WEG CFW-11M Variable Frequency Drives User`s Guide

advertisement
Motors | Energy | Automation | Coatings
Frequency Inverter
Convertidor de Frecuencia
Inversor de Freqüência
CFW-11M
User's Guide
Manual del Usuario
Manual do Usuário
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
FREQUENCY
INVERTER
MANUAL
Series: CFW-11M
Language: English
Document: 10000069202 / 02
Models: 600...2850 A / 380...480 V
470...2232 A / 500...600 V
427...2028 A / 660...690 V
03/2009
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Summary of Revisions
Revision
4
Description
Chapter
0
First edition
-
1
Updating of the tables, figures, identification labels and general revision
-
2
Book updating revision B, mounting rack
-
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Index
CHAPTER 1
Safety Instructions
1.1 Safety Warnings in the Manual......................................................................................................1-1
1.2 Safety Warnings in the Product......................................................................................................1-1
1.3 Preliminary Recommendations......................................................................................................1-2
CHAPTER 2
General Instructions
2.1 About the Manual ......................................................................................................................2-1
2.2 Terms and Definitions...................................................................................................................2-1
2.3 About the CFW-11M...................................................................................................................2-4
2.4 Identification Label for the UC11..................................................................................................2-9
2.5 Identification Labels for the UP11................................................................................................2-10
2.6 How to Specify the CFW-11M (Smart Code)................................................................................2-11
2.7 Receiving and Storage...............................................................................................................2-12
CHAPTER 3
Installation and Connection
3.1 Installation Environment...............................................................................................................3-1
3.2 List of Components.....................................................................................................................3-1
3.3 Mechanical Installation................................................................................................................3-3
3.3.1 HMI Installation at the Cabinet Door or Command Panel (Remote HMI).................................3-8
3.4 Electrical Installation....................................................................................................................3-8
3.4.1 Input Rectifier.....................................................................................................................3-8
3.4.2 Bus Bars..........................................................................................................................3-11
3.4.3 Fuses..............................................................................................................................3-11
3.4.4 General Connection Diagram and Layout..........................................................................3-12
3.4.5 UP11 Connections...........................................................................................................3-18
3.4.6 UC11 Connections..........................................................................................................3-22
3.4.7 Dynamic Braking..............................................................................................................3-24
3.4.7.1 Sizing the Braking Resistor....................................................................................3-25
3.4.7.2 Motor Connections..............................................................................................3-26
3.4.8 Control Connections........................................................................................................3-28
3.4.9 Typical Control Connections..............................................................................................3-32
3.5 Installation According to the European Directive of Electromagnetic Compatibility...........................3-35
3.5.1 Conformal Installation......................................................................................................3-35
3.5.2 Standard Definitions.........................................................................................................3-35
3.5.3 Emission and Immunity Levels............................................................................................3-36
3.5.4 External RFI Filters............................................................................................................3-37
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Index
CHAPTER 4
Keypad and Display
4.1 Integral Keypad - HMI-CFW11.....................................................................................................4-1
4.2 Parameters Organization..............................................................................................................4-4
CHAPTER 5
First Time Power-up and Start-up
5.1 Prepare for Start-up.....................................................................................................................5-1
5.1.1 Precautions during the Energization/Start-up.........................................................................5-1
5.2 Start-up......................................................................................................................................5-3
5.2.1 Password Setting in P0000..................................................................................................5-3
5.2.2 Oriented Start-Up..............................................................................................................5-4
5.2.3 Setting Basic Application Parameters....................................................................................5-6
5.3 Setting Date and Time..................................................................................................................5-9
5.4 Blocking Parameters Modification.................................................................................................5-9
5.5 How to Conect a PC..................................................................................................................5-10
5.6 FLASH Memory Module.............................................................................................................5-10
CHAPTER 6
Troubleshooting and Maintenance
6.1 Operation of the Faults and Alarms...............................................................................................6-1
6.2 Faults, Alarms, and Possible Causes..............................................................................................6-2
6.3 Solutions for the Most Frequent Problems.......................................................................................6-9
6.4 Information for Contacting Technical Support...............................................................................6-10
6.5 Preventive Maintenance..............................................................................................................6-10
6.5.1 Cleaning Instructions........................................................................................................6-12
CHAPTER 7
Option Kits and Accessories
7.1 Option Kits.................................................................................................................................7-1
7.1.1 Safety Stop According to EN 954-1 Category 3 (Pending Certification)...................................7-1
7.2 Accessories.................................................................................................................................7-2
CHAPTER 8
Technical Specifications
8.1 Power Data.................................................................................................................................8-1
8.2 Electrical / General Specifications.................................................................................................8-4
8.2.1 Codes and Standards.........................................................................................................8-5
8.3 Mechanical Data.........................................................................................................................8-7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Safety Instructions
SAFETY INSTRUCTIONS
This manual provides information for the proper installation and
operation of the CFW-11M frequency inverter.
Only trained and qualified personnel should attempt to install,
start-up, and troubleshoot this type of equipment.
1
1.1 SAFETY WARNINGS IN THE MANUAL
The following safety warnings are used in this manual:
DANGER!
Failure to follow the recommended procedures listed in this warning may result in death, serious
injury, and equipment damage.
ATTENTION!
Failure to follow the recommended procedures listed in this warning may result in equipment
damage.
NOTE!
This warning provides important information for the proper understanding and operation of the
equipment.
1.2 SAFETY WARNINGS IN THE PRODUCT
The following symbols are attached to the product and require special attention:
Indicates a high voltage warning.
Electrostatic discharge sensitive components.
Do not touch them.
Indicates that a ground (PE) must be connected securely.
Indicates that the cable shield must be grounded.
Indicates a hot surface warning.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
1-1
Safety Instructions
1.3 PRELIMINARY RECOMMENDATIONS
DANGER!
Only trained personnel, with proper qualifications, and familiar with the CFW-11M and associated
machinery shall plan and implent the installation, starting, operation, and maintenance of this
equipment.
The personnel shall follow all the safety instructions described in this manual and/or defined by the
local regulations.
Failure to comply with the safety instructions may result in death, serious injury, and equipment
damage.
1
NOTE!
For the purpose of this manual, qualified personnel are those trained and able to:
1. Install, ground, power-up, and operate the CFW-11M according to this manual and to the current
legal safety procedures;
2. Use the protection equipment according to the established regulations;
3. Provide first aid.
DANGER!
Always disconnect the main power supply before touching any electrical device associated with the
inverter.
Several components may remain charged with high voltage and/or in movement (fans), even after
the AC power supply has been disconnected or turned off.
Wait at least 10 minutes to guarantee the fully discharge of capacitors.
Always connect the equipment frame to the ground protection (PE).
ATTENTION!
The electronic boards contain components sensitive to electrostatic discharges. Do not touch the
components and terminals directly. If needed, touch first the grounded metal frame or wear an
adequate ground strap.
Do not perform a withstand voltage test on any part of the inverter!
If needed, please, consult WEG.
NOTE!
Frequency inverters may cause interference in other electronic devices. Follow the recommendations
listed in Chapter 3 – Installation and Connection, to minimize these effects.
NOTE!
Fully read this manual before installing or operating the inverter.
1-2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Safety Instructions
ATTENTION!
Operation of this equipment requires detailed installation and operation instructions provided in the
User's Manual, Software Manual and Manual/Guides for Kits and Accessories. Only User's Manual is
provided on a printed version. The other manuals are provided on the CD supplied with the product.
This CD should be retained with this equipment at all times. A hard copy of this information may be
ordered through your local WEG representative.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
1-3
1
Safety Instructions
1
1-4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
General Instructions
GENERAL INSTRUCTIONS
2.1 ABOUT THE MANUAL
The purpose of this manual is to provide you with the basic
information needed to install, start-up in the V/f control mode
(scalar), and troubleshoot the most common problems of the
CFW-11M (Modular Drive) frequency inverter series.
It is also possible to operate the CFW-11M in the following control modes: V V W, Sensorless Vector and Vector with
Encoder. For further details on the inverter operation with other control modes, refer to the Software Manual.
2
For information on other functions, accessories, and communication, please refer to the following manuals:
Software Manual, with a detailed description of the parameters and advanced functions of the CFW-11M.
Incremental Encoder Interface Module Manual.
I/O Expansion Module Manual.
RS-232/RS-485 Serial Communication Manual.
CANopen Slave Communication Manual.
Anybus-CC Communication Manual.
These manuals are included on the CD supplied with the inverter or can be downloaded from the WEG
website.
2.2 TERMS AND DEFINITIONS
Normal Duty Cycle (ND): Inverter duty cycle that defines the maximum continuous operation current (IRAT-ND) and
the overload current (110 % for 1 minute). The ND cycle is selected by setting P0298 (Application) = 0 (Normal
Duty (ND)). This duty cycle shall be used for the operation of motors that are not subjected to high torque loads
(with respect to the motor rated torque) during its operation, starting, acceleration, or deceleration.
IRAT-HD: Inverter rated current for use with the normal duty (ND) cycle.
Overload: 1.1 x IRAT-ND / 1 minute.
Heavy Duty Cycle (HD): Inverter duty cycle that defines the maximum continuous operation current (IRAT-HD) and
the overload current (150 % for 1 minute). The HD cycle is selected by setting P0298 (Application) = 1
(Heavy Duty (HD)). This duty cycle shall be used for the operation of motors that are subjected to high torque
(with respect to the motor rated torque) during its operation, starting, acceleration, or deceleration.
IRAT-HD: Inverter rated current for use with the heavy duty (HD) cycle.
Overload: 1.5 x IRAT-HD / 1 minute.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
2-1
General Instructions
Current Unbalance (%):
Unbalance at power unit X - phase Y =
IY1 + IY2 + ... + IYN
IYAVG =
N
IYX - IYAVG
IYAVG
x 100
Where:
N = number of power units
IYN = Y phase current (U, V or W) of the power unit N (P0815 to P0829)
IYAVG = Y phase average current
Rectifier: Input circuit of inverters that transforms the AC input voltage in DC voltage. It is composed of power
diodes.
2
Pre-charge Circuit: Charges the DC bus capacitors with limited current, which avoids higher peak currents
at the inverter power-up.
DC Bus: Inverter intermediate circuit; DC voltage obtained from the rectification of the AC input voltage or
from an external power supply; feeds the output inverter bridge with IGBTs.
Power Modules U, V, and W: Set of two IGBTs of the inverter output phases U, V, and W.
IGBT: Insulated Gate Bipolar Transistor; basic component of the output inverter bridge. The IGBT works as an
electronic switch in the saturated (closed switch) and cut-off (open switch) modes.
Braking IGBT: Works as a switch to activate the braking resistors. It is controlled by the DC bus voltage
level.
PTC: Resistor which resistance value in ohms increases proportionally to the temperature increase; used as a
temperature sensor in electrical motors.
NTC: Resistor which resistance value in ohms decreases proportionally to the temperature increase; used as a
temperature sensor in power modules.
Keypad: Device that allows controlling the motor, and viewing/editing inverter parameters. The HMI presents
keys for motor command, navigation keys and a graphic LCD display.
FLASH Memory: Non-volatile memory that can be electronically written and erased.
RAM Memory: Random Access Memory (volatile).
USB: Universal Serial Bus; is a serial bus standard that allows devices to be connected using the ”Plug and
Play” concept.
PE: Protective Earth.
RFI Filter: Radio-Frequency Interference Filter for interference reduction in the Radio-Frequency range.
2-2
PWM: Pulse Width Modulation; pulsed voltage that feeds the motor.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
General Instructions
Switching Frequency: Frequency of the IGBTs switching in the inverter bridge, normally expressed in kHz.
General Enable: When activated, this function accelerates the motor via acceleration ramp set in the inverter.
When deactivated, this function immediately blocks the PWM pulses. The general enable function may be
controlled through a digital input set to this function or via serial communication.
Start/Stop: When enabled in the inverter (start), this function accelerates the motor via acceleration ramp up
to the speed reference. When disabled (stop), this function decelerates the motor via deceleration ramp up to
the complete motor stop; at this point, the PWM pulses are blocked. The start/stop function may be controlled
through a digital input set for this function or via serial communication. The operator keys
(Start) and
(Stop) of the keypad work in a similar way.
Heatsink: Metal device designed to dissipate the heat generated by the power semiconductors.
°C: Celsius degree.
°F: Fahrenheit degree.
AC: Alternated Current.
Amp, A: Ampères.
CFM: Cubic Feet per Minute; unit of flow.
cm: Centimeter.
DC: Direct Current.
ft: Foot.
hp: Horse Power = 746 Watts; unit of power, used to indicate the mechanical power of electrical motors.
Hz: Hertz.
in: Inch.
kg: Kilogram = 1000 grams.
kHz: Kilohertz = 1000 Hertz.
l/s: Liters per second.
lb: Pound.
m: Meter.
mA: Miliampère = 0.001 Ampère.
min: Minute.
mm: Millimeter.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
2-3
2
General Instructions
ms: Millisecond = 0.001 seconds.
Nm: Newton meter; unit of torque.
rms: "Root mean square"; effective value.
rpm: Revolutions per minute; unit of speed.
s: Second.
V: Volts.
2
Ω: Ohms.
2.3 ABOUT THE CFW-11M
The CFW-11M frequency inverter is a high performance product designed for speed and torque control of
threephaseinduction motors. The main characteristic of this product is the “Vectrue” technology, which has the
following advantages:
Scalar control (V/f), V V W, or vector control programmable in the same product;
The vector control may be programmed as “Sensorless” (which means standard motors without using
encoders) or as “Vector Control” with the use of an encoder;
The “Sensorless” control allows high torque and fast response, even in very low speeds or at the starting;
The “Vector with Encoder” control allows high speed precision for the whole speed range (even with a
standstill motor);
“Optimal Braking” function for the vector control: It allows the controlled braking of the motor, avoiding the
use of the braking resistor in some applications;
“Self-Tuning” feature for vector control. It allows the automatic adjustment of the regulators and control
parameters from the identification (also automatic) of the motor parameters and load.
The inverters of the CFW-11M series present a modular structure, with conFiguretions from one to five power
units (UP11 - generically called books), one control unit (UC11) and interconnecting cables. There is just one
control unit (UC11) that is able to control up to 5 UP11s.
The UP11 are fed directly from DC Bus (DC Link) and the UC11 is fed by means of a 24 Vdc power supply. An
application example with a 6 pulse input rectifier is presented in the figure 2.1.
The control of the power units is done by the UC11 control unit. The control unit contains the CFW-11M control
rack and the IPS1 board. This board sends signals to all the UP11 units (PWM, fan control, etc.) and receives
signals from them (feedbacks of voltage, current, etc.).
2-4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
General Instructions
UP11
UP11
Line
Motor
UP11
24 Vdc
power
supply
UC11
2
UP11
UP11
Figure 2.1 - A conFiguretion example with 5 UP11 and a 6 pulse rectifier
The CFW-11M can be supplied as a complete drive (AFW-11M) or as a panel mounting kit.
The panel mounting kit is composed by the control set and by UP11 power units, whose number varies according
to the current. The control set contains the UC11 control unit, the necessary cable sets for the connections between
the IPS1 and the power units, and the flat cable that connects the IPS1 board to the CC11 control board.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
2-5
General Instructions
Power section fans
UP11
Ext. 220V
Cabinet aux.
power supply
Precharge
Capacitor
bank
Motor
Line
Capacitor
bank
Three-phase
rectifier
Inverter with
IGBTs transistors
DC bus
(DC Link)
2
Power section fans
UP11
Feedback:
- voltage
- current
Power Section
PE
Control UC11
PC
SuperDrive G2 Software
WLP Software
USB
IPS1
Electronics power supplies and interface
between power and control
Accessories
I/O Expansion
(Slot 1 - white)
Keypad (remote)
Keypad
Digital
Inputs
(DI1 to DI6)
CC11
Control
Board with
a 32 bits
"RISC"
CPU
Analog
Inputs
(AI1 and AI2)
Encoder Interface
(Slot 2 - yellow)
COMM 1
(Slot 3 - green)
COMM 2
(anybus) (Slot 4 )
FLASH
Memory
Module
Analog
Outputs
(AI1 and AI2)
Digital Outputs
DO1 (RL1) to
DO3 (RL3)
Figure 2.2 - Block diagram for the CFW-11M
NOTE!
Several additional items are necessary for mounting the complete drive, such as input rectifier, fuses
in the DC supply of each power unit UP11, external pre-charge circuit and an input reactor with a
minimum impedance of 3 % in case of a 6 pulse rectifier.
NOTE!
The inclusion of a current transformer (CT) in the drive for the output short-circuit to the ground
protection is not necessary because each UP11 has its own internal protection.
2-6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
General Instructions
Keypad
Front Cover
Control Rack
IPS1 shield
2
IPS1 shield base
IPS1 board - Interface between
power and control
Figure 2.3 - UC11 main components
DC bus
DC Bus Capacitors
IGBTs module decoupling
capacitors
Set of IGBTs modules
Gate resistor board
Gate driver board
PSB1 board – Switched
mode power supply
CIM1 board – Interface
with the control
Hall Effect CT
Fan
Output reactor
Figure 2.4 - UP11 main components
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
2-7
General Instructions
UP11
UC11
CC11
XC60
XC60
Keypad
N1
N2
N3
N4
N5
N6
UP
UN
VP
VN
WP
WN
IPS1
XC40
XC40
External
Supply
Power Supply
24 Vdc(*)
CIM1
XC9
2
(*) Tolerance: ± 10 %;
Current: 4 A.
Figure 2.5 - UP11: Connections between the IPS1 and the CIM1 interface boards
XP
XN
+UD
- UD
PSB1
+ 20 V
XC5
+5V
+ 15 V
XC3
XC3
XC5
XP
+UD
- UD
CIM1
XN
Figure 2.6 - UP11: Connections between the CIM1 interface board and the PSB1 power supply board
CIM1
XC4A
XC33
Ext. 220 V
XC4AB
XC16A
XC16B
V4
V5
Power Section Fans
Figure 2.7 - UP11: Connections between the CIM1 interface board and the fans
2-8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
General Instructions
+UD
-UD
GDB5
XC1U
XC1
XC4
1
CRG9
2
3
4
5
8
XC2
XC14
XC14U
XC64U
XU
XC1
XC4
CIM1
1
3
4
5
8
XC2
XC14
10
11
10
11
10
11
TCV V
L1
(0,5 %)
+UD
-UD
GDB5
XC1W
2
CRG9
XC14V
XC64V
XV
TCU U
+UD
-UD
GDB5
XC1V
10
11
10
11
10
11
XC1
XC4
CRG9
1
2
3
4
5
XC2
XC14
8
UOUT
VOUT
2
WOUT
10
11
10
11
10
11
TCW W
XC14W
XC64W
XW
Figure 2.8 - UP11: connections between the CIM1 interface board, gate driver boards,
modules and sensors for the output voltage and output current
2.4 IDENTIFICATION LABEL FOR THE UC11
The UC11 identification label is located on the control rack.
WEG part number
UC11 model number
Serial number
Manufacturing date (day/month/year)
Figure 2.9 - UC11 identification label
Identification label
Figure 2.10 - Location of the identification label
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
2-9
General Instructions
2.5 IDENTIFICATION LABELS FOR THE UP11
There are two identification labels, one located at the inverter front cover and another inside the UP11, close
to the fans.
Manufacturing date (day/month/year)
Serial number
Maximum surrounding air temperature
UP11 Model
WEG part number
Inverter net weight
Rated input data (voltage, rated currents for
use with Normal Duty (ND) and Heavy Duty
(HD) cycles, frequency)
2
Rated output data (voltage, number of
power phases, rated currents for use with
Normal Duty (ND) and Heavy Duty (HD)
cycles, overload currents for 1 min and 3 s,
and frequency range)
Current specifications for use with the
Normal Duty (ND) cycle
Current specifications for use with the
Heavy Duty (HD) cycle
Available certifications
Figure 2.11 - UP11 identification label
Figure 2.12 - Location of the identification labels
2-10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
General Instructions
2.6 HOW TO SPECIFY THE CFW-11M MODEL (SMART CODE)
In order to specify the CFW-11M it is necessary only to fill in the desired voltage and current values in the
respective fields for the nominal supply voltage and the rated output current for normal overload regime (ND)
in the intelligent code according to the example of the table 2.1.
Table 2.1 - Smart code
Inverter Model
Example
EX
Field
Market
description identification
(defines
the manual
language
and
the factory
settings)
Available
options
2 characters
Available Option Kits
Refer to chapter 8 for a list of models for
the CFW-11M series and for a complete
inverter's technical specification
Refer to the chapter 7 for more details on the options.
CFW11M
WEG
CFW-11M
frequency
inverter
series
T
5 (*)
S
Number Nominal Option kit
of
output
output voltage
phases
__
Braking
__
Safety stop
__
Special
hardware
__
Special
software
T=
threephase
Blank=
standard
(without
internal
dynamic
braking)
RB=
regenerative
braking
Blank=
standard
(safety stop
function is
not available)
Y=
safety stop
according to
EN-954-1
category 3
Blank=
standard
H1=special
hardware
#1
Blank=
standard
S1=special
software #1
0470
Rated
output
current for
use with
the
Normal
Duty
(ND) cycle
4=380...
480 V
5=500...
600 V
6=660...
690 V
S=standard
product
O=product
with option
kit
Z
Character
that
identifies
the code
end
(*) This field (voltage) represents the three-phase input voltage for the rectifier that supplies the CFW-11M with DC voltage. The rectifier is not
part of the CFW-11M.
E.g.: CFW11M0470T5SZ corresponds to a modular CFW-11 470 A three-phase, with power supply voltage
from 500 V to 600 V, standard. An inverter for 380-480 V would be specified as CFW11MXXXXT4SZ and
for voltage of 660-690 V it would be specified as CFW11MXXXXT6SZ (where XXXX is replaced by the inverter
current). The possible nominal current options for an inverter in normal overload regime (ND) are showed in
the table 2.2, according to the rated input voltage.
Table 2.2 - Nominal currents at normal overload regime (ND)
380-480 V
500-600 V
660-690 V
0600 = 600 A
1140 = 1140 A
1710 = 1710 A
2280 = 2280 A
2850 = 2850 A
0470 = 470 A
0893 = 893 A
1340 = 1340 A
1786 = 1786 A
2232 = 2232 A
0427 = 427 A
0811= 811 A
1217 = 1217 A
1622 = 1622 A
2028 = 2028 A
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
2-11
2
General Instructions
2.7 RECEIVING AND STORAGE
The CFW-11M power units, as well as the control sets, are supplied packed in wooden boxes (refer to the figure 2.14).
2
Figure 2.13 - Power unit packing
There are identification labels outside these boxes, the same as the ones fixed on the respective products.
In order to open the box:
1- Put the control set box on a table with the help of two people; in case of the power units, put the box on
the floor.
2- Open the wood crate.
3- Remove all the packing material (the cardboard or styrofoam protection) before removing the inverter.
Check the following items once the inverter is delivered:
Verify that the product identification label corresponds to the model number on your purchase order.
Inspect the product for external damage during transportation.
Report any damage immediately to the carrier that delivered your product.
If the products were note installed immediately, store them in a clean and dry place (temperature between -25 °C
and 60 °C) with a cover in order to avoid the contamination with dust.
2-12
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
General Instructions
ATTENTION!
Capacitor reforming is required if the inverter or power units are stored for long periods of time
without power. Refer to the procedures in item 6.5 - table 6.3.
2
Figure 2.14 - Do not tilt the power units
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
2-13
General Instructions
2
2-14
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
INSTALLATION AND CONNECTION
This chapter provides information on installing and wiring the
CFW-11M. The instructions and guidelines listed in this manual
shall be followed to guarantee personnel and equipment safety,
as well as the proper operation of the inverter.
3.1 INSTALLATION ENVIRONMENT
Avoid installing the inverter in an area with:
Direct exposure to sunlight, rain, high humidity, or sea-air;
Inflammable or corrosive gases or liquids;
Excessive vibration;
Dust, metallic particles, and oil mist.
Environment conditions for the operation of the inverter:
Temperature:
CFW11M…T4 models with switching frequencies of 1.25 kHz or 2.5 kHz, CFW11M…T5 and CFW11M…
T6 with switching frequency of 1.25 kHz:
-10 °C to 45 °C (14 °F to 113 °F) - (measured around the inverter) nominal conditions.
From 45 °C to 55 °C (113 °F to 131 °F) - 2 % current reduction for every Celsius degree (or 1.11 % each °F)
above 45 °C (113 °F).
CFW11M…T5 and CFW11M…T6 with switching frequency of 2.5 kHz:
-10 °C to 40 °C (14 °F to 104°F) - (measured around the inverter) nominal conditions.
From 40 °C to 55 °C (104 °F to 131°F) - 2 % current reduction for every Celsius degree (or 1.11 % each °F)
above 40 °C (104 °F).
Humidity: from 5 % to 90 % non-condensing.
Altitude: up to 1000 m (3,300 ft) - standard conditions (no derating required).
From 1000 m to 4000 m (3,300 ft to 13,200 ft) - 1 % of current derating for each 100 m (or 0.3 % each
100 ft) above 1000 m (3,300 ft) altitude.
Pollution degree: 2 (according to EN50178 and UL508C) with non-conductive pollution. Condensation
shall not originate conduction through the accumulated residues.
3.2 LIST OF COMPONENTS
The panel mounting kit is composed by the control set and by UP11 power units, whose number varies according
to the current. The control set contains the UC11 control unit, the necessary cable sets for the connections between
the IPS1 and the power units, and the flat cable that connects the IPS1 board to the CC11 control board.
Table 3.1 - Currents and conFiguretion in 380-480 V
Nominal Current (A)
ND
HD
Number of Power Units
UP11-02
600
515
1
1140
979
2
1710
1468
3
2280
1957
4
2850
2446
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-1
3
Installation and Connection
Table 3.2 - Currents and conFiguretion in 500-600 V
Nominal Current (A)
ND
HD
Number of Power Units
UP11-01
470
380
1
893
722
2
1340
1083
3
1786
1444
4
2232
1805
5
Table 3.3 - Currents and conFiguretion in 660-690 V
Nominal Current (A)
ND
HD
3
Number of Power Units
UP11-01
427
340
1
811
646
2
1217
969
3
1622
1292
4
2028
1615
5
Each cable set contains one optical fiber and one DB-25 cable. Both do the connection between the IPS1
board (control unit) and the CIM1 board (power unit).
Table 3.4 - Cable sets
Weg Part
Number
Optical Fiber Length
mm (in)
DB-25 Cable Length
mm (in)
10411757
2350 (92.52)
2550 (100.39)
10509891
2800 (110.24)
3000 (118.11)
10411758
3400 (133.86)
3600 (141.73)
10411759
3900 (153.54)
4100 (161.42)
The cable sets that come with the control sets are described in the table 3.5.
Table 3.5 - Number of cable sets
Number of Power Units
1
2
Number of Cable Sets
1X 10411757
2X 10411757
3
2X 10411757
1X 10509891
4
2X 10411757
1X 10509891
1X 10411758
5
2X 10411757
1X 10509891
1X 10411758
1X 10411759
The other components of the drive are responsibility of the integrator. Among these components we are able
to point out the input rectifier, the power bus bars, the pre-charge circuit, the panel fans, the protection fuses,
input reactance, etc.
3-2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
3.3 MECHANICAL INSTALLATION
The power units must be properly secured in the drive cabinet, making it possible the easy withdrawal and
reinsertion in case of maintenance. The fastening must also be done so that it prevents panel transportation
damage.
VENTILADOR DO PAINEL
(QUANDO NECESSÁRIO)
250
The “Panel Mounting Rack” accessory simplifies the mounting of the power units and
allows their simple fastening
SAÍDA DE AR
and movement. Refer to the section 7.2 for more details.
SAÍDA DE AR
150
Ø22.5 HOISTING EYES - WEIGHT 171 kg
3
ABERTURA DE
NA SUPERFÍCIE
PAI
VENTILADOR DO
PAINEL DO
VENTILADOR
VENTILADOR
PAINEL DO PAINEL
(QUANDO NECESSÁRIO)
(QUANDO NECESSÁRIO)
(QUANDO NECESSÁRIO)
250
Figure 3.1 - UP11: Hoisting holes
SAÍDA DE ARSAÍDA DE ARSAÍDA DE AR
250
250
SAÍDA DE ARSAÍDA DE ARSAÍDA DE AR
ENTRADA DE AR
150
150
150
ABERTURA DE
VENTILAÇÃO
ABERTURA
DE
ABV
NA SUPERFÍCIE
FRONTALNA
DOS
NA SUPERFÍCIE
PAINEL
PAINE
ENTRADA DEENTRADA
AR
DEENTRADA
AR
DE AR
Figure 3.2 - Mounting of the UP11 side by side without lateral spacing
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-3
Installation and Connection
VENTILADOR DO PAINEL
(QUANDO
NECESSÁRIO)
PANEL
FAN (WHEN
REQUIRED)
250
250
(9.84)
OUTLET
SAÍDA AIR
DE AR
OUTLET
AIRAR
SAÍDA DE
150
150
(5.91)
VENTILATION OPENINGS ON
FRONTAL
PANEL
ABERTURA
DESURFACE
VENTILAÇÃO
NA SUPERFÍCIE FRONTAL DO
PAINEL
3
INLET
AIR
ENTRADA
DE AR
Figure 3.3 - Clearance requirements for air circulation
The UP11 wheels facilitate its insertion into and withdrawal from the panel (figure 3.4).
211
56,5
221,9
584,9
61,5
550,6
221,9
85
175
18,9
18,9
193
WHEELS (BALL-BEARINGS)
COVERED
WITH
RODAS
(ROLAMENTOS)
REVESTIDAS
NYLON
FOR MOVEMENT
IN THE CABINET
DE
NYLON
PARA MOVIMENTAÇÃO
8,9
Figure 3.4 - UP11: bottom view mm (in)
3-4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
Figure 3.5 - Fixing holes of the power unit
3
509,8
SUPPORTSPARA
FOR
SUPORTE
TOP FIXING
OF THE
FIXAÇÃO
SUPERIOR
DRIVE
DO DRIVE
9,2
14,5
14,5
100,5
100,5
Figure 3.6 - Supports for top fixing mm (in)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-5
Installation and Connection
Mounting of the UC11 at the panel door: Control rack with flange mounting and IPS1 module mounted at the bottom
part of the door. The control rack is secured with four M3 screws (tightening torque: 0.5 Nm).
CFW-11
INTERFACE CARD
POWER-CONTROL
3
Figure 3.7 - Example of the mounting of the control rack and its base
Figure 3.8 - Final mounting aspect
3-6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
190
(7.48)
Ø 5.2 (4x)
(0.20)
286.5
(11.28)
290
(11.42)
143.3
(5.64)
R8 (4x)
(0.32)
186.5
(7.34)
93.3
(3.67)
2 (0.08)
7 (0.27)
7 (0.27)
11
(0.43)
3
Figure 3.9 - Control rack fixing and the necessary cuts mm (in)
292
(11.5)
41.5
(1.63)
283.6
(11.17)
M6 (4x) FOR THE IPS1
MODULE FIXING
Figure 3.10 - IPS1 module base fixing mm (in)
The IPS1 module base is fixed with four M6 bolts (tightening torque: 8.5 Nm).
The total air outflow of the power unit is 1150 m3/h (320 l/s; 677 CFM). It is recommended an outflow of 1350
m3/h (375 l/s; 795 CFM) per power unit at the air exhaustion.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-7
Installation and Connection
3.3.1 HMI Installation at the Cabinet Door or Command Panel (Remote HMI)
28.5 [1.12]
23.5 [0.93]
103.0 [4.06]
113.0 [4.45]
23.4 [0.92]
16.0 [0.63]
35.0 [1.38]
∅4.0 [0.16] (3X)
65.0 [2.56]
3
Figure 3.11 - Data for the HMI installation at the cabinet door or command panel – mm (in)
The keypad frame accessory can also be used to fix the HMI, as mentioned in the section 7.2.
3.4 ELECTRICAL INSTALLATION
DANGER!
The following information is merely a guide for proper installation. Comply with applicable local
regulations for electrical installations.
DANGER!
Make sure the AC power supply is disconnected before starting the installation.
ATTENTION!
The CFW-11M can be connected in circuits with symmetrical short circuit capability up to
150000 Arms (480 V/690 V maximum).
ATTENTION!
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with applicable local codes.
3.4.1 Input Rectifier
The main rectifier bridge is selected to comply with the nominal power of the drive. The heat dissipation caused
by losses at the rectifier bridge should be taken into account for the sizing of the heatsink, as well as in the
heating up of the panel internal air.
3-8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
Table 3.6 - Sizing of the main bridge
Reverse Voltage
Output DC current
Main Rectifier Bridge
≥1600 V
1.15 Drive output current
The pre-charge circuit resistors must be sized according to the following criteria:
- Maximum voltage;
- Maximum energy;
- Power overload capacity of the resistors during the pre-charge period (energy dissipation capacity).
The characteristics of the resistors must be obtained with their manufacturer.
3
0
0.2
0.4
0.6
0.8
t
1
1.2
1.4
0.4 s
t
0.6 s
Figure 3.12 - Current during the pre-charge
Table 3.7 - Sizing of the pre-charge
Peak current during the pre-charge (A)
Energy stored in the capacitor bank (J)
Pre-charge duration (s)
0.82∙(Vline/R)
400 V line
N∙0.016∙Vline2
Other lines
N∙0.073∙Vline2
400 V line
0.09∙N∙R
Other lines
0.04∙N∙R
Where R is the ohmic value of the resistor used for each phase and N is the number of power units.
E.g.:
At a drive composed by three power units, whose line voltage at the input of the rectifier was 380 Vrms
(400 V line), the obtained values would be the following:
- Energy stored in the capacitor bank: 3∙0.016∙(380)2 = 6931 J.
- By using three 10 Ω resistors (one per phase), each resistor must withstand 2310 J.
- The resistor manufacturer is able to inform the power supported by the component.
- The peak current during the pre-charge would be 31 A and the pre-charge duration would be of 2.7 s.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-9
Installation and Connection
Ponte
Retificadora
K1
+UD
R
A
B
S
C
T
-UD
Pré-carga
K(PCR)
R
R
R
Stop
RT1
SOFF
KA1
KA2
KA2
IPS
XC3:1
220 VAC
Externo
NA
SON
KA1
K(PCR)
KA1
RT1
KA2
2
C
3
NF
PCR
3
KA2
K(PCR)
K1
Figure 3.13 - Pre-charge circuit example
The CFW-11M input rectifier can be supplied through a contactor or a motorized circuit breaker (represented
by K1), whose command must be interlocked with the pre-charge contactor K(PCR) command. The figure 3.14
presents an example of the recommended pre-charge circuit for the CFW-11M inverter, with simplified power
and command diagrams. There is already a relay (XC3:1/2/3) configured with the function "Pre-charge OK" in
the IPS board (refer to the table 3.21). This relay must be used to command the pre-charge contactor and the
main contactor (motorized circuit breaker). Furthermore, the pre-charge length must be timed for the protection
of the auxiliary circuit (resistors, rectifier bridge). This function is carried out by a timer with a normally-closed
on-delay contact, represented as RT1 in the figure 3.14.
3-10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
L1.a
+UD
L1.b
-UD
Figure 3.14 - 12 pulse parallel with interphase reactance (L1) conFiguretion
The 12 pulse parallel conFiguretion requires the use of an interphase reactance in order to assure the correct
current division between the bridges. In the case of using this conFiguretion, consult WEG.
3.4.2 Bus Bars
The panel bus bars must be sized according to the rectifier output current and the drive output current. It is
recommend the use of copper bars. In case that aluminum bars have to be used, it is necessary to clean the
contacts and to apply an antioxidant compound. If the compound is not used, any copper-aluminum junction
will suffer an accelerated oxidation.
3.4.3 Fuses
It is recommended the use of fuses suitable for operation with direct current at the UP11 DC supply. The
maximum bus voltage at the 400 V line is 800 Vdc, at the other lines it is 1200 Vdc (IGBT overvoltage trip
level). Fuses used in AC lines can be used; however, a derating in the AC voltage must be applied. Consult the
fuse manufacturer in order to obtain the derating factor.
Fuse examples:
- 400 V line: 12,5URD73TTF900 (FERRAZ)
- Other lines: 12,5URD73TTF630 (FERRAZ)
Figure 3.15 - DC link fuses
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-11
3
Installation and Connection
3.4.4 General Connection Diagram and Layout
The figure 3.16 presents a general diagram for an inverter with five Power Units (UP11), with the connections
between the Control Unit UC11 and the UP’s (XC40 DB25 connectors and optical fibers), the power connections
of the UP’s (+UD, -UD, U, V, W and GND), besides the auxiliary ventilation (220 V) and UC11 (24 Vdc) supply
connections. For a reduced number of UP11’s, connect them in crescent order (1, 2, 3, etc.), leaving the last
positions without connections.
+UD -UD
UC11
XC40E
UH5
UL5
VH5
VL5
WH5
WL5
V
XC40
W
+UD
UP11
UH
UL
VH
VL
WH
WL
UH
UL
VH
VL
WH
WL
XC33
-UD
220V Ext.
U
V
W
+UD
UP11
XC33
-UD
220V Ext.
U
U
V
V
W
W
MOTOR
+UD
-UD
UP11
XC33
UH
UL
VH
VL
WH
WL
220V Ext.
U
XC40
UH
UL
VH
VL
WH
WL
XC33
UP11
220V Ext.
U
V
W
+UD
-UD
UP11
XC33
XC40D
UH4
UL4
VH4
VL4
WH4
WL4
-UD
XC40
XC40B
XC60
Braking module
DB9 connector
+UD
XC40
+24 Vdc DI’s
output
1-NO
2-C
3-NC
4-GND_24
5-+24V
UH3
UL3
VH3
VL3
WH3
WL3
XC40C
Pre-charge
relay
1
2
3
IPS1
(*) Tolerance +/- 10 %
Current: 4 A
UH2
UL2
VH2
VL2
WH2
WL2
XC9
External 24 Vdc*
power supply
XC3
CC11
XC6
HMI
XC60
3
UH
UL
VH
VL
WH
WL
XC40
XC40A
UH1
UL1
VH1
VL1
WH1
WL1
220V Ext.
U
V
W
Figure 3.16 - General Diagram
3-12
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
The power electrical connections of the panel must assure equal impedance at the DC bus and output connections.
Refer to the example in the figure 3.17 and to the lateral section views in figures 3.18, 3.19 and 3.21. At the
input (DC bus) and the motor output busbars, the dimensions identified as A, B, C and D must be approximately
equal to the dimensions A’, B’, C’ and D’, respectively, as exemplified in the figure 3.17.
1
A
2
B
C
D
E
3
2
1
3
F
F
F
3
A’
B´
C´
D´
Figure 3.17 - Symmetry details of the panel constructive layout
The interconnection between the DC bus and each UP11 can be done with flat braided cables according to the
figure 3.18 example, sized to withstand the DC bus current, according to the table 8.1. The figure 3.20 presents
an example of flat braided cable used by WEG, using a fuse at +UD. Alternatively, fuses at both connections
(+UD and –UD) can be used.
NOTE!
It is important that all the flat braided cables present the same length (defined by the dimension “E”)
that will depend on the panel construction, and that all the fuses mounted on the DC bus are identical
and mounted on the same busbar (+UD or –UD) in all the UP11’s when only one fuse per UP11 is
used (in order to get more details refer to the section 3.4.3).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-13
Installation and Connection
1
E
2
E
-UD
+UD
RECTIFIER
1
2
Figure 3.19 - Lateral section view: Detail of the DC bus
connections
17
(0.67)
3
30
(1.18)
26
(1.02)
60
(2.36)
Figure 3.18 - Lateral section view: Detail of the flat braided cables
and fuse connections
17
(0.67)
26
(1.02)
Ø 14 (3x)
(0.55)
25
(0.98)
8±1
60
(2.36)
E
50
(1.97)
BRAIDED WIRE GAUGE: AWG-40 (0.08 mm)
Figure 3.20 - Example of flat braided cable
Besides the panel constructive form, some precautions must be taken regarding the connection of the output
cables to the motor, in order to assure equal impedances among the UP’s connected in parallel. The figures
3.19 and 3.21 present details in lateral section views of the DC bus (+UD and –UD) input connections and
the output to the motor (U, V, W and GND) connections.
NOTE!
The length of the cables that connect each of the Power Units to the output busbars, represented by
the “F” dimension on the figure 3.21, must be the same for all the phases (U, V and W). Refer to the
table 3.8 for more details on the cables.
3-14
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
3
F
F
F
3
W
V
U
GND
MOTOR
Figure 3.21 - Lateral section view: Detail of the output to the motor connections
The figure 3.22 presents the adequate installation layout for five Power Units.
3
RECTIFIER
Figure 3.22 - Example of adequate installation layout for 5 UP11’s
NOTE!
The connection of the motor cables at points different from the presented in the figure 3.22 (figures
3.23 and 3.24 present some inadequate connection forms) does not assure the impedance balance
between the UP’s connected in parallel, being able to cause current imbalance among the UP’s.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-15
Installation and Connection
3
Figure 3.23 - Example of inadequate installation layout for 5 UP11’s
Figure 3.24 - Example of inadequate installation layout for 5 UP11’s
3-16
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
The figure 3.25 presents the adequate installation layout for three Power Units.
RECTIFIER
3
Figure 3.25 - Example of adequate installation layout for 3 UP11’s
NOTE!
The connection of the motor cables at points different from the presented in the figure 3.25 (the
figure 3.26 an inadequate connection form) does not assure the impedance balance between the
UP’s connected in parallel, being able to cause current imbalance among the UP’s.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-17
Installation and Connection
3
Figure 3.26 - Example of inadequate installation layout for 3 UP11’s
3.4.5 UP11 Connections
The fastening of the UP11 input connections is done with four M12 x 25 bolts (tightening torque: 60 Nm), refer
to the figure 3.27.
95,5
NEGATIVE
INPUT
BAR (-UD)
BARRAMENTO
DE ENTRADA
NEGATIVO (- UD)
170
26
26
60
61,3
BARRAMENTO
DE ENTRADA
POSITIVO (+ UD)
POSITIVE
INPUT
BAR (+UD)
Figure 3.27 - UP11 input bus bars: Input DC connections mm (in)
3-18
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
The output connections at the internal reactance are done by means of six M12 x 30 bolts (tightening torque:
60 Nm), 2 bolts per phase are used. The bus bars are of 40 x 10 mm and the fastening is done through M12
nuts inserted into the bar. Refer to the figure 3.28.
Ø22.5 HOISTING
HOLE
22,5 OLHA
(0.89in) PARA IÇAMENTO
OUTPUT
BARRA DEBARS
SAÍDA''U''
"U"
OUTPUT
BARRA DEBARS
SAÍDA''V''
"V"
95
3
55,2
95
40
OUTPUT
BARRA DEBARS
SAÍDA''W''
"W"
20
87,4
40
Figure 3.28 - UP11 output bus bars: Output connections to the motor mm (in)
Use two cables in parallel, with the recommended gauge indicated in the table 3.8, for connecting the UP11
output reactor to the output bus bar (motor connection).
Table 3.8 - Output cables
Current (A)
600
515
470
418
427
340
Voltage (V)
380-480
500-600
660-690
ND
Minimum cable cross-section
area (mm2)
(2X) 240
Regimen
HD
(2X) 185
ND
(2X) 150
HD
(2X) 120
ND
(2X) 120
HD
(2X) 70
The bolt used to connect the UP11 grounding cable is M12 x 30 (tightening torque: 60 Nm). Refer to the
figure 3.29.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-19
Installation and Connection
3
ATERRAMENTO
FRONTAL
FRONT GROUNDING
COM
PARAFUSO
M12BOLT
WITH
AN M12
Figure 3.29 - UP11 ground connection point
Use cables with the recommended gauge indicated in the table 3.9 for grounding the UP11 power units.
Table 3.9 - Grounding cables
Current (A)
600
515
470
418
427
340
3-20
Voltage (V)
380-480
500-600
660-690
Regimen
Minimum cable cross-section area (mm2)
ND
240
HD
185
ND
150
HD
120
ND
120
HD
70
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
Connectors for Optical Fibers
DB25 Connectors
3
Figure 3.30 - Connection points for the control cables on the UP11
Keep the optic fiber bending radius bigger or equal to 35 mm. If the control is mounted on the panel door, let
a curvature that causes a minimum stress on the optic fiber cables when the door is opened or closed.
CONECTOR
DE CONNECTOR
ENTRADA 220V
220 V INPUT
Figure 3.31 - Fan supply terminals: 220 V/4 A
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-21
Installation and Connection
3.4.6 UC11 Connections
The DIM1 and DIM2 digital inputs located on the IPS1 board (figure 3.35) monitor the F406, F408, F410, F412
and A010 faults/alarm. They are CLOSED during normal operation. When they OPEN faults/alarm occur.
- The DIM1 digital input is connected at XC1:4 and XC1:5 (common).
- The DIM2 digital input is connected at XC2:4 and XC2:5 (common).
3
1
2
3
XC1
No Function
No Function
DGND
4
DIM1
5
COM
Factory Default Function
DGND Reference.
Isolated digital input DIM1,
programmable at P0832. Refer to High level ≥ 18 V.
Low level ≤ 3 V.
the programming manual.
Maximum input voltage: 30 V.
Common point of the IPS board
Input current: 11 mA @ 24 Vdc.
digital inputs.
1
2
3
XC2
No Function
No Function
DGND
4
DIM2
5
COM
Factory Default Function
DGND Reference.
Specifications
Grounded via the IPS board shield.
Isolated digital input DIM2,
programmable at P0833. Refer to High level ≥ 18 V.
the programming manual.
Low level ≤ 3 V.
Maximum input voltage: 30 V.
Common point of the IPS board
Input current: 11 mA @ 24 Vdc.
digital inputs.
XC3
Factory Default Function
1
PCR1 (NO)
2
PCR2 (C)
3
PCR3 (NC)
4
GND_24.
5
Specifications
Grounded via the IPS board shield.
RL digital output with pre-charge
function (PCR).
0 V reference for the 24 Vdc
power supply.
+24 V
24 Vdc power supply.
Specifications
Contact capacity: 1 A
Maximum voltage: 240 Vac
NO - Normally open contact;
C - Common;
NC - Normally closed contact.
Isolated 24 Vdc ± 8 % power supply.
Capacity: 600 mA.
Note 1: This power supply may be used for
feeding the IPS board digital inputs
DIM1 (ISOL) and DIM2 (ISOL).
Note 2: This power supply is isolated from
the 24 Vdc input used to feed the IPS.
Figure 3.32 - Application example with high level at the DIs
Table 3.10 - Functions of the digital inputs
3-22
Parameters
Sequential
Number
P0832/P0833
0
1
2
3
4
5
Digital Input Function
Not Used
Extern Fault
Refrigeration Fault
Braking Resistor Overtemperature
Rectifier Overtemperature
Rectifier High Temperature
Associated
Fault/Alarm
F406
F408
F410
F412
A010
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
XC60: Connection with the
control rack
DB25 connectors
XC40A to XC40E
(connection with the UP11)
XC9 connector:1,3
+24 Vdc power supply
DB9 connector (XC6) for
DBW-01 (380-480 V) and
DBW-02 (500-690 V)
Braking Modules
DIM 1 (XC1:4/5)
Connectors for Optical Fibers
(connection with the UP11)
Pre-charge RL (XC3:1/2/3)
DIM 2 (XC2:4/5)
Figure 3.33 - IPS1 connection points
The IPS1 board mechanical installation itself makes its ground connection. This is done in several points.
3
Grounding point
Figure 3.34 - IPS1board grounding
The IPS1 shield securing screws must assure the electric contact between the shield and the panel for grounding
purposes.
Figure 3.35 - IPS1 shield fixed on the panel
The control rack grounding must be done with a flat type braided ground strap with a minimum width of 5 mm
and a minimum cross section of 3 mm2, with standard 6.35 mm FASTON terminal (e.g., TYCO 735075-0 and
180363-2) and M4 ring terminal. Refer to the figure 3.36.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-23
Installation and Connection
Braided Ground Strap
Figure 3.36 - Control rack grounding
The panel door must be grounded with a braided ground strap.
3
Figure 3.37 - Panel door grounding
The IPS1 board is fed by a +24 Vdc ±10 % power supply. This supply must have a minimum capacity of 4 Adc.
3.4.7 Dynamic Braking
The braking torque that can be obtained from the frequency inverter without braking resistors varies from 10 %
to 35 % of the motor rated torque.
Braking resistors shall be used to obtain higher braking torques. In this case, the energy regenerated in excess
is dissipated in a resistor mounted externally to the inverter.
This type of braking is used in cases where short deceleration times are desired or when high inertia loads are
driven.
The “Optimal Braking” feature may be used with the vector control mode, which eliminates in most cases the
need of an external braking resistor.
NOTE!
Set P0151 and P0185 to their maximum values (400 V, 800 V or 1200 V) when using dynamic
braking.
3-24
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
3.4.7.1 Sizing the Braking Resistor
The following application data shall be considered for the adequate sizing of the braking resistor:
- Desired deceleration time;
- Load inertia;
- Braking duty cycle.
The maximum braking current defines the minimum braking resistor value in ohms.
The DC bus voltage level for the activation of the dynamic braking function is defined by parameter P0153
(dynamic braking level).
The power of the braking resistor is a function of the deceleration time, the load inertia, and the load torque.
If the use of dynamic braking is necessary, the IPS1 board (XC6 connector – DB9) has the capability of
commanding a DBW-01/DBW-02. Refer to the DBW-01/DBW-02 Installation, ConFiguretion and Operation
Guide.
If necessary, accessory boards will be mounted on the standard control rack. All the CFW-11 line accessory
boards are available.
DBW-01/02
Interconnection
cable
IPS1
Supply
Network
XC6
XC3
Contactor
R
S
T
-UD
+UD
Fan
110 V or 220 V
DIX (CC11)
No External
Fault
Thermal
Relay
Thermostat
Control
Supply
Braking
Resistor
Figure 3.38 - Connections between the DBW, the IPS1 board and the Braking Resistor
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-25
3
Installation and Connection
XC6
Figure 3.39 - IPS1 board - XC6 connector location
3.4.7.2 Motor Connections
ATTENTION!
The inverter has an electronic motor overload protection that shall be adjusted according to the
driven motor. When several motors are connected to the same inverter, install individual overload
relays for each motor.
3
ATTENTION!
The motor overload protection available in the CFW-11 is in accordance with the IEC60947-4-2 and the
UL508C standards.
Important considerations for the UL508C:
Trip current equal to 1.25 times the motor nominal current (P0401) adjusted in the "Oriented
Start-up" routine.
The maximum allowed value for the parameter P0159 (Motor Thermal Class) is 3 (Class 20).
The maximum allowed value for the parameter P0398 (Motor Service Factor) is 1.15.
ATTENTION!
If a disconnect switch or a contactor is installed between the inverter and the motor, never operate
them with a spinning motor or with voltage at the inverter output.
The characteristics of the cable used for the inverter and motor interconnection, as well as the physical location are
extremely important to avoid electromagnetic interference in other equipment and to not affect the life cycle
of motor windings and motor bearings controlled by inverters.
Recommendations for the motor cables:
Unshielded Cables:
Can be used when it is not necessary to meet the European directive of electromagnetic compatibility
(89/336/EEC).
Keep motor cables away from other cables (signal cables, sensor cables, control cables, etc.), according to
table 3.11.
The emission of the cables may be reduced by installing them inside a metal conduit, which shall be grounded
at both ends.
Connect a fourth cable between the motor ground and the inverter ground.
3-26
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
Note:
The magnetic field created by the current circulation in these cables may induce current in close metal pieces, heat
them, and cause additional electrical losses. Therefore, keep the 3 (three) cables (U, V, W) always together.
Shielded Cables:
Are mandatory when the electromagnetic compatibility directive (89/336/EEC) shall be met, as defined by
the standard EN 61800-3 “Adjustable Speed Electrical Power Drive Systems”.
These cables act mainly by reducing the irradiated emission in the radio-frequency range.
Are mandatory when RFI filters, internally or externally mounted, are installed at the inverter input.
In reference to the type and details of installation, follow the recommendations of IEC 60034-25 “Guide
for Design and Performance of Cage Induction Motors Specifically Designed for Converter Supply” – refer
to a summary in figure 3.40. Refer to the standard for further details and eventual modifications related to
new revisions.
Keep motor cables away from other cables (signal cables, sensor cables, control cables, etc.), according to
table 3.11.
The grounding system shall be well interconnected among the several installation locations such as the
grounding points of the motor and the inverter. Voltage difference or impedance between the several points
may cause the circulation of leakage currents among the equipment connected to the ground, resulting in
electromagnetic interference problems.
Table 3.11 - Minimum separation distance between motor cables and all other cables
Cable length
≤ 30 m (100 ft)
> 30 m (100 ft)
Minimum separation distance
≥ 10 cm (3.94 in)
≥ 25 cm (9.84 in)
oooooooo
oo
U
W
V
oooooooooo
oo
ooooooooo
o
oo
(a) Symmetrical shielded cables: three concentric conductors with or without a ground conductor, symmetrically manufactured, with
an external shield of copper or aluminum.
ooo ooooo
oo
PEs
AFe
Notes:
(1) SCu = copper or aluminum external shielding.
(2) AFe = steel or galvanized iron.
(3) PE = ground conductor.
(4) Cable shielding shall be grounded at both ends (inverter and motor). Use 360º connections for a low impedance to high-frequencies.
(5) For using the shield as a protective ground, it shall have at least 50 % of the power cables conductivity. Otherwise, add an external ground
conductor and use the shield as an EMC protection.
(6) Shielding conductivity at high-frequencies shall be at least 10 % of the power cables conductivity.
Figure 3.40 - Motor connection cables recommended by IEC 60034-25
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-27
3
Installation and Connection
3.4.8 Control Connections
The control connections (analog inputs/outputs, and digital inputs/outputs) must be made at the electronic
control board CC11 terminal strip XC1, at the UC11 control unit.
Functions and typical connections are presented in figures 3.41 (a) and (b).
CW
Connector XC1
rpm
+REF
2
AI1+
Analog input #1:
Speed reference (remote)
3
AI1-
Differential
Resolution: 12 bits
Signal: 0 to 10 V (RIN=400 kΩ) / 0 to 20 mA / 4 to 20 mA (RIN=500 Ω)
Maximum voltage: ±30 V
4
REF-
Negative reference for
potentiometer
Output voltage: -4.7 V, ±5 %.
Maximum output current: 2 mA
5
AI2+
Analog input #2:
No function
6
AI2-
Differential
Resolution: 11 bits + signal
Signal: 0 to ±10 V (RIN=400 kΩ) / 0 to 20 mA / 4 to 20 mA (RIN=500 Ω)
Maximum voltage: ±30 V
Analog output #1:
Speed
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (RL ≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (RL ≤ 500 Ω)
Protected against short-circuit.
Reference (0 V) for the
analog outputs
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor.
Analog output #2:
Motor current
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (RL ≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (RL ≤ 500 Ω)
Protected against short-circuit.
Reference (0 V) for the
analog outputs
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor.
Reference (0 V) for the
24 Vdc power supply
Common point of the
digital inputs
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor.
24 Vdc power supply
24 Vdc power supply, ±8 %.
Capacity: 500 mA.
Note: In the models with the 24 Vdc external control power supply
(CFW11MXXXXXXOW) the terminal 13 of XC1 becomes an input, i.e.,
the user must connect a 24 V power supply for the inverter. In all the
other models this terminal is an output, i.e., the user has a 24 V power
supply available there.
7
AO1
8
AGND
(24 V)
3
amp
Specifications
1
≥5 kΩ
CCW
Factory Default Function
Positive reference for
potentiometer
9
AO2
10
AGND
(24 V)
11
DGND*
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
Common point of the
digital inputs
Digital input #1:
Start / Stop
Digital input #2:
Direction of rotation (remote)
Digital input #3:
No function
Digital input #4:
No function
Digital input #5:
Jog (remote)
Digital input #6:
2nf ramp
Digital output #1 DO1
(RL1):
No fault
22
C1
23
NO1
24
25
26
NC2
C2
NO2
Digital output #2 DO2
(RL2):
N > NX - Speed > P0288
27
NC3
Digital output #3 DO3
(RL3):
N* > NX - Speed reference
> P0288
28
C3
29
NO3
Output voltage:+5.4 V, ±5 %.
Maximum output current: 2 mA
6 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Maximum input voltage = 30 V
Input current: 11 mA @ 24 Vdc
Contact rating:
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - Normally closed contact;
C - Common;
NO - Normally open contact.
Figure 3.41 (a) - Signals at connector XC1 - Digital inputs working as 'Active High'
3-28
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
Connector XC1
CW
≥ 5 kΩ
CCW
rpm
amp
Factory Default Function
Specifications
1
+REF
Positive reference for
potentiometer
Output voltage:+5.4 V, ±5 %.
Maximum output current: 2 mA
2
AI1+
Analog input #1:
Speed reference (remote)
3
AI1-
Differential
Resolution: 12 bits
Signal: 0 to 10 V (RIN= 400 kΩ) / 0 to 20 mA / 4 to 20 mA (RIN= 500 Ω)
Maximum voltage: ±30 V
4
REF-
Negative reference for
potentiometer
Output voltage: -4.7 V, ±5 %.
Maximum output current: 2 mA
5
AI2+
Analog input #2:
No function
6
AI2-
Differential
Resolution: 11 bits + signal
Signal: 0 to ±10 V (RIN= 400 kΩ) / 0 to 20 mA / 4 to 20 mA (RIN= 500 Ω)
Maximum voltage: ±30 V
Analog output #1:
Speed
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (RL ≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (RL ≤ 500 Ω)
Protected against short-circuit.
Reference (0 V) for the
analog outputs
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor.
Analog output #2:
Motor current
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (RL ≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (RL ≤ 500 Ω)
Protected against short-circuit.
7
AO1
8
AGND
(24 V)
9
AO2
10
AGND
(24 V)
11
12
Reference (0 V) for the
analog outputs
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor.
DGND*
Reference (0 V) for the
24 Vdc power supply
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor.
COM
Common point of the
digital inputs
24 Vdc power supply
13
24 Vdc
14
COM
15
DI1
Digital input #1:
Start / Stop
16
DI2
Digital input #2:
Direction of rotation (remote)
17
DI3
Digital input #3:
No function
18
DI4
Digital input #4:
No function
19
DI5
Digital input #5:
Jog (remote)
20
DI6
Digital input #6:
2nf ramp
21
NC1
22
C1
23
NO1
24
NC2
25
C2
26
NO2
27
NC3
28
C3
29
NO3
24 Vdc power supply, ±8 %.
Capacity: 500 mA.
Note: In the models with the 24 Vdc external control power supply
(CFW11MXXXXXXOW) the terminal 13 of XC1 becomes an input,
i.e., the user must connect a 24 V power supply for the inverter. In all
the other models this terminal is an output, i.e., the user has a 24 V
power supply available there.
Common point of the
digital inputs
Digital output #1 DO1
(RL1):
No fault
Digital output #2 DO2
(RL2):
N > NX - Speed > P0288
6 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Input voltage ≤ 30 V
Input current: 11 mA @ 24 Vdc
Contact rating:
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - Normally closed contact;
C - Common;
NO - Normally open contact.
Digital output #3 DO3
(RL3):
N* > NX - Speed reference
> P0288
Figure 3.41 (b) - Signals at connector XC1 - Digital inputs working as 'Active Low'
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-29
3
Installation and Connection
NOTE!
Remove the jumper between XC1:11 and 12 and install it between XC1:12 and 13 to use the digital
inputs as 'Active Low'.
Slot 5
Slot 1 (white)
Slot 2 (yellow)
3
Slot 3 (green)
Slot 4
Figure 3.42 - Connector XC1 and DIP-switches for selecting the signal type of the analog inputs and outputs
The analog inputs and outputs are factory set to operate in the range from 0 to 10 V; this setting may be
changed by using DIP-switch S1.
Table 3.12 - DIP-switches conFiguretion for the selection of the signal type for the analog inputs and outputs
Signal
Factory Default Function
DIPswitch
Selection
Factory Setting
AI1
Speed Reference (remote)
S1.4
OFF: 0 to 10 V (factory setting)
ON: 4 to 20 mA / 0 to 20 mA
OFF
AI2
No Function
S1.3
OFF: 0 to ±10 V (factory setting)
ON: 4 to 20 mA / 0 to 20 mA
OFF
AO1
Speed
S1.1
OFF: 4 to 20 mA / 0 to 20 mA
ON: 0 to 10 V (factory setting)
ON
AO2
Motor Current
S1.2
OFF: 4 to 20 mA / 0 to 20 mA
ON: 0 to 10 V (factory setting)
ON
Parameters related to the analog inputs and outputs (AI1, AI2, AO1, and AO2) shall be programmed according
to the DIP-switches settings and desired values.
Follow instructions below for the proper installation of the control wiring:
1) Wire gauge: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG);
2) Maximum tightening torque: 0.5 Nm (4.50 lbf.in);
3) Use shielded cables for the connections in XC1 and run the cables separated from the remaining circuits
(power, 110 V / 220 Vac control, etc.), as presented in table 3.13. If control wiring must cross other cables
(power cables for instance), make it cross perpendicular to the wiring and provide a minimum separation
of 5 cm (1.9 in) at the crossing point.
3-30
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
Table 3.13 - Minimum separation distances between wiring
Inverter Rated
Output Current
≤ 24 A
≥ 28 A
Cable Length
≤ 100 m (330 ft)
> 100 m (330 ft)
≤ 30 m (100 ft)
> 30 m (100 ft)
Minimum Separation
Distance
≥ 10 cm (3.94 in)
≥ 25 cm (9.84 in)
≥ 10 cm (3.94 in)
≥ 25 cm (9.84 in)
4) The adequate connection of the cable shield is shown in figure 3.43. Figure 3.44 shows how to connect
the cable shield to the ground.
Isolate with tape
Inverter
side
3
Do not ground
Figure 3.43 - Shield connection
Figure 3.44 - Example of shield connection for the control wiring
5) Relays, contactors, solenoids or coils of electromechanical brakes installed close to the inverter may eventually
create interferences in the control circuit. To eliminate this effect, RC suppressors (with AC power supply) or
free-wheel diodes (with DC power supply) shall be connected in parallel to the coils of these devices.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-31
Installation and Connection
3.4.9 Typical Control Connections
Control connection #1 - Start/Stop function controlled from the keypad (Local Mode).
With this control connection it is possible to run the inverter in local mode with the factory default settings. This
operation mode is recommended for first-time users, since no additional control connections are required.
For the start-up in this operation mode, please follow instructions listed in chapter 5.
Control connection #2 - 2 - Wire Start/Stop function (Remote Mode).
This wiring example is valid only for the default factory settings and if the inverter is set to remote mode.
With the factory default settings, the selection of the operation mode (local/remote) is performed through the
operator key
(local mode is default). Set P0220 = 3 to change the default setting of operator key
to remote mode.
3
H
≥5 kΩ
AH
Start/Stop
Direction of Rotation
Jog
Connector XC1
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND*
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
22
C1
23
NO1
24
NC2
25
C2
26
NO2
27
NC3
28
C3
29
NO3
DO1
(RL1)
DO2
(RL2)
DO3
(RL3)
Figure 3.45 - XC1 wiring for Control Connection #2
3-32
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
Control connection #3 - 3 - Wire Start/Stop function.
Enabling the Start/Stop function with 3 Wire control.
Parameters to set:
Set DI3 to START
P0265 = 6
Set DI4 to STOP
P0266 = 7
Set P0224 = 1 (DIx) for 3 wire control in Local mode.
Set P0227 = 1 (DIx) for 3 wire control in Remote mode.
Set the Direction of Rotation by using digital input #2 (DI2).
Set P0223 = 4 to Local Mode or P0226 = 4 to Remote Mode.
S1 and S2 are Start (NO contact) and Stop (NC contact) push-buttons respectively.
The speed reference can be provided through the analog input (as in Control Connection #2), through the
keypad (as in Control Connection #1) or through any other available source.
Connector XC1
Direction of Rotation S3
(FWD/REV)
Start S1
Stop S2
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND*
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
22
C1
23
NO1
24
NC2
25
C2
26
NO2
27
NC3
28
C3
29
NO3
DO1
(RL1)
DO2
(RL2)
DO3
(RL3)
Figure 3.46 - XC1 wiring for Control Connection #3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-33
3
Installation and Connection
Control connection #4 - Forward/Reverse.
Enabling the Forward/Reverse function.
Parameters to set:
Set DI3 to FORWARD
P0265 = 4
Set DI4 to REVERSE
P0266 = 5
When the Forward/Reverse function is set, it will be active either in Local or Remote mode. At the same time,
the operator keys
and
will remain always inactive (even if P0224 = 0 or P0227 = 0).
The direction of rotation is determined by the forward and reverse inputs.
Clockwise to forward and counter-clockwise to reverse.
The speed reference can be provided by any source (as in Control Connection #3).
Connector XC1
3
Stop/Forward S1
Stop/Reverse S2
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND*
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
22
C1
23
NO1
24
NC2
25
C2
26
NO2
27
NC3
28
C3
29
NO3
DO1
(RL1)
DO2
(RL2)
DO3
(RL3)
Figure 3.47 - XC1 wiring for Control Connection #4
3-34
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
3.5
INSTALLATION ACCORDING TO THE EUROPEAN DIRECTIVE OF ELECTROMAGNETIC COMPATIBILITY
The CFW-11M inverters , when properly installed, meet the requirements of the electromagnetic compatibility
directive - "EMC Directive 2004 / 108 / EC".
3.5.1 Conformal Installation
For the conformal installation use:
1) CFW-11M standard inverter for emission levels in accordance with IEC/EN 61800-3 "Adjustable Speed
Electrical Power Drive Systems", C4 category.
2) Additional external filters in order to comply with the conducted emission levels C2 or C3 categories.
3) Shielded output cables (motor cables) and connect the shield at both ends (motor and inverter) with a low
impedance connection for high frequency. The required cable separation is presented in table 3.11.
4) Shielded control cables, keeping them separate from the other cables as described in item 3.4.8.
5) Inverter grounding according to the instructions on item 3.4.5.
3.5.2 Standard Definitions
IEC/EN 61800-3: “Adjustable Speed Electrical Power Drives Systems”
- Environment:
First Environment: includes domestic premises. It also includes establishments directly connected without
intermediate transformer to a low-voltage power supply network which supplies buildings used for domestic
purposes.
Example: houses, apartments, commercial installations, or offices located in residential buildings.
Second Environment: includes all establishments other than those directly connected to a low-voltage power
supply network which supplies buildings used for domestic purposes.
Example: industrial area, technical area of any building supplied by a dedicated transformer.
- Categories:
Category C1: inverters with a voltage rating less than 1000 V and intended for use in the First Environment.
Category C2: inverters with a voltage rating less than 1000 V, intended for use in the First Environment,
not provided with a plug connector or a movable installations, and installed and commissioned by a
professional.
Note: a professional is a person or organization familiar with the installation and/or commissioning of inverters,
including the EMC aspects.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-35
3
Installation and Connection
Category C3: inverters with a voltage rating less than 1000 V and intended for use in the Second Environment
only (not designed for use in the First Environment).
Category C4: inverters with a voltage rating equal to or greater than 1000 V, or with a current rating equal to
or greater than 400 Amps, or intended for use in complex systems in the Second Environment.
EN 55011: “Threshold values and measuring methods for radio interference from industrial,
scientific and medical (ISM) high-frequency equipment”
Class B: equipment intended for use in the low-voltage power supply network (residential, commercial, and
light-industrial environments).
Class A1: equipment intended for use in the low-voltage power supply network. Restricted distribution.
Note: must be installed and commissioned by a professional when applied in the low-voltage power supply
network.
3
Class A2: equipment intended for use in industrial environments.
3.5.3 Emission and Immunity Levels
Table 3.14 - Emission and immunity levels
EMC Phenomenon
Basic Standard
Level
Emission:
Mains Terminal Disturbance Voltage
Frequency Range: 150 kHz to 30 MHz)
Electromagnetic Radiation Disturbance
Frequency Range: 30 kHz to 1 GHz)
IEC/EN61800-3
- Without external filter:
C4 Category.
- With external filter:
C2 or C3 Category.
Immunity:
Electrostatic Discharge (ESD)
IEC/EN61000-4-2
4 kV for contact discharge and 8 kV for air discharge.
Fast Transient-Burst
IEC/EN61000-4-4
2 kV/5 kHz (coupling capacitor) power input cables;
1 kV/5 kHz control cables, and remote keypad cables;
2 kV/5 kHz (coupling capacitor) motor output cables.
Conducted Radio-Frequency Common Mode
IEC/EN61000-4-6
0.15 to 80 MHz; 10 V; 80 % AM (1 kHz).
Motor cables, control cables, and remote keypad cables.
Surge Immunity
IEC/EN61000- 4-5
Radio-Frequency Electromagnetic Field
IEC/EN61000-4-3
3-36
1.2/50 µs, 8/20 µs;
1 kV line-to-line coupling;
2 kV line-to-ground coupling.
80 to 1000 MHz;
10 V/m;
80 % AM (1 kHz).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Installation and Connection
3.5.4 External RFI Filters
To be used only if necessary to comply with conducted emission levels Category C2 or C3 according to IEC/
EN61800-3. The models bellow are from the manufacturer Epcos.
Table 3.15 - Filters for 380-480 V lines
Inverter
Model
Regimen
Filter Model
ND
B84143-B600-S20
600
Table 3.16 - Filters for 500-600 V lines
Inverter
Regimen
Model
Filter Model
ND
B84143-B600-S21
HD
B84143-B600-S21
ND
B84143-B1000-S21
HD
B84143-B1000-S21
ND
B84143-B1600-S21
470
HD
B84143-B600-S20
ND
B84143-B1600-S20
1140
893
HD
B84143-B1000-S20
ND
B84143-B2500-S20
1710
1340
HD
B84143-B1600-S20
HD
B84143-B1600-S21
ND
B84143-B2500-S20
ND
B84143-B2500-S21
HD
B84143-B2500-S20
HD
B84143-B1600-S21
ND
----
ND
B84143-B2500-S21
HD
B84143-B2500-S21
2280
3
1786
2850
2232
HD
B84143-B2500-S20
Table 3.17 - Filters for 660-690 V lines
Inverter
Model
Regimen
Filter Model
ND
B84143-B600-S21
HD
B84143-B600-S21
ND
B84143-B1000-S21
HD
B84143-B1000-S21
ND
B84143-B1600-S21
HD
B84143-B1000-S21
ND
B84143-B2500-S21
HD
B84143-B1600-S21
ND
B84143-B2500-S21
HD
B84143-B2500-S21
427
811
1217
1622
2028
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
3-37
Installation and Connection
Controling and Signal Wiring
Filter
Q1
Transforme
F1
F2
F3
L1 L1
R
L2 L2
S
Rectifier
-
L3 L3
E
E
U
+
CFW-11M V
W
T
PE
PE
Motor
PE
Panel or Metallic
Enclosure
Ground Rod/Grid
or Building Steel
Structure
Protective Grounding - PE
Figure 3.48 - External RFI filter connections
Use the listed filters only in lines with a solidly grounded neutral point. Do not use them in IT networks, lines
that are not grounded or grounded via a high impedance.
3
Take the usual precautions for EMC filters installation: Do not cross the filter input cables with the output cables,
mount the filter on a metallic plate assuring the biggest possible contact surface between the filter and the plate,
connect this plate to the ground via cordage, etc.
Filter technical data:
Table 3.18 - Filter characteristics
Filter
B84143-B600-S20
3-38
Nominal
Current [A]
Watt Losses [W]
Weight
[kg]
600
57
22
B84143-B1000-S20
1000
99
28
B84143-B1600-S20
1600
169
34
B84143-B2500-S20
2500
282
105
B84143-B600-S21
600
57
22
B84143-B1000-S21
1000
99
28
B84143-B1600-S21
1600
169
34
B84143-B2500-S21
2500
282
105
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Keypad and Display
KEYPAD AND DISPLAY
This chapter describes:
- The operator keys and their functions;
- The indications on the display;
- How parameters are organized.
4.1 INTEGRAL KEYPAD - HMI-CFW11
The integral keypad can be used to operate and program (view / edit all parameters) of the CFW-11 inverter.
The inverter keypad navigation is similar to the one used in cell phones and the parameters can be accessed
in numerical order or through groups (Menu).
Left soft key: press this key to select the
above highlighted menu feature.
Right soft key: press this key to select
the above highlighted menu feature.
1. Press this key to advance to the next parameter or to increase a parameter value.
2. Press this key to increase the speed.
3. Press this key to select the previous
group in the Parameter Groups.
1. Press this key to move back to the previous
parameter or to decrease a parameter value.
2. Press this key to decrease speed.
3. Press this key to select the next group in the
Parameter Groups.
4
Press this key to define the direction of
rotation for the motor.
This option is active when:
P0223 = 2 or 3 in LOC and/or
P0226 = 2 or 3 in REM.
Press this key to accelerate the motor in the
time set for the acceleration ramp.
This option is active when:
P0224 = 0 in LOC or
P0227 = 0 in REM.
Press this key to switch between LOCAL or
REMOTE modes.
This option is active when:
P0220 = 2 or 3.
Press this key to stop the motor in the time set
for the deceleration ramp.
This option is active when:
P0224 = 0 in LOC or
P0227 = 0 in REM.
Press this key to accelerate the motor to the speed set in
P0122 in the time set for the acceleration ramp.
The motor speed is kept while this key is pressed.
Once this key is released, the motor will stop by following the
deceleration ramp.
This function is active when all conditions below are satisfied:
1. Start/Stop = Stop;
2. General Enable = Active;
3. P0225 = 1 in LOC and/or P0228 = 1 in REM.
Figure 4.1 - Operator keys
Battery:
NOTE!
The battery is necessary only to keep the internal clock operation when the inverter stays without
power. If the battery is completely discharged or if it is not installed in the keypad, the displayed clock
time will be invalid and an alarm condition A181 - Invalid clock time will be indicated whenever the
AC power is applied to the inverter.
The battery life expectancy is of approximately 10 years. When necessary, replace the battery by another of the
CR2032 type.
4-1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Keypad and Display
1
Cover
2
3
Cover for battery access
Press the cover and rotate it
counterclockwise
Remove the cover
4
5
6
Remove the battery with the
help of a screwdriver positioned
in the right side
HMI without the battery
Install the new battery positioning it first at
the left side
4
7
8
Press the battery for its insertion
Put the cover back and rotate it clockwise
Figure 4.2 - HMI battery replacement
NOTE!
At the end of the battery useful life, please do not discard batteries in your waste container, but use
a battery disposal site.
4-2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Keypad and Display
Installation:
The keypad can be installed or removed from the inverter with or without AC power applied to the
inverter.
The HMI supplied with the product can also be used for remote command of the inverter. In this case, use
a cable with male and female D-Sub9 (DB-9) connectors wired pin to pin (mouse extension type) or a
market standard Null‑Modem cable. Maximum cable length: 10 m (33 ft). It is recommended the use of the
M3 x 5.8 standoffs supplied with the product.Recommended torque: 0.5 Nm (4.50 lbf in).
When power is applied to the inverter, the display automatically enters the monitoring mode. Figure 4.3 (a)
presents the monitoring screen displayed for the factory default settings. By properly setting specific inverter
parameters, other variables can be displayed in the monitoring mode or the value of a parameter can be
displayed using bar graphs or with larger characters as presented in figures 4.3 (b) and (c).
Indication of the
control mode:
- LOC: local mode;
- REM: remote mode.
Indication of the
direction of rotation of
the motor.
Inverter status:
- Run
- Ready
- Config
- Self-tuning
- Last fault: FXXX
- Last alarm: AXXX
- etc.
Run
LOC
1800
1.0
60.0
12:35
1800rpm
rpm
A
Hz
Menu
Indication of the motor
speed in rpm.
Monitoring parameters:
- Motor speed in rpm;
- Motor current in Amps;
- Output frequency in Hz (default).
P0205, P0206, and P0207: selection of parameters that will be displayed in the monitoring mode.
4
P0208 to P0212: engineering unit for the speed
indication.
Right soft key feature.
Left soft key feature.
Clock.
Settings via:
P0197, P0198, and
P0199.
(a) Monitoring screen with the factory default settings
Run
rpm
1800rpm
LOC
100%
77%
A
Hz
P0205, P0206, and P0207: selection of parameters
that will be displayed in the monitoring mode.
100%
12:35
Monitoring parameters:
- Motor speed in rpm;
- Motor current in Amps;
- Output frequency in Hz (default).
Menu
P0208 to P0212: engineering unit for the speed
indication.
(b) Example of a monitoring screen with bar ghaphs
Run
LOC
1800rpm
1800
rpm
12:35
Menu
Value of one of the parameters defined in P0205,
P0206, or P0207 displayed with a larger font size.
Set parameters P0205, P0206 or P0207 to 0 if it is not
desirable to display them.
(c) Example of a monitoring screen displaying a parameter with a larger font size
Figure 4.3 - Keypad monitoring modes
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
4-3
Keypad and Display
4.2 PARAMETERS ORGANIZATION
When the right soft key ("MENU") is pressed in the monitoring mode, the display shows the first 4 groups of
parameters. An example of how the groups of parameters are organized is presented in table 4.1. The number
and name of the groups may change depending on the firmware version used. For further details on the existent
groups for the firmware version used, please refer to the Software Manual.
Table 4.1 - Groups of parameters
Level 0
Monitoring
00
01
 Level 1
ALL PARAMETERS
PARAMETER GROUPS
4
4-4
02
03
04
05
06
07
 
ORIENTED START-UP
CHANGED PARAMETERS
BASIC APPLICATION
SELF-TUNING
BACKUP PARAMETERS
I/O CONFigureTION
08
09
FAULT HISTORY
READ ONLY PARAMS.
 Level 2
 
20
21
22
23
24
25
26
27
28
29
 
 Level 3
 
Ramps
Speed References
Speed Limits
V/f Control
Adjust. V/f Curve
VVW Control
V/f Current Limit.
V/f DC Volt.Limit.
Dynamic Braking
Vector Control
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
 
HMI
Local Command
Remote Command
3-Wire Command
FWD/REV Run Comm.
Zero Speed Logic
Multispeed
Electr. Potentiom.
Analog Inputs
Analog Outputs
Digital Inputs
Digital Outputs
Inverter Data
Motor Data
FlyStart/RideThru
Protections
PID Regulator
DC Braking
Skip Speed
Communication
50
51
52
 
SoftPLC
PLC
Trace Function
38
39
40
41
 
Analog Inputs
Analog Outputs
Digital Inputs
Digital Outputs
90
91
92
93
94
95
96
 
Speed Regulator
Current Regulator
Flux Regulator
I/F Control
Self-Tuning
Torque Curr.Limit.
DC Link Regulator
110
111
112
113
114
115
 
Local/Rem Config.
Status/Commands
CANopen/DeviceNet
Serial RS232/485
Anybus
Profibus DP
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
First Time Power-Up and Start-Up
FIRST TIME POWER-UP AND
START-UP
This chapter describes how to:
- Check and prepare the inverter before power-up.
- Power-up the inverter and check the result.
- Set the inverter for the operation in the V/f mode based on the
power supply and motor information by using the Oriented Start-Up
routine and the Basic Application group.
NOTE!
For a detailed description of the V V W or Vector control modes and for other available functions,
please refer to the CFW-11 Software Manual.
5.1 PREPARE FOR START-UP
The inverter shall have been already installed according to the recommendations listed in Chapter 3 – Installation
and Connection. The following recommendations are applicable even if the application design is different from
the suggested control connections.
DANGER!
Always disconnect the main power supply before performing any inverter connection.
5.1.1 Precautions during the Energization/Start-up
1) Verify all the connections of the panel.
5
2) Search for short-circuits at the input, DC link, etc.
3) Make sure all the cables are correctly connected between the control and power units.
4) Verify the condition of all the fuses.
5) Inspect all the ground connections (panel, the door where the control is installed, etc.).
6) Remove all the material rests from the inverter or panel interior.
7) Close the inverter or panel covers.
8) Energize the control (+24 Vdc power supply).
9) The HMI must indicate undervoltage error with the control energized and the power units deenergized. The
electronics of the power units stay without power (SMPS off) and the DC link monitoring signal remains at
0 V.
10) Measure the line voltage making sure it is inside the permitted range.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
5-1
First Time Power-Up and Start-Up
11) Verify if the automatic hardware identification has correctly recognized the inverter current and voltage. The
inverter current must be compatible with the number of installed power units.
12) Command the drive, perform the DC link pre-charge and close the main contactor/circuit breaker.
13) Verify the proper operation of the fans. The fan control conFiguretion is done via software through the
parameter P0352 (refer to the CFW-11 Software Manual). The power units do not have internal fans at the
electronics, only at the heatsinks. At the factory default the fans stay on for a while during the energization
and then they are switched off. They will only be switched on again if the heatsink temperature reaches
70 °C (158 ºF), and off if the temperature drops below 60 °C (140 ºF).
14) Observe the existence of faults/alarms. In case that a fault or alarm occurs, verify the possible causes and
solve the problem.
15) Enable the inverter via HMI. Verify the output current of each power unit phase by programming the password
637 at the parameter P0000 (refer to the section 5.2.1), which makes the visualization of the parameters
from P0815 to P0829 possible. Because the drive is with no load, the measured current is the one that
circulates between the parallel power units, which must be less than 2.5 % of the nominal ND current of the
power unit.
16) Disable the inverter via HMI.
17) Verify if the temperature reading parameters of the installed power units, P0800 to P0814 according to the
case, indicate values close to the ambient temperature.
18) Deenergize the drive and wait until the DC link capacitors discharge completely. Then connect a motor with
power close to 100 HP (75 kW) or the application motor with no load. Verify the motor connection and if its
current and voltage match the inverter. If the application motor is going to be used, decouple it mechanically
from the load. If the motor cannot be decoupled, make sure that the rotation in any direction (clockwise or
counterclockwise) will not cause damage to the machine or accident risks.
5
19) Command the drive, perform the DC link pre-charge and close the main contactor/circuit breaker.
20) Enable the inverter via HMI. Verify the output current of each power unit phase: The current unbalance
(P0815 to P0829) of each phase must stay below 5 %. Verify if the difference between the temperatures of
the power units (P0800 to P0814) is of maximum 10 °C (50 ºF).
5-2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
First Time Power-Up and Start-Up
5.2 START-UP
The start-up procedure for the V/f is described in three simple steps by using the Oriented Start-up routine
and the Basic Application group.
Steps:
(1) Set the password for parameter modification.
(2) Execute the Oriented Start-up routine.
(3) Set the parameters of the Basic Application group.
5.2.1 Password Setting in P0000
Step
Action/Result
Display indication
Ready
1
Monitoring Mode.
- Press“Menu”
(rigth soft key).
rpm
A
Hz
15:45
Ready
2
- Group “00 ALL
PARAMETERS” is already
selected.
- Press “Select”.
00
01
02
03
Return
3
4
Return
5
6
Return
Ready
0rpm
8
- The display returns to the
Monitoring Mode.
Select
15:45
Select
0rpm
LOC
0
0.0
0.0
rpm
A
Hz
15:45
Menu
0rpm
15:45
LOC
Select
5
0rpm
Access to Parameters
0
Return
15:45
LOC
Save
0rpm
P0000
Access to Parameters
5
Return
- If the setting has been
properly performed, the
keypad should display
“Access to Parameters
P0000: 5”.
- Press “Return”
(left soft key).
Menu
0rpm
LOC
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
P0000
Ready
- When number 5 is
displayed in the keypad,
press “Save”.
LOC
- Press ”Return”.
00
01
02
03
Access to Parameters
P0000:
0
Speed Reference
P0001:
90 rpm
Ready
- To set the password,
press the Up Arrow
until number 5 is
displayed in the keypad.
15:45
Display indication
Ready
7
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Ready
- Parameter “Access to
Parameters P0000: 0” is
already selected.
- Press “Select”.
LOC
Action/Result
0rpm
LOC
0
0.0
0.0
Step
Ready
15:45
LOC
Save
0rpm
Access to Parameters
P0000:
5
Speed Reference
P0001:
90 rpm
Return
15:45
Select
Figure 5.1 - Steps for allowing parameters modification via P0000
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
5-3
First Time Power-Up and Start-Up
5.2.2 Oriented Start-Up
There is a group of parameters named ”Oriented Start-up” that makes the inverter settings easier. Inside this
group, there is a parameter – P0317 – that shall be set to enter into the Oriented Start-up routine.
The Oriented Start-up routine allows you to quickly set up the inverter for operation with the line and motor
used. This routine prompts you for the most commonly used parameters in a logic sequence.
In order to enter into the Oriented Start-up routine, follow the steps presented in figure 5.2, first modifying
parameter P0317 to 1 and then, setting all remaining parameters as they are prompted in the display.
The use of the Oriented Start-up routine for setting the inverter parameters may lead to the automatic modification
of other internal parameters and/or variables of the inverter.
During the Oriented Start-up routine, the message “Config” will be displayed at the left top corner of the
keypad.
Step
Action/Result
Display indication
Ready
1
rpm
A
Hz
13:48
2
- Group “00
ALL PARAMETERS” has
been already selected.
Ready
00
01
02
03
3
- Group “01
PARAMETER GROUPS”
is selected.
Ready
00
01
02
03
Ready
4
00
01
02
03
6
- Parameter “Oriented
Start-Up P0317: No”
has been already selected.
- Press “Select”.
- The value of
“P0317 = [000] No”
is displayed.
0rpm
8
Select
Return
13:48
0rpm
LOC
Ready
13:48
Select
0rpm
LOC
P0317
Oriented Start-up
[000] No
Return
13:48
P0317
Oriented Start-up
[001] Yes
Config
13:48
LOC
Save
0rpm
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
Reset
13:48
Select
Select
Oriented Start-Up
P0317: No
Return
- At this point the Oriented
Start-up routine starts
and the “Config” status
is displayed at the top left
corner of the keypad.
- The parameter
“Language P0201:
English” is already
selected.
- If needed, change the
language by pressing
“Select”. Then, press
0rpm
LOC
to scroll through the
available options and
press “Save” to select a
different language.
0rpm
LOC
Ready
or
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Ready
5
Select
LOC
13:48
- The parameter value is
modified to “P0317 =
[001] Yes”.
- Press “Save”.
Display indication
Return
0rpm
LOC
13:48
Action/Result
Menu
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Return
- Group “02
ORIENTED START-UP” is
then selected.
- Press “Select”.
7
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Return
5
0rpm
LOC
0
0.0
0.0
- Modo Monitoração.
- Pressione “Menu”
(soft key direita).
Step
Save
9
- If needed, change the
value of P0202 according
to the type of control. To
do so, press "Select".
- The settings listed
here are valid only for
P0202 = 0 (V/f 60 Hz) or
P0202 = 1 (V/f 50 Hz). For
other options (Adjustable
V/f, VVW, or Vector
modes), please refer to
the Software Manual.
Config
LOC
0rpm
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
Reset
13:48
Select
Figure 5.2 - Oriented Start-up
5-4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
First Time Power-Up and Start-Up
Step
10
11
Action/Result
- If needed, change the
value of P0296 according
to the line rated voltage.
To do so, press "Select".
This modification will
affect P0151, P0153,
P0185, P0321, P0322,
P0323, and P0400.
- If needed, change the
value of P0298 according
to the inverter application.
To do so, press "Select".
This modification will
affect P0156, P0157,
P0158, P0401, P0404
and P0410 (this last one
only if P0202 = 0, 1, or
2 – V/f control). The time
and the activation level of
the overload protection
will be affected as well.
Display indication
Config
0rpm
LOC
Type of Control
P0202: V/F 60 HZ
Line Rated Voltage
P0296: 440 - 460 V
Reset
Config
13:48
Step
15
Select
0rpm
LOC
16
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Heavy Duty
Reset
13:48
12
13
- If needed, change
the value of P0400
according to the motor
rated voltage. To do
so, press “Select”. This
modification adjusts the
output voltage by a factor
x = P0400/P0296.
Config
LOC
0rpm
Application
P0298: Heavy Duty
Motor Service Factor
P0398:
1.15
Reset
13:48
Select
18
Config
LOC
13:48
Select
19
14
- If needed, change the
value of P0401 according
to the motor rated current.
To do so, press “Select”.
This modification will
affect P0156, P0157,
P0158, and P0410.
Config
LOC
13:48
0rpm
LOC
Motor Rated Current
P0401: 13.5 A
Motor Rated Speed
P0402:
1750 rpm
Reset
Config
13:48
Select
0rpm
LOC
Motor Rated Speed
P0402:
1750 rpm
Motor Rated Frequency
P0403:
60 Hz
Reset
13:48
Select
- If needed, change the
value of P0404 according
to the motor rated power.
To do so, press “Select”.
This modification affects
P0410.
- This parameter will only
be visible if the encoder
board ENC1 is installed in
the inverter.
- If there is an encoder
connected to the motor,
set P0405 according
to the encoder pulses
number. To do so, press
“Select”.
Config
0rpm
LOC
Motor Rated Frequency
P0403: 60 Hz
Motor Rated Power
P0404: 4hp 3kW
Reset
Config
13:48
Select
0rpm
LOC
Motor Rated Power
P0404:
4hp 3kW
Encoder Pulses Number
P0405:
1024 ppr
Reset
13:48
Select
5
- If needed, set P0406
according to the motor
ventilation. To do so, press
“Select”.
- To complete the
Oriented Start-Up routine,
press “Reset”
(left soft key) or
.
Config
0rpm
LOC
Encoder Pulses Number
P0405:
1024 ppr
Motor Ventilation
P0406: Self-Vent.
Reset
13:48
Select
0rpm
Motor Rated Voltage
P0400:
440V
Motor Rated Current
P0401:
13.5 A
Reset
Config
0rpm
Motor Service Factor
P0398:
1.15
Motor Rated Voltage
P0400:
440 V
Reset
- If needed, set P0403
according to the motor
rated frequency. To do
so, press “Select”. This
modification affects
P0402.
Display indication
Select
17
- If needed, change the
value of P0398 according
to the motor service factor.
To do so, press “Select”.
This modification will
affect the current value
and the activation time
of the motor overload
function.
Action/Result
- If needed, set P0402
according to the motor
rated speed. To do so,
press “Select”. This
modification affects
P0122 to P0131, P0133,
P0134, P0135, P0182,
P0208, P0288, and
P0289.
Select
Ready
20
- After few seconds, the
display returns to the
Monitoring Mode.
0rpm
LOC
0
0.0
0.0
rpm
A
Hz
13:48
Menu
Figure 5.2 (cont) - Oriented Start-up
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
5-5
First Time Power-Up and Start-Up
5.2.3 Setting Basic Application Parameters
After running the Oriented Start-up routine and properly setting the parameters, the inverter is ready to operate
in the V/f mode.
The inverter has a number of other parameters that allow its adaptation to the most different applications.
This manual presents some basic parameters that shall be set in most cases. There is a group named “Basic
Application” to make this task easier. A summary of the parameters inside this group is listed in table 5.1. There
is also a group of read only parameters that shows the value of the most important inverter variables such as
voltage, current, etc. The main parameters comprised in this group are listed in table 5.2. For further details,
please refer to the CFW-11 Software Manual.
Follow steps outlined in figure 5.3 to set the parameters of the Basic Application group.
The procedure for start-up in the V/f operation mode is finished after setting these parameters.
Step
Action/Result
Display indication
Ready
1
- Monitoring Mode.
- Press “Menu”
(right soft key).
rpm
A
Hz
15:45
2
- Group “00
ALL PARAMETERS” has
been already selected.
Ready
00
01
02
03
3
- Group “01
PARAMETER GROUPS” is
then selected.
Ready
00
01
02
03
4
Ready
00
01
02
03
15:45
LOC
15:45
LOC
15:45
- Group “04 BASIC
APPLICATION” is
selected.
- Press “Select”.
Select
0rpm
Display indication
Ready
01
02
03
04
7
Select
- Parameter “Acceleration
Time P0100: 20.0 s” has
been already selected.
- If needed, set P0100
according to the desired
acceleration time. To do
so, press “Select”.
- Proceed similarly until all
parameters of group “04
BASIC APPLICATION”
have been set. When
finished, press “Return”
(left soft key).
Ready
5
Ready
00
01
02
03
LOC
15:45
Select
0rpm
LOC
Return
15:45
Select
0rpm
Ready
8
- Press “Return”.
Select
01
02
03
04
0rpm
LOC
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
BASIC APPLICATION
15:45
Select
0rpm
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Return
15:45
Acceleration Time
P0100: 20.0s
Deceleration Time
P0101:
20.0s
Return
- Group “03
CHANGED
PARAMETERS” is
selected.
0rpm
LOC
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
BASIC APPLICATION
Return
0rpm
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Return
Action/Result
Menu
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Return
- Group “02
ORIENTED START-UP” is
then selected.
LOC
6
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Return
5
0rpm
LOC
0
0.0
0.0
Step
Select
Ready
9
- The display returns to the
Monitoring Mode and the
inverter is ready to run.
0rpm
LOC
0
0.0
0.0
rpm
A
Hz
15:45
Menu
Figure 5.3 - Setting parameters of the Basic Application group
5-6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
First Time Power-Up and Start-Up
Table 5.1 - Parameters comprised in the Basic Application group
P0100
Acceleration
Time
- Defines the time to linearly accelerate from 0 up to the maximum
speed (P0134).
- If set to 0.0 s, it means no acceleration ramp.
0.0 to 999.0 s
Factory
Setting
20.0 s
P0101
Deceleration
Time
- Defines the time to linearly decelerate from the maximum speed
(P0134) up to 0.
- If set to 0.0 s, it means no deceleration ramp.
0.0 to 999.0 s
20.0 s
P0133
Minimum
Speed
- Defines the minimum and maximum values of the speed reference 0 to 18000 rpm
90 rpm
when the drive is enabled.
(60 Hz motor)
- These values are valid for any reference source.
75 rpm
(50 Hz motor)
P0134
Maximum
Speed
Parameter
Name
Description
Setting Range
Reference
User
Setting
1800 rpm
(60 Hz motor)
1500 rpm
(50 Hz motor)
P0134
P0133
0
Alx Signal
0................................. 10 V
0................................20 mA
4 mA.............................20 mA
10 V...................................0
20 mA................................0
20 mA.............................4 mA
P0135
Max. Output
Current (V/f
control mode
current
limitation)
- Avoids motor stall under torque overload condition during the
acceleration or deceleration.
- The factory default setting is for “Ramp Hold”: if the motor
current exceeds the value set at P0135 during the acceleration or
deceleration, the motor speed will not be increased (acceleration)
or decreased (deceleration) anymore. When the motor current
reaches a value below the programmed in P0135, the motor speed
is again increased or decreased.
- Other options for the current limitation are available. Refer to the
CFW-11 Software Manual.
Motor current
0.2 x Irat-HD to
2 x Irat-HD
1.5 x Irat-HD
Motor current
P0135
P0135
5
Time
Time
Speed
Speed
Ramp
deceleration
(P0101)
Ramp
acceleration
(P0100)
Time
During
acceleration
P0136
Manual Torque
Boost
During
deceleration
Time
- Operates in low speeds, modifying the output voltage x frequency
curve to keep the torque constant.
- Compensates the voltage drop at the motor stator resistance. This
function operates in low speeds increasing the inverter output voltage to
keep the torque constant in the V/f mode.
- The optimal setting is the smallest value of P0136 that allows the
motor to start satisfactorily. An excessive value will considerably increase
the motor current in low speeds, and may result in a fault (F048, F051,
F071, F072, F078 or F183) or alarm (A046, A047, A050 or A110)
condition.
0 to 9
1
Output voltage
Rated
P0136 = 9
0.5x Rated
P0136 = 0
0
Nrat/2
Nrat
Speed
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
5-7
First Time Power-Up and Start-Up
Parameter
P0001
P0002
P0003
P0004
P0005
P0006
 
 
 
 
 
P0007
P0009
P0010
P0012
P0013
P0018
P0019
P0020
P0021
P0023
P0027
P0028
P0029
P0030
P0031
P0032
5
P0033
P0034
P0036
P0037
P0038
P0040
P0041
P0042
P0043
P0044
P0045
P0048
P0049
P0050
P0051
P0052
P0053
P0054
P0055
P0056
P0057
P0058
P0059
P0060
P0061
P0062
5-8
Table 5.2 - Main read only parameters
Parameter
P0063
P0064
P0065
P0066
P0067
P0068
P0069
P0070
P0071
P0072
P0073
P0074
P0075
Motor Voltage
P0076
Motor Torque
P0077
Output Power
P0078
DI8 to DI1 Status
P0079
DO5 to DO1 Status
P0080
AI1 Value
P0081
AI2 Value
P0082
AI3 Value
P0083
AI4 Value
P0084
Software Version
P0085
Accessories Config. 1
P0086
Accessories Config. 2
P0087
P0088
P0089
Power Hardware Config. Hexadecimal code according
to the available models and
P0090
option kits. Refer to the software
P0091
manual for a complete code list.
P0092
IGBTs Temperature U
-20.0 to 150.0 °C
P0093
(-4 °F to 302 °F)
P0094
IGBTs Temperature V
-20.0 to 150.0 °C
P0095
(-4 °F to 302 °F)
P0096
TIGBTs Temperature W -20.0 to 150.0 °C
P0097
(-4 °F to 302 °F)
P0800
Rectifier Temperature
-20.0 to 150.0 °C
P0801
(-4 °F to 302 °F)
P0802
Temper. Ar Interno
-20.0 to 150.0 °C
P0803
(-4 °F to 302 °F)
P0804
Fan Heatsink Speed
0 to 15000 rpm
P0805
Motor Overload Status 0 to 100 %
P0806
Encoder Speed
0 to 65535 rpm
P0807
PID Process Variable
0.0 to 100.0 %
P0808
PID Setpoint Value
0.0 to 100.0 %
P0809
Time Powered
0 to 65535 h
P0810
Time Enabled
0.0 to 6553.5 h
P0811
kWh Output Energy
0 to 65535 kWh
P0812
Fan Enabled Time
0 to 65535 h
P0813
Present Alarm
0 to 999
P0814
Present Fault
0 to 999
P0815
Last Fault
0 to 999
P0816
Last Fault Day/Month
00/00 to 31/12
P0817
Last Fault Year
00 to 99
P0818
Last Fault Time
00:00 to 23:59
P0819
Second Fault
0 to 999
P0820
Second Flt. Day/Month 00/00 to 31/12
P0821
Second Fault Year
00 to 99
P0822
Second Fault Time
00:00 to 23:59
P0823
Third Fault
0 to 999
P0824
Third Fault Day/Month
00/00 to 31/12
P0825
Third Fault Year
00 to 99
P0826
Third Fault Time
00:00 to 23:59
P0827
Fourth Fault
0 to 999
P0828
P0829
Description
Speed Reference
Motor Speed
Motor Current
DC Link Voltage (Ud)
Motor Frequency
VFD Status
 
 
 
 
 
Setting Range
0 to 18000 rpm
0 to 18000 rpm
0.0 to 4500.0 A
0 to 2000 V
0.0 to 300.0 Hz
0 = Ready
1 = Run
2 = Undervoltage
3 = Fault
4 = Self-tuning
5 = ConFiguretion
6 = DC-Braking
7 = STO
0 to 2000 V
-1000.0 to 1000.0 %
0.0 to 6553.5 kW
0000h to 00FFh
0000h to 001Fh
-100.00 to 100.00 %
-100.00 to100.00 %
-100.00 to100.00 %
-100.00 to 100.00 %
0.00 to 655.35
Hexadecimal code
representing the identified
accessories.
Refer to chapter 7.
Description
Fourth Flt. Day/Month
Fourth Fault Year
Fourth Fault Time
Fifth Fault
Fifth Fault Day/Month
Fifth Fault Year
Fifth Fault Time
Sixth Fault
Sixth Fault Day/Month
Sixth Fault Year
Sixth Fault Time
Seventh Fault
Seventh Flt.Day/Month
Seventh Fault Year
Seventh Fault Time
Eighth Fault
Eighth Flt. Day/Month
Eighth Fault Year
Eighth Fault Time
Ninth Fault
Ninth Fault Day/Month
Ninth Fault Year
Ninth Fault Time
Tenth Fault
Tenth Fault Day/Month
Tenth Fault Year
Tenth Fault Time
Current At Last Fault
DC Link At Last Fault
Speed At Last Fault
Reference Last Fault
Frequency Last Fault
Motor Volt.Last Fault
DIx Status Last Fault
DOx Status Last Fault
Phase U Book 1 Temper
Phase V Book 1 Temper
Phase W Book 1 Temper
Phase U Book 2 Temper
Phase V Book 2 Temper
Phase W Book 2 Temper
Phase U Book 3 Temper
Phase V Book 3 Temper
Phase W Book 3 Temper
Phase U Book 4 Temper
Phase V Book 4 Temper
Phase W Book 4 Temper
Phase U Book 5 Temper
Phase V Book 5 Temper
Phase W Book 5 Temper
Phase U Book 1 Current
Phase V Book 1 Current
Phase W Book 1 Current
Phase U Book 2 Current
Phase V Book 2 Current
Phase W Book 2 Current
Phase U Book 3 Current
Phase V Book 3 Current
Phase W Book 3 Current
Phase U Book 4 Current
Phase V Book 4 Current
Phase W Book 4 Current
Phase U Book 5 Current
Phase V Book 5 Current
Phase W Book 5 Current
Setting Range
00/00 to 31/12
00 to 99
00:00 to 23:59
0 to 999
00/00 to 31/12
00 to 99
00:00 to 23:59
0 to 999
00/00 to 31/12
00 to 99
00:00 to 23:59
0 to 999
00/00 a 31/12
00 to 99
00:00 to 23:59
0 to 999
00/00 to 31/12
00 to 99
00:00 to 23:59
0 to 999
00/00 to 31/12
00 to 99
00:00 to 23:59
0 to 999
00/00 to 31/12
00 to 99
00:00 to 23:59
0.0 to 4000.0 A
0 to 2000 V
0 to 18000 rpm
0 to 18000 rpm
0.0 to 300.0 Hz
0 to 2000 V
0000h to 00FFh
0000h to 00F8h
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-20 to 150 °C (-4 °F to 302 °F)
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
-1000 to 1000 A
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
First Time Power-Up and Start-Up
5.3 SETTING DATE AND TIME
Step
Action/Result
Display indication
Ready
1
rpm
A
Hz
16:10
2
- Group “00
ALL PARAMETERS” is
already selected.
Ready
00
01
02
03
Ready
3
4
- A new list of groups is
displayed and group “20
Ramps” is selected.
- Press
until you
reach group "30 HMI".
5
- Group “30 HMI” is
selected.
- Press “Select”.
00
01
02
03
6
0rpm
16:10
LOC
Ready
16:10
LOC
16:10
Select
0rpm
7
Select
16:10
to
- Once the setting of
P0199 is over, the Real
Time Clock is now
updated.
- Press “Return”
(left soft key).
0rpm
8
- Press “Return”.
Select
0rpm
LOC
Day
P0194:
Month
P0195:
Return
Ready
06
10
16:10
Select
Return
- Press “Return”.
Select
00
01
02
03
Ready
- The display is back to
the Monitoring Mode.
34
18:11
Select
18:11
Select
0rpm
LOC
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Return
10
11
Ready
0rpm
LOC
27 V/F DC Volt. Limit.
28 Dynamic Braking
29 Vector Control
30 HMI
Ready
9
0rpm
LOC
Minutes
P0198:
Seconds
P0199:
Return
Ready
0rpm
LOC
27 V/F DC Volt. Limit.
28 Dynamic Braking
29 Vector Control
30 HMI
Return
or
Ready
- Follow the same steps
to set parameters "Month
P0195” to “Seconds
P0199”.
Ramps
Speed References
Speed Limits
V/F Control
Return
Display indication
change P0194 value..
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Return
20
21
22
23
Menu
ALL PARAMETERS
PARAMETER GROUPS
ORIENTED START-UP
CHANGED PARAMETERS
Return
- Group “01
PARAMETER GROUPS" is
selected.
- Press “Select”
LOC
Action/Result
- Parameter “Day P0194”
is already selected.
- If needed, set P0194
according to the actual
day. To do so, press
“Select” and then,
0rpm
LOC
0
0.0
0.0
Monitoring Mode.
- Press “Menu”
(right soft key).
Step
18:11
Select
0rpm
LOC
0
0.0
0.0
rpm
A
Hz
18:11
5
Menu
Figure 5.4 - Setting date and time
5.4 BLOCKING PARAMETERS MODIFICATION
To prevent unauthorized or unintended parameters modification, parameter P0000 should be set to a value
different from 5. Follow the same procedures described in item 5.2.1.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
5-9
First Time Power-Up and Start-Up
5.5 HOW TO CONECT A PC
NOTES!
- Always use a standard host/device shielded USB cable. Unshielded cables may lead to communication
errors.
- Recommended cables: Samtec:
USBC-AM-MB-B-B-S-1 (1 meter);
USBC-AM-MB-B-B-S-2 (2 meters);
USBC-AM-MB-B-B-S-3 (3 meters).
- The USB connection is galvanically isolated from the mains power supply and from other high
voltages internal to the inverter. However, the USB connection is not isolated from the Protective
Ground (PE). Use an isolated notebook for the USB connection or a desktop connected to the same
Protective Ground (PE) of the inverter.
Install the SuperDrive G2 software to control motor speed, view, or edit inverter parameters through a personal
computer (PC).
Basic procedures for transferring data from the PC to the inverter:
1. Install the SuperDrive G2 software in the PC;
2. Connect the PC to the inverter through a USB cable;
3. Start SuperDrive G2;
4. Choose “Open” and the files stored in the PC will be displayed;
5. Select the file;
6. Use the command “Write Parameters to the Drive”.
All parameters are now transferred to the inverter.
For further information on SuperDrive G2 software, please refer SuperDrive Manual.
5
5.6 FLASH MEMORY MODULE
Features:
- Store a copy of the inverter parameters;
- Transfer parameters stored in the FLASH memory to the inverter;
- Transfer firmware stored in the FLASH memory to the inverter;
- Store programs created by the SoftPLC.
Whenever the inverter is powered up, this program is transferred to the RAM memory located in the inverter
control board and executed.
Refer to the CFW-11 Software Manual and to SoftPLC Manual for further details.
ATTENTION!
Before installing or removing the FLASH memory module, disconnect the inverter power supply and
wait for the complete discharge of the capacitors.
5-10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Troubleshooting and Maintenance
TROUBLESHOOTING AND MAINTENANCE
This chapter:
- Lists all faults and alarms that may occur.
- Indicates the possible causes of each fault and alarm.
- Lists most frequent problems and corrective actions.
- Presents instructions for periodic inspections and preventive
maintenance in the equipment.
6.1 OPERATION OF THE FAULTS AND ALARMS
When a fault is detected (fault (FXXX)):
The PWM pulses are blocked;
The keypad displays the fault code and description;
The “STATUS” LED starts flashing red;
The output relay set to "NO FAULT" opens;
Some control circuitry data is saved in the EEPROM memory:
- Keypad and EP (Electronic Pot) speed references, in case the function “Reference backup” is enabled in P0120;
- The fault code that occurred (shifts the last nine previous faults and alarms);
- The state of the motor overload function integrator;
- The state of the operating hours counter (P0043) and the powered-up hours counter (P0042).
Reset the inverter to return the drive to a “READY” condition in the event of a fault. The following reset
options are available:
Removing the power supply and reapplying it (power-on reset);
Pressing the operator key
(manual reset);
Through the "Reset" soft key;
Automatically by setting P0206 (auto-reset);
Through a digital input: DIx = 20 (P0263 to P0270).
6
When an alarm situation (alarm (AXXX)) is detected:
The keypad displays the alarm code and description;
The “STATUS” LED changes to yellow;
The PWM pulses are not blocked (the inverter is still operating).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
6-1
Troubleshooting and Maintenance
6.2 FAULTS, ALARMS, AND POSSIBLE CAUSES
Table 6.1 - Faults, alarms and possible causes
Fault/Alarm
6
Description
Possible Causes
F021:
DC Bus Undervoltage
DC bus undervoltage condition occurred.
The input voltage is too low and the DC bus voltage
dropped below the minimum permitted value (monitor
the value at Parameter P0004):
Ud < 223 V - For a 200-240 V input voltage
(P0296 = 0);
Ud < 170 V - For a 200-240 V single-phase input
voltage (models CFW11MXXXXS2 or CFW11MXXXXB2)
(P0296 = 0);
Ud < 385 V - For a 380 V input voltage (P0296 = 1);
Ud < 405 V - For a 400-415 V input voltage
(P0296 = 2);
Ud < 446 V - For a 440-460 V input voltage
(P0296 = 3);
Ud < 487 V - For a 480 V input voltage (P0296 = 4);
Ud < 530 V - For a 500-525 V input voltage
(P0296 = 5);
Ud < 580 V - For a 550-575 V input voltage
(P0296 = 6);
Ud < 605 V - For a 600 V input voltage (P0296 = 7);
Ud < 696 V - For a 660-690 V input voltage
(P0296 = 8).
Phase loss in the input power supply.
Pre-charge circuit failure.
Parameter P0296 was set to a value above of the power
supply rated voltage.
F022:
DC Bus Overvoltage
DC bus overvoltage condition occurred.
The input voltage is too high and the DC bus voltage
surpassed the maximum permitted value:
Ud > 400 V - For 220-230 V input models (P0296 = 0);
Ud > 800 V - For 380-480 V input models (P0296 = 1,
2, 3, or 4);
Ud > 1200 V - For 500-690 V input models (P296 = 5,
6, 7 and 8).
Inertia of the driven-load is too high or deceleration time
is too short.
Wrong settings for parameters P0151, or P0153, or P0185.
F030(*):
Power Module U Fault
U phase IGBT desaturation fault.
Short-circuit between motor phases U and V or U and W.(2)
F034(*):
Power Module V Fault
V phase IGBT desaturation fault.
Short-circuit between motor phases V and U or V and W.(2)
F038(*):
Power Module W Fault
W phase IGBT desaturation fault.
Short-circuit between motor phases W and U or W and V.(2)
A046:
High Load on Motor
Load is too high for the used motor.
Note:
It may be disabled by setting P0348 = 0 or 2.
Settings of P0156, P0157, and P0158 are too low for
the used motor.
Motor shaft load is excessive.
Inverter output current is too high.
A047:
IGBT Overload Alarm
An IGBT overload alarm occurred.
Note:
It may be disabled by setting P0350 = 0 or 2.
F048:
IGBT Overload Fault
A050:
IGBT High Temperature
An IGBT overload fault occurred.
Inverter output current is too high.
A high temperature alarm was detected by the NTC
temperature sensors located on the IGBTs.
Note:
It may be disabled by setting P0353 = 2 or 3.
Surrounding air temperature is too high (> 50 °C (122 °F))
F051:
IGBT Overtemperature
IGBT overtemperature fault [measured with the
temperature sensors (NTC)].
F067:
Incorrect Encoder/
Motor Wiring
Fault related to the phase relation of the encoder
signals.
Note:
- This fault can only happen during the self-tuning
routine.
- It is not possible to reset this fault.
- In this case, turn off the power supply, solve the
problem, and then turn it on again.
and output current is too high.
Blocked heatsink fan.
Inverter heatsink is completely covered with dust.
Output motor cables U, V, W are inverted.
Encoder channels A and B are inverted.
Encoder was not properly mounted.
(*) In the case of the modular drive, the book where the fault has occurred is not indicated on the HMI. Therefore, it is necessary to verify the
indication LEDs on the IPS1 board (refer to note (2)).
6-2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Troubleshooting and Maintenance
Table 6.1 (cont.) - Faults, alarms and possible causes
Fault/Alarm
Description
Possible Causes
F070:
Overcurrent /
Short-circuit
Overcurrent or short-circuit detected at the output,
in the DC bus, or at the braking resistor.
Short-circuit between two motor phases.
Short-circuit between the connection cables of the
dynamic braking resistor.
IGBT modules are shorted.
F071:
Output Overcurrent
The inverter output current was too high for too long.
Excessive load inertia or acceleration time too short.
Settings of P0135, P0169, P0170, P0171, and P0172
are too high.
F072:
Motor Overload
The motor overload protection operated.
Note:
It may be disabled by setting P0348 = 0 or 3.
Settings of P0156, P0157, and P0158 are too low for
F074:
Ground Fault
F076:
Motor Current
Imbalance
A ground fault occured either in the cable between
the inverter and the motor or in the motor itself.
Note:
It may be disabled by setting P0343 = 0.
Fault of motor current unbalance.
Note:
It may be disabled by setting P0342 = 0.
the used motor.
Motor shaft load is excessive.
Shorted wiring in one or more of the output phases.
Motor cable capacitance is too large, resulting in current
peaks at the output. (1)
Loose connection or broken wiring between the motor
and inverter connection.
Vector control with wrong orientation.
Vector control with encoder, encoder wiring or encoder
motor connection inverted.
F077:
DB Resistor Overload
The dynamic braking resistor overload protection
operated.
Excessive load inertia or desacceleration time too short.
Motor shaft load is excessive.
Wrong setttings for parameters P0154 and P0155.
F078:
Motor
Overtemperature
Fault related to the PTC temperature sensor installed
in the motor.
Note:
- It may be disabled by setting P0351 = 0 or 3.
- It is required to set the analog input / output to the
PTC function.
Excessive load at the motor shaft.
Excessive duty cycle (too many starts / stops per minute).
Surrounding air temperature too high.
Loose connection or short-circuit (resistance < 100 Ω) in
the wiring connected to the motor termistor.
Lack of encoder signals.
Motor termistor is not installed.
Blocked motor shaft.
Broken wiring between motor encoder and option kit for
F080:
CPU Watchdog
Microcontroller watchdog fault.
Defective encoder.
Electrical noise.
F082:
Copy Function Fault
Fault while copying parameters.
An attempt to copy the keypad parameters to an inverter
with a different firmware version.
F084:
Auto-diagnosis Fault
Auto-diagnosis fault.
Please contact WEG.
A088:
Keypad Comm. Fault
Indicates a problem between the keypad and control
board communication.
Loose keypad cable connection.
Electrical noise in the installation.
A090:
External Alarm
External alarm via digital input.
Note:
It is required to set a digital input to "No external
alarm".
External fault via digital input.
Note:
It is required to set a digital input to "No external fault".
Wiring was not connected to the digital input (DI1 to DI8)
F099:
Invalid Current Offset
Current measurement circuit is measuring a wrong
value for null current.
Defect in the inverter internal circuitry.
A110:
High Motor
Temperature
Alarm related to the PTC temperature sensor installed
in the motor.
Note:
- It may be disabled by setting P0351 = 0 or 2.
- It is required to set the analog input / output to the
PTC function.
Excessive load at the motor shaft.
A128:
Timeout for Serial
Communication
Indicates that the inverter stopped receiving valid
messages within a certain time interval.
Note:
It may be disabled by setting P0314 = 0.0 s.
Check the wiring and grounding installation.
Make sure the inverter has sent a new message within the
F079:
Encoder Signal Fault
F091:
External Fault
encoder interface.
set to “No external alarm”.
Wiring was not connected to the digital input (DI1 to DI8)
set to “No external fault”.
Excessive duty cycle (too many starts / stops per minute).
Surrounding air temperature too high.
Loose connection or short-circuit (resistance < 100 Ω) in
the wiring connected to the motor termistor.
Motor termistor is not installed.
Blocked motor shaft.
time interval set at P0314.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
6-3
6
Troubleshooting and Maintenance
Table 6.1 (cont.) - Faults, alarms and possible causes
Fault/Alarm
A129:
Anybus is Offline
Description
Alarm that indicates interruption of the Anybus-CC
communication.
Possible Causes
PLC entered into the idle state.
Programming error. Master and slave set with a different
number of I/O words.
Communication with master has been lost (broken cable,
unplugged connector, etc.).
A130:
Anybus Access Error
Alarm that indicates an access error to the
Anybus-CC communication module.
module.
Conflict with a WEG option board.
Broken or loose cable.
A133:
CAN Not Powered
Alarm indicating that the power supply was not
connected to the CAN controller.
A134:
Bus Off
Inverter CAN interface has entered into the bus-off
state.
A135:
CANopen
Communication Error
Alarm that indicates a communication error.
A136:
Idle Master
Network master has entered into the idle state.
A137:
DNet Connection Timeout
I/O connection timeout - DeviceNet communication
alarm.
F150:
Motor Overspeed
Overspeed fault.
It is activated when the real speed exceeds the value
of P0134+P0132 for more than 20 ms.
Wrong settings of P0161 and/or P0162.
Problem with the hoist-type load.
F151:
FLASH Memory Module
Fault
FLASH Memory Module fault (MMF-01).
Defective FLASH memory module.
Check the connection of the FLASH memory module.
A152:
Internal Air High
Temperature
Alarm indicating that the internal air temperature is
too high.
Note:
It may be disabled by setting P0353 = 1 or 3.
High environment temperature (> 40 °C or 45 °C
F153:
Internal air overtemperature fault.
Internal Air Overtemperature
6
Defective, unrecognized, or improperly installed Anybus-CC
Power supply is off.
Incorrect communication baud-rate.
Two nodes configured with the same address in the network.
Wrong cable connection (inverted signals).
Communication problems.
Wrong master conFiguretion/settings.
Incorrect conFiguretion of the communication objects.
PLC in IDLE mode.
Bit of the PLC command register set to zero (0).
One or more allocated I/O connections have entered
into the timeout state.
(> 104 ºF or 113 ºF) depending on the model, refer to
the section 3.1) and high output current.
Blocked or defective fan.
Fins of the book heatsink too dirty, impairing the air flow.
F156:
Undertemperature
Undertemperature fault (below -30 °C (-22 °F)) in the
IGBT or rectifier measured by the temperature sensors.
Surrounding air temperature ≤ -30 °C (-22 °F).
A177:
Fan Replacement
Fan replacement alarm (P0045 > 50000 hours).
Note:
This function may be disabled by setting P0354 = 0.
Maximum number of operating hours for the heatsink fan
A181:
Invalid Clock Value
Invalid clock value alarm.
It is necessary to set date and time at parameters P0194
F182:
Pulse Feedback Fault
Indicates a fault on the output pulses feedback.
Keypad battery is discharged, defective, or not installed.
Defect in the inverter internal circuitry.
F183:
IGBT Overload +
Temperature
Overtemperature related to the IGBTs overload
protection.
Surrounding air temperature too high.
Operation with frequencies < 10 Hz under overload.
A300:
High temperature at IGBT
U B1
F301:
Overtemperature at IGBT
U B1
A303:
High Temperature at IGBT
V B1
F304:
Overtemperature at IGBT
V B1
A306:
High Temperature at IGBT
W B1
High temperature alarm measured with the
temperature sensor (NTC) of the book 1 U phase IGBT
6-4
has been reached.
to P0199.
Overtemperature fault measured with the temperature
sensor (NTC) of the book 1 U phase IGBT
High temperature alarm measured with the
temperature sensor (NTC) of the book 1 V phase IGBT
Overtemperature fault measured with the temperature
sensor (NTC) of the book 1 V phase IGBT
High environment temperature (> 40 °C or 45 °C
(> 104 °F or 113 °F) depending on the model, refer to
the section 3.1) and high output current.
Blocked or defective fan.
Fins of the book heatsink too dirty, impairing the air flow.
High temperature alarm measured with the
temperature sensor (NTC) of the book 1 W phase IGBT
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Troubleshooting and Maintenance
Table 6.1 (cont.) - Faults, alarms and possible causes
Fault/Alarm
Description
F307:
Overtemperature at IGBT
W B1
Overtemperature fault measured with the temperature
sensor (NTC) of the book 1 W phase IGBT
A309:
High Temperature at IGBT
U B2
F310:
Overtemperature at IGBT
U B2
High temperature alarm measured with the
temperature sensor (NTC) of the book 2 U phase IGBT
A312:
High Temperature at IGBT
V B2
F313:
Overtemperature at IGBT
V B2
High temperature alarm measured with the
temperature sensor (NTC) of the book 2 V phase IGBT
A315:
High Temperature at IGBT
W B2
High temperature alarm measured with the
temperature sensor (NTC) of the book 2 W phase IGBT
F316:
Overtemperature at IGBT
W B2
Overtemperature fault measured with the temperature
sensor (NTC) of the book 2 W phase IGBT
A318:
High Temperature at IGBT
U B3
F319:
Overtemperature at IGBT U B3
High temperature alarm measured with the
temperature sensor (NTC) of the book 3 U phase IGBT
A321:
High Temperature at IGBT
V B3
F322:
Overtemperature at IGBT V B3
High temperature alarm measured with the
temperature sensor (NTC) of the book 3 V phase IGBT
A324:
High Temperature at IGBT
W B3
High temperature alarm measured with the
temperature sensor (NTC) of the book 3 W phase IGBT
F325:
Overtemperature at IGBT
W B3
Overtemperature fault measured with the temperature
sensor (NTC) of the book 3 W phase IGBT
A327:
High Temperature at IGBT
U B4
F328:
Overtemperature at IGBT U B4
High temperature alarm measured with the
temperature sensor (NTC) of the book 4 U phase IGBT
A330:
High Temperature at IGBT
V B4
F331:
Overtemperature at IGBT V B4
High temperature alarm measured with the
temperature sensor (NTC) of the book 4 V phase IGBT
A333:
High Temperature at IGBT
W B4
High temperature alarm measured with the
temperature sensor (NTC) of the book 4 W phase IGBT
F334:
Overtemperature at IGBT
W B4
Overtemperature fault measured with the temperature
sensor (NTC) of the book 4 W phase IGBT
A336:
High Temperature at IGBT
U B5
F337:
Overtemperature at IGBT U B5
High temperature alarm measured with the
temperature sensor (NTC) of the book 5 U phase IGBT
A339:
High Temperature at IGBT
V B5
High temperature alarm measured with the
temperature sensor (NTC) of the book 5 V phase IGBT
Possible Causes
Overtemperature fault measured with the temperature
sensor (NTC) of the book 2 U phase IGBT
Overtemperature fault measured with the temperature
sensor (NTC) of the book 2 V phase IGBT
Overtemperature fault measured with the temperature
sensor (NTC) of the book 3 U phase IGBT
Overtemperature fault measured with the temperature
sensor (NTC) of the book 3 V phase IGBT
High environment temperature (> 40 °C or 45 °C
(> 104 °F or 113 °F) depending on the model, refer to
the section 3.1) and high output current.
Blocked or defective fan.
Fins of the book heatsink too dirty, impairing the air flow.
Overtemperature fault measured with the temperature
sensor (NTC) of the book 4 U phase IGBT
6
Overtemperature fault measured with the temperature
sensor (NTC) of the book 4 V phase IGBT
Overtemperature fault measured with the temperature
sensor (NTC) of the book 5 U phase IGBT
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
6-5
Troubleshooting and Maintenance
Table 6.1 (cont.) - Faults, alarms and possible causes
Fault/Alarm
6
Description
F340:
Overtemperature at IGBT
V B5
Overtemperature fault measured with the temperature
sensor (NTC) of the book 5 V phase IGBT
A342:
High Temperature at IGBT
W B5
High temperature alarm measured with the
temperature sensor (NTC) of the book 5 W phase IGBT
F343:
Overtemperature at IGBT
W B5
Overtemperature fault measured with the temperature
sensor (NTC) of the book 5 W phase IGBT
A345:
High Load at IGBT U B1
Overload alarm at book 1 U phase IGBT
F346:
Overload at IGBT U B1
Overload fault at book 1 U phase IGBT
A348:
High Load at IGBT V B1
Overload alarm at book 1 V phase IGBT
F349:
Overload at IGBT V B1
Overload fault at book 1 V phase IGBT
A351:
High Load at IGBT W B1
Overload alarm at book 1 W phase IGBT
F352:
Overload at IGBT W B1
Overload fault at book 1 W phase IGBT
A354:
High Load at IGBT U B2
Overload alarm at book 2 U phase IGBT
F355:
Overload at IGBT U B2
Overload fault at book 2 U phase IGBT
A357:
High Load at IGBT V B2
Overload alarm at book 2 V phase IGBT
F358:
Overload at IGBT V B2
Overload fault at book 2 V phase IGBT
A360:
High Load at IGBT W B2
Overload alarm at book 2 W phase IGBT
F361:
Overload at IGBT W B2
Overload fault at book 2 W phase IGBT
A363:
High Load at IGBT U B3
Overload alarm at book 3 U phase IGBT
F364:
Overload at IGBT U B3
Overload fault at book 3 U phase IGBT
A366:
High Load at IGBT V B3
Overload alarm at book 3 V phase IGBT
F367:
Overload at IGBT V B3
Overload fault at book 3 V phase IGBT
A369:
High Load at IGBT W B3
Overload alarm at book 3 W phase IGBT
F370:
Overload at IGBT W B3
Overload fault at book 3 W phase IGBT
A372:
High Load at IGBT U B4
Overload alarm at book 4 U phase IGBT
F373:
Overload at IGBT U B4
Overload fault at book 4 U phase IGBT
A375:
High Load at IGBT V B4
Overload alarm at book 4 V phase IGBT
F376:
Overload at IGBT V B4
Overload fault at book 4 V phase IGBT
6-6
Possible Causes
High environment temperature (> 40 °C or 45 °C
(> 104 °F or 113 °F) depending on the model, refer to
the section 3.1) and high output current.
Blocked or defective fan.
Fins of the book heatsink too dirty, impairing the air flow.
High current at the inverter output (see figure 8.1).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Troubleshooting and Maintenance
Table 6.1 (cont.) - Faults, alarms and possible causes
Fault/Alarm
Description
A378:
High Load at IGBT W B4
Overload alarm at book 4 W phase IGBT
F379:
Overload at IGBT W B4
Overload fault at book 4 W phase IGBT
A381:
High Load at IGBT U B5
Overload alarm at book 5 U phase IGBT
F382:
Overload at IGBT U B5
Overload fault at book 5 U phase IGBT
A384:
High Load at IGBT V B5
Overload alarm at book 5 V phase IGBT
F385:
Overload at IGBT V B5
Overload fault at book 5 V phase IGBT
A387:
High Load at IGBT W B5
Overload alarm at book 5 W phase IGBT
F388:
Overload at IGBT W B5
Overload fault at book 5 W phase IGBT
Possible Causes
High current at the inverter output (see figure 8.1).
A390:
Phase U book 1current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
U B1
between this phase and the smallest current of the same
phase in other book, only when the current in this phase
is higher than 75 % of its nominal value.
A391:
Phase V book 1current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
V B1
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
A392:
Phase W book 1current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
W B1
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
A393:
Phase U book 2 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
U B2
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
A394:
Phase V book 2 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
V B2
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
Bad electric connection between the DC bus and the
power unit.
Bad electric connection between the power unit output
and the motor.
Note: In case of fast acceleration or braking, this alarm may
be indicated momentarily, disappearing after a few seconds.
This is not an indication of any anomaly in the inverter.
If this alarm persists when the motor is operating at a
constant speed, it is an indication of an anomaly in the
current distribution among the power units.
A395:
Phase W book 2 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
W B2
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
A396:
Phase U book 3 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
U B3
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
A397:
Phase V book 3 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
V B3
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
6-7
6
Troubleshooting and Maintenance
Table 6.1 (cont.) - Faults, alarms and possible causes
Fault/Alarm
Description
Possible Causes
A398:
Phase W book 3 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
W B3
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
A399:
Phase U book 4 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
U B4
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
A400:
Phase V book 4 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
V B4
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
Bad electric connection between the DC bus and the
power unit.
Bad electric connection between the power unit output
A401:
Phase W book 4 current unbalance alarm.
and the motor.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
W B4
between this phase and the smallest current of the
Note: In case of fast acceleration or braking, this alarm may
same phase in other book, only when the current in
be indicated momentarily, disappearing after a few seconds.
this phase is higher than 75 % of its nominal value.
This is not an indication of any anomaly in the inverter.
If this alarm persists when the motor is operating at a
A402:
Phase U book 5 current unbalance alarm.
constant speed, it is an indication of an anomaly in the
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
current distribution among the power units.
U B5
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
A403:
Phase V book 5 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
V B5
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
A404:
Phase W book 5 current unbalance alarm.
Current Unbalance at Phase It indicates a 20 % unbalance in the current distribution
W B5
between this phase and the smallest current of the
same phase in other book, only when the current in
this phase is higher than 75 % of its nominal value.
F406:
Overtemperature at the
Braking Module
F408:
Failure in the Cooling System
6
F410:
External Fault
F412:
Overtemperature at the
Rectifier
These faults/alarms are associated to the conFiguretion
of the parameters P0832 and P0833.
- Function of the DIM1 input.
- Function of the DIM2 input.
Overtemperature (rectifier/braking).
Failure in the connection between the digital input and
the sensor.
Failure of the corresponding sensor.
Failure in the device being monitored by the sensor.
A010:
Overtemperature at the
Rectifier
(1) Long motor cables (with more than 100 meters) will have a high leakage capacitance to the ground. The circulation of leakage currents through
these capacitances may activate the ground fault protection after the inverter is enabled, and consequently, the occurrence of fault F074. Possible
solution:
- Decrease the carrier frequency (P0297).
(2) In case of the faults F030 (U Arm Fault), F034 (V Arm Fault) and F038 (W Arm Fault), the indication of which book has caused the fault is done
by IPS1 board LEDs. When a RESET is performed the LEDs are switched off, going on again if the fault persists.
6-8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Troubleshooting and Maintenance
Figure 6.1 - Power unit arm fault (desaturation) indication LEDs
6.3 SOLUTIONS FOR THE MOST FREQUENT PROBLEMS
Table 6.2 - Solutions for the most frequent problems
Point to be
Verified
Problem
Motor does not start
Incorrect wiring connection
Corrective Action
1. Check all power and control connections. For instance, the digital inputs set to start/
stop, general enable, or no external error shall be connected to the 24 Vdc or to
DGND* terminals (refer to figure 3.31).
Analog reference
1. Check if the external signal is properly connected.
(if used)
2. Check the status of the control potentiometer (if used).
Incorrect settings
1. Check if parameters are properly set for the application.
Fault
1. Check if the inverter is not blocked due to a fault condition.
2. Check if terminals XC1:13 and XC1:11 are not shorted (short-circuit at the 24 Vdc
power supply).
Motor stall
1. Decrease motor overload.
Loose connection
1. Stop the inverter, turn off the power supply, and check and tighten fluctuates
2. Increase P0136, P0137 (V/f), or P0169/P0170 (vector control).
Motor speed
fluctuates (oscillates)
(oscillates) all power connections.
2. Check all internal connections of the inverter.
Defective reference
1. Replace potentiometer.
potentiometer
Oscillation of the external
analog reference
1. Identify the cause of the oscillation. If it is caused by electrical noise, use shielded
cables or separate from the power and control wiring.
6
Incorrect settings
1. Check parameters P0410, P0412, P0161, P0162, P0175, and P0176.
(vector control)
2. Refer to the Software Manual.
Motor speed
Incorrect settings
1. Check if the values of P0133 (minimum speed) and P0134 (maximum speed) are
too high or too low
(reference limits)
properly set for the motor and application used.
Control signal from
1. Check the level of the reference control signal.
the analog reference
2. Check the settings (gain and offset) of parameters P0232 to P0249.
(if used)
Motor does not reach
Settings the rated speed,
Motor nameplate
1. Check if the motor has been properly sized for the application.
Settings
1. Decrease P0180.
2. Check P0410.
or motor speed starts
oscillating around the rated
speed (Vector Control)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
6-9
Troubleshooting and Maintenance
Table 6.2 (cont.) - Solutions for the most frequent problems
Point to be
Verified
Problem
Off display
Corrective Action
Keypad connections
1. Supply the IPS at the XC9 connector points 1 and 4 with 24 Vdc ± 10 %/4 A.
IPS1 24 Vdc power supply
1. Apply a voltage of 24 Vdc ± 10 %.
voltage
Open power supply fuse(s)
1. Replace fuses.
Settings
1. Decrease P0180.
Low motor speed and
Encoder signals are
1. Check signals A - A, B - B, refer to the incremental encoder interface manual. If
P0009 = P0169 or P0170
inverted or power
signals are properly installed, exchange two of the output phases.
(motor operating with torque
connection is inverted
For instance U and V.
Motor does not operate in
the field weakning region
(Vector Control)
limitation), for P0202 = 4 vector with encoder
6.4 INFORMATION FOR CONTACTING TECHNICAL SUPPORT
NOTE!
For technical support and servicing, it is important to have the following information in hand:
Inverter model;
Serial number, manufacturing date, and hardware revision that are listed in the product nameplate
(refer to item 2.6);
Installed software version (check parameter P0023);
Application data and inverter settings.
6.5 PREVENTIVE MAINTENANCE
DANGER!
Always turn off the mains power supply before touching any electrical component associated to the inverter.
High voltage may still be present even after disconnecting the power supply.
To prevent electric shock, wait at least 10 minutes after turning off the input power for the complete discharge of the power capacitors.
Always connect the equipment frame to the protective ground (PE). Use the adequate connection terminal in the inverter.
6
ATTENTION!
The electronic boards have electrostatic discharge sensitive components.
Do not touch the components or connectors directly. If needed, first touch the grounded mettalic
frame or wear a ground strap.
6-10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Troubleshooting and Maintenance
Do not perform any withstand voltage test!
If needed, consult WEG.
The inverters require low maintenance when properly installed and operated . Table 6.3 presents main procedures
and time intervals for preventive maintenance. Table 6.4 provides recommended periodic inspections to be
performed every 6 months after inverter start-up.
Table 6.3 - Preventive maintenance
Maintenance
Fan replacement
Keypad battery replacement
If the inverter is
stocked (not being
Electrolytic used):
capacitors “Reforming”
Inverter is being used:
replace
Interval
After 50000 operating hours. (1)
Every 10 years.
Every year from the manufacturing
date printed in the inverter identification label (refer to item 2.6).
Every 10 years.
Instructions
Replacement procedure shown in figures 6.2.
Refer to chapter 4.
Supply the UP11 (at the +UD ans -UD terminal) with a voltage
250 to 350 Vdc, during 1 hour at least. Then, disconnect the
power supply and wait at least 24 hours before using the inverter
(reapply power).
Contact WEG technical support to obtain replacement procedures.
(1) The inverters are factory set for automatic fan control (P0352 = 2), which means that they will be turned on only when the heatsink temperature
exceeds a reference value. Therefore, the operating hours of the fan will depend on the inverter usage conditions (motor current, output frequency,
cooling air temperature, etc.). The inverter stores the number of operating hours of the fan in parameter P0045. When this parameter reaches
50000 operating hours, the keypad display will show alarm A177.
FANS
VENTILADORES
6
RAILS FOR
FANDESLIZAMENTO
SLIDING
TRILHOS
PARA
DO VENTILADORES
LOCK
SYSTEM
FOR P/
FAST
FAN
SISTEMA
DE TRAVA
TROCA
RÁPIDA DOS VENTILADORES
REPLACEMENT
Figure 6.2 - Fan replacement
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
6-11
Troubleshooting and Maintenance
Table 6.4 - Recommended periodic inspections - Every 6 months
Component
Terminals, connectors
Problem
Loose screws
Corrective Action
Tighten
Loose connectors
Fans / Cooling system
Dirty fans
Cleaning
Abnormal acoustic noise
Replace fan. Refer to figure 6.2.
Blocked fan
Check the fan connection.
Abnormal vibration
Dust in the cabinet air filter
Printed circuit boards
Cleaning or replacement
Accumulation of dust, oil, humidity, etc.
Cleaning
Odor
Replacement
Power module /
Accumulation of dust, oil, humidity, etc.
Cleaning
Power connections
Loose connection screws
Tighten
DC bus capacitors
Discoloration / odor / electrolyte leakage
Replacement
(DC Link)
Expanded or broken safety valve
Frame expansion
Power resistors
Discoloration
Replacement
Odor
Heatsink
Dust accumulation
Cleaning
Dirty
6.5.1 Cleaning Instructions
When it becomes necessary to clean the inverter, follow the instructions below:
Ventilation system:
Cut off the inverter supply and wait 10 minutes.
Remove the dust accumulated at the ventilation inlets with a plastic brush or a flannel.
Remove the dust accumulated on the heatsink fins and on fan blades using compressed air.
Electronic boards:
Cut off the inverter supply and wait 10 minutes.
Remove the dust accumulated on the boards using an anti-static brush or ionized compressed air (E.g.:
Charges Burtes Ion Gun (non nuclear) reference A6030-6DESCO).
If necessary, remove the boards from the inverter.
Use always an ESD wrist strap.
6
6-12
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Troubleshooting and Maintenance
Inspect the heatsink fins of the power units regularly verifying if there is any dirt accumulation that could impair
the inverter cooling. Therefore, remove the power unit side cover.
DISSIPADORES
HEATSINKS
JANELAS
PARA
HEATSINK FIN
CLEANING
LIMPEZA DOS
OPENINGS
DISSIPADORES
6
Figure 6.3 - Covers to get access for inspection/cleaning of the heatsink fins
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
6-13
Troubleshooting and Maintenance
6
6-14
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Option Kits and Accessories
OPTION KITS AND ACCESSORIES
This chapter presents:
The option kit that can be incorporated to the inverter from
the factory:
- Safety Stop according to EN 954-1 category 3.
Instructions for the proper use of the option kit.
The accessories that can be incorporated to the inverters.
Details for the installation, operation, and programming of the accessories are described in their own manuals
and were not included in this chapter.
7.1 OPTION KITS
7.1.1 Safety Stop According to EN 954-1 Category 3 (Pending Certification)
Inverters with the following codification: CFW11MXXXXXXOY.
The inverters with this option are equipped with an additional board (SRB2) that contains 2 safety relays and
an interconnection cable with the power circuit.
Figure 7.1 shows the location of the SRB2 board and the location of the connector XC25 (used for the connection
of the SRB2 board signals).
The relay coils are available through the connector XC25, as presented in table 7.1.
DANGER!
The activation of the Safety Stop, i.e., disconnection of the 24 Vdc power supply from the safety relay
coil (XC25:1(+) and 2(-); XC25:3(+) and 4(-)) does not guarantee the electrical safety of the motor
terminals (they are not isolated from the power supply in this condition).
Operation:
1. The Safety Stop function is activated by disconnecting the 24 Vdc voltage from the safety relay coil (XC25:1(+)
and 2(-); XC25:3(+) and 4(-)).
2. Upon activation of the Safety Stop, the PWM pulses at the inverter output will be blocked and the motor will
coast to stop.
The inverter will not start the motor or generate a rotating magnetic field even in the event of an internal
failure (pending certification).
The keypad will display a message informing that the Safety Stop is active.
3. Apply 24 Vdc voltage to the safety relay coil (XC25:1(+) and 2(-); XC25:3(+) and 4(-)) to get back to normal
operation after activation of the Safety Stop.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
7-1
7
Option Kits and Accessories
XC25
Figure 7.1 - SRB2 board location in the control rack
Table 7.1 - XC25 connections
Connector XC25
Function
1
R1+
Terminal 1 of relay 1 coil
2
R1-
Terminal 2 of relay 1 coil
3
R2+
Terminal 1 of relay 2 coil
4
R2-
Terminal 2 of relay 2 coil
Specifications
Rated coil voltage: 24 V, range from 20 to 30 Vdc.
Coil resistance: 960 Ω ±10 % @ 20 °C (68 °F).
Rated coil voltage: 24 V, range from 20 to 30 Vdc.
Coil resistance: 960 Ω ±10 % @ 20 °C (68 °F).
7.2 ACCESSORIES
The accessories are installed to the inverter easily and quickly using the "Plug and Play" concept. Once the
accessory is connected to the slot, the control circuitry identifies the model and displays the installed accessory
code in P0027 or P0028. The accessory shall be installed with the inverter power supply off.
The code and model of each availabe accessory is presented in the table 7.2. The accessories can be ordered
separately and will be shippe in an individual package containing the components and the manual with detailed
instructions for the product installation, operation, and programming.
ATTENTION!
Only one module can be fitted at once in each slot (1, 2, 3, 4, or 5).
7
7-2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Option Kits and Accessories
Table 7.2 - Accessory models
WEG Part
Number
Name
Description
Control accessories for installation in the Slots 1, 2 and 3
IOA module: 1 voltage/current analog input (14 bits); 2 digital inputs; 2
voltage/current analog outputs (14 bits); 2 open-collector digital outputs.
Slot
Identification
Parameters
P0027
P0028
1
FD--
----
11008162
IOA-01
11008099
IOB-01
IOB module: 2 isolated analog inputs (voltage/current); 2 digital inputs; 2
isolated analog outputs (voltage/current) (the programming of the outputs
is identical as in the standard CFW-11); 2 open-collector digital outputs.
1
FA--
----
11008100
ENC-01
5 to 12 Vdc incremental encoder module, 100 kHz, with an encoder signal
repeater.
2
--C2
----
11008101
11008102
11008103
11008104
ENC-02
RS485-01
RS232-01
RS232-02
5 to 12 Vdc incremental encoder module, 100 kHz.
RS-485 serial communication module (Modbus).
RS-232C serial communication module (Modbus).
RS-232C serial communication module with DIP-switches for programming
the microcontroller FLASH memory.
2
3
3
3
--C2
----------
---CE-CC-CC--
3
3
1, 2
and 3
----------
CA-CD---xx(1)(3)
----------------
--xx(2)(3)
--xx(2)(3)
--xx(2)(3)
--xx(2)(3)
--xx(2)(3)
----
--xx(3)
-
-
-
-
11008105
11008106
11008911
11008107
11008158
10933688
11008160
11008161
11008912
11008913
11010521
11010298
10960847
10960846
11077222
11077221
CAN/RS485-01 CAN and RS-485 interface module (CANopen / DeviceNet / Modbus).
CAN-01
CAN interface module (CANopen / DeviceNet).
PLC11-01
PLC module.
Anybus-CC Accessories for installation in the Slot 4
PROFDP-05 ProfibusDP interface module.
4
DEVICENET-05 DeviceNet interface module.
4
ETHERNET IP-05 Ethernet/IP interface module.
4
RS232-05
RS-232 (passive) interface module (Modbus).
4
RS485-05
RS-485 (passive) interface module (Modbus).
4
Flash Memory Module for installation in the slot 5 – included as a standard feature
MMF-01
FLASH memory module.
5
HMI, blank cover and remote keypad frame
HMI-01
Keypad.(4)
HMI
RHMIF-01
Remote keypad frame Kit (IP56).
HMID-01
Blank cover for the keypad slot.
HMI
Miscellanea
CCS-01
Kit for control cables shielding (included in the standard product).
CONRA-01
Control rack (containing the CC11 control board).
RACK 2
Rack para montagem de 2 unidades UP11 em painel (5)
RACK 3
Rack para montagem de 3 unidades UP11 em painel (5)
-
(1) Refer to the PLC Module Manual.
(2) Refer to the Anybus-CC Communication Manual.
(3) Refer to the Software Manual.
(4) Use DB-9 pin, male-to-female, straight-through cable (serial mouse extension type) for connecting the keypad to the inverter or Null-Modem
standard cable. Maximum cable length: 10 m (33 ft).
Examples:
- Mouse extension cable - 1.80 m (6 ft); Manufacturer: Clone.
- Belkin pro series DB9 serial extension cable 5 m (17 ft); Manufacturer: Belkin.
- Cables Unlimited PCM195006 cable, 6 ft DB9 m/f; Manufacturer: Cables Unlimited.
(5) Refer to the rack mounting guide.
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
7-3
Option Kits and Accessories
7
7-4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Technical Specifications
TECHNICAL SPECIFICATIONS
This chapter describes the technical specifications (electrical and
mechanical) of the CFW-11M inverter series.
8.1 POWER DATA
See table 8.1.
8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
8-1
8-2
8
CFW11M 0600 T 4
CFW11M 1140 T 4
CFW11M 1710 T 4
CFW11M 2280 T 4
CFW11M 2850 T 4
CFW11M 0470 T 5
CFW11M 0893 T 5
CFW11M 1340 T 5
CFW11M 1786 T 5
CFW11M 2232 T 5
CFW11M 0427 T 6
CFW11M 0811 T 6
CFW11M 1217 T 6
CFW11M 1622 T 6
CFW11M 2028 T 6
Model
758...1025
574...891
436...713
Power
supply
[Vdc]
600 (1)
1140 (1)
1710 (1)
2280 (1)
2850 (1)
470 (2)
893 (2)
1340 (2)
1786 (2)
2232 (2)
427 (2)
811 (2)
1217 (2)
1622 (2)
2028 (2)
Rated
output
current
[Arms]
500/370
900/700
1400/1050
1800/1400
2300/1750
500/400
900/710
1400/1120
1800/1500
2300/1850
500/400
1000/800
1500/1200
2000/1600
2500/2000
690
1311
1967
2622
3278
541
1027
1541
2054
2567
491
933
1400
1865
2332
4.8
9.6
14.4
19.2
24
6
12
18
24
30
6.2
12.4
18.6
24.8
31
515 (1)
979 (1)
1468 (1)
1957 (1)
2446 (1)
380 (2)
722 (2)
1083 (2)
1444 (2)
1805 (2)
340 (2)
646 (2)
969 (2)
1292 (2)
1615 (2)
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
660
1254
1881
2508
3135
517
982.3
1474
1965
2455
469.7
892.1
1339
1784
2232
900
1710
2565
3420
4275
705
1340
2010
2679
3348
641
1217
1826
2433
3042
Rated
output
current
[Arms]
Use with Normal Duty (ND) cycle
Overload
current (3)
Carrier
Maximum Rated input Dissipated
[Arms]
frequency
motor (4)
current
power
[kHz]
[CV/kW]
[Adc]
[kW](5)
1 min
3s
773
1468.5
2202
2935.5
3669
570
1083
1624
2166
2707
510
969
1453.5
1938
2422.5
1030
1958
2936
3914
4892
760
1444
2166
2888
3610
680
1292
1938
2584
3230
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
450/320
800/600
1200/900
1600/1200
2000/1500
400/315
800/630
1200/900
1500/1120
1900/1400
400/315
800/630
1250/1000
1600/1280
2000/1600
Use with Heavy Duty (HD) cycle
Overload
current (3)
Carrier
Maximum
[Arms]
frequency
motor (4)
[kHz]
[CV/kW]
1 min
3s
592
1126
1688
2251
2813
437
830
1245
1660
2075
391
743
1114
1486
1857
Rated
input
current
[Adc]
4
8
12
16
20
5
8
12
19
24
5
10
15
20
25
Dissipated
power
[kW](5)
Technical Specifications
Table 8.1 - Technical specification for the CFW-11M series
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Technical Specifications
Note:
(1)Steady-state rated current in the following conditions:
- Surrounding air temperature: -10 °C to 45 °C (14 °F to 113 °F). The inverter is capable of operating with
an maximum surrounding air temperature of 55 °C (131 °F) if an output current derating of 2 % is applied
for each ºC (or 1.11 % each °F) above 45 °C (113 °F).
- Relative air humidity: 5 % to 90 % non-condensing.
- Altitude: 1000 m (3.300 ft). Above 1000 m (3.300 ft) up to 4000 m (13.200 ft) the output current shall
be derated by 1 % for each 100 m (or 0.3 % each 100 ft) above 1000 m (3.300 ft).
- Ambient with pollution degree 2 (according to EN50178 and UL508C).
(2) Nominal current in permanent regimen at the following conditions:
- Temperature around the inverter: -10 °C to 40 °C (14 °F to 104 °F). The inverter is able to operate in
environments with temperatures up to 55 °C (131 °F), if a reduction of 2 % in the output current is applied
for each Celsius degree (or 1.11 % each °F) above 40 °C (104 °F).
- Relative humidity: 5 % to 90 % without condensation.
- Altitude: 1000 m (3.300 ft). Above 1000 m up to 4000 m (3.300 ft to 13.200 ft) the output current must
be reduced in 2% for each 100 m (or 0.6 % each 100 ft) above 1000 m (3.300 ft).
- Environment with pollution degree 2 (according to EN50178 and UL508C).
(3)Table 8.1 presents only two points of the overload curve (activation time of 1 min and 3 s). The complete
information about the IGBTs overload for Normal and Heavy Duty Cycles is presented below.
Io
IRAT ND
2.0
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1.0
0.9
∆ t (s)
0
10 20 30 40 50 60 70 80 90 100 110 120
(a) IGBTs overload curve for the Normal Duty (ND) cycle
Io
IRAT ND
2.0
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
8
1.1
1.0
0
10 20 30 40 50 60 70
80 90 100 110 120
∆ t (s)
(b) IGBTs overload curve for the Heavy Duty (HD) cycle
Figure 8.1 - Overload curves for the IGBTs
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
8-3
Technical Specifications
(4) The motor ratings are merely a guide for 440 V (400 V line), 575 V (500 V line) and 690 V (600 V line), IV
pole WEG motors. The adequate inverter sizing shall be based on the rated current of the motor used.
(5) The information provided about the inverter losses is valid for the rated operating condition, i.e., for rated
output current and rated carrier frequency.
8.2 ELECTRICAL / GENERAL SPECIFICATIONS
CONTROL
METHOD
Voltage source
Type of control:
- V/f (Scalar);
- V V W : Voltage vector control;
- Vector control with encoder;
- Sensorless vector control (without encoder).
PWM SVM (Space Vector Modulation);
Full digital (software) current, flux, and speed regulators.
Execution rate:
- current regulators: 0.2 ms (5 kHz)
- flux regulator: 0.4 ms (2.5 kHz)
- speed regulator / speed measurement: 1.2 ms
OUTPUT
FREQUENCY
to 300 Hz in the scalar mode and from 30 Hz to 120 Hz in the vector mode.
PERFORMANCE
SPEED
V/f (Scalar):
(Vector Control)
CONTROL
0 to 3.4 x rated motor frequency (P0403). The rated frequency is programmable from 0 Hz Regulation (with slip compensation): 1 % of the rated speed.
Speed variation range: 1:20.
V V W:
Regulation: 1 % of the rated speed.
Speed variation range: 1:30.
Sensorless:
Regulation: 0.5 % of the rated speed.
Speed variation range: 1:100.
Vector with Encoder:
Regulation:
±0.01 % of the rated speed with a 14-bits analog input (IOA);
±0.01 % of the rated speed with a digital reference (Keypad, Serial, Fieldbus,
Electronic Potentiometer, Multispeed);
±0.05 % of the rated speed with a 12-bits analog input (CC11).
TORQUE
Range: 10 to 180 %, regulation: ±5 % of the rated torque (with encoder);
CONTROL
Range: 20 to 180 %, regulation: ±10 % of the rated torque (sensorless above 3 Hz).
INPUTS
ANALOG
2 isolated differential inputs; resolution of AI1: 12 bits, resolution of AI2: 11bits + signal, (0 to 10) V, (0 to 20) mA or (4 to 20) mA, Impedance: 400 kΩ for (0 to 10) V, 500 Ω for
(CC11 board)
(0 to 20) mA or (4 to 20) mA, programmable functions.
DIGITAL
OUTPUTS ANALOG
2 isolated analog outputs, (0 to 10) V, RL ≥ 10 kΩ (maximum load), 0 to 20 mA / 4 to 20 mA
(RL ≤ 500 Ω) resolution: 11 bits, programmable functions.
(CC11 board)
6 isolated digital inputs, 24 Vdc, programmable functions.
RELAY
3 relay outputs with NO/NC contacts, 240 Vac, 1 A, programmable functions.
8
8-4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Technical Specifications
8.2 ELECTRICAL / GENERAL SPECIFICATIONS (cont.)
SAFETY
Output overcurrent/short-circuit;
PROTECTION
Under / Overvoltage;
Overtemperature;
Braking resistor overload;
IGBTs overload;
Motor overload;
External fault / alarm;
CPU or memory fault;
Output phase-ground short-circuit.
INTEGRAL
STANDARD
KEYPAD KEYPAD (HMI)
9 operator keys: Start/Stop, Up Arrow, Down Arrow, Direction of Rotation, Jog,
Local/Remote, Right Soft Key and Left Soft Key;
Graphical LCD display;
View/edition of parameters;
Indication accuracy:
- current: 5 % of the rated current;
- speed resolution: 1 rpm;
Possibility of remote mounting.
ENCLOSURE
IP00
PC CONNECTION USB CONNECTOR
FOR INVERTER
PROGRAMMING
USB standard Rev. 2.0 (basic speed);
Type B (device) USB plug;
Interconnection cable: standard host/device shielded USB cable.
8.2.1 Codes and Standards
SAFETY
UL 508C - Power conversion equipment.
STANDARDS
UL 840 - Insulation coordination including clearances and creepage distances for electrical
equipment.
EN61800-5-1 - Safety requirements electrical, thermal and energy.
EN 50178 - Electronic equipment for use in power installations.
EN 60204-1 - Safety of machinery. Electrical equipment of machines. Part 1: General
requirements.
Note: The final assembler of the machine is responsible for installing an safety stop device
and a supply disconnecting device.
EN 60146 (IEC 146) - Semiconductor converters.
EN 61800-2 - Adjustable speed electrical power drive systems - Part 2: General requirements Rating specifications for low voltage adjustable frequency AC power drive systems.
8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
8-5
Technical Specifications
8.2.1 Codes and Standards (cont.)
ELECTROMAGNETIC
COMPATIBILITY (EMC)
EN 61800-3 - Adjustable speed electrical power drive systems - Part 3: EMC product standard including specific test methods.
EN 55011 - Limits and methods of measurement of radio disturbance characteristics of
industrial, scientific and medical (ISM) radio-frequency equipment.
CISPR 11 - Industrial, scientific and medical (ISM) radio-frequency equipment - Electromagnetic disturbance characteristics - Limits and methods of measurement.
EN 61000-4-2 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement
techniques - Section 2: Electrostatic discharge immunity test.
EN 61000-4-3 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement
techniques - Section 3: Radiated, radio-frequency, electromagnetic field immunity test.
EN 61000-4-4 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement
techniques - Section 4: Electrical fast transient/burst immunity test.
EN 61000-4-5 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement
techniques - Section 5: Surge immunity test.
EN 61000-4-6 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 6: Immunity to conducted disturbances, induced by radio-frequency fields.
MECHANICAL
EN 60529 - Degrees of protection provided by enclosures (IP code).
STANDARDS
UL 50 - Enclosures for electrical equipment.
8
8-6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Technical Specifications
103,9
103.9 (4.1)
58.7
58,7 (6.2)
8.3 MECHANICAL DATA
138,9
62.7
62,7 (2.5)
138.9 (5.5)
578.2
(22.7)
578,2
555.8
555,8(21.9)
100.5
100,5
(3.10)
100,5
(3.10)
100.5
1460
1460(57.5)
Ø 22.5
22,5 (0.8)
1506.7
1506,7(159.3)
230230
(9.1)
Ø 9.2 (0.3)
9,2
509.8
(20.1)
509,8
8
Figure 8.2 - UP11 dimensions mm (in)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
8-7
60.3
60,3
(2.37)
85.7
85,7
(3.37)
75.5
(2.97)
75,5
Technical Specifications
180.1
180,1(7.09)
313.3
313,3
(12.34)
213.1
213,1(8.39)
Figure 8.3 - Control rack dimensions mm (in)
8
8-8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Technical Specifications
255255
(10.04)
47.4
47,4
(1.86)
69.4
69,4
(2.73)
179.5
179,5(7.06)
375
(14.76)
375
295.7
(11.64)
295,7
Figure 8.4 - IPS1 board metallic case dimensions (mm)
8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
8-9
Motors | Automation | Energy | Transmission & Distribution | Coatings
Frequency Inverter
Convertidor de Frecuencia
Inversor de Frequência
CFW-11 Sizes/Mec. E, F, G
CFW-11M
Addendum to the User’s Manual
Adendo al Manual del Usuario
Adendo ao Manual do Usuário
English / Español / Português
Summary / Índice
SUMMARY
1 INTRODUCTION..................................................................................................5
2 MODIFICATIONS ON SLOT 5 (FLASH MEMORY MODULE)..........................5
3 MODIFICATIONS ON SLOT 4 (ANYBUS-CC COMMUNICATION
MODULES)..............................................................................................................6
4 ACCESSORIES....................................................................................................7
ÍNDICE
1 INTRODUCCIÓN.................................................................................................8
2 MODIFICACIONES EN EL SLOT 5 (MÓDULO DE MEMORIA FLASH)..........8
3 MODIFICACIONES EN EL SLOT 4 (MÓDULOS DE COMUNICACIÓN
ANYBUS-CC)..........................................................................................................9
4 ACCESORIOS....................................................................................................10
ÍNDICE
1 INTRODUÇÃO...................................................................................................11
2 MODIFICAÇÕES NO SLOT 5 (MÓDULO DE MEMÓRIA FLASH).................11
3 MODIFICAÇÕES NO SLOT 4 (MÓDULOS DE COMUNICAÇÃO
ANYBUS-CC)........................................................................................................12
4 ACESSÓRIOS....................................................................................................13
Addendum to the User's Manual
1 INTRODUCTION
This addendum provides specific information on CFW-11/CFW-11M inverters with
serial number starting at 1011361739 and firmware version V3.00. On those inverters
the control board revision is “C” (CC11C).
ATTENTION!
Firmware version V3.00 or higher CANNOT be used on inverters
with serial number under 1011361739, that use a control board with
revision prior to “C”.
„„ Any firmware version prior to V3.00 CANNOT be used on inverters
with control board revision “C” or higher.
„„
Further information on the new features and corrections of firmware version V3.00 is
provided in a specific addendum to the programming manual (available only on the CD).
2 MODIFICATIONS ON SLOT 5 (FLASH MEMORY MODULE)
To avoid connection failures and to improve the ease of connection to the inverter,
the FLASH memory module (MMF) was modified from MMF-01 to MMF-03. The
following picture shows the differences between MMF-01 and MMF-03 modules
and the ones implemented on the inverter.
The MMF-03 module is incompatible with the older MMF-01 and can only be used
on inverters with serial number starting at 1011361739 that have revision “C” of the
control board.
(a) MMF-01
Figure 2.1 (a): Differences between MMF-01 and MMF-03 modules
Addendum to the User's Manual
(b) MMF-03
Figure 2.1 (b): Differences between MMF-01 and MMF-03 modules
On the MMF-03 module there is an area reserved to user annotations. (e.g.: writing
the SoftPLC application version).
3 MODIFICATIONS ON SLOT 4 (ANYBUS-CC COMMUNICATION
MODULES)
In order to ensure the proper connection of Anybus-CC communication accessory in Slot
4, a support with guide rails was included in the product according to the following picture.
Support with
guide rails
Figure 3.1: Anybus-CC accessory connection
Addendum to the User's Manual
4 ACCESSORIES
New accessories were developed for CFW-11/CFW-11M inverter series, that complement
table 7.2 of user’s manual as follows:
Accessory models
WEG Part
Number
Nome
Description
Slot
Identification
Parameters
P0027 P0028
Control accessories for installation in the Slots 1, 2 and 3
11094251
11045488
PLC11-02
PROFIBUS DP-01
PLC module.
Profibus DP communication
module.
1, 2 and 3
----
--xx (1)(3)
3
----
C9--
Anybus-CC accessories for installation in the Slot 4
11550476
MODBUSTCP-05
Modbus TCP interface module.
4
----
--xx (2)(3)
11550548
PROFINETIP-05
PROFINET IO interface module.
4
----
--xx (2)(3)
FLASH Memory Module for installation in the Slot 5 – Factory Settings Included
10413633
MMF-01
FLASH memory module – old.
5
----
--xx (3)
11719952
MMF-03
FLASH memory module – new.
5
----
--xx (3)
Stand-alone keypad, blank cover, and frame for remote mounted keypad
1 m HMI Cable
1 m serial remote keypad
cable set.
-
-
-
2 m HMI Cable
2 m serial remote keypad
cable set.
-
-
-
10951223
3 m HMI Cable
3 m serial remote keypad
cable set.
-
-
-
10951227
5 m HMI Cable
5 m serial remote keypad
cable set.
-
-
-
10951240
7.5 m HMI Cable
7.5 m serial remote keypad
cable set.
-
-
-
10 m HMI Cable
10 m serial remote keypad
cable set.
-
-
-
-
-
-
10950192
10951226
10951239
Miscellaneous
10790788 DBW030380D3848SZ
380...480 V dynamic braking
module.
Adendo al Manual del Usuario
1 INTRODUCCIÓN
Este adendo contiene informaciones específicas para convertidores de la línea
CFW-11/CFW-11M con número de serie a partir de 1011361739 y con versión de
software V3.00 o superior. Estos convertidores utilizan tarjeta de control de revisión C
(CC11C).
¡ATENCIÓN!
La versión de software V3.00 o superior NO debe ser utilizada en
convertidores con número de serie inferior a 1011361739, los cuales
utilizan tarjeta de control con revisión inferior a la revisión C.
„„ Las versiones de software inferiores a la versión V3.00 NO deben ser
utilizadas en convertidores con la revisión C de la tarjeta de control
o superior.
„„
Más informaciones sobre las atualizaciones de la versión de software V3.00 son
suministradas en el adendo específico al manual de programación (solamente
disponible en el CD).
2 MODIFICACIONES EN EL SLOT 5 (MÓDULO DE MEMORIA FLASH)
Para su correcto funcionamiento y para facilitar su conexión en el convertidor, el
módulo de memoria (MMF) fue alterado de MMF-01 para MMF-03. La figura que
sigue presenta las diferencias existentes entre el módulo MMF-01 y MMF-03 y las
implementadas en el convertidor.
El módulo MMF-03 es incompatible con el módulo MMF-01 y solamente puede ser
usado en convertidores con número de serie 1011361739 o mayor, o sea, que poseen
la tarjeta de control revisión C.
(a) MMF-01
Adendo al Manual del Usuario
(b) MMF-03
Figura 2.1 (b): Diferencias entre el módulo MMF-01 y MMF-03
El módulo MMF-03 posee un espacio reservado para la utilización del usuario
(ejemplo: escribir la versión de software del aplicativo SoftPLC).
3 MODIFICACIONES EN EL SLOT 4 (MÓDULOS DE COMUNICACIÓN
ANYBUS-CC)
Para conectar correctamente el accesorio de comunicación Anybus-CC en el Slot 4,
fue incluido en el producto un soporte guía, como es presentado en la figura que sigue.
Soporte guía
Figura 3.1: Conexión del módulo Anybus-CC
Adendo al Manual del Usuario
4 ACCESORIOS
Fueron desarrollados nuevos accesorios para la línea de conver tidores
CFW-11/CFW-11M, los cuales complementan la tabla 7.2 del manual del usuario
conforme sigue:
Modelos de los accesorios
Ítem WEG
(n° de
material)
Nombre
Descripción
Slot
Parámetros de
Identificación
P0027 P0028
Accesorios de control para instalación en los Slots 1, 2 y 3
11094251
PLC11-02
11045488
PROFIBUS DP-01
Módulo PLC.
Módulo de comunicación Profibus DP.
1, 2 y 3
----
--xx (1)(3)
3
----
C9--
Accesorios Anybus-CC para instalación en el Slot 4
11550476
MODBUSTCP-05
Módulo de interfaz Modbus TCP.
4
----
--xx (2)(3)
11550548
PROFINETIP-05
Módulo de interfaz PROFINET IO.
4
----
--xx (2)(3)
Módulo de Memoria FLASH para instalación en el Slot 5 - Incluido Padrón Fábrica
10413633
MMF-01
Módulo de memoria FLASH - antiguo.
5
----
--xx (3)
11719952
MMF-03
Módulo de memoria FLASH - nuevo.
5
----
--xx (3)
-
Cable HMI 1 m
Conjunto cable para HMI remota
serial 1 m.
-
-
-
-
Cable HMI 2 m
Conjunto cable para HMI remota
serial 2 m.
-
-
-
Cable HMI 3 m
Conjunto cable para HMI remota
serial 3 m.
-
-
-
Cable HMI 5 m
Conjunto cable para HMI remota
serial 5 m.
-
-
-
-
Cable HMI 7,5 m
Conjunto cable para HMI remota
serial 7,5 m.
-
-
-
-
Cable HMI 10 m
Conjunto cable para HMI remota
serial 10 m.
-
-
-
-
-
-
HMI suelta, Tapa Ciega y Moldura para HMI Externo
-
Diversos
10790788 DBW030380D3848SZ Módulo frenado 380...480 V.
Adendo ao Manual do Usuário
1 INTRODUÇÃO
Este adendo traz informações específicas para inversores da linha CFW-11/CFW-11M
com número de série a partir de 1011361739 e com versão de software V3.00 ou
superior. Tais inversores usam cartão de controle revisão C (CC11C).
ATENÇÃO!
„„
„„
A versão de software V3.00 ou superior NÃO deve ser utilizada em
inversores com número de série inferior à 1011361739, os quais
utilizam cartão de controle com revisão inferior à revisão C.
As versões de software inferiores à versão V3.00 NÃO devem ser utilizadas
em inversores com a revisão C do cartão de controle ou superior.
Mais informações sobre as atualizações da versão de software V3.00 são fornecidas
no adendo específico ao manual de programação (somente disponível no CD).
2 MODIFICAÇÕES NO SLOT 5 (MÓDULO DE MEMÓRIA FLASH)
Para o seu correto funcionamento e para facilitar a sua conexão no inversor, o módulo
de memória (MMF) foi alterado de MMF-01 para MMF-03. A figura a seguir apresenta
as diferenças existentes entre o módulo MMF-01 e MMF-03 e as implementadas
no inversor.
O módulo MMF-03 é incompatível com o módulo MMF-01 e somente pode ser usado
em inversores com número de série 1011361739 ou acima, ou seja, que possuem
o cartão de controle revisão C.
(a) MMF-01
Figura 2.1 (a): Diferenças entre o módulo MMF-01 e MMF-03
Adendo ao Manual do Usuário
(b) MMF-03
Figura 2.1 (b): Diferenças entre o módulo MMF-01 e MMF-03
O módulo MMF-03 possui um espaço reservado para a utilização do usuário
(exemplo: escrever a versão de software do aplicativo SoftPLC).
3 MODIFICAÇÕES NO SLOT 4 (MÓDULOS DE COMUNICAÇÃO
ANYBUS-CC)
Para conectar corretamente o acessório de comunicação Anybus-CC no Slot 4 , um
suporte-guia foi incluído no produto conforme apresentado na figura a seguir.
Suporte-guia
Figura 3.1: Conexão do módulo Anybus-CC
Adendo ao Manual do Usuário
4 ACESSÓRIOS
Foram desenvolvidos novos acessórios para a linha de inversores CFW-11/CFW-11M,
os quais complementam a tabela 7.2 do manual do usuário conforme a seguir:
Modelos dos acessórios
Item WEG
Nome
Descrição
Slot
Parâmetros de
Identificação
P0027 P0028
Acessórios de controle para instalação nos Slots 1, 2 e 3
11094251
PLC11-02
11045488
PROFIBUS DP-01
Módulo PLC.
Módulo de interface Profibus DP.
1, 2 e 3
----
--xx (1)(3)
3
----
C9--
Acessórios Anybus-CC para a instalação no Slot 4
11550476
MODBUSTCP-05
Módulo de interface Modbus TCP.
4
----
--xx (2)(3)
11550548
PROFINETIP-05
Módulo de interface PROFINET IO.
4
----
--xx (2)(3)
Módulo de Memória FLASH para instalação no Slot 5 – Incluído Padrão Fábrica
10413633
MMF-01
Módulo de memória FLASH.
5
----
--xx (3)
11719952
MMF-03
Módulo de memória FLASH.
5
----
--xx (3)
10950192
Cabo HMI 1 m
Conjunto cabo para HMI
remota serial 1 m.
-
-
-
10951226
Cabo HMI 2 m
Conjunto cabo para HMI
remota serial 2 m.
-
-
-
Cabo HMI 3 m
Conjunto cabo para HMI
remota serial 3 m.
-
-
-
Cabo HMI 5 m
Conjunto cabo para HMI
remota serial 5 m.
-
-
-
10951240
Cabo HMI 7,5 m
Conjunto cabo para HMI
remota serial 7,5 m.
-
-
-
10951239
Cabo HMI 10 m
Conjunto cabo para HMI
remota serial 10 m.
-
-
-
-
-
-
HMI avulsa, tampa cega e moldura para HMI externa
10951223
10951227
Diversos
10790788 DBW030380D3848SZ Módulo Frenagem 380...480 V.
Download