g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Wave Cast Type SCB Series of Cast Resin Dry-Type Power Transformers Technical Manual Shanghai GE Guangdian CO., LTD g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Table of Contents 1. Introduction of the Enterprise...................................................................3 2. Features of Products .................................................................................4 3. Core.............................................................................................................5 4. Windings.....................................................................................................6 5. Accessories................................................................................................8 6. On-load Tap Switch ...................................................................................9 7. Technical Specifications .........................................................................10 8. Tests .........................................................................................................12 9. Dry-Type transformer dimensions and terminal drawings...................12 10. Specifications and dimensions for SCB type 10kV three-phase cast resin dry-type distribution transformer with off-circuit tap changing.....13 11. SCZB9 type 10KV dry-type distribution transformer with on-load tap changing.......................................................................................................15 12. Specifications and dimensions for SCB9 type 1KV and lower threephase cast resin dry-type isolation transformer .......................................17 13. Specifications for SCB9 type 10kV three-phase cast resin dry-type power transformer .......................................................................................18 14. Specifications for SCB9 type 20kV three-phase cast resin dry-type distribution transformer ..............................................................................18 15. Specifications and dimensions for SCB9 types 35kV three-phase cast resin dry-type distribution transformer .............................................19 16. Specifications for SCB9 type 35kV three-phase cast resin dry-type power transformer .......................................................................................20 Page 2 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers 17. Dry type transformer with protection enclosure .................................21 18. Inquiry, Order .........................................................................................27 1. Introduction of the Enterprise Shanghai GE Guangdian Co., Ltd. has introduced advanced production technology, facilities and testing instruments in designing, manufacturing and selling three-phase cast resin dry-type transformers, which are also exported to the United States and all over the world. Our products have passed all the quality tests carried out by the National Center of Quality Supervision and Inspection for Transformers, the shortcircuit test for SCB type distribution transformers by KEMA lab, and the test of resistance to vibration for transformer with cubicle and connection busbar run by the Main National Lab for Civil Engineering Disaster Prevention of Tongji University. Shanghai GE Guangdian Co., Ltd. Dry-type Transformer with Outdoors Enclosure IP23 Page 3 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Certificate of the ISO 9001 Quality System SCB9-10000/35/10.5 large-scale dry-type power transformer 2. Features of Products • • • • • • Safe, fire self-extinguishing, fireproof, low noise level, pollution-free; available at load center. Made up of all-copper foil, the H&L voltage windings have high short circuit withstand capabilities, high lightning impulse withstand capability and high reliability. The H&L voltage windings are molded with epoxy resin on high vacuum. The partial discharge is lower. Air channels can be installed. Humid-resistant and high heat dissipating ability. It is able to run normally under the relative humidity of 100%. Rated capacity can increase 40% as air-cooling. Convenient installation; easy maintenance; low losses and general operation cost. Temperature display and controlling system, which resists the interference from electric and magnetic field, is installed on windings to ensure safe operation of transformer. Computer interface can be fixed so that it can be controlled and monitored remotely. It can be equipped with protection enclosure and connection busar, which enables it to be used both indoors and outdoors. Indoor built-up structures may be immune to the limitation of the doorframes in the installation location. Connection busbar can be directly connected to the busbar of switchgear, which is really convenient. Page 4 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Dry-type Distribution Transformer with Protection Enclosure IP30 ZSCB-1500/15.75/0.5 Dry-type field Transformer SCB9-3150/10/0.4 Dry-type Distribution Transformer SCB9-10000/35/10.5 Dry-type Distribution Transformer 3. Core • Made of high-quality cold-rolled grain-oriented steel sheets Page 5 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers • • • • Mitred type adopts 45 degrees cuts; multistage step-by-step stacking No punching holes on yokes; connecting plate structure Coated with resin-emulsion paint. The surface of yokes locking armature has been treated by electrostatic painting to protect them against humidity, rusts and salt fog. It has the advantages of lower no-load losses and current as well as lower noise. Slitting line for silicon steel sheet (Japanese plant) Cut-to-length line for silicon steel sheet (Swiss plant) Core with Non-stacking Top Yoke Mitred type core of the limbs and the yokes 4. Windings • All the low and high voltage windings are made up of copper bands (foils). Voltage between layers is low, while layer capacity is great. Its Page 6 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers • • • • • • lighting impulse withstand capacity is high. The reactance of high and low voltage is the same. There’s no helical angle. For ampere turns of the high and low voltage windings are best leveled, the windings are capable of withstanding short circuit. Therefore, they have high operating reliability. Molded with epoxy resin at high vacuum, the high and low voltage windings have well electrical and mechanical performance. Partial discharge of them is less than 5pC. High and low voltage winding can be equipped with ventilating air passages according to requirements for heat dissipation. The isolating resin on the surface is 2.0~2.5mm thick in average, ensuring the temperature increase and strength of the windings and securing the 30-year service life. Because of the quartz powder on the epoxy resin and the glass-fiber net banded inside and outside the windings, they have high heatdissipating ability, humidity-resistance and flame resistance. There is no need to worry about cracking. They can work normally under the humidity of 100%. Their flame-resistant performance accords with the Britain BS7806F2. The interior of the low and high voltage windings are credibly welded automatically and protectively by argon with low resistance. The imported equipment of high-precision and automation and highquality imported isolating materials ensure the stable high quality and the safe operation of the windings. F and H stands for the two insulation levels. The temperature-rise limitation and voltage combination can be designed according to the customer’s specific requirements. H&L voltage epoxy resin windings With heat-dissipating air passages H.V windings casted with epoxy resin for special purpose Page 7 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Low voltage foil winding machine (Swiss plant) Vacuum casting plant (Italian plant) High voltage foil winding machine (Swiss plant) Large-scale 35KV winding casted with epoxy resin 5. Accessories Temperature Controller • A set of temperature controller can be set on the transformer to ensure its normal services life through displaying and controlling the temperature of the transformer windings in work. • The temperature measure sensors, Pt100 platinum resistant, are flushed into low voltage windings to get the temperature signals and circularly show the temperature of windings of each phase on the control panel after being treated by circuit. The temperature control system is capable of temperature setting, saving the highest temperature after power failure, fan picking-up and stopping automatically/manually, fault alarming, over temperature alarming with sound and light, over temperature tripping function besides the electromagnetic interference proof feature of national standard. Page 8 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers • Computer interface and software are available to carry out remote control. Types and functions of temperature controllers of BWD-3K series Type Function BWD-3K Regularly inspecting and displaying temperature, sensor fault alarming, and the fan is not controlled. BWD-3K130 Regularly temperature displaying, over temperature alarming, over temperature trip, sensor fault alarming, picking-up and stopping the fan BWDSame as those of BWD-3K130, added by the networking 3K130A function with the aid of computer interface. Fan • Low noise flow fan can reduce the winding temperature, improve its ability of running under over-load, expand the service life of the transformer. In forced air-cooling mode, output will be increased by 40%. • Features: low noise, low power and convenient installation The configuration of fan is shown below: Capacity of transformer (kVA) 160 ~ 160 ~ ≥ ~ 160 1000 1000 6300 1000 Account ×power of fan (W) 4×40 4×60 6×90 6 × 250 Temperature Controller Low sound flow fan 6. On-load Tap Switch When the voltage of the electric net fluctuates, the transformer’s tapping can be changed over automatically or electrically in on-load operation to ensure that the user get the tap switches which employ the stable voltage. Page 9 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers MFK type complex on-load pneumatic tap switch As an uninflammable novel on-load tap switch using air as the isolating and arc-extinguishing media, it is equipped with ZTK self-controller and may be connected to computer interface to carry out remote control. It is suitable for dry-type power transformers of 6~10kV, 3150kVA and lower. Features: Reliable quality; convenient installation and maintenance; low priced; patented. KY and CVT series of vacuum on-load tap switches As a transitional unit-resistance on-load tap switch employing air as the isolating media and using vacuum switch pipe in switching over, it is furnished with ZDT20 (40) or HMK-2Z types of automatic tap changing controller and may be linked to computer interface to carry out remote control. It is suitable for dry-type power transformers of 6~10kV, 2500kVA or lower. Features: Reliable quality; convenient installation and maintenance; widely used. They are classified into two types: cylindric and cubicle type. MFK type complex on-load pneumatic tap switch Cubicle vacuum on-load tap Automatic tap changing controller 7. Technical Specifications • Standards: GB6450, 《Dry-type Power Transformer》 GB/T10228-1997 《 Technical Specification and requirements of Dry-type Power Transformer》 IEC726-82 《Dry-type Power Transformer》 IEEE Std C57.12.01-1998 《General Technical Conditions of Dry-type Distribution and Power Transformer》 • Capacity: 160~10000kVA • Voltage: 35kV and below Page 10 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers • • • • • • • • • Changing method: Off-circuit tap changing ±5% or ±2×2.5%, On-load tap changing ±4×2.5% or ±3×2.5% Phase: 3 phases Frequency: 50Hz or 60Hz Connection: Dyn11, Yyn0, Yd11, Ynd11 or others Insulation Level: AC3 for 1kV Ll60AC25 for 6kV Ll75AC35 for 10kV Ll125AC50 for 20kV Ll170AC70 for 35kV Cooling: Natural cooling (AN) Natural (AN)/forced air (AF) or others Protection degree: IP00, IP20, IP30, IP23 or others Service conditions: Altitude ≤1000m Ambient temperature ≤40℃ Min. temperature: ≥-5℃ for indoor use ≥-30℃ for outdoor use Special service: Special design and service are offered for customer with special applications and operation conditions. Shockproof Test Report Short-circuit Test Certification provided by American KEMA Company for SCB-2500 type dry-type transformers Page 11 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers 8. Tests Routine tests: a. Measurement of winding resistance b. Calibration of voltage ratio and voltage vector relationship c. Measurement of insulation resistance d. Measurement of short circuit impedance and load losses e. Measurement of no-load losses and current f. Separate-source power-frequency voltage withstand test g. Induced over voltage withstand test h. Measurement of partial discharge Type tests: a. Temperature rising test b. Lightning impulse withstand test Special tests: a. Sound level test b. Short-circuit test Others: Other special tests could be carried out per requirements of the customers Partial Discharge Testing Instrument (Imported from Germany) 9. Dry-Type transformer dimensions and terminal drawings Page 12 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers 10. Specifications and dimensions for SCB type 10kV three-phase cast resin dry-type distribution transformer with off-circuit tap changing Type: SCB Connection symbol: Dyn11 or Yyn0 H.V: 10 (11、10.5、6.3、6.0) kV L.V: 0.4kV Tapping range of H.V: ±5% or ±2×2.5% Changing method: Off-circuit tap changing Insulation class: F or H Page 13 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Mo del nu mb er lev el 9 10 Rated Capaci ty (kVA) Noload Losse s (W) 160 580 200 680 250 780 315 980 400 1080 500 1300 630 1480 630 1400 800 1620 1000 1860 1250 Load Losses (W) Noload Curren t (%) Load Imped ance 120℃ (%) Sound Level LPA (dB) Wei ght (kg) Dimensions (mm) Termin als B×δ (mm) L B H W a b c e 750 953 660 255 315 390 634 40×3 111 0 130 0 133 0 150 0 175 0 207 0 201 0 242 0 275 0 117 0 115 5 119 0 123 0 126 0 131 0 141 0 146 0 150 0 156 0 750 992 660 227 314 385 674 40×4 750 1034 660 232 321 400 704 40×4 750 1036 660 253 325 410 677 50×5 750 1101 660 273 329 420 746 50×5 750 1156 660 284 336 435 797 60×6 750 1211 660 300 355 470 837 80×6 750 1161 660 284 361 485 787 80×6 920 1246 820 300 369 500 837 80×6 920 1296 820 316 381 520 877 52 319 0 158 0 920 1436 820 319 384 525 979 6 54 397 0 176 0 920 1511 820 355 415 585 0.4 6 56 487 0 195 0 920 1562 820 368 445 650 18200 0.4 6 56 586 0 204 0 117 0 1712 1070 392 460 680 200 00 23000 0.4 6 58 700 0 207 0 117 0 1900 1070 412 479 715 5500 240 00 27000 0.4 6 60 911 0 206 0 131 0 2520 1070 402 469 690 315 880 3460 1.0 4 48 660 253 325 410 3980 1.0 4 48 750 1101 660 273 329 420 746 50×5 500 1160 4870 1.0 4 50 750 1156 660 284 336 435 797 60×6 630 1340 5870 1.0 4 50 750 1211 660 300 355 470 837 80×6 630 1300 5950 1.0 6 50 750 1161 660 284 361 485 787 80×6 800 1520 6950 0.8 6 52 920 1246 820 300 369 500 837 80×6 1000 1760 8120 0.8 6 52 123 0 126 0 131 0 141 0 146 0 150 0 156 0 1036 970 133 0 150 0 175 0 207 0 201 0 242 0 275 0 750 400 302 0 348 0 426 0 512 0 520 0 607 0 709 0 102 1 105 0 117 0 138 2 180 1 677 100× 6 100× 8 100× 10 120× 12 120× 15 150× 15 180× 20 50×5 920 1296 820 316 381 520 877 1250 2000 846 0 9690 0.6 6 52 319 0 158 0 920 1436 820 319 384 525 979 1600 2400 102 40 11730 0.6 6 54 406 0 176 0 920 1511 820 355 415 585 2000 3300 126 00 14450 0.4 6 54 487 0 185 0 920 1668 820 356 425 615 2500 3700 146 70 16800 0.4 6 56 572 0 191 0 117 0 1737 1070 385 436 635 102 1 115 0 120 0 100× 6 100× 8 100× 10 120× 12 120× 15 75 ℃ 120℃ 196 0 232 0 254 0 302 0 348 0 426 0 512 0 520 0 607 0 709 0 2240 1.1 4 48 980 2650 1.0 4 48 2900 1.0 4 48 3460 1.0 4 48 3980 1.0 4 48 4870 1.0 4 50 5870 1.0 4 50 5950 1.0 4 50 6950 0.8 6 52 8120 0.8 6 52 2100 846 0 9690 0.6 6 1600 2600 107 00 12200 0.6 2000 3500 131 00 15000 2500 4200 159 00 3150 4800 4000 Page 14 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Note: 1) The holes in the base plate are of 4×Φ22. To facilitate moving, 4 wheels of Φ150 are fixed on it, which result in an increase of approximately 130mm in height (H) and 40kg increase in weight. 2) According to request of users, the products of other different connections or other impedance voltage or other H.V. tapping range can be supplied. 11. SCZB9 type 10KV dry-type distribution transformer with on-load tap changing ● ● ● ● ● ● ● ● ● With big tap changing range, it is suitable when the voltage of electric net fluctuates dramatically. With automatic on-load tap changing, high-quality stable voltage can be gained. Equipped with automatic tap-changing controller, which bears the functions of automatic and electrical operation and remote control. Compact structure makes the maintenance easy. Reliable operation can be achieved. Tap switches fall into pneumatic and vacuum type, cubicle type and disc type, which makes it suitable for many occasions. Of series dry-type distribution transformer with on-load tap changing are the same with those of the series dry-type transformer with offcircuit tap changing, having the same capacity. The differences from the SCB series are listed below: 1) Tapping range: ±4x2.5%; 2) The differences in length, width and height are illustrated in the figure below; 3) The weight will increase by 180kg when the cylinder tap switches are applied. The weight will increase by 460kg when the cubicle tap switches are applied. The normal positions, where tap switches are installed on the transformer body, are shown in the figure below. The tap switches and the transformer body are arranged centrosymmetrically. The outside dimensions of the enclosure of the dry type transformer with on-load tap changing are different from those of the enclosure of the off-circuit tap changing dry type transformers with the same capacity in terms of the following aspects: where tap switches are fixed on the side, the L increases by 620mm; the B increases by 750mm when cylinder tap switches are located in the front; the B increase by 640mm when cubicle tap switches are arranged in the front. Page 15 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Cylindric On-load Switch on the Side Cylindric On-load Switch on Front Side Cubicle On-load Switch on Front Side OSCZB9-2500/10 series of dry type self-coupling transformer with on-load tap changing Page 16 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers SCB9 type of transformer with cylindric on-load switches on the side SCB9 type of transformer with cylindric on-load switches on front side 12. Specifications and dimensions for SCB9 type 1KV and lower three-phase cast resin dry-type isolation transformer Type: SCBG Connection symbol: Dyn、Yd、YNd、Yyn Primary voltage (V): 575、480、400、380 Secondary voltage (V): 400、220、210、208、120、100 Tapping range: ±5% Insulation level: AC3/AC3 Insulation class: F or H Load losses 120 (w) No-load Current (%) 650 750 850 2500 2970 3240 1.4 315 1000 3700 1.0 400 1100 4200 500 1300 5000 Rated capacit y (KVA) No-load Losses (w) 160 200 250 Sound level Short circuit impe danc e (%) (dB) 4 48 49 50 Weight (kg) L B H W 845 1140 1320 1080 1040 1230 750 660 1405 1230 1590 1230 1750 1290 916 993 105 9 111 9 118 3 122 0 Note: Caster wheel and shielding as well as products of other voltage ratio or three-winding transformers are available on request. HV Terminal LV Terminal Page 17 of 29 Remarks Dimensions (mm) Selected terminals shall be correspond ent to rated current (see the figure below). If the external windings current is not more than 500A, bolt terminals can be adopted. g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers 13. Specifications for SCB9 type 10kV three-phase cast resin dry-type power transformer Rated capacity (kVA) 630 800 1000 1250 1600 2000 2500 3150 4000 5000 6300 Combination of various rated voltages H.V H.V LV (kV) tapping (kV range ) Connection Symbol 6; 6.3; 6.6; 10; 10.5; 11 Yd11 ±5% ; ±2× 2.5% 3; 3.1 5; 6; 6.3 No-load Losses (W) 1600 1800 2200 2500 3000 4000 4800 5700 6800 8000 9500 10; 10.5; 11 Load Losses (W) 75℃ 120℃ 145℃ 5850 6810 8030 9600 11700 13970 16500 19200 23100 27400 32400 6700 7800 9200 11000 13400 16000 18900 22000 26500 31400 37200 7170 8350 9850 11770 14340 17100 20200 23500 28400 33600 39800 Noload curre nt Shortcircuit imped ance( %) 0.9 0.9 0.9 0.8 0.8 0.7 0.7 0.6 0.6 0.5 0.5 6 7 Sou nd Lev el LP A(d B) 56 56 56 56 58 58 60 62 62 62 62 14. Specifications for SCB9 type 20kV three-phase cast resin drytype distribution transformer Rated capacity (kVA) 160 Combination of various rated voltages H.V H.V LV (kV) tapping (kV) range 18; ±5% ; 0.4 Connection Symbol Yyn0; Noload Losses (W) 680 Page 18 of 29 Load Losses (W) 75℃ 120℃ 145℃ 2180 2500 2670 Noload Current (%) Shortcircuit Impedance (%) Sound Level LPA(dB) 1.4 6 50 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 20; 22 Dyn11 ±2× 2.5% 780 900 1140 1300 1550 1760 2070 2340 2740 3170 3900 4700 2570 2820 3490 4270 5230 6200 7330 8550 10300 12400 15000 17900 2950 3240 4000 4900 6000 7100 8400 9800 11800 14300 17200 20500 3150 3470 4280 5240 6420 7600 9000 10500 12600 15300 18400 22000 1.2 1.2 1.0 1.0 1.0 0.7 0.7 0.7 0,6 0.6 0.5 0.5 50 50 50 52 52 52 54 54 54 54 56 56 15. Specifications and dimensions for SCB9 types 35kV three-phase cast resin dry-type distribution transformer Type: SCB9 Connection symbol: Dyn11 or Yyn0 H.V: 35 (38.5) kV L.V: 0.4kV Tapping range of H.V: ±5% or ±2×2.5% Changing method: Off-circuit tap changing Insulation class: F Rated Capacit y (kVA) Noload Losse s (W) Load Losses (W) 75℃ 120 ℃ Noload curre nt (%) 800 2430 8400 9630 0.9 1000 2700 9660 1107 0 1250 3150 11700 1600 3600 2000 4230 Load imped ance 120℃ (%) 6 Soun d level LPA (dB) Wei ght (kg) 58 350 0 0.9 58 410 0 1340 0 0.8 60 464 0 14100 1620 0 0.8 60 497 0 16600 1910 0 0.7 62 594 0 Page 19 of 29 Dimensions (mm) L B H W a b c e 1 8 8 0 1 9 4 0 1 9 7 0 2 0 3 0 2 1 2 0 920 1 7 4 0 1 8 9 0 1 9 8 0 2 1 4 0 2 2 8 0 8 2 0 320 45 5 6 2 5 8 2 0 327 46 4 6 4 5 8 2 0 330 47 0 6 5 5 1 0 7 0 1 0 7 0 340 49 5 6 7 5 370 51 0 7 0 5 1 0 7 0 1 2 1 0 1 2 9 0 1 4 8 2 1 5 3 2 920 920 1170 1170 Busbar terminals B×δ (mm) 80×60 100×6 100×8 100×10 120×12 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers 2500 4950 20000 2290 0 0.7 62 721 0 3150 6200 22500 2580 0 0.6 64 885 0 2 2 4 0 2 3 1 0 1310 1310 2 2 4 0 2 4 1 2 1 0 7 0 1 0 7 0 350 52 5 7 4 5 434 52 8 7 7 0 1 4 5 2 1 6 0 2 120×15 150×15 16. Specifications for SCB9 type 35kV three-phase cast resin drytype power transformer Rated Capacit y (kVA) 800 1000 1250 1600 Combination of various rated voltage H.V H.V LV (kV) tappin (kV) g range 35; ±5%; 3.15 38. ±2× ; 5 6; 2.5% 6.3; 10; 10.5 ; 11 Connectio n symbol Yyn0; Yd 11 NoLoad Losses load (W) Losse s 75℃ 120 (W) ℃ 2500 9640 9900 2970 1005 0 1170 0 1410 0 1660 0 2000 0 2250 0 1152 0 1350 0 1620 0 1910 0 2290 0 2580 0 3480 4100 2000 4720 2500 5400 3150 6750 Page 20 of 29 145 ℃ 1060 0 1230 0 1450 0 1740 0 2050 0 2450 0 2760 0 Noload curre nt (%) Shortcircuit impeda nce (%) Sho rt level LPA (dB) 0.9 6 58 0.9 58 0.8 60 0.8 60 0.7 7 0.7 0.6 61 61 8 62 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers 4000 7830 5000 9360 6300 1100 0 1260 0 1440 0 8000 10000 Yd11; Ynd11 2700 0 3200 0 3700 0 4100 0 5100 0 3100 0 3680 0 4300 0 4770 0 5850 0 3320 0 3940 0 4600 0 5100 0 6260 0 0.6 62 0.5 63 0.5 63 0.5 9 0.5 17. Dry type transformer with protection enclosure Products for domestic market: Enclosure protection level of the transformers targeted at the domestic market shall be of standard GB4208-93 (eqvIEC529: 1989), while that of the to-be-exported products shall be in accordance with the American standard NEMA. Indoor-installed: IP20, which can prevent human body from approaching the enclosed dangerous components and provide protection against entrance of objects with diameter bigger than 12mm. IP30, which cannot only prevent human body from approaching the enclosed dangerous components, but also provide protection against entrance of objects with diameter bigger than 2.5mm. Outdoor-installed: IP23, which can not only provide functions as IP20, but also prevent entrance of water drops at a vertical angle of less than 60°. Products to be exported: NEMA1 enclosure can prevent human body from approaching the enclosed dangerous component and provide protection against entrance of alien objects with diameter bigger than 12.7mm. NEMA3R (ventilation type) can not only provide functions as IP30, but also prevent entrance of water drops at a vertical angle of less than 75°. The enclosures of above-mentioned types are all made out of sheet steel finished with resin static paint, which enables it to stand salt fog for 200 hours. They can also be made of stainless steel sheets or aluminum alloy sheet. Structural features: Page 21 of 29 65 65 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Enclosures for indoor-installed transformers are constructed with bolts and rivets, unlimited by the doorframes on the installation site. Transformers can be moved outside or inside from the front side in case of maintenance. They can be transported and erected in whole. Those for outdoor-installed transformers are constructed with bolts and rivets, or by welding. They provide protection against rain, snow, hail and ice formation. They can be transported and erected in whole. Temperature controller and electrical control cabinet are installed in the door panel of the enclosure. There are lighting devices inside. Tap changing controller is fixed in the door panel of the enclosure for the transformer with on-load tap changing controller. We provide enclosures of various protection classes and the corresponding tin-coated copper line banks of several wiring methods. They can stand the test of the ground acceleration ag: caused by earthquake, whose horizontal component is 0.6g and vertical component is 0.3g. The dimensions of some commonly used enclosures of dry-type distribution transformers and their forms of incoming and outgoing are listed below for reference. 1.Dimension drawing illustrating normal form of incoming and outgoing of high and low voltage for SCB9 type 10kV transformer Type SCB9160/10 SCB9200/10 SCB9250/10 SCB9、 10315/10 SCB9、 10400/10 SCB9、 10500/10 SCB9、 10630/10 SCB9、 10630/10 Uk 4% Dimensions (mm) Remarks 1310 H.V and LV outgoing terminals are the same with those of the transformer L B H W a b c D e f g 1400 1200 2200 660 255 315 390 1073 774 175 100 227 314 385 1112 814 160 1440 232 321 400 1154 844 180 1630 253 325 410 1136 817 180 140 1690 273 329 420 1201 886 185 130 1860 284 336 435 1266 937 190 300 355 470 1311 977 195 284 361 485 1261 927 205 1600 1800 6% Weight (kg) Page 22 of 29 2110 140 2490 2430 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers 1400 SCB9、 10800/10 SCB9、 101000/10 SCB9、 101250/10 SCB91600/10 SCB101600/10 SCB92000/10 SCB102000/10 SCB92500/10 SCB102500/10 820 2000 2200 160 300 369 500 1346 977 210 316 381 520 4386 1017 210 3310 319 384 525 1526 1119 215 3750 355 415 585 1601 1161 245 170 2520 4590 4680 2400 1600 1070 180 368 445 650 1642 1190 265 5490 356 425 615 1748 1150 250 5490 392 460 680 1792 1310 280 6660 385 436 635 1817 1200 260 6520 2. Drawing of LV enclosed upper-outgoing busbar for SCB type 10kV transformer Type Uk Dimensions (mm) Weight Page 23 of 29 Busbar g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers SCB9160/10 SCB9200/10 SCB9250/10 SCB9、 10315/10 SCB9、 10400/10 SCB9、 10500/10 SCB9、 10630/10 SCB9、 10630/10 SCB9、 10800/10 SCB9、 101000/10 SCB9、 101250/10 SCB91600/10 SCB101600/10 SCB92000/10 SCB102000/10 SCB92500/10 SCB102500/10 4% L B H W a b c D e f g (kg) 1400 1200 2200 660 400 315 390 120 774 130 460 1320 314 385 814 1450 321 400 844 1640 325 410 817 1700 329 420 886 1870 1×50× 6 336 435 937 2130 1×100 ×6 355 470 977 2510 1×100 ×6 361 485 927 2450 1×100 ×6 369 500 977 2550 1×100 ×6 381 520 1017 3340 1×100 ×8 384 525 3810 2×100 ×6 415 585 4650 2×100 ×8 1600 1800 6% 1400 820 2000 500 2200 180 180 660 1119 1161 4750 2400 1600 1070 445 650 1190 425 615 1150 5570 460 680 1310 6740 436 635 1200 6600 200 5570 3. Drawing illustrating standard horizontal arrangement for SCB type 10kV transformer Page 24 of 29 terminals N×B× δ 1×50× 4 1×50× 4 1×50× 4 1×50× 6 2×120 ×10 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Type SCB9160/10 SCB9200/10 SCB9250/10 SCB9 、10315/10 SCB9 、10400/10 U k 4 % Dimensions (mm) Weight (kg) Busbar terminals N×B×δ 1320 1×50×4 814 1450 1×50×4 L B H W a B c d e f 1800 1200 2200 660 10 0 315 390 774 205 0 314 385 1 0 0 321 400 844 1640 1×50×4 325 410 817 1860 1×60×4 329 420 886 2030 1×60×6 2000 14 0 Page 25 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers SCB9 、10500/10 SCB9 、10630/10 SCB9 、10630/10 SCB9 、10800/10 SCB9 、101000/1 0 SCB9 、101250/1 0 SCB91600/1 0 SCB10 1600/1 0 SCB92000/1 0 SCB10 2000/1 0 SCB92500/1 0 SCB10 2500/1 0 2200 12 0 1400 6 % 820 10 0 2400 336 435 937 2280 1×60×6 355 470 977 2730 1×80×6 361 485 927 2670 1×80×6 369 500 977 3080 1×100×8 381 520 101 7 3430 1×100×10 384 525 111 9 3890 2×100×6 415 585 116 1 4730 2×100×8 1 5 0 4820 2600 1600 445 107 0 460 650 680 119 0 5870 115 0 5870 131 0 6860 120 0 6720 2×100×10 3×100×8 4. Drawing illustrating standard vertical arrangement for SCB type 10kV transformer Type SCB9160/10 SCB9200/10 U k 4 % Dimensions (mm) L B H W a B c d e f 180 0 120 0 220 0 660 25 5 31 5 31 4 39 0 38 5 10 0 774 151 2.5 Page 26 of 29 814 Weight (kg) Busbar terminals N×B×δ 1440 1×50×4 1570 1×50×4 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers SCB9250/10 SCB9 、10315/10 SCB9 、10400/10 SCB9 、10500/10 SCB9 、10630/10 SCB9 、10630/10 SCB9 、10800/10 SCB9 、101000/1 0 SCB9 、101250/1 0 SCB91600/1 0 SCB10 1600/1 0 SCB92000/1 0 SCB10 2000/1 0 SCB92500/1 0 SCB10 2500/1 0 200 0 220 0 140 0 6 % 820 240 0 32 1 32 5 40 0 41 0 844 1640 1×50×4 817 1860 1×60×4 32 9 42 0 886 2030 1×60×6 33 6 43 5 937 2280 1×60×6 35 5 47 0 977 2730 1×80×6 36 1 48 5 927 2670 1×80×6 36 9 50 0 977 3080 1×100×8 38 1 52 0 101 7 3430 1×100×10 38 4 52 5 111 9 3890 2×100×6 41 5 58 5 116 1 4730 2×100×8 12 0 14 0 4820 260 0 160 0 44 5 107 0 46 0 65 0 68 0 18. Inquiry, Order Page 27 of 29 119 0 5870 115 0 5870 131 0 6860 120 0 6720 2×100×10 3×100×8 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers You are kindly requested to inform us of the following items for inquiries and orders: Items Type Rated capacity Number of phases Frequency HV rated voltage HV tapping range LV rated voltage Changing method Connection symbol Short-circuit impedance Insulation level Cooling method Protection degree Enclosure material Content □single phase □three phase or Others or Others □50 □60 □6 □6.3 □6.6 □10 □10.5 □11 □35 □38.5 or Others or Others □±5 □±2×2.5%□±3×2.5%□±4×2.5% □0.4 □0.69 □6.3 □10 □10.5 □11 □with off-circuit tap changing □with on-load tap changing or Others □Dyn11 □Yn0 □Y d11 □Ynd11 or Others □4 □6 □8 or Others □F □H □Air natural(AN) □(AN)/Air-forced(AF) or Others or Others □IP00 □IP20 □IP30 □IP23 □Steel sheet(with static paint) □Al Alloy Sheet or Others □Stainless Steel Sheet Temperature thermometer □Temperature thermometer □Temperature controller and temperature control □Temperature controller with computer interface box □None Fan □Yes □No Forms of LV outgoing □Conventional □Enclosed busbar upper outgoing □Standard horizontally-lined busbar side outgoing □Standard vertically-lined busbar side outgoing or Others Service Altitude or Others □1000 and lower Conditions Max. temp. or Others □40 Min. temp. or Others □-5(indoors) □-30(outdoors) Indoor/outdoor □indoor or Others □Outdoor Packing Quantities ordered (unit) Time of delivery Delivery taking Page 28 of 29 g GE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power Transformers Transportation Delivery point Miscellaneous The transformers are numbering according to JB/T3837-1996 Numbering of Transformer Category. Dry-type transformer model number: SCB9-1000/10 H.V. voltage levels (kV) Rated capacity (kVA) Performance calss code name The winding is made of copper foil Moulded with epoxy resin Three-phase Notes: a. “Z” is prefixed to the model number of the transformer with rectification. b. There is an “O” in front of the S in the model number of the selfcoupling transformer. c. There is an “S” behind to the S for three-phase transformers. d. There is a “Z” behind the C for transformers with on-load tap changing. e. There is an “L” before the B for transformers with windings made of copper foil. f. There is a “G” behind the B for isolated transformers. g. According to GB/T10288-1997, the performance class of Group Ⅰ is signified with “8”. Those whose no-load and load losses are 10% lower than the “8” type are signified with “9”. Those whose no-load losses are 20% lower than the “8”type while load losses 15% lower are signified with “10”. Page 29 of 29