination that minimizes the
impact of short circuits and ensures maximum service continuity.
Direct access to maintenance indicators
Discrimination
Schneider Electric leverages over 30 years of experience and
expertise in discrimination to ensure customers of maximum service
continuity:
>> The downstream circuit breaker trips as close as possible to the
fault, so that the upstream circuit breaker is not overloaded.
100%
service continuity
Total service continuity
The Compact NSX range offers innovative capabilities to ensure
maximum continuity and uptime for your facilities:
>> R, HB1, and HB2 high breaking capacity levels enable the circuit
breakers to withstand demanding fault conditions, staying reliably
in service after 3 faults. After a fault is cleared, remote control
reclosing functionality puts circuits back into operation quickly.
>> SDTAM module allows remote indication of motor overloads and
actuation of a contact switch. The SDTAM switches the contact
instead of tripping the circuit breaker. The module allows for
machine restart directly from the contact switch without having to
operate circuit breakers.
Preventive maintenance
Maintenance indicators provide information on the number
of operations, level of wear on contacts, and total load rates.
Maintenance is now preventive, avoiding faults.
IX
Added simplicity
The Compact NSX range incorporates the same principles of easy installation and
use that made its predecessor so successful, and takes these to a higher level.
65%
time savings in installation
compared with a classic
monitoring solution
The green ‘Ready’ LED
flashes to show that all
is well
Simple in design
>> Installers mount and wire Compact NSX in the same way as Compact NS, which makes
engineering for a retrofit or extension simple.
>> Design is simplified using support software that helps you with parameter settings and
planning switchboard installation.
LTS installation system
Simple to install
>> A Limited Torque Screw (LTS) system ensures proper installation of the tripping device for
added flexibility.
>> A transparent sealed flap protects access to tripping device switches and prevents settings
from being changed.
>> New electrical control adjustment also has a transparent sealable cover to prevent it from
being operated accidentally.
>> Pre-wired connectivity and plug-and-play interface modules allow for easy integration with
communication networking.
Simple to use
>> Users customize alarms for all parameters, assign them to indicator lights, choose display
priorities, and configure time delay thresholds and modes.
>> A wealth of information, including continuously-activated event logs and tables, helps
you ensure that the installed equipment base is operating correctly and that settings are
optimized.
X
Transparent
protective cover
Choose the expertise of
Schneider Electric
Whether in buildings, factories or mission-critical infrastructures, Schneider Electric
commits to helping you reduce energy costs and CO2 emissions.
We offer products, solutions, and services that integrate with all levels of the
energy value chain.
Solutions adapted to all needs
Through flexible solutions for commercial and industrial buildings, Schneider Electric commits
to help customers gradually move towards an active approach to their energy efficiency.
We help you get more return from investments and future design solutions.
up to
30%
savings in energy costs
Energy performance contracts
Schneider Electric offers innovative service to modernise technical installations.
Our objective is: to dramatically reduce energy costs, whilst improving comfort and safety,
all in an environmentally friendly way.
4 steps
> Diagnosis
> Proposals
> Implementation
> Follow-up
Energy Audit
& Measure
building,
industrial process
Fix the basics
Low consumption
devices,
Insulation material,
Power factor
correction...
Optimize through
Automation and
regulation HVAC
control,
lighting control,
variable speed drives...
Passive
Energy Efficiency
Monitor, maintain,
improve
Meters installation,
Monitoring services,
EE analysis software
Control
Improve
Active
Energy Efficiency
Environmentally responsible
Compact NSX circuit breakers are part and parcel of the Schneider Electric energy efficiency
approach. Designed for easy disassembly and recycling at end of life, Compact NSX complies
with environmental directives RoHS* and WEEE**, and with ISO 14001 standards, thanks to
non-polluting factories.
* RoHS = Restriction of Hazardous Substances
** WEEE = Waste Electrical and Electronic Equipment
XI
XII
Compact NSX100 to 630 A
up to 690 V
Contents
Introduction2
Overview of applications
Characteristics and performance of Compact NSX circuit breakers
from 100 to 630 A up to 690 V
Protection of 440 - 690 V Network
Compact NSX trip units
Functions and characteristics
Characteristics and performance of Compact NSX circuit
breakers from 100 to 630 A
Accessories and auxiliaries
Overview of Compact NSX100 to 630 fixed version
Overview of Compact NSX100 to 630 plug-in and withdrawable versions
Installation recommendations
Installation in switchboards
Safety clearances and minimum distances
Installation example
Additional characteristics
Current and energy limiting curves
How to use the discrimination table
Catalogue numbers
2
2
3
4
6
6
8
8
10
12
12
12
13
14
14
16
29
NSX100/250R: complete fixed/FC device
30
NSX100/250HB1: complete fixed/FC device
32
Compact NSX100/250R
(200 kA 380/415 V - 45 kA 690 V)
Compact NSX100/250HB1
(85 kA 500 V - 75 kA 690 V)
Compact NSX100/250HB1
(85 kA 500 V - 75 kA 690 V)
NSX100/250HB2: complete fixed/FC device
Compact NSX100/250HB2
(100 kA 500 V - 100 kA 690 V)
Compact NSX100/250HB2
(100 kA 500 V - 100 kA 690 V)
30
32
33
34
34
35
NSX400/630R: complete fixed/FC device
36
NSX400/630HB1: complete fixed/FC device
37
NSX400/630HB2: complete fixed/FC device
38
Compact NSX400/630R
(200 kA 380/415 V - 45 kA 690 V)
Compact NSX400/630HB1
(85 kA 500 V - 75 kA 690 V)
Compact NSX400/630HB2
(100 kA 500 V - 100 kA 690 V)
Order form
Compact NSX100 to NSX630
Circuit breakers and switch-disconnectors
36
37
38
39
39
39
1
Overview of applications
Introduction
Characteristics and performance
of Compact NSX circuit breakers
from 100 to 630 A up to 690 V
Applications
Protection of distribution systems
(AC 440/690 V)
DB112087.eps
G
DB112089.eps
DB413431.eps
Compact NSX devices are equipped with MA or TM thermal-magnetic trip units or
Micrologic 2 / 5 / 6 electronic trip units to provide protection against short-circuits
and overloads for:
bb distribution systems supplied by transformers
bb distribution systems supplied by engine generator sets
bb long cables in IT and TN systems.
They can be easily installed at all levels in distribution systems, from the main LV
switchboard to the subdistribution boards and enclosures.
Protection of motors (AC 440/690 V)
The Compact NSX range includes a number of versions to protect motor
applications:
bb basic short-circuit protection with MA magnetic trip units or the electronic
Micrologic 1-M version, combined with an external relay to provide thermal protection
bb protection against overloads, short-circuits and phase unbalance or loss with
Micrologic 2-M trip units
bb more complete protection against overloads and short-circuits with additional
motor-specific protection (phase unbalance, locked rotor, underload and long start)
with Micrologic 6 E-M trip units. These versions also offer communication, metering
and operating assistance.
The exceptional limiting capacity of Compact NSX circuit breakers automatically
provides type-2 coordination with the motor starter, in compliance with standard
IEC 60947-4-1.
Offer structure
The Compact NSX HB offer has some differences compared to the standard NSX
offer.
bb 100 A frame and 250 A frame, there is no 160 A frame. The 125 - 160 A trip units
are used in a 250 A frame.
bb All R, HB1, and HB2 circuit breakers are restricted for use as line-load
connection. They can not have power fed into the bottom of the circuit breaker.
They will be marked with Line and Load markings.
bb All trip units will be installed at the factory.
Type of protection
Distribution protection
TMD
Micrologic
Motor protection
MA
Compact NSX100
40-100
2.2: 40-100
5.2 E: 40-100
6.2 E: 40-100
12.5-100
2.2 M: 25, 50, 100
6.2 E-M: 25, 50, 100
Compact NSX250
125-250
2.2: 100, 160, 250
5.2 E: 100, 160, 250
6.2 E: 100, 160, 250
150, 220
2.2 M: 150, 220
6.2 E-M: 150, 220
Compact NSX400
-
2.3: 250, 400
5.3 E: 250, 400
6.3 E: 250, 400
-
1.3 M: 320
2.3 M: 320
6.3 M: 320
Compact NSX630
2
2.3: 630
5.3 E: 630
6.3 E: 630
Micrologic
1.3 M: 500
2.3 M: 500
6.3 M: 500
Protection of 440 - 690 V Network
DB413275.eps
Compact NSX HB circuit breaker is designed
specifically for the needs of systems operating
at 440 to 690 V.
Compact
NSX250 HB2
Ui 800 V
Uimp 8 kV
Ue (V)
Icu (kA) Ics
500
525
660/690
~
~
~
100
100
100
100
100
100
50/60Hz
cat A
IEC / EN 60947-2
HIC (kA)
NEMA AB1
480V
100
600V
100
1
2
3
4
5
6
7
8
9
10
440-690 V applications
There are three new breaking capacities: R, HB1, and HB2.
Markets
bb Marine.
bb Oil and gas.
bb Data centers.
bb Other markets pursuing energy efficiency (water, industrial, etc.).
Ability to service high power densities
bb Upgrade voltage from ~415-440 to 690 V system allows:
vv smaller cables can be used
-- reduced cost and space
-- reduced energy loss in transmission
vv motors are more efficient at 690 V.
bb Consider 690 V as an alternative MV system:
vv lower cost, smaller footprint, and improved maintenance.
Safety
bb IACS (International Association of Classification Societies) change, requires Ics
rating for emergency systems:
vv key influence on Marine systems of high Ics ratings
vv continuity of service after 3 faults.
DB413276.eps
Technology
1
Compact
NSX630 HB2
Ui 800 V
Uimp
Ue (V)
Icu(kA)
Ir 225 - 500A
500
~ 100
525
~ 100
660/690 ~ 100
Ir 501 - 630A
500
~ 100
525
~ 100
660/690 ~ 100
50/60Hz
8 kV
Ics
100
100
100
100
25
25
cat A
2
3
4
5
6
7
NEMA AB1
480V
600V
60947-2
HIC (kA)
100
100
Enhancing solutions
bb Using smaller frames for 440-690 V high performance circuits:
vv space and cost benefit
vv NSX family consistency with same NSX accessories.
bb 200 kA breaking capacity on R rating will be mainly used for:
vv high power factor applications : around 2.8 instead of 2.2
vv selectivity with Masterpact UR.
Type I & II coordination for motor applications
9
bb Type I & II coordination with Tesys contactors is available up to 690 V.
bb Coordination tables are prepared with external overload relays and protection
integrated into the Micrologic trip units.
bb See complimentary bulletin for ratings.
10
Compliance with standards
8
IEC / EN
bb Best in class technology and performance:
vv high breaking capacity
vv NSX family consistency of energy metering, alarming and diagnosis.
bb Provides alternative to fuse protection at 440 - 690 V applications.
Standardised characteristics indicated on the rating plate:
1 Type of device: frame size and breaking capacity class.
2 Ui: rated insulation voltage.
3 Uimp: rated impulse withstand voltage.
4 Ics: service breaking capacity.
5 Icu: ultimate breaking capacity for various values of the
rated operational voltage Ue.
6 Ue: operational voltage.
7 Circuit breaker-disconnector symbol.
8 Colour label indicating the breaking capacity class.
9 Reference standard.
10 Main standards with which the device complies.
Compact NSX circuit breakers and auxiliaries comply with the following:
bb international recommendations:
vv IEC 60947-1: general rules
vv IEC 60947-2: circuit breakers
vv IEC 60947-3: switch-disconnectors
vv IEC 60947-4: contactors and motor starters
vv IEC 60947-5.1 and following: control circuit devices and switching elements;
automatic control components
bb European (EN 60947-1 and EN 60947-2) and corresponding national standards:
vv France NF
vv Germany VDE
vv United Kingdom BS
vv Australia AS
vv Italy CEI
bb the specifications of the marine classification companies (Veritas, Lloyd's
Register of Shipping, Det Norske Veritas, etc.), standard NF C 79-130 and
recommendations issued by the CNOMO organisation for the protection of
machine tools.
For U.S. UL, Canadian CSA, Mexican NOM and Japanese JIS standards, please
consult us.
3
Introduction
Compact NSX trip units
With Micrologic electronic trip units, Compact NSX
stands out from the crowd. Thanks to the new
generation of sensors and its processing capability,
protection is enhanced even further. It also provides
measurements and operating information.
Thermal-magnetic or electronic trip unit?
Thermal-magnetic trip units protect against overcurrents and short-circuits
using tried and true techniques. But today, installation optimisation and
energy efficiency have become decisive factors and electronic trip units
offering more advanced protection functions combined with measurements
are better suited to these needs.
Micrologic electronic trip units combine reflex tripping and intelligent
operation. Thanks to digital electronics, trip units have become faster as
well as more accurate and reliable. Wide setting ranges make installation
upgrades easier. Designed with processing capabilities, Micrologic trip units
can provide measurement information and device operating assistance. With
this information, users can avoid or deal more effectively with disturbances
and can play a more active role in system operation. They can manage the
installation, anticipate on events and plan any necessary servicing.
Accurate measurements for complete protection
Compact NSX devices take advantage of the vast experience acquired since the
launch of Masterpact NW circuit breakers equipped with Micrologic trip units.
From 40 amperes on up to the short-circuit currents, they offer excellent
measurement accuracy. This is made possible by a new generation of current
transformers combining "iron-core" sensors for self-powered electronics and "aircore" sensors (Rogowski toroids) for measurements.
The protection functions are managed by an ASIC component that is independent
of the measurement functions. This independence ensures immunity to conducted
and radiated disturbances and a high level of reliability.
Numerous security functions
Torque-limiting screws
The screws secure the trip unit to the circuit breaker. When the correct
tightening torque is reached, the screw heads break off. Optimum tightening
avoids any risk of temperature rise. A torque wrench is no longer required.
"Ready" LED for a continuous self-test
The LED on the front of the electronic trip units indicates the result of the
self-test runs continuously on the measurement system and the tripping
release. As long as the green LED is flashing, the links between the CTs, the
processing electronics and the Mitop release are operational. The circuit
breaker is ready to protect. No need for a test kit. A minimum current of 15 to
50 A, depending on the device, is required for this indication function.
A patented dual adjustment system for protection functions.
Available on Micrologic 5 / 6, the system consists of:
bb an adjustment using dials sets the maximum value
bb an adjustment, made via the keypad or remotly, fine-tunes the setting. This
setting may not exceed the first one. It can be read directly on the Micrologic
screen, to within one ampere and a fraction of a second.
Coordinated tripping systems
Compact NSX detects faults even faster and its tripping time is reduced. It protects
the installation better and limits contact wear.
DB413407.eps
Time delay
Protection
function
100 A
L
1 - 200 s
Overload:
Slow trip inversely
proportional to
the current level
Ii
Isd
1000 A
z
Currents
Ir
S or S0
20 - 500 ms
Short time:
Impedant short-circuit,
instantaneous trip with
adjustable S or fixed
S0 time delay
1500 A
I
10 - 50 ms
Instantaneous:
Ultra-fast detection
with micro delay
for discrimination
(1) This tripping system is completely independent of the trip unit.
Because it directly actuates the mechanism, it precedes the trip unit by a few milliseconds.
4
Reflex threshold
z
E.g. NSX100R
2400 A
< 5 ms
Reflex:
Energy-based ultra-fast
detection with major current
limiting (1)
Icu
36000 A
New performance offers same level of discrimination
at 440 V as NSX range.
For 690 V see tables.
Unmatched discrimination
Discrimination
Compact NSX provides maximum continuity of service and savings through an
unmatched level of discrimination:
bb given the high accuracy of measurements, overload discrimination is ensured
even between very close ratings
bb for major faults, the fast processing of the Micrologic trip units means the
upstream device can anticipate the reaction of the downstream device. The
upstream breaker adjusts its tripping delay to provide discrimination
bb for very high faults, the energy of the arc dissipated by the short-circuit in the
downstream breaker causes reflex tripping. The current seen by the upstream
device is significantly limited. The energy is not sufficient to cause tripping, so
discrimination is maintained whatever the short-circuit current.
Understanding the names of Micrologic electronic trip units
Protection
1: I
Frame
2: NSX160/250
Measurements
A: Ammeter
I:
Instantaneous
L:
Long time
S0: Short time (1)
(fixed delay)
Short time
Ground fault
3: NSX400/630
DB112120.eps
DB112155.eps
6: LSIG
M: Motors
E: Energy
DB112156.eps
DB112094.eps
5: LSI
G:
Distribution, otherwise
G: Generator
2: LS0I
S:
Applications
Examples
Micrologic 1.3
Instantaneous only
400 or 630 A
Micrologic 2.3
LS0I
400 or 630 A
Micrologic 5.2 A
LSI
100, 160 or 250 A
Ammeter
Distribution
Micrologic 6.3 E-M
LSIG
400 or 630 A
Energy
Motor
Distribution
Distribution
(1) LS0I protection is standard on Micrologic 2. To ensure discrimination, it offers short-time protection S0 with a non-adjustable
delay and instantaneous protection.
5
Functions
and characteristics
Characteristics and
performance of Compact NSX
circuit breakers
from 100 to 630 A
PB110406_40.eps
Common characteristics
Rated voltages
Insulation voltage (V)
Ui
800
Impulse withstand voltage
(kV)
Uimp
8
Operational voltage (V)
Ue
Suitability for isolation
AC 50/60 Hz
690
IEC/EN 60947-2
yes
Utilisation category
A
Pollution degree
IEC 60664-1
3
Circuit breakers
PB110420_40.eps
Compact NSX250 R.
Breaking capacity levels
Electrical characteristics as per IEC 60947-2
Rated current (A)
Number of poles
Breaking capacity (kA rms)
In
40 °C
lcu
AC 50/60 Hz 220/240 V
380/415 V
440 V
500 V
525 V
660/690 V
lcs
AC 50/60 Hz 220/240 V
380/415 V
440 V
500 V
525 V
660/690 V
Mechanical
Electrical
440 V
Service breaking capacity (kA rms)
PB111001_44.eps
Compact NSX250 HB2.
Durability (C-O cycles)
690 V
Characteristics as per Nema AB1
Breaking capacity (kA rms)
AC 50/60 Hz 240 V
480 V
600 V
Characteristics as per UL 508
Breaking capacity (kA rms)
Compact NSX630 R.
In/2
In
In/2
In
AC 50/60 Hz 240 V
480 V
600 V
Protection and measurements
Magnetic only
Thermal magnetic
Electronic
with neutral protection (Off-0.5-1-OSN) (2)
with ground-fault protection
with zone selective interlocking (ZSI) (3)
Display / I, U, f, P, E, THD measurements / interrupted-current measurement
Options
Power Meter display on door
Operating assistance
Counters
Histories and alarms
Metering Com
Device status/control Com
Earth-leakage protection
By Vigi module (5)
By Vigirex relay
PB111013_44.eps
Short-circuit protection
Overload / short-circuit protection
Compact NSX630 HB2.
(1) There is no 160 A frame, use the 250 A frame with lower
amperage trip units.
(2) OSN: Over Sized Neutral protection for neutrals carrying
high currents (e.g. 3rd harmonics).
(3) ZSI: Zone Selective Interlocking using pilot wires.
(4) 2P circuit breaker in 3P case for B and F types, only with
thermal-magnetic trip unit.
(5) Vigi module is not available for breaking capacity levels
HB1 and HB2.
6
Installation / connections
Dimensions and weights
Dimensions (mm)
WxHxD
Fixed, front connections
Weight (kg)
Fixed, front connections
Connections
3P
4P
3P
4P
Connection terminals
Pitch
With/without spreaders
Large Cu or Al cables
Cross-section
mm²
Common characteristics
Control
Manual
Electrical
With toggle
b
With direct or extended rotary handle
b
With remote control
b
Versions
Fixed
b
Withdrawable
NSX100-250 (1)
R
HB1
Plug-in base
b
Chassis
b
NSX400
HB2
R
NSX630
HB1
HB2
Ir = 225 - 500 A
R
HB1
100-250
400
630
2 (4), 3, 4
3, 4
3, 4
HB2
Ir = 501 - 630 A
R
HB1
HB2
200
200
200
80
65
45
85
80
75
100
100
100
200
200
200
80
65
45
85
80
75
100
100
100
200
200
200
80
65
45
85
80
75
100
100
100
200
200
200
80
65
45
85
80
75
100
100
100
200
200
200
80
65
45
20000
20000
10000
10000
5000
85
80
75
100
100
100
200
200
200
80
65
45
15000
12000
6000
6000
3000
85
80
75
100
100
100
200
200
200
80
65
45
15000
8000
4000
6000
2000
85
80
75
100
100
100
200
200
200
80
16
12
85
20
19
100
25
25
200
150
50
85
75
100
100
200
150
50
85
75
100
100
200
150
50
85
75
100
100
200
150
50
85
75
100
100
-
-
-
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
105 x 161 x 86
140 x 161 x 86
2.4
2.8
105 x 161 x 86
140 x 161 x 86
6.05
7.90
140 x 255 x 110
185 x 255 x 110
6.2
8.13
35/45 mm
45/52.5 mm
45/70 mm
4 x 240
45/52.5 mm
45/70 mm
4 x 240
300
7
Accessories and auxiliaries
Functions
and characteristics
Overview of Compact NSX100 to 630
fixed version
DB413406.eps
Insulation accessories
Interphase barriers
Sealable terminal
shields
Electrical auxiliaries
Indication contact
Voltage release
SDTAM module
SDx module
Protection and measurements
Micrologic 2 trip unit
Micrologic 5 / 6 trip unit
TM-D trip unit
8
Connection
One-piece spreader
Cable connectors
Rear connectors
Terminal
extensions
Cable connectors
Communication and display
BSCM module
NSX cord
Modbus interface
FDM121
Control accessories
Direct rotary handle
Extended rotary handle
Motor mechanism
9
Accessories and auxiliaries
Functions
and characteristics
Overview of Compact NSX100 to 630
plug-in and withdrawable versions
DB115888.eps
Insulation accessories
Interphase barriers
Sealable long terminal
shields for plug-in base
Electrical accessories
Automatic withdrawable auxiliary connector
Manual auxiliary connector
Mechanical accessories
Circuit-breaker side plate
Chassis side plate
10
Connection
Cable connectors
Rear connectors
Lugs
Rear connectors
Adapter
Cable connectors
Terminal extensions
Circuit breaker
Plug-in base
Power connection
accessories
Power connections
Power connections for Vigicompact
11
Installation in switchboards
Installation
recommendations
Safety clearances and minimum distances
General rules
When installing a circuit breaker, minimum distances (safety clearances) must
be maintained between the device and panels, bars and other protection devices
installed nearby. These distances, which depend on the ultimate breaking capacity,
are defined by tests carried out in accordance with standard IEC 60947-2.
If installation conformity is not checked by type tests, it is also necessary to:
bb use insulated bars for circuit-breaker connections
bb segregate the busbars using insulating screens.
For Compact NSX100 to 630 devices, terminal shields and interphase barriers are
recommended and may be mandatory depending on the operating voltage of the
device and type of installation (fixed, withdrawable, etc.).
Power connections
The table below indicates the rules to be respected for Compact NSX100 to 630
devices to ensure insulation of live parts for the various types of connection.
bb fixed devices with front connection (FC) or rear connection (RC)
bb plug-in or withdrawable devices.
Connection accessories such as crimp lugs, bare-cable connectors, terminal
extensions (straight, right-angle, double-L and 45°) and spreaders are supplied
with interphase barriers.
Long terminal shields provide a degree of protection of IP40 (ingress) and IK07
(mechanical impact).
Compact NSX100 to 630: rules to be respected to ensure insulation of live parts
Fixed, rear
connection
Plug-in or withdrawable
operating voltage
DB115057.eps
DB115061
DB115061
Short terminal
shields
Short terminal
shields
type of conductor
Bare cables +
connectors
Possible
Possible
Possible
Recommended Recommended
Mandatory
No
Mandatory
(supplied)
Possible
(instead of ph. Recommended Recommended
barriers)
Mandatory
Possible
for cable
connectors
NSX100 to 250
Possible
for cable
connectors
NSX100 to 250
Mandatory
No
Mandatory (1)
(supplied)
Possible
for cable
connectors
NSX100 to 250 Recommended Recommended
Possible (1)
(instead of ph.
barriers)
Mandatory
Mandatory
Insulated bars
Extension terminals
Cables + crimp lugs
Bare cables +
connectors
No
No
Mandatory
(use of short
Mandatory
terminal shield
possible)
No
No
Mandatory
Mandatory
Mandatory
Mandatory
No
No
Mandatory
Mandatory
Mandatory
Mandatory
(1) Long terminal shields, mandatory if the device is fixed through the door, whatever the voltage.
12
Short terminal
shields
Through panel
Insulated bars
Extension terminals
Cables + crimp lugs
u 500 V
Long terminal
shields
DB115060
With:
< 500 V
Interphase
barriers
DB115059
Possible, recommended or mandatory accessories: No insulating
accessory
DB115056.eps
DB115055.eps
On backplate
DB115058.eps
Fixed, front connection
DB115061
Type of connection
Installation example
Safety clearance
Minimum distance between circuit
breaker and front or rear panels
DB115697.eps
DB115046.eps
Minimum distance between two
adjacent circuit breakers
A1
Bare or painted sheetmetal
F
Front
panel
B=0
F
Note: if F < 8 mm: an insulating screen or long
terminal shield is mandatory.
D2
D1
D1
DB413246.eps
D1
DB413245.eps
DB413244.eps
DB413243.eps
Minimum distance between circuit breaker and top, bottom or side panels
D1
C1
Devices without accessories.
Devices with interphase barriers or long or short terminal shields.
Minimum safety clearances for Compact NSX100 to 630
Operating voltage
Clearance (mm)
Between Between device and sheetmetal
devices Painted sheet metal Bare sheet metal
DB115698.eps
Spacing y 60 mm
Spacing > 60 mm
Bars
F1
F1
U y 440 V
for devices equipped with:
b no accessories
b short terminal shields
b interphase barriers
b long terminal shields
440 V < U y 600 V
for devices equipped with:
b short terminal shields
b interphase barriers (1)
b long terminal shields (2)
U > 600 V
for devices equipped with:
b short terminal shields
b long terminal shields
(1) Only for NSX100 to 250.
(2) For all cases.
A1
C1
D1
D2
C1
D1
D2
0
0
0
0
0
0
0
0
30
30
0
0
30
30
0
0
5
5
5
0
40
40
0
0
40
40
0
0
0
0
0
0
0
0
30
0
0
30
0
0
10
20
10
40
10
10
40
10
10
0
0
10
10
50
30
50
30
20
20
100
40
100
40
Clearances with respect to live bare busbars
Minimum clearances for Compact NSX100 to 630
Operating voltage
Clearances with respect to live bare busbars
spacing y 60 mm
spacing > 60 mm
F2
F2
Bars
Live busbars.
F1
F2
F1
F2
350
350
80
80
350
350
120
120
prohibited: insulating screen required between device and
busbars
These clearances can be reduced for special installations as long as the configuration is checked
by tests.
U < 440 V
440 V y U y 600 V
U > 600 V
13
Additional characteristics
Current and energy limiting
curves
The limiting capacity of a circuit breaker is its aptitude
to let through a current, during a short-circuit, that is
less than the prospective short-circuit current.
Ics = 100 % Icu
DB115719.eps
(Isc)
Prospective
Isc peak
Prospective
current
Prospective
Isc
Limited Isc
peak
Actual
current
Limited
Isc
(t)
The exceptional limiting capacity of the Compact NSX range is
due to the rotating double-break technique (very rapid natural
repulsion of contacts and the appearance of two arc voltages
in-series with a very steep wave front).
The exceptional limiting capacity of the Compact NSX range greatly reduces the
forces created by fault currents in devices.
The result is a major increase in breaking performance.
In particular, the service breaking capacity Ics is equal to 100 % of Icu.
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
the following steps:
bb break three times consecutively a fault current equal to 100 % of Icu
bb check that the device continues to function normally, that is:
vv it conducts the rated current without abnormal temperature rise
vv protection functions perform within the limits specified by the standard
vv suitability for isolation is not impaired.
Longer service life of electrical installations
Current-limiting circuit breakers greatly reduce the negative effects of short-circuits
on installations.
Thermal effects
Less temperature rise in conductors, therefore longer service life for cables.
Mechanical effects
Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars
being deformed or broken.
Electromagnetic effects
Fewer disturbances for measuring devices located near electrical circuits.
Economy by means of cascading
Cascading is a technique directly derived from current limiting. Circuit breakers with
breaking capacities less than the prospective short-circuit current may be installed
downstream of a limiting circuit breaker. The breaking capacity is reinforced by the
limiting capacity of the upstream device. It follows that substantial savings can be
made on downstream equipment and enclosures.
Current and energy limiting curves
The limiting capacity of a circuit breaker is expressed by two curves which are a
function of the prospective short-circuit current (the current which would flow if no
protection devices were installed):
bb the actual peak current (limited current)
bb thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 Ω.
Example
What is the real value of a 150 kA rms prospective short-circuit (i.e. 330 kA peak)
limited by an NSX250L upstream ?
The answer is 30 kA peak.
Maximum permissible cable stresses
The table below indicates the maximum permissible thermal stresses for cables
depending on their insulation, conductor (Cu or Al) and their cross-sectional area
(CSA). CSA values are given in mm² and thermal stresses in A2s.
CSA
PVC
Cu
1.5 mm²
2.97x104
2.5 mm²
8.26x104
4 mm²
2.12x105
6 mm²
4.76x105
4.10x10
1.39x10
2.92x10
6.56x10
Al
PRC
Cu
5.41x105
4
5
5
5
Al
CSA
PVC
PRC
10 mm²
1.32x106
1.82x106
7.52x105
16 mm²
25 mm²
35 mm²
50 mm²
Cu
3.4x106
8.26x106
1.62x107
3.31x107
Al
1.39x106
3.38x106
6.64x106
1.35x107
Cu
4.69x10
6
1.39x10
7
2.23x10
7
4.56x107
Al
1.93x10
6
4.70x10
6
9.23x10
6
1.88x107
Example
Is a Cu/PVC cable with a CSA of 10 mm² adequately protected by an NSX160F?
The table above indicates that the permissible stress is 1.32x106 A2s.
All short-circuit currents at the point where an NSX160F (Icu = 35 kA) is installed
are limited with a thermal stress less than 6x105 A2s.
Cable protection is therefore ensured up to the limit of the breaking capacity of the
circuit breaker.
14
Current-limiting curves
Voltage 400/440 V AC
Voltage 660/690 V AC
Limited short-circuit current (k peak)
Limited short-circuit current (k peak)
300
DB413433.eps
DB413432.eps
300
200
200
146
146
100
80
70
60
50
100
80
70
60
50
40
k peak
30
F
20
F
B
10
8
7
6
5
4
2
3
4
6
10
20
N
N
30 40
H
H
60
65
kA rms
S
S
L
L
100
R
NSX630
NSX400
R
NSX250
NSX100
NSX160
HB1 HB2 NSX630
40
k peak
30
H
20
L
F, N
10
8
7
6
5
4
2
200 300
F
3
4
6
S
L
S
R
NSX400
R
HB1 HB2 NSX250
NSX100
NSX160
N, H
10
20
30 40
kA rms
60
65
100
200 300
Energy-limiting curves
Voltage 400/440 V AC
Voltage 660/690 V AC
Limited energy
9
5
3
2
1.41
8
10
2
9
5
3
2
1.41
8
10
5
5
3
2
3
2
10
As
10
DB413435.eps
DB413434.eps
10
Limited energy
7
10
5
F
3
2
10
6
F
B
5
N
N
H
H
S
S
L
L
R
R
NSX630
NSX400
NSX250
NSX100
NSX160
3
2
10
5
H
3
2
10
L
S
F, N
6
F
5
N, H
S
L
R
HB1 HB2
R
HB1 HB2 NSX250
NSX630
NSX400
NSX100
NSX160
3
2
5
10
5
3
2
2
As
7
5
5
2
3
4
6
10
20
30 40 50 70 100 150 200 300
kA rms
3
2
2
3
4
6
10
20
30 40 50 70 100 150 200 300
kA rms
15
Additional characteristics
How to use the discrimination
table
Combinaisons providing full discrimination are indicated by the symbol T.
In that case the discrimination is ensured up to downstream breaker breaking
capacity.
If discrimination is partial, the table indicates the maximum fault current value (kA)
until which discrimination is ensured.
Requisite conditions
The value indicated in the tables are valid for operational rated voltage 550 V, 660
V, 690 V 50-60 Hz.
Following ratios shall be respected in order to avoid overlapping of tripping curves.
Upstream
Micrologic
TM
Downstream
Ir up / Ir down
Im up / Im down
TM
u 1.6
u 1.5
Micrologic
u 1.3
u 1.5
MA + OL relay
u3
u2
TM
u 1.6
u2
Micrologic
u 1.6
u 1.5
MA + OL relay
u3
u2
DB413430.eps
Additional settings conditions according to trip unit type
CB1
bb Short time pick up (Isd)
Tables indicate selectivity limits assuming Isd = 10 x Ir. In many cases when
discrimination is total lower thresholds could be used if ratio condition between
two magnetic protections is fulfilled. When selectivity limit indicated in the tables is
equal to 10 x Ir, the selectivity limit is upstream circuit breaker short time pick up
(Isd).
bb Instantaneous pick up (Ii)
Tables indicate selectivity limits assuming instantaneous pick up is set at the
maximum value and when it is inhibited (Type B circuit breaker only). With
Masterpact, when selectivity limit indicated in the tables is equal to 15 x In, the
selectivity limit is upstream circuit breaker instantaneous pick up (Ii). When
upstream circuit breaker is A type, and downstream circuit breaker is B type
upstream instantaneous setting can be set lower than 15 In as far as it stay higher
than downstream circuit breaker reflex tripping limit. When a Micrologic 5.x is used
downstream a Micrologic 2.x Tsd shall be set at 0 and Ii shall be set at Isd.
bb Short time delay (Tsd)
When upstream and downstream breaker are equipped with Micrologic 5.x, 6.x,
7.x: the minimum non tripping-time of the upstream device must be greater than
the maximum tripping time of the downstream device.
Tsd CB1 > Tsd CB2 (One Step)
CB2
16
bb I²t Off / On
Tables indicate selectivity limits assuming I²t Function is Off. If I²t function is ON
user shall check curves.
Protection discrimination 690 V
Additional characteristics
Upstream: Compact NSX100-250 TM-D
Downstream: TeSys GV2, GV3, TeSys U
Upstream
NSX100L
NSX100L/R/HB1/HB2
NSX160L
NSX250L/R/HB1/
HB2
Trip unit
TM-D
TM-D
TM-D
TM-D
Downstream
Icu
O/L
Rating (A)
16
25
32
40
50
63
80
100
80
100
125
160
160
200
250
Ir range
Discrimination limit (kA)
GV2 L03
100 kA
LRD 03
0.25/0.40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L04
100 kA
LRD 04
0.40/0.63
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L05
100 kA
LRD 05
0.63/1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L06
100 kA
LRD 06
1/1.6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L07 + LA9 LB920
50 kA
LRD 07
1.6/2.5
0.19 0.25 0.4
1
5
6
10
10
10
10
T
T
T
T
T
GV2 L08 + LA9 LB920
50 kA
LRD 08
2.5/4
0.19 0.25 0.4
0.5
0.5
0.5
1
1.5
1
1.5
T
T
36
T
T
GV2 L10 + LA9 LB920
50 kA
LRD 10
4/6.3
0.25 0.4
0.5
0.5
0.5
0.63 0.8
0.63
0.8
1.25
1.6
1.6
T
T
GV2 L14 + LA9 LB920
50 kA
LRD 14
7/10
0.4
0.5
0.5
0.5
0.63 0.8
0.63
0.8
1.25
1.6
1.6
T
T
GV2 L16 + LA9 LB920
50 kA
LRD 16
9/13
0.5
0.5
0.63 0.8
0.63
0.8
1.25
1.6
1.6
T
T
GV2 L20 + LA9 LB920
50 kA
LRD 21
12/18
0.63 0.8
0.63
0.8
1.25
1.6
1.6
T
T
GV2 L22 + LA9 LB920
50 kA
LRD 22
17/25
0.63 0.8
0.63
0.8
1.25
1.6
1.6
T
T
GV2 L32 + LA9 LB920
50 kA
LRD 32
23/32
0.8
0.8
1.25
1.6
1.6
T
T
GV3 P13
6 kA
Integrated
9/13
GV3 P18
6 kA
Integrated
12/18
GV3 P25
6 kA
Integrated
17/25
GV3 P32
6 kA
Integrated
23/32
0.8
GV3 P40
6 kA
Integrated
30/40
GV3 P50
6 kA
Integrated
37/50
GV3 P65
6 kA
Integrated
48/65
GV3 L25
6 kA
LRD 22
20/25
0.63 0.8
GV3 L32
6 kA
LRD 32
23/32
0.8
GV3 L40
6 kA
LRD 340
30/40
GV3 L50
6 kA
LRD 350
37/50
GV3 L65
6 kA
LRD 365
48/65
LUB12 + LA9 LB20
35 kA
LUC*X6
0.15…0.6
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*1X
0.35…1.4
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*05
1.25…5
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*12
3…12
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*X6
0.15…0.6
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*1X
0.35…1.4
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*05
1.25…5
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*12
3…12
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*18
4.5…18
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*32
8…32
0.8
1
1.6
1.6
T
T
LUC*X6
0.15…0.6
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*1X
0.35…1.4
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*05
1.25…5
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*12
3…12
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*X6
0.15…0.6
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*1X
0.35…1.4
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*05
1.25…5
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*12
3…12
0.5
0.5
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*18
4.5…18
0.5
0.63 0.8
0.7
0.8
1
1.6
1.6
T
T
LUC*32
8…32
0.8
1
1.6
1.6
T
T
LUB32 + LA9 LB20
LUB12 + LUA LB1
LUB32 + LUA LB1
35 kA
70 kA
70 kA
0.5
0.5
0.63 0.8
0.63
0.8
1
1.25
1.25
T
T
0.5
0.63 0.8
0.63
0.8
1
1.25
1.25
T
T
0.63 0.8
0.63
0.8
1
1.25
1.25
T
T
0.8
1
1.25
1.25
T
T
1.25
1.25
T
T
T
T
T
0.63
0.8
1
1.25
1.25
T
T
0.8
1
1.25
1.25
T
T
1
1.25
1.25
T
T
T
T
T
0.8
T
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
4
Discrimination limit = 4 kA.
0.8
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
17
Protection discrimination 690 V
Additional characteristics
Upstream: Compact NSX100-250 Micrologic
Downstream: TeSys GV2, GV3, TeSys U
Upstream
NSX100L/R/HB1/HB2
NSX160L
NSX250L/R/HB1/
HB2
Trip unit
Micrologic
Micrologic
Micrologic
Downstream
Icu
O/L
Rating (A)
40
Setting Ir
16
100
25
32
40
40
160
63
80
100 80
250
100
125
160
160
200
250
Discrimination limit (kA)
GV2 L03
100 kA
LRD 03
0.25/0.40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L04
100 kA
LRD 04
0.40/0.63
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L05
100 kA
LRD 05
0.63/1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L06
100 kA
LRD 06
1/1.6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L07 + LA9 LB920
50 kA
LRD 07
1.6/2.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L08 + LA9 LB920
50 kA
LRD 08
2.5/4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L10 + LA9 LB920
50 kA
LRD 10
4/6.3
GV2 L14 + LA9 LB920
50 kA
LRD 14
7/10
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L16 + LA9 LB920
50 kA
LRD 16
9/13
T
T
T
T
T
T
T
T
T
GV2 L20 + LA9 LB920
50 kA
LRD 21
12/18
T
T
T
T
T
T
T
T
T
T
GV2 L22 + LA9 LB920
50 kA
LRD 22
17/25
GV2 L32 + LA9 LB920
50 kA
LRD 32
23/32
GV3 P13
6 kA
Integrated
9/13
GV3 P18
6 kA
Integrated
12/18
GV3 P25
6 kA
Integrated
17/25
GV3 P32
6 kA
Integrated
23/32
GV3 P40
6 kA
Integrated
30/40
GV3 P50
6 kA
Integrated
37/50
GV3 P65
6 kA
Integrated
48/65
GV3 L25
6 kA
LRD 22
20/25
GV3 L32
6 kA
LRD 32
23/32
GV3 L40
6 kA
LRD 340
30/40
GV3 L50
6 kA
LRD 350
37/50
GV3 L65
6 kA
LRD 365
48/65
LUB12 + LA9 LB20
35 kA
LUB32 + LA9 LB20
LUB12 + LUA LB1
LUB32 + LUA LB1
35 kA
70 kA
70 kA
T
0.6
1.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1.5
1.5
1.5
4
4
4
4
T
T
T
1.5
1.5
1.5
3.5
3.5
3.5
3.5
T
T
T
1.5
3
T
1.5
1.5
3
3
T
T
3
3
T
T
T
2.4
2.4
T
T
T
2.4
1.5
1.5
3
1.5
3
3
3
T
T
T
3
3
3
T
T
T
2.4
2.4
T
T
T
2.4
LUC*X6
0.15…0.6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*1X
0.35…1.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*05
1.25…5
T
T
T
LUC*12
3…12
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*X6
0.15…0.6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*1X
0.35…1.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*05
1.25…5
T
T
T
LUC*12
3…12
LUC*18
4.5…18
LUC*32
8…32
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*X6
0.15…0.6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*1X
0.35…1.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*05
1.25…5
T
T
T
LUC*12
3…12
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*X6
0.15…0.6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*1X
0.35…1.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUC*05
1.25…5
T
T
T
LUC*12
3…12
LUC*18
4.5…18
LUC*32
8…32
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
4
Discrimination limit = 4 kA.
T
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
18
3
3
T
T
T
T
T
T
T
T
T
T
T
T
Protection discrimination 690 V
Additional characteristics
Upstream: Compact NSX100-250 TM-D
Downstream: Compact NSX100-250 TM-D Micrologic - MA + LRD
Upstream
NSX100L
NSX100L/R/HB1/HB2
NSX160L
NSX250L/R/HB1/
HB2
Trip unit
TM-D
TM-D
TM-D
TM-D
Downstream
O/L
Rating (A)
16
25
32
40
50
63
80
100 80
100
125
160
160
200
250
Ir range
Discrimination limit (kA)
NSX100 L
TM-D
16
0.5
25
0.5
0.5
0.63 0.8
0.63
0.8
1.25
1.25
1.25
2
2.5
0.5
0.5
0.63 0.8
0.63
0.8
1.25
1.25
1.25
2
2.5
32
NSX100 L/R/HB1/HB2
0.63 0.8
0.63
0.8
1.25
1.25
1.25
2
2.5
40
0.5
0.63 0.8
0.63
0.8
1.25
1.25
1.25
2
2.5
50
0.63 0.8
0.63
0.8
1.25
1.25
1.25
2
2.5
63
0.8
0.8
1.25
1.25
1.25
2
2.5
1.25
1.25
1.25
2
2.5
1.25
1.25
2
2.5
80
100
NSX160 L
TM-D
y 63
1.25
1.25
1.25
2
2.5
80
1.25
1.25
1.25
2
2.5
1.25
1.25
2
2.5
1.25
2
2.5
2
2.5
100
160
NSX250 L/R/HB1/HB2
TM-D
2.5
y 100
125
160
2.5
200
NSX100 L/R/HB1/HB2
Micrologic
40
NSX160 L
Micrologic
40
0.5
0.63 0.8
0.63
0.8
1.25
100
0.5
0.63 0.8
0.63
0.8
1.25
100
1.25
1.25
2
2.5
1.25
1.25
2
2.5
1.25
1.25
2
2.5
1.25
1.25
2
2.5
1.25
2
160
NSX250 L/R/HB1/HB2
Micrologic
2.5
y 100
160
2.5
2.5
250
NSX100 L MA 2.5
LRD 06
1/1.6
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.63
0.8
1
1
1
20
20
NSX100 L MA 2.5
LRD 07
1.6/2.5
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.63
0.8
1
1
1
20
20
NSX100 L MA 6.3
LRD 08
2.5/4
0.19 0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.63
0.8
1
1
1
20
20
NSX100 L MA 6.3
LRD 10
4/6.3
0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.63
0.8
1
1
1
20
20
NSX100 L/R/HB1/HB2 MA 12.5
LRD 12
5.5/8
0.3
0.4
0.5
0.5
0.5
0.63 0.8
0.63
0.8
1
1
1
6
6
NSX100 L/R/HB1/HB2 MA 12.5
LRD 14
7/10
0.4
0.5
0.5
0.5
0.63 0.8
0.63
0.8
1
1
1
6
6
0.5
0.5
0.5
0.63 0.8
0.63
0.8
1
1
1
6
6
0.5
0.63 0.8
0.63
0.8
1
1
1
5
5
0.63
0.8
1
1
1
5
5
NSX100 L/R/HB1/HB2 MA 12.5
LRD 16
9/13
NSX100 L/R/HB1/HB2 MA 25
LRD 21
12/18
NSX100 L/R/HB1/HB2 MA 25
LRD 22
17/25
0.63 0.8
0.8
NSX100 L/R/HB1/HB2 MA 50
LRD 32
23/32
NSX100 L/R/HB1/HB2 MA 50
LRD 33 55
30/40
NSX100 L/R/HB1/HB2 MA 50
LRD 33 57
37/50
NSX100 L/R/HB1/HB2 MA 100
LRD 33 59
48/65
NSX100 L/R/HB1/HB2 MA 100
LRD 33 63
63/80
NSX100 L/R/HB1/HB2 MA 100
LRD 33 65
or 43 65
80/100
NSX100 L/R/HB1/HB2
Micrologic
25/50
2.2 M or 6.2 E-M 100
4
0.8
1
1
1
5
5
1
1
1
5
5
1
1
5
5
4
4
4
0.8
1
1
1
2
2.5
2.5
Discrimination limit = 4 kA.
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
19
Protection discrimination 690 V
Additional characteristics
Upstream: Compact NSX100-250 Micrologic
Downstream: Compact NSX100-250 TM-D Micrologic - MA
Upstream
NSX100L/R/HB1/HB2
NSX160L
NSX250L/R/HB1/
HB2
Trip unit
Micrologic
Micrologic
Micrologic
Downstream
O/L
Rating (A)
40
Setting Ir
16
100
25
32
40
160
250
40
63
80
100 80
100
125
160
160
200
250
16
1.5
1.5
1.5
1.5
2.4
2.4
2.4
2.4
3
3
3
25
1.5
1.5
1.5
1.5
2.4
2.4
2.4
2.4
3
3
3
1.5
1.5
1.5
2.4
2.4
2.4
2.4
3
3
3
1.5
1.5
2.4
2.4
2.4
2.4
3
3
3
1.5
2.4
2.4
2.4
2.4
3
3
3
2.4
2.4
2.4
3
3
3
2.4
2.4
3
3
3
2.4
3
3
3
2.4
2.4
3
3
3
2.4
2.4
3
3
3
2.4
3
3
3
3
3
3
3
3
Discrimination limit (kA)
NSX100 L
TM-D
32
NSX100 L/R/HB1/HB2
40
50
63
80
100
NSX160 L
TM-D
y 63
2.4
80
100
160
NSX250 L/R/HB1/HB2
TM-D
3
y 100
125
160
3
200
NSX100 L/R/HB1/HB2
Micrologic
40
NSX160 L
Micrologic
40
1.5
1.5
1.5
1.5
2.4
2.4
2.4
100
2.4
2.4
2.4
100
2.4
3
3
3
2.4
3
3
3
2.4
3
3
3
2.4
3
3
3
3
3
160
NSX250 L/R/HB1/HB2
Micrologic
3
y 100
160
3
3
250
NSX100 L MA 2.5
LRD 06
1/1.6
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
NSX100 L MA 2.5
LRD 07
1.6/2.5
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
NSX100 L MA 6.3
LRD 08
2.5/4
4
4
4
4
4
4
4
4
8
8
8
8
20
20
20
NSX100 L MA 6.3
LRD 10
4/6.3
4
4
4
4
4
4
4
4
8
8
8
8
20
20
20
2
2
2
2
2
2
2
2.4
2.4
2.4
2.4
20
20
20
2
2
2
2
2
2
2.4
2.4
2.4
2.4
20
20
20
2
2
2
2
2
2.4
2.4
2.4
2.4
20
20
20
2
2
2
2.4
2.4
2.4
2.4
13
13
13
2
2
2.4
2.4
2.4
2.4
13
13
13
2.4
2.4
2.4
11
11
11
2.4
2.4
11
11
11
2.4
11
11
11
NSX100 L/R/HB1/HB2 MA 12.5
LRD 12
5.5/8
NSX100 L/R/HB1/HB2 MA 12.5
LRD 14
7/10
NSX100 L/R/HB1/HB2 MA 12.5
LRD 16
9/13
NSX100 L/R/HB1/HB2 MA 25
LRD 21
12/18
NSX100 L/R/HB1/HB2 MA 25
LRD 22
17/25
NSX100 L/R/HB1/HB2 MA 50
LRD 32
23/32
NSX100 L/R/HB1/HB2 MA 50
LRD 33 55
30/40
NSX100 L/R/HB1/HB2 MA 50
LRD 33 57
37/50
NSX100 L/R/HB1/HB2 MA 100
LRD 33 59
48/65
10
10
NSX100 L/R/HB1/HB2 MA 100
LRD 33 63
63/80
10
10
NSX100 L/R/HB1/HB2 MA 100
LRD 33 65
or 43 65
80/100
NSX100 L/R/HB1/HB2
Micrologic
25/50
2.2 M or 6.2 E-M 100
4
1
10
1.5
Discrimination limit = 4 kA.
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
20
2.4
2.4
2.4
2.4
3
3
3
3
Protection discrimination 690 V
Additional characteristics
Upstream: Compact NSX400-630
Downstream: TeSys GV2, GV3, TeSys U
Upstream
NSX400L/R/HB1/HB2
NSX630L/R/HB1/HB2
Trip unit
Micrologic
Micrologic
Downstream
Icu
O/L
Rating (A)
400
Ir range
160
200
250
320
400
630
250
320
400
500
630
T
Discrimination limit (kA)
GV2 L03
100 kA
LRD 03
0.25/0.40
T
T
T
T
T
T
T
T
T
GV2 L04
100 kA
LRD 04
0.40/0.63
T
T
T
T
T
T
T
T
T
T
GV2 L05
100 kA
LRD 05
0.63/1
T
T
T
T
T
T
T
T
T
T
T
GV2 L06
100 kA
LRD 06
1/1.6
T
T
T
T
T
T
T
T
T
GV2 L07 + LA9 LB920
50 kA
LRD 07
1.6/2.5
T
T
T
T
T
T
T
T
T
T
GV2 L08 + LA9 LB920
50 kA
LRD 08
2.5/4
T
T
T
T
T
T
T
T
T
T
T
GV2 L10 + LA9 LB920
50 kA
LRD 10
4/6.3
T
T
T
T
T
T
T
T
T
GV2 L14 + LA9 LB920
50 kA
LRD 14
7/10
T
T
T
T
T
T
T
T
T
T
GV2 L16 + LA9 LB920
50 kA
LRD 16
9/13
T
T
T
T
T
T
T
T
T
T
GV2 L20 + LA9 LB920
50 kA
LRD 21
12/18
T
T
T
T
T
T
T
T
T
T
GV2 L22 + LA9 LB920
50 kA
LRD 22
17/25
T
T
T
T
T
T
T
T
T
T
T
GV2 L32 + LA9 LB920
50 kA
LRD 32
23/32
T
T
T
T
T
T
T
T
T
GV3 P13
6 kA
Integrated
9/13
T
T
T
T
T
T
T
T
T
T
GV3 P18
6 kA
Integrated
12/18
T
T
T
T
T
T
T
T
T
T
GV3 P25
6 kA
Integrated
17/25
T
T
T
T
T
T
T
T
T
T
GV3 P32
6 kA
Integrated
23/32
T
T
T
T
T
T
T
T
T
T
GV3 P40
6 kA
Integrated
30/40
T
T
T
T
T
T
T
T
T
T
GV3 P50
6 kA
Integrated
37/50
T
T
T
T
T
T
T
T
T
T
GV3 P65
6 kA
Integrated
48/65
T
T
T
T
T
T
T
T
T
T
T
GV3 L25
6 kA
LRD 22
20/25
T
T
T
T
T
T
T
T
T
GV3 L32
6 kA
LRD 32
23/32
T
T
T
T
T
T
T
T
T
T
GV3 L40
6 kA
LRD 340
30/40
T
T
T
T
T
T
T
T
T
T
GV3 L50
6 kA
LRD 350
37/50
T
T
T
T
T
T
T
T
T
T
GV3 L65
6 kA
LRD 365
48/65
T
T
T
T
T
T
T
T
T
T
LUB12 + LA9 LB20
35 kA
LUC*X6
0.15…0.6
T
T
T
T
T
T
T
T
T
T
LUC*1X
0.35…1.4
T
T
T
T
T
T
T
T
T
T
LUC*05
1.25…5
T
T
T
T
T
T
T
T
T
T
LUC*12
3…12
T
T
T
T
T
T
T
T
T
T
LUC*X6
0.15…0.6
T
T
T
T
T
T
T
T
T
T
LUC*1X
0.35…1.4
T
T
T
T
T
T
T
T
T
T
LUC*05
1.25…5
T
T
T
T
T
T
T
T
T
T
LUC*12
3…12
T
T
T
T
T
T
T
T
T
T
LUC*18
4.5…18
T
T
T
T
T
T
T
T
T
T
LUC*32
8…32
T
T
T
T
T
T
T
T
T
T
LUC*X6
0.15…0.6
T
T
T
T
T
T
T
T
T
T
LUC*1X
0.35…1.4
T
T
T
T
T
T
T
T
T
T
LUC*05
1.25…5
T
T
T
T
T
T
T
T
T
T
LUC*12
3…12
T
T
T
T
T
T
T
T
T
T
LUC*X6
0.15…0.6
T
T
T
T
T
T
T
T
T
T
LUC*1X
0.35…1.4
T
T
T
T
T
T
T
T
T
T
LUC*05
1.25…5
T
T
T
T
T
T
T
T
T
T
LUC*12
3…12
T
T
T
T
T
T
T
T
T
T
LUC*18
4.5…18
T
T
T
T
T
T
T
T
T
T
LUC*32
8…32
T
T
T
T
T
T
T
T
T
T
LUB32 + LA9 LB20
LUB12 + LUA LB1
LUB32 + LUA LB1
T
35 kA
70 kA
70 kA
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
21
Protection discrimination 690 V
Additional characteristics
Upstream: Compact NSX400-630
Downstream: Compact NSX100-250 TM-D Micrologic - MA + LRD
Upstream
NSX400L/R/HB1/HB2
NSX630L/R/HB1/HB2
Trip unit
Micrologic
Micrologic
Downstream
O/L
Discrimination limit (kA)
NSX100 L
TM-D
NSX100 L/R/HB1/HB2
NSX160 L
TM-D
NSX250 L/R/HB1/HB2
TM-D
NSX100 L/R/HB1/HB2
Micrologic
NSX160 L
Micrologic
NSX250 L/R/HB1/HB2
Micrologic
NSX400 L/R/HB1/HB2
Micrologic
NSX100 L MA 2.5
NSX100 L MA 2.5
NSX100 L MA 6.3
NSX100 L MA 6.3
NSX100 L/R/HB1/HB2 MA 12.5
NSX100 L/R/HB1/HB2 MA 12.5
NSX100 L/R/HB1/HB2 MA 12.5
NSX100 L/R/HB1/HB2 MA 25
NSX100 L/R/HB1/HB2 MA 25
NSX100 L/R/HB1/HB2 MA 50
NSX100 L/R/HB1/HB2 MA 50
NSX100 L/R/HB1/HB2 MA 50
NSX100 L/R/HB1/HB2 MA 100
NSX100 L/R/HB1/HB2 MA 100
NSX100 L/R/HB1/HB2 MA 100
NSX160 L MA 150
NSX250 L/R/HB1/HB2 MA 220
NSX100 L/R/HB1/HB2
NSX160 L
NSX250 L/R/HB1/HB2
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
LRD 33 65
or 43 65
LRD 43 67
LR9 F5371
Micrologic
2.2 M or 6.2 E-M
Rating (A)
400
Ir range
160
200
250
320
400
250
320
400
500
630
16
25
32
40
50
63
80
100
y 100
125
160
y 100
125
160
200
250
40
100
40
100
160
y 100
160
250
160
200
250
320
400
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7/10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
80/100
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
12
12
12
12
12
12
12
12
10
10
10
6.9
6.9
6.9
12
12
12
12
12
12
12
12
10
10
10
6.9
6.9
6.9
6.9
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
12
12
10
10
10
6.9
6.9
12
12
10
10
10
6.9
6.9
6.9
6.9
6.9
12
12
12
12
12
12
12
12
10
10
10
6.9
6.9
6.9
6.9
6.9
12
12
10
10
10
6.9
6.9
6.9
6.9
6.9
6.9
12
12
12
12
12
12
12
12
10
10
10
6.9
6.9
6.9
6.9
6.9
12
12
10
10
10
6.9
6.9
6.9
6.9
6.9
6.9
6.9
T
T
T
T
T
T
T
T
T
12
12
12
10
T
T
T
T
T
T
T
T
T
12
12
12
10
10
10
T
T
T
T
T
T
T
T
T
12
12
12
10
10
10
T
T
T
T
T
T
T
T
T
12
12
12
10
10
10
12
12
12
12
12
12
12
12
10
10
10
6.9
6.9
6.9
6.9
6.9
12
12
10
10
10
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9
T
T
T
T
T
T
T
T
T
12
12
12
10
10
10
8
8
12
12
10
10
10
6.9
6.9
12
12
10
10
10
6.9
6.9
95/150
132/220
25/50
100
Micrologic
25/50
2.2 M or 6.2 E-M 100
150
Micrologic
y 100
2.2 M or 6.2 E-M 150
220
T
T
T
T
T
T
T
13
13
11
11
11
630
T
T
T
T
T
T
T
13
13
11
11
11
4.8
T
T
T
T
T
T
T
13
13
11
11
11
4.8
4.8
4.8
T
T
T
T
T
T
T
13
13
11
11
11
4.8
4.8
4.8
T
T
T
T
T
T
T
13
13
11
11
11
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
T
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
4
Discrimination limit = 4 kA.
4.8
4.8
4.8
4.8
4.8
4.8
4.8
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
22
12
12
10
10
12
12
10
10
6.9
6.9
8
8
12
12
10
10
10
6.9
6.9
6.9
Protection discrimination 690 V
Additional characteristics
Upstream: Compact NS630b-1600N/H
Downstream: TeSys GV2, GV3, TeSys U,
Compact NSX100-630
Upstream
NS630b-1600N (30 kA) / H (40 kA) NS630b-1600N (30 kA) / H (40 kA)
NS630b-1600N (30 kA) / H (40 kA)
Trip unit
Micrologic 2.0
Micrologic 5.0 - 6.0 - 7.0
Inst OFF
Downstream
Rating (A) 630
Setting Ir
Micrologic 5.0 - 6.0 - 7.0
Inst 15 In
800 1000 1250 1600 630
800 1000 1250 1600 630
800 1000 1250 1600
250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600
Discrimination limit (kA)
GV2 L03 - L06
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L07 - L32
+ LA9 LB920
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV3 32-65
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100
L/R/HB1/HB2
MA < 100
y 100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L
MA < 150
y 150
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
L/R/HB1/HB2
MA < 220
y 220
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100
y 100
L/R/HB1/HB2 TM-D
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L TM-D
y 160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
L/R/HB1/HB2
TM-D
y 125
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100
L/R/HB1/HB2
Micrologic
250
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L
Micrologic
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
y 100
2.5
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
2.5
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
L/R/HB1/HB2
Micrologic
250
NSX400
320
S/L/R/HB1/HB2 1.3 M
NSX400
S/L/R/HB1/HB2
Micrologic
160
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
200
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
250
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.5
NSX630
500
S/L/R/HB1/HB2 1.3 M
NSX630
S/L/R/HB1/HB2
Micrologic
250
T
6.3
T
T
T
T
T
T
T
T
T
T
T
T
T
320
6.3
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
6.3
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
500
630
4
T
T
T
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
4
Discrimination limit = 4 kA.
T
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
23
Protection discrimination 690 V
Additional characteristics
Upstream: Compact NS1600b-3200N
Downstream: TeSys GV2, GV3, TeSys U,
Compact NSX100-630, Compact NS630b-3200
Upstream
NS1600-3200N (65 kA)
NS1600-3200N (65 kA)
NS1600-3200N (65 kA)
Trip unit
Micrologic 2.0
Micrologic 5.0 - 6.0 - 7.0
Inst 15 In
Micrologic 5.0 - 6.0 - 7.0
Inst OFF
Downstream
Rating (A)
1600
2000
2500
3200
1600
2000
2500
3200
1600
2000
2500
3200
GV2 L03 - L06
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L07 - L32 + LA9 LB920
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
GV3 32-65
T
T
T
T
T
T
T
T
T
T
T
T
Discrimination limit (kA)
Compact NSX L/R/HB1/HB2
TM-D / MA
NSX100
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
T
T
T
T
T
T
T
T
T
T
T
T
Compact NSX L
TM-D / MA
NSX160
T
T
T
T
T
T
T
T
T
T
T
T
Compact NSX L/R/HB1/HB2
Micrologic
NSX100
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
T
T
T
T
T
T
T
T
T
T
T
T
Compact NSX L
Micrologic
NSX160
T
T
T
T
T
T
T
T
T
T
T
T
Compact NSX L/R/HB1/HB2
NSX400
T
T
T
T
T
T
T
T
T
T
T
T
NSX630
T
T
T
T
T
T
T
T
T
T
T
T
NS630b
16
20
25
T
24
T
T
T
T
T
T
T
NS800
16
20
25
T
24
T
T
T
T
T
T
T
NS1000
16
20
25
T
24
T
T
T
T
T
T
T
20
25
T
T
T
T
T
T
T
25
T
T
T
T
T
Compact NS
N
NS1250
NS1600
Compact NS
H
NS630b
16
20
25
32
24
30
37.5
T
T
T
T
T
NS800
16
20
25
32
24
30
37.5
T
T
T
T
T
NS1000
16
20
25
32
24
30
37.5
T
T
T
T
T
20
25
32
30
37.5
T
T
T
T
NS1600
25
32
37.5
T
T
T
NS1600b
25
32
37.5
T
60
60
NS1250
Compact NS
N
NS2000
T
32
60
NS2500
NS3200
Compact NS
LB
NS630b LB T
T
T
T
T
T
T
T
T
T
T
T
NS800LB
T
T
T
T
T
T
T
T
T
T
T
T
T
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
4
Discrimination limit = 4 kA.
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
24
Protection discrimination 690 V
Additional characteristics
Upstream: NS630b-800LB
Downstream: TeSys GV2, GV3, TeSys U,
Compact NSX100-630, Compact NS630b-800
Upstream
NS630b-800LB (75 kA)
NS630b-800LB (75 kA)
NS630b-800LB (75 kA)
Trip unit
Micrologic 2.0
Micrologic 5.0 - 6.0 - 7.0
Inst 15 In
Micrologic 5.0 - 6.0 - 7.0
Inst OFF
Downstream
Discrimination limit (kA)
GV2 L03 - L06
GV2 L07 - L32 + LA9 LB920
LUB12 + LA9 LB20
LUB32 + LA9 LB20
LUB12 + LUA LB1
LUB32 + LUA LB1
NSX100 L/R/HB1/HB2 MA
NSX160 L MA
NSX250 L/R/HB1/HB2 MA
NSX100 L TM-D
NSX100 R/HB1/HB2 TM-D
NSX160 L TM-D
NSX100 R/HB1/HB2 TM-D
NSX250 L TM-D
NSX100 L
Micrologic
NSX100 R/HB1/HB2
Micrologic
NSX160 L
Micrologic
NSX250 L/R/HB1/HB2
Micrologic
NSX400 S/L
Micrologic
NSX630 S/L
Micrologic
NS630b N/H
Micrologic
NS800 N/H
Micrologic
NS630b LB
Micrologic
NS800 LB
Micrologic
Rating (A)
630
Setting Ir
250
400
630
630
800
250
400
630
630
800
250
400
630
630
800
T
T
T
T
T
T
15
10
10
15
15
10
10
10
T
T
T
T
T
T
15
10
10
15
15
10
10
10
10
10
15
15
15
15
10
10
4
4
4
4
4
4
T
T
T
T
T
T
15
10
10
15
15
10
10
10
10
10
15
15
15
15
10
10
10
10
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
30
30
10
T
30
T
30
10
10
10
T
T
30
30
T
T
15
15
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
30
30
10
T
30
T
30
10
10
10
T
T
30
30
T
T
15
15
8
8
8
8
8
8
8
8
8
T
T
T
T
T
T
15
10
10
15
15
10
10
10
T
T
T
T
T
T
15
10
10
15
15
10
10
10
10
10
15
15
15
15
10
10
10
10
6.3
6.3
6.3
6.3
T
T
T
T
T
T
15
10
10
15
15
10
10
10
10
10
15
15
15
15
10
10
10
10
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
30
30
10
T
30
T
30
10
10
10
T
T
30
30
T
T
15
15
8
8
8
8
8
8
8
8
T
T
T
T
T
T
30
30
10
T
30
T
30
10
10
10
T
T
30
30
T
T
15
15
8
8
8
8
8
8
8
8
8
T
T
T
T
T
T
15
10
10
15
15
10
10
10
T
T
T
T
T
T
15
10
10
15
15
10
10
10
10
10
15
15
15
15
10
10
10
10
6.3
6.3
6.3
6.3
T
T
T
T
T
T
15
10
10
15
15
10
10
10
10
10
15
15
15
15
10
10
10
10
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
30
30
10
T
30
T
30
10
10
10
T
T
30
30
T
T
15
15
8
8
8
8
8
8
8
8
T
T
T
T
T
T
30
30
10
T
30
T
30
10
10
10
T
T
30
30
T
T
15
15
8
8
8
8
8
8
8
8
8
6.3
6.3
6.3
6.3
6.3
6.3
8
8
8
8
6.3
6.3
6.3
8
8
8
8
8
8
8
6.3
6.3
6.3
8
8
8
8
8
8
8
6.3
6.3
8
8
8
8
8
6.3
6.3
8
8
8
8
8
6.3
6.3
8
8
8
8
8
6.3
6.3
6.3
6.3
6.3
6.3
8
8
8
8
6.3
6.3
6.3
8
8
8
8
8
8
8
6.3
6.3
6.3
8
8
8
8
8
8
8
6.3
6.3
6.3
6.3
8
8
8
6.3
6.3
8
8
8
8
8
6.3
6.3
8
8
8
8
8
y 100
y 150
y 220
y 100
y 100
y 160
y 160
y 160
200
250
40
100
40
100
40-100
160
y 160
250
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
320
400
500
u 630
250
320
400
500
630
320
400
500
u 630
15
15
15
15
2.5
2.5
2.5
2.5
800
4
4
4
630
15
15
15
15
10
10
10
6.3
T
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
4
Discrimination limit = 4 kA.
800
6.3
6.3
6.3
630
15
15
15
15
10
10
10
6.3
800
6.3
6.3
6.3
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
25
Protection discrimination 690 V
Additional characteristics
Upstream: Masterpact NT06-16H1/H2
Downstream: TeSys GV2, GV3, TeSys U,
Compact NSX100-630
Upstream
Masterpact NT06-16H1/2 (42 kA) Masterpact NT06-16H1/2 (42 kA)
Masterpact NT06-16H1/2 (42 kA)
Trip unit
Micrologic 2.0
Micrologic 5.0 - 6.0 - 7.0
Inst OFF
Downstream
Rating (A) 630
Setting Ir
Micrologic 5.0 - 6.0 - 7.0
Inst 15 In
800 1000 1250 1600 630
800 1000 1250 1600 630
800 1000 1250 1600
250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600
Discrimination limit (kA)
GV2 L03 - L06
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L07 - L32
+ LA9 LB920
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV3 32-65
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100
L/R/HB1/HB2 MA
y 100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L
MA
y 150
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
L/R/HB1/HB2 MA
y 220
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100
L/R/HB1/HB2 TM-D
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L
TM-D
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
y 125
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
L/R/HB1/HB2
TM-D
200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100
L/R/HB1/HB2
Micrologic
250
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L
Micrologic
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
y 100
2.5
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
2.5
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
L/R/HB1/HB2
Micrologic
250
NSX400
320
S/L/R/HB1/HB2 1.3 M
NSX400
S/L/R/HB1/HB2
Micrologic
160
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
200
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
250
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.5
NSX630
500
S/L/R/HB1/HB2 1.3 M
NSX630
S/L/R/HB1/HB2
Micrologic
250
T
6.3
T
T
T
T
T
T
T
T
T
T
T
T
T
320
6.3
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
6.3
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
500
630
4
T
T
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
4
Discrimination limit = 4 kA.
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
26
T
T
Protection discrimination 690 V
Additional characteristics
Upstream: Masterpact NW08-20N1/H1/H2/L1
Downstream: TeSys GV2, GV3, TeSys U,
Compact NSX100-630
Upstream
Masterpact NW08-20N1 (42 kA) /
H1 (65 kA) / H2 (85 kA) /
L1 (100 kA)
Masterpact NW08-20N1 (42 kA) /
H1 (65 kA) / H2 (85 kA) /
L1 (100 kA)
Masterpact NW08-20N1 (42 kA) /
H1 (65 kA) / H2 (85 kA) /
L1 (100 kA)
Trip unit
Micrologic 2.0
Micrologic 5.0 - 6.0 - 7.0
Inst 15 In
Micrologic 5.0 - 6.0 - 7.0
Inst OFF
Downstream
Rating (A) 800
1000 1250 1600 2000 800
1000 1250 1600 2000 800
1000 1250 1600 2000
Setting Ir 320 630 800 1000 1250 1600 2000 320 630 800 1000 1250 1600 2000 320 630 800 1000 1250 1600 2000
Discrimination limit (kA)
GV2 L03 - L06
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L07 - L32
+ LA9 LB920
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV3 32-65
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100 L/R/HB1/HB2 y 100
MA < 100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L
MA < 150
y 150
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250 L/R/HB1/HB2 y 220
MA < 220
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100 L/R/HB1/HB2
TM-D
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L
TM-D
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
y 125
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
200
3.2 T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
L/R/HB1/HB2
TM-D
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100
L/R/HB1/HB2
Micrologic
250
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L
Micrologic
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
y 100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250
L/R/HB1/HB2
Micrologic
250
NSX400
320
S/L/R/HB1/HB2 1.3 M
NSX400
S/L/R/HB1/HB2
Micrologic
160
3.2 T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
200
3.2 T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
250
3.2 T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX630
500
S/L/R/HB1/HB2 1.3 M
NSX630
S/L/R/HB1/HB2
Micrologic
250
3.2 6.3 T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
320
6.3 T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
6.3 T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
T
T
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
4
Discrimination limit = 4 kA.
T
No discrimination.
Note: respect the basic rules of discrimination, for overload and short-circuit, see introduction or check curves.
27
Protection discrimination 690 V
Additional characteristics
Upstream: Masterpact NW25-40H1/H2/H3,
NW40b-63H1/H2
Downstream: TeSys GV2, GV3, TeSys U,
Compact NSX100-630, Compact NS630b-3200
Upstream
NW25-40
H1/H2/H3
Trip unit
Micrologic 2.0
Downstream
NW40b-63
H1/H2
NW25-40
H1/H2/H3
NW40b-63
H1/H2
NW25-40
H1/H2/H3
Micrologic 5.0 - 6.0 - 7.0
Inst 15 In
NW40b-63
H1/H2
Micrologic 5.0 - 6.0 - 7.0
Inst OFF
Rating (A) 2500 3200 4000 4000 5000 6300 2500 3200 4000 4000 5000 6300 2500 3200 4000 4000 5000 6300
Discrimination limit (kA)
GV2 L03 - L06
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GV2 L07 - L32 + LA9 LB920
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LA9 LB20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB12 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LUB32 + LUA LB1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX100 L/R/HB1/HB2 MA
y 100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX160 L MA
y 150
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX250 L/R/HB1/HB2 MA
y 220
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Compact NSX L/R/HB1/HB2 NSX100
TM-D
NSX250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Compact NSX L
TM-D
NSX160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Compact NSX L/R/HB1/HB2 NSX100
Micrologic
NSX250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Compact NSX L
Micrologic
NSX160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Compact NSX
S/L/R/HB1/HB2
NSX400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NSX630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Compact NS
N
Micrologic
NS630b
25
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NS800
25
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NS1000
25
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NS1250
25
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NS1600
25
T
T
T
25
32
40
40
T
T
T
NS630b
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NS800
25
32
40
40
T
T
T
37.5 T
37.5 T
T
T
T
T
T
T
T
T
T
T
NS1000
25
32
40
40
T
T
T
T
T
T
T
T
T
T
T
T
NS1250
25
32
40
40
T
T
37.5 T
37.5 T
T
T
T
T
T
T
T
T
T
T
NS1600
25
32
40
40
T
T
37.5 T
T
T
T
T
T
T
T
T
T
T
NS1600b
25
32
40
40
50
63
37.5 48
60
60
T
T
T
T
T
T
T
T
NS2000
25
32
40
40
50
63
37.5 48
60
60
T
T
T
T
T
T
T
T
32
40
40
50
63
48
60
60
T
T
T
T
T
T
T
T
40
T
50
T
63
T
T
T
T
T
T
T
T
T
60
T
T
T
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Compact NS
H
Micrologic
Compact NS
N
Micrologic
NS2500
NS3200
Compact NS LB
Micrologic
NS630b
T
T
40
T
NS800
T
T
T
T
Total discrimination, up to the breaking capacity of the downstream circuit breaker.
4
Discrimination limit = 4 kA.
No discrimination.
28
Catalogue numbers
Contents
NSX100/250R: complete fixed/FC device
Compact NSX100/250R
(200 kA 380/415 V - 45 kA 690 V)
NSX100/250HB1: complete fixed/FC device
Compact NSX100/250HB1
(85 kA 500 V - 75 kA 690 V)
Compact NSX100/250HB1
(85 kA 500 V - 75 kA 690 V)
NSX100/250HB2: complete fixed/FC device
Compact NSX100/250HB2
(100 kA 500 V - 100 kA 690 V)
Compact NSX100/250HB2
(100 kA 500 V - 100 kA 690 V)
NSX400/630R: complete fixed/FC device
Compact NSX400/630R
(200 kA 380/415 V - 45 kA 690 V)
NSX400/630HB1: complete fixed/FC device
Compact NSX400/630HB1
(85 kA 500 V - 75 kA 690 V)
NSX400/630HB2: complete fixed/FC device
Compact NSX400/630HB2
(100 kA 500 V - 100 kA 690 V)
Order form
Compact NSX100 to NSX630
Circuit breakers and switch-disconnectors
30
30
32
32
33
34
34
35
36
36
37
37
38
38
39
39
39
29
Catalogue numbers
NSX100/250R:
complete fixed/FC device
Compact NSX100/250R
(200 kA 380/415 V - 45 kA 690 V)
Compact NSX100/250R
With thermal-magnetic trip unit TM-D
DB112222.eps
Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
TM40D
LV433200
TM50D
LV433202
TM63D
LV433204
TM80D
LV433206
TM100D
LV433208
Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
TM125D
LV433470
TM160D
LV433472
TM200D
LV433474
TM250D
LV433476
With electronic trip unit Micrologic 2.2 (LSOI protection)
DB112223.eps
Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
40
LV433270
100
LV433272
Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
100
LV433510
160
LV433512
250
LV433514
DB112224.eps
With electronic trip unit Micrologic 5.2 E (LSI protection, energy meter)
OK
Mode
Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
40
LV433277
100
LV433279
Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
100
LV433518
160
LV433520
250
LV433522
DB112224.eps
With electronic trip unit Micrologic 6.2 E (LSIG protection, energy meter)
OK
Mode
30
Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
40
LV433281
100
LV433283
Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
100
LV433524
160
LV433526
250
LV433528
4P 4d
LV433201
LV433203
LV433205
LV433207
LV433209
4P 4d
LV433471
LV433473
LV433475
LV433477
4P 3d, 4d, 3d + N/2
LV433271
LV433273
4P 3d, 4d, 3d + N/2
LV433511
LV433513
LV433515
4P 3d, 4d, 3d + N/2, OSN
LV433278
LV433280
4P 3d, 4d, 3d + N/2, OSN
LV433519
LV433521
LV433523
4P 3d, 4d, 3d + N/2, OSN
LV433282
LV433284
4P 3d, 4d, 3d + N/2, OSN
LV433525
LV433527
LV433529
Catalogue numbers
NSX100/250R:
complete fixed/FC device
Compact NSX100/250R
(200 kA 380/415 V - 45 kA 690 V)
Compact NSX100/250R
DB115664.eps
With magnetic trip unit MA
Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
MA12.5
LV433242
MA25
LV433243
MA50
LV433244
MA100
LV433245
Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
MA150
LV433500
MA220
LV433501
DB112223.eps
With electronic trip unit Micrologic 2.2 M (LSOI motor protection)
Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
25
LV433274
50
LV433275
100
LV433276
Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
150
LV433516
220
LV433517
DB112223.eps
With electronic trip unit Micrologic 6.2 E-M (LSIG motor protection, energy meter)
Compact NSX100R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
25
LV433285
50
LV433286
100
LV433287
Compact NSX250R (200 kA at 380/415 V - 45 kA at 690 V)
Rating
3P 3d
150
LV433530
220
LV433531
31
Catalogue numbers
NSX100/250HB1:
complete fixed/FC device
Compact NSX100/250HB1
(85 kA 500 V - 75 kA 690 V)
Compact NSX100/250HB1
With thermal-magnetic trip unit TM-D
DB112222.eps
Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
TM40D
LV433210
TM50D
LV433212
TM63D
LV433214
TM80D
LV433216
TM100D
LV433218
Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
TM125D
LV433478
TM160D
LV433480
TM200D
LV433482
TM250D
LV433484
With electronic trip unit Micrologic 2.2 (LSOI protection)
DB112223.eps
Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
40
LV433300
100
LV433302
Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
100
LV433540
160
LV433542
250
LV433544
DB112224.eps
With electronic trip unit Micrologic 5.2 E (LSI protection, energy meter)
OK
Mode
Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
40
LV433307
100
LV433309
Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
100
LV433548
160
LV433550
250
LV433552
DB112224.eps
With electronic trip unit Micrologic 6.2 E (LSIG protection, energy meter)
OK
Mode
32
Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
40
LV433311
100
LV433313
Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
100
LV433554
160
LV433556
250
LV433558
4P 4d
LV433211
LV433213
LV433215
LV433217
LV433219
4P 4d
LV433479
LV433481
LV433483
LV433485
4P 3d, 4d, 3d + N/2
LV433301
LV433303
4P 3d, 4d, 3d + N/2
LV433541
LV433543
LV433545
4P 3d, 4d, 3d + N/2,OSN
LV433308
LV433310
4P 3d, 4d, 3d + N/2, OSN
LV433549
LV433551
LV433553
4P 3d, 4d, 3d + N/2, OSN
LV433312
LV433314
4P 3d, 4d, 3d + N/2, OSN
LV433555
LV433557
LV433559
Catalogue numbers
NSX100/250HB1:
complete fixed/FC device
Compact NSX100/250HB1
(85 kA 500 V - 75 kA 690 V)
Compact NSX100/250HB1
DB115664.eps
With magnetic trip unit MA
Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
MA12.5
LV433248
MA25
LV433249
MA50
LV433250
MA100
LV433251
Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
MA150
LV433502
MA220
LV433503
DB112223.eps
With electronic trip unit Micrologic 2.2 M (LSOI motor protection)
Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
25
LV433304
50
LV433305
100
LV433306
Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
150
LV433546
220
LV433547
DB112223.eps
With electronic trip unit Micrologic 6.2 E-M (LSIG motor protection, energy meter)
Compact NSX100HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
25
LV433315
50
LV433316
100
LV433317
Compact NSX250HB1 (85 kA at 500 V - 75 kA at 690 V)
Rating
3P 3d
150
LV433560
220
LV433561
33
Catalogue numbers
NSX100/250HB2:
complete fixed/FC device
Compact NSX100/250HB2
(100 kA 500 V - 100 kA 690 V)
Compact NSX100/250HB2
With thermal-magnetic trip unit TM-D
DB112222.eps
Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
TM40D
LV433220
TM50D
LV433222
TM63D
LV433224
TM80D
LV433226
TM100D
LV433228
Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
TM125D
LV433486
TM160D
LV433488
TM200D
LV433490
TM250D
LV433492
With electronic trip unit Micrologic 2.2 (LSOI protection)
DB112223.eps
Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
40
LV433330
100
LV433332
Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
100
LV433570
160
LV433572
250
LV433574
DB112224.eps
With electronic trip unit Micrologic 5.2 E (LSI protection, energy meter)
OK
Mode
Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
40
LV433337
100
LV433339
Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
100
LV433578
160
LV433580
250
LV433582
DB112224.eps
With electronic trip unit Micrologic 6.2 E (LSIG protection, energy meter)
OK
Mode
34
Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
40
LV433341
100
LV433343
Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
100
LV433584
160
LV433586
250
LV433588
4P 4d
LV433221
LV433223
LV433225
LV433227
LV433229
4P 4d
LV433487
LV433489
LV433491
LV433493
4P 3d, 4d, 3d + N/2
LV433331
LV433333
4P 3d, 4d, 3d + N/2
LV433571
LV433573
LV433575
4P 3d, 4d, 3d + N/2, OSN
LV433338
LV433340
4P 3d, 4d, 3d + N/2, OSN
LV433579
LV433581
LV433583
4P 3d, 4d, 3d + N/2, OSN
LV433342
LV433344
4P 3d, 4d, 3d + N/2, OSN
LV433585
LV433587
LV433589
Catalogue numbers
NSX100/250HB2:
complete fixed/FC device
Compact NSX100/250HB2
(100 kA 500 V - 100 kA 690 V)
Compact NSX100/250HB2
DB115664.eps
With magnetic trip unit MA
Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
MA12.5
LV433254
MA25
LV433255
MA50
LV433256
MA100
LV433257
Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
MA150
LV433504
MA220
LV433505
DB112223.eps
With electronic trip unit Micrologic 2.2 M (LSOI motor protection)
Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
25
LV433334
50
LV433335
100
LV433336
Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
150
LV433576
220
LV433577
DB112223.eps
With electronic trip unit Micrologic 6.2 E-M (LSIG motor protection, energy meter)
Compact NSX100HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
25
LV433345
50
LV433346
100
LV433347
Compact NSX250HB2 (100 kA at 500 V - 100 kA at 690 V)
Rating
3P 3d
150
LV433590
220
LV433591
35
Catalogue numbers
NSX400/630R:
complete fixed/FC device
Compact NSX400/630R
(200 kA 380/415 V - 45 kA 690 V)
Compact NSX400/630R
Electronic trip unit Micrologic 2.3 (LSOI protection)
DB111455.eps
NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 250 A
400 A
NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 630 A
Electronic trip unit Micrologic 5.3 E (LSI protection, ammeter)
DB111456.eps
NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 400 A
NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 630 A
3P 3d
LV433600
LV433602
LV433700
4P 3d, 4d, 3d + N/2
LV433601
LV433603
LV433701
3P 3d
LV433606
LV433704
4P 3d, 4d, 3d + N/2, 3d + OSN
LV433607
LV433705
3P 3d
LV433608
LV433706
4P 3d, 4d, 3d + N/2, 3d + OSN
LV433609
LV433707
OK
Mode
Electronic trip unit Micrologic 6.3 E (LSIG protection, energy meter)
DB111456.eps
NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 400 A
NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 630 A
OK
Mode
Electronic trip unit Micrologic 1.3 M-A (I motor protection)
DB111457.eps
NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 320 A
NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 500 A
Electronic trip unit Micrologic 2.3 M (LSOI motor protection)
DB111457.eps
NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 320 A
NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 500 A
3P 3d
LV433604
LV433702
3P 3d
LV433605
LV433703
With electronic trip unit Micrologic 6.3 E-M (LSIG motor protection, energy meter)
DB111457.eps
NSX400R (200 kA at 380/415 V - 45 kA at 690 V) 320 A
NSX630R (200 kA at 380/415 V - 45 kA at 690 V) 500 A
36
3P 3d
LV433610
LV433708
Catalogue numbers
NSX400/630HB1:
complete fixed/FC device
Compact NSX400/630HB1
(85 kA 500 V - 75 kA 690 V)
Compact NSX400/630HB1
Electronic trip unit Micrologic 2.3 (LSOI protection)
DB111455.eps
NSX400HB1 (85 kA at 500 V - 75 kA at 690 V)
NSX630HB1 (85 kA at 500 V - 75 kA at 690 V)
250 A
400 A
630 A
3P 3d
LV433620
LV433622
LV433720
4P 3d, 4d, 3d + N/2
LV433621
LV433623
LV433721
400 A
630 A
3P 3d
LV433626
LV433724
4P 3d, 4d, 3d + N/2, 3d + OSN
LV433627
LV433725
400 A
630 A
3P 3d
LV433628
LV433726
4P 3d, 4d, 3d + N/2, 3d + OSN
LV433629
LV433727
320 A
500 A
3P 3d
LV433624
LV433722
320 A
500 A
3P 3d
LV433625
LV433723
Electronic trip unit Micrologic 5.3 E (LSI protection, ammeter)
DB111456.eps
NSX400HB1 (85 kA at 500 V - 75 kA at 690 V)
NSX630HB1 (85 kA at 500 V - 75 kA at 690 V)
OK
Mode
Electronic trip unit Micrologic 6.3 E (LSIG protection, energy meter)
DB111456.eps
NSX400HB1 (85 kA at 500 V - 75 kA at 690 V)
NSX630HB1 (85 kA at 500 V - 75 kA at 690 V)
OK
Mode
DB111457.eps
Electronic trip unit Micrologic 1.3 M-A (I motor protection)
NSX400HB1 (85 kA at 500 V - 75 kA at 690 V)
NSX630HB1 (85 kA at 500 V - 75 kA at 690 V)
DB111457.eps
Electronic trip unit Micrologic 2.3 M (LSOI motor protection)
NSX400HB1 (85 kA at 500 V - 75 kA at 690 V)
NSX630HB1 (85 kA at 500 V - 75 kA at 690 V)
DB111457.eps
With electronic trip unit Micrologic 6.3 E-M (LSIG motor protection, energy meter)
NSX400HB1 (85 kA at 500 V - 75 kA at 690 V)
NSX630HB1 (85 kA at 500 V - 75 kA at 690 V)
320 A
500 A
3P 3d
LV433630
LV433728
37
Catalogue numbers
NSX400/630HB2:
complete fixed/FC device
Compact NSX400/630HB2
(100 kA 500 V - 100 kA 690 V)
Compact NSX400/630HB2
Electronic trip unit Micrologic 2.3 (LSOI protection)
DB111455.eps
NSX400HB2 (100 kA at 500 V - 100 kA at 690 V)
NSX630HB2 (100 kA at 500 V - 100 kA at 690 V)
250 A
400 A
630 A
3P 3d
LV433640
LV433642
LV433740
4P 3d, 4d, 3d + N/2
LV433641
LV433643
LV433741
400 A
630 A
3P 3d
LV433646
LV433744
4P 3d, 4d, 3d + N/2, 3d + OSN
LV433647
LV433745
400 A
630 A
3P 3d
LV433648
LV433746
4P 3d, 4d, 3d + N/2, 3d + OSN
LV433649
LV433747
320 A
500 A
3P 3d
LV433644
LV433742
320 A
500 A
3P 3d
LV433645
LV433743
Electronic trip unit Micrologic 5.3 E (LSI protection, ammeter)
DB111456.eps
NSX400HB2 (100 kA at 500 V - 100 kA at 690 V)
NSX630HB2 (100 kA at 500 V - 100 kA at 690 V)
OK
Mode
Electronic trip unit Micrologic 6.3 E (LSIG protection, energy meter)
DB111456.eps
NSX400HB2 (100 kA at 500 V - 100 kA at 690 V)
NSX630HB2 (100 kA at 500 V - 100 kA at 690 V)
OK
Mode
Electronic trip unit Micrologic 1.3 M-A (I motor protection)
DB111457.eps
NSX400HB2 (100 kA at 500 V - 100 kA at 690 V)
NSX630HB2 (100 kA at 500 V - 100 kA at 690 V)
Electronic trip unit Micrologic 2.3 M (LSOI motor protection)
DB111457.eps
NSX400HB2 (100 kA at 500 V - 100 kA at 690 V)
NSX630HB2 (100 kA at 500 V - 100 kA at 690 V)
With electronic trip unit Micrologic 6.3 E-M (LSIG motor protection, energy meter)
DB111457.eps
NSX400HB2 (100 kA at 500 V - 100 kA at 690 V)
NSX630HB2 (100 kA at 500 V - 100 kA at 690 V)
38
320 A
500 A
3P 3d
LV433650
LV433748
Compact NSX100 to NSX630
Order form
Circuit breakers and switch-disconnectors
Name of customer: .....................................................................................
Address for delivery: ..................................................................................
....................................................................................................................
Requested delivery date:............................................................................
Customer order no.:....................................................................................
To indicate your choices, check the applicable square boxes
or note the
quantity
and enter the appropriate information in the rectangles
Circuit breaker or switch-disconnector
NSX100/160/250 - 160A not available
with R, HB1or HB2
NSX400/630
Rating
A
Circuit breaker
B, F, N, H, S, L, R, HB1, HB2
Switch-disconnector NA
Number of poles
2, 3 or 4
Number of poles
2d, 3d or 4d
tripped
Fixed device
Front connections
Plug-in/withdr.
Plug-in
Withdrawable
Earth-leakage
ME, MH, MB - not available with R,
protection
HB1or HB2
Vigi module
Voltage not available with HB1 or HB2 V
4P option on 3P NSX
Compact type
Trip unit
Thermal-mag.
TMD rating (16 ... 250 A) (40 ….250 A)
with R, HB1 and HB2
TMG rating (16 ... 63 A) - not available
with R, HB1or HB2
MA rating (2.5 ... 220 A) (12.5 ….220
A) with R, HB1 and HB2
Micrologic 2.2
Micrologic 2.3
Electronic
* Not available with Micrologic 2.2 G*
Micrologic 2.3 AB*
R, HB1 or HB2
Micrologic 2.2 AB*
Micrologic 5.3 A*
Micrologic 5.2 A*
Micrologic 5.3 E
Micrologic 5.2 E
Micrologic 5.3 A-Z*
Micrologic 5.2 A-Z*
Micrologic 6.3 A*
Micrologic 6.2 A*
Micrologic 6.3 E
Micrologic 6.2 E
Micrologic 1.3 M
Micrologic 2.2 M
Micrologic 2.3 M
Micrologic 6.2 E-M
Micrologic 6.3 E-M
SDTAM Module
External neutral CT
24 V DC power supply connector
ZSI wiring accessory for NS630b NW/NT
External power supply module 24 V DC
24-30 V DC
48-60 V DC
100-125 V AC
110-130 V AC
200-240 V AC
380-415 V AC
Battery module
Connection
Rear-connection kit
NSX100/250 connectors
NSX400/630 connectors
Right-angle terminal extensions
Straight extensions
Edgewise extensions
Spreader
Short
Long
Mixed
Snap-on 1.5v to 95v (< 160 A)
Snap-on 25v to 95v (< 250 A)
Snap-on 120v to 185v (< 250 A)
Distribution 6 x 1.5v to 35v
Aluminium 2 cables 50v to 120v
1 cable 35v to 300v
2 cables 35v to 240v
NSX100/250
45° terminal
extension
Double-L terminal
extensions
NSX100/250 (one piece)
(45 mm)
NSX400/630 (52.5 mm)
(70 mm)
Cu cable lugs
NSX100/250
120v
150v
185v
NSX400/630
240v
300v
AI cable lugs
NSX100/250
150v
185v
NSX400/630
240v
300v
Voltage measurement
For lugs NSX100/250 y 185v
Input for connector
For lugs NSX400/630
Terminal shields
NSX100/250
Short
Long
NSX400/630
Short
Long
Long for 52.5 mm spreaders
Interphase barriers
Set of 6
2 insulating screens:NSX100/250
NSX400/630
70 pitch
Indication and measurement
Ammeter module
standard
I max
3P
3P
3P
3P
3P
Current-transformer module
Current-transformer module + TCU
Insulation-monitoring module - not available with HB1 or HB2
Voltage-presence indicator - not available with HB1 or HB2
Auxiliary contact
OF, SD, SDE or SDV
SDE adapter (TM, MA or Micrologic 2 trip units)
SDX module
Remote operation
Electrical operation
Voltage releases
Rotary handles
Direct
Extended
Indication auxiliary
Locking
Toggle (1 to 3 padlocks)
Rotary handle
Motor mechanism
Interlocking
Mechanical
By key (2 keylocks, 1 key)
for rotary handle
Motor mechanism
Instantaneous
MX
MN
Fixed time delay MN
Adjust. time delay MN
4P
4P
4P
Standard
AC
AC
AC
AC
AC
Black
MCC conversion access.
Black
Telescopic handle for withdrawable device
1 early-break switch
Removable
Keylock adapter (keylock not included)
Keylocks Ronis 1351B.500
Keylock adapter + keylock Ronis (special)
Keylock adapter (keylock not included)
Keylocks Ronis 1351B.500
Toggle operated
Locking kit without locks
Keylocks Ronis 1351B.500
Installation accessories
4P
Low level
DC
DC
DC
DC
DC
V
V
V
V
V
Red and yellow front
CNOMO conversion access.
Red and yellow front
2 early-make switches
Fixed
Profalux KS5 B24 D4Z
NSX100/250
NSX400/630
Profalux KS5 B24 D4Z
Rotary Handle
Profalux KS5 B24 D4Z
IP30 escutcheon for all types (toggle/rotary handle/motor mechanism)
IP30 escutcheon (with access to toggle + trip unit)
IP30 escutcheon for Vigi module
IP40 escutcheon for all types (toggle/rotary handle/motor mechanism)
IP40 escutcheon for Vigi module
IP40 escutcheon for Vigi or ammeter module
Toggle cover
Sealing accessories
DIN rail adapter
NSX100/250
3P 60 mm busbar adapter
Plug-in / withdrawable configuration accessories
Auxiliary connections
1 automatic connector fixed part with 9 wires (for base)
1 automatic connector moving part with 9 wires (for circuit breaker)
1 support for 3 automatic connector
1 support for 2
moving parts
automatic connector
9-wire manual auxiliary connector (fixed + moving)
Plug-in base accessories
Long insulated terminals
Set of 2
2 IP4 shutters for base
Chassis accessories
Escutcheon collar
Toggle
Vigi
Locking kit (keylock not included)
2 carriage switches (conn./disconnected position indication)
Parts or plug-in
Plug-in base FC/RC
2P
3P
4P
Withdrawable kits
Set of two power connections
Standard
Vigi
Safety trip for advanced opening
For 3P/4P chassis
Moving part
Fixed part
Adapter for plug-in base (for terminal shield or interphase barriers)
Communication
NSX Cord L = 0.35 m
NSX Cord U > 480 V AC L = 0.35 m
BSCM
Communicating motor mechanism 220-240V
Switchboard front display module FDM121
FDM mounting accessory
Modbus interface
Stacking accessory
ULP line termination
RJ45 connectors female/female
Wire length RJ45
L = 0.3 m
Wire length RJ45
L=1m
Wire length RJ45
L=3m
NSX Cord L = 1.3 m
NSX Cord L = 3 m
Wire length RJ45
L = 0.6 m
Wire length RJ45
L=2m
Wire length RJ45
L=5m
Test tool
Pocket battery for Micrologic
Maintenance case
USB maintenance interface
Power supply 110-240 V AC
Spare Micrologic cord
39
35, rue Joseph Monier
CS 30323
F- 92506 Rueil Malmaison Cedex
France
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
RCS Nanterre 954 503 439
Capital social 896 313 776 €
www.schneider-electric.com
Design: Schneider Electric
Photos: Schneider Electric
Edition:
COM-POWER-NSX up to 690 V
This document has been printed on ecological paper
06-2012
© 2012 - Schneider Electric - All rights reserved.
Schneider Electric Industries SAS
Download