Utility

advertisement
DC Power Distribution
Alternatives for Datacom
Applications
BJ Sonnenberg
Manager Business Development
Data Center Trends
Increasing rack
power density
Increasing drive for
efficiency
Increasing component
integration on site
`
AC Power
>40kW
New
High Efficiency
Topologies
DC Power
Future Higher
Voltage
Topologies
New 48V DC
Topologies
< 2 kW
Traditional
Telecom 48V DC
AC UPS Powered Configurations
Forces re-evaluation of all available topologies
2
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Modularity
& Scalability
Data Center Power Protection and
Distribution Basic Architectures
Traditional
AC UPS
Maintenance Bypass
PDU
B
PSU
CDU
DC/DC
B
UPS
Bypass
480V
MV
Primary
Dist.
AC
AC/DC
DC/AC
B
12V
VR
B
B
B
B
AC/DC
Server
Rack
300-400VDC
48V/380DC
Modular System, Row-based
DC UPS
480V
CDU
PSU
AC/DC
AC
DC/DC
B
MV
VR
B
Rectifier
12V
Server
PDU
Rack
Attributes of a DC UPS:
ƒ Simple input and output distribution, easy to parallel ,no
load balancing (derating)
ƒ Minimal conversion stages grid to chip –
high end-to-end efficiency and reliability
ƒ High power quality - isolated from mains, no harmonics
ƒ Safe voltages at point of use (48VDC systems)
3
Advantages of integrated, modular UPS systems:
ƒ High power density in a compact footprint
ƒ Reduced field wiring and copper content
ƒ Targeted for row-based deployments; no need for
dedicated power room
System optimization challenge – best overall system topology for a
specific application , not necessarily optimization of individual existing
components.
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Source: Intel
Improved Efficiency with DC Solutions
Elimination of conversion stages and simplified distribution
4
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Megatrends in Data Center Distribution Evolution
Renewable
resources
Microgrids
5
Facility
distribution
optimization
Rack/server
distribution
optimization
• Decrease utility power consumption – peak shaving and over time.
Address all loads , not only compute loads (lighting , cooling , etc)
Server virtualization
• Maintain high availability
• Best system utilization – rightsizing , no stranded power
• Scalability
• TCO
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Impact of Renewable Energy Sources - Example of Telecom
Facility Transformation Vision
Present
Facility
AC loads
Utility
Gen
AC
Batt
DC UPS
Ultimate
AC compute
loads
AC UPS
DC
Facility
AC loads
Telco and dc
compute loads
Batt
48VDC
Facility
DC loads
Many transition
paths
Utility
Interim
Facility
AC loads
AC
AC compute
Legacy loads
Utility
DC UPS
Gen
Batt
400VDC
DC compute
And telco loads
DC
Batt
DC compute
And telco loads
Green
Generator
Facility
DC loads
DC
DC
Energy
Station
DC
48VDCTelco
Legacy loads
6
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
400VDC
DC facilitates and
optimizes use of
renewable resources
Elements of an Optimized Power
Distribution –Grid to Chip
BEST COMPROMISE OF THE FOLLOWING
ƒ Efficient facility distribution to equipment racks
ƒ Ability to easily connect renewable energy resources
ƒ Efficient equipment rack distribution
ƒ Efficient server PCB distribution – optimize conversion stages
Eliminate stranded power
Operate at peak efficiency at any load
Scalability
Low TCO
Low initial cost
Reliability
7
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Why 380VDC - Voltage Range
Selection Based on Several Criteria
1500 IEC
High Long
DC Voltage
800
Server
PS
750 Ordinance (JPN)
600 NEC(U.S.)
600
450
575 [to 48]
428 (192cell) Validus
405
374 (168cell) 380
380
321 (144cell)
US DC Demo
373(U.K.)
350
320
300
300
NEDO PJ.
(Sendai)
Cable Distance
900 BS (U.K.)
Distribution
efficiency
1000
420
380
354(EU)
324V (US
311(JPN)
Operating
bulk - voltage
260
200
Low
0
8
Law,
Regulation,
Code, and
Stds.
Distr.
Gen.
Telecom
(Number of
Cells)
Demos
(Reference)
Rating
voltage of
parts and
elements
AC ICT
input
voltages
( Peak )
Edited from source: NTT FACILITIES, INC.
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Short
Benefit of
HVDC system
ETSI Std.
(draft)
Which DC Voltage?
Depends on facility size/application :
1. Scalable facility level distribution
Sites/PODs requiring battery back-up - -48VDC “in row”
solutions
Facility/application with renewable energy availability –
380VDC – simpler interface
2. Server rack level distribution
-48VDC or 380VDC for racks with power densities > 10kW
9
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Power Room Constraint
As rack densities increase, power room size increases proportionally;
i.e. a 10x increase in density results in a 10x increase in power room size.
Power and
Switchgear
Room
10
No UPS
Room,
Increased
computing
space
UPS /
Battery
Room
Data Center
Raised
Floor
Switchgear
Row-based
UPS
Data Center
Raised Floor
High-Density Data Center
@ 20kW per Rack
Switchgear
Room-based
UPS
Data Center
@ 2kW per Rack
Additional
Data Center
Raised
Floor Space
Data Center
Raised
Floor
Row-based UPS architecture offers ~30%
more computing capacity
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
380V DC Application Alternatives
ƒ Facility level distribution
ƒ Server rack distribution
11
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
380VDC System Components
CONVERSION
Communications
System cabinet
Rectifier
FACILITY
DISTRIBUTION
Bus duct,
ancillary
switchgear
RACK
DISTRIBUTION
Power strips
connectors to
servers
Controller
Storage , battery
flywheel ,etc
12
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Power supply
DC Rectifier and System Design
Philosophy
ƒ Modular approach selected for scalability and reliability
ƒ Maintain same reliability and maintainability as 48VDC systems
ƒ Provide input/output isolation to avoid protection coordination issues
ƒ Minimize footprint – space savings
ƒ High scalability and ease of expansion ( from 12.5kW up )
ƒ Efficiency gains through conversion improvement and facility design
ƒ Ready to accept renewable energy sources
ƒ Offer multiple ratings by use of standard building blocks and conversion
cabinet configurations and a set of input/output interface accessories
13
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Advantage of High Modularity – Improved
Efficiency with Energy Optimization Mode
Active power management
increases overall system efficiency
ƒ
ƒ
ƒ
ƒ
Unneeded power conversion units (PCU’s)
set to standby in low-load conditions
Optimizes individual PCU load
for greater system efficiency
Useful for sites with variances in load
Periodically cycles energized PCU’s
for even run time
33%
33%
56%
56%
33%
33%
56%
56%
33%
33%
Standby
Standby
33%
33%
56%
56%
33%
33%
Standby
Standby
33%
33%
Standby
56%
Without Energy Optimization
N+1 redundancy
maintained
With Energy Optimization
14
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
1U high 10KW Rectifier
Feature
Input voltage windows
260 to 530VAC
Output power
10KW
Power factor
0.99
THD
<5%
Output voltage
297 to 400V
Max output current
30A
Efficiency
95%
Safety
UL/CE
15
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Emerson’s 380V V0 Solution (Present)
Feature
Input
480VAC with 3 phase 4 wire
Output
297 to 400V
Provides up to 100KW in each rack
Load insulation detection function
Max 7 output load connection with load measurement
Over load and on/off detection function
Standard server rack
600(w)*1000(D)*2000(H) :mm
16
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Future Offer -System Sizing and
Configuration Considerations
ƒ Rectifiers space in cabinet (cooling,safety)
ƒ DC output configurations – bus duct vs hard wire/Tier level
ƒ AC input configurations – Tier level
ƒ Maintainability level – facility level and DC UPS system
ƒ Components rating limitation (today)
ƒ Footprint optimization
ƒ Ease of installation/expansion
Tier 1/2/3 – N+M configuration with multiple inputs/outputs
Tier 4 configuration – 2N
17
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
400VDC System Building Block
Implementation Example
480VAC Battery or
Loads A
Loads B
flywheel
Include
provision
for internal
bussing
1000A
CB
Current /
Voltage
Monitor
1000A
CB
C
Draw-out or Plug-in
Breakers Preferred
Fused Disconnects
acceptable
20 -22
Rectifiers
250kW
N+1
400A
CB
480VAC
Distr. A
Distr. B
40 MCCBs
40 MCCBs
8 brks
up to 125A
8 brks
up to 125A
Individually
monitored
option
Individually
monitored
option
400A
CB
Battery or Loads A
Loads B
flywheel
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
18
1. Any part of the system can be
maintained without system
shutdown
2. Distribution breakers can be added
and wired without system shutdown
3. Top and bottom entry provided
4. All external wiring run in conduits –
sufficient space to be provided for
conduit terminations
5. Failure of either bus A or B should
not affect the other bus
6. For single corded loads only one
distribution is required
7. Rectifiers can be added or replaced
without system shutdown
8. System can operate without battery
9. Individual Rectifier failure does not
affect the output bus
10. All cabinet connections must be with
conduit
11. UL / CSA / CE approved
C
Controller
Output Connectivity Options –Bus
Duct Advantage
Bus duct
Wire in conduit
Distribution options:
A
Battery
Flywheel
1.Fuses – shorter clearing time
2.Breakers – easier to operate
3.Bus duct plug-ins – space,scalability
Server
Rack
400VDC
UPS
Bus duct
DistrA
400VDC
UPS
DistrB
800A CB limit
230kW
A
Battery
Flywheel
B
Bus duct
B
Server
Rack
19
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
A
Battery
Flywheel
400VDC
UPS
B
Server
Rack
AC Input Configurations –
Example of 250kW System Scalable to 750kW
Utility
Utility
A
OR
1200A
250kW
250kW
400A
250kW
250kW
Utility
400A
250kW
Utility
400A
250kW
Utility Utility Utility Utility Utility Utility
A
B
B
A
B
A
Utility Utility
A
B
OR
400A
1200A
250kW
TIER 2
250kW
250kW
250kW
400A
250kW
20
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
400A
250kW
TIER 3
Partial 2N Concept
Server Room or
Electrical Room
Server Room or
Electrical Room
Server Room
400VDC
UPS
N+1
Battery
Flywheel
Optional
B
A
Battery
Flywheel
Future
Battery
Flywheel
400VDC
UPS
n=+1
400VDC
UPS
N+1
400VDC
UPS
Red.
N+1
400VDC
UPS
Future
N+1
21
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Server
Rack
Critical
Server
Rack
Non critical
Server
Rack
Future
Facility
Loads
Server Rack Distribution
Feed A
Feed B
12- 40
servers
Feed A
Feed B
Power strip
50A input ~14.5kW 12 positions
Power strip
50A input ~14.5kW 12 positions
Single strip can power up to 12
2U servers at 1200W – A or A+B or
24 1U servers at 600W
Single strip can power up to 2
blade chassis at 14.5kW – A or A+B
For A only configuration up to
20 2U servers,40 1U servers
(two strips) – total
rack power available – 29kW
For A only configuration up to 4
blade chassis (two strips) – total
rack power available – 29kW
Blade chassis example
HPc7000 today
3x2700W power
supplies ~8kW max
Typical load- 4-6kW
Connector UL listed at 5A or 20A
End of discharge voltage ~ 290VDC
22
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
380V DC Application Alternatives
ƒ Facility level distribution
ƒ Server rack level distribution
23
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
380VDC Sub-Rack
Sun Container–UCSD POC Site
2 X 10kW 400VDC
Controller
Output Breakers
400V-48V Converters
24
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
48VDC or 380VDC
Sub-Rack Concept
Horizontal shelf mounting shown . Shelves can also be mounted vertically
Building blocks:
• 12.5-15kW 380VDC
• 6000W 48VDC
25
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Rack Distribution Copper Content
Assumptions:
1. 92 servers/rack at 275W-300W
2. Two power systems/rack – 13.5kW each, n+1
3. Rack power ~ 27kW
4. Currents calculated at end of battery discharge – 1.75VDC
26
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Rack Layout -Optimized
11x300W
11x300W
servers
3375W
servers
3375W
Cross bar – 20”
12V – 625A @1.75V
48V - 156A @1.75 V
380V – 23A @1.75V
30A,480V, AC,3phase input plug
13.5kW
11x300W
11x300W
servers
3375W
servers
3375W
11x300W
11x300W
servers
3375W
servers
3375W
13.5kW
11x300W
11x300W
servers
3375W
servers
3375W
Distribution bar – 47.25”
12V – 312 A
48V – 78A
380V – 12A
Server plug
12V - 25A
48V – 6.25A
380V - ? (5A plug standard)
27
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Rack Layout –Full Bus Sizes
11x300W
11x300W
servers
3375W
servers
3375W
Cross bar – 20”
12V –1250A @1.75V
48V - 312A @1.75 V
380V – 46A @1.75V
30A,480V, AC,3phase input plug
13.5kW
11x300W
11x300W
servers
3375W
servers
3375W
11x300W
11x300W
servers
3375W
servers
3375W
13.5kW
11x300W
11x300W
servers
3375W
servers
3375W
Distribution bar – 47.25”
12V – 614A
48V – 156A
380V – 24A
Server plug
12V - 25A
48V – 6.25A
380V - ? (5A plug standard)
28
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Back-up
29
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Example of Hybrid System Evolution in Enterprise Building Existing System
Meter
100kW
350-800V
Solar
Array
480Vac
480Vac
PV
Inverter
Eff 93%
AC
Distr.
Utility
480Vac
Load larger than PV
output .Solar power
fed back to utility.
480/208V
PDU
Lighting
208/120VA
servers
Solar to server eff = .93x.98x.92= .838
Utility to server eff = .98x.92=.90
Lighting and distribution losses not included
30
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Eff – 98%?
PS eff – 92%?
Hybrid System Migration -Scenario 1
Meter
100kW
350-800V
Solar
Array
480Vac
480Vac
PV
Inverter
AC
Distr.
Utility
480Vac
NetSure ITM
48V DC UPS
380VDC
Converter
Already
existing on site
48VDC
Loads
Solar to server eff = .93x.97x.95=.856
Utility to server eff = .97x.95=.92
Lighting and distribution losses not
included
31
380VDC
Loads
Converter to
24VDC
Lighting
24VDC
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Existing Emerson
products
PS eff – 95%?
Hybrid System Migration -Scenario 2
100kW
300-400V
Solar
Array
Replaces
Existing PV
Inverter
DC/DC
Regulator
380VDC
output
Eff- 97%
380VDC
Converter
No battery
480Vac
AC
Distr.
Eff- 97%
NetSure ITM
With Battery
380VDC distr. backbone
(already considered for
buildings/residential applications)
Converter to
24VDC
Lighting
24VDC
Utility
380VDC
Loads
380-48VDC
Converter
PS eff – 95%?
48VDC
Loads
Vehicle charge
station
Appliances
32
Estimated efficiencies – detailed study in progress
Solar to server eff = .97x.95 = .92
Utility to server eff = .97x.95 = .92
Lighting and distribution losses not included
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
400VDC System Voltages
Cell type
VRLA -6 V
block
Wet cells
Single cell
Number of
cells
Number of
blocks
Nominal
VDC
Operating VDC
@2.25VDC/cell
144
150
156
162
168
174
180
186
24
25
26
27
28
29
30
31
288
300
312
324
336
348
360
372
324.00
337.50
351.00
364.50
378.00
391.50
405.00
418.50
equalize
162
324
364.50
163
326
366.75
164
328
369.00
165
330
371.25
166
332
373.50
167
334
375.75
168
336
378.00
169
338
380.25
170
340
382.50
171
342
384.75
172
344
387.00
173
346
389.25
174
348
391.50
175
350
393.75
176
352
396.00
177
354
398.25
178
356
400.50
179
358
402.75
180
360
405.00
To optimize battery applications the voltage range should be:
Nominal
Min
Max
Typical operating voltage
33
Operating VDC
@2.17VDC/cell
351.54
353.71
355.88
358.05
360.22
362.39
364.56
366.73
368.90
371.07
373.24
375.41
377.58
379.75
381.92
384.09
386.26
388.43
390.60
336VDC-352VDC
294VDC
400VDC
378VDC
VRLA
386VDC
Flooded cells
Not counting cable voltage drop.
Emerson Network Power, Energy Systems North America, Inc.; Proprietary and Confidential Information.
Min VDC
@ 1.75VDC/cell
end of discharge
252.00
262.50
273.00
283.50
294.00
304.50
315.00
325.50
283.50
285.25
287.00
288.75
290.50
292.25
294.00
295.75
297.50
299.25
301.00
302.75
304.50
306.25
308.00
309.75
311.50
313.25
315.00
48VDC
multiples
6.00
6.25
6.50
6.75
7.00
7.25
7.50
7.75
Outside
ETSI
spec
Download