Fixture Type APPROVAL Lamp Type Job Ref. / Location SERIES FG APPLICATION Ideally suited for commercial/institutional environments requiring inconspicuous emergency lighting with directional light distribution. Typical spacing to mounting height ratio – 1.5. Ceiling heights 10' – 15'. Recessed 6 Volt PAR 36 Gimbal Emergency Lighting Unit STANDARD FEATURES q q q q q q Fully recessed matte white adjustable gimbal rotates 358˚, tilts 20° High lumen output halogen or tungsten lamp Supplied complete with plaster frame 120/277 volt input Test switch monitor light located in trim Factory cycle tested REPLACEMENT PARTS CHARGER/BATTERY q q q q q q q q Solid state, patented POWER PULSE* charger Sealed lead acid maintenance free battery – 8 yr. life expectancy Optional maintenance free nickel cadmium battery – 15 yr. life expectancy Low battery voltage disconnect, brownout, power-on latch, solid state switch Temperature compensation Controls: Red LED power on Push to test switch D.C. fuse * Patent No. 4890004 Lamps Part # Halogen 6V 8W..... 050-785 Tungsten 6V 9W..... 050--908 Batteries 6V 12W........ 010-002 OPTIONS Add Suffix/Prefix Maintenance Free Nickel Cadmium Battery............. #–NI 220 Volt 50Hz input........................................... #–220V50Hz Sealed Beam Lamp............................................. #–SB Halogen Sealed Beam Lamp................................. #–HSB Black Finish....................................................... B–# SELECTION GUIDE Type Model Lamp Lamp Volts/Watts Number Type Wattage 6V/12W 6V/12W 6V/18W 6V/18W FG12-1H FG12-1 FG18-1H FG18-1 Halogen Tungsten Halogen Tungsten Total D.C. Wattage For Sustained Illumination 1.5 Hours 2 Hours 4 Hours 8 9 8 9 12 8 5 18 12 7 INSTALLATION DATA RECESSED HOUSING TRIM " -13/16 12 8-3/4" 7-1 /4" 6-1 /2" 7-1/2" Rough Opening 6-1/4" diameter Approved For Use in Insulated Ceilings All products manufactured in accordance with U.L. standard 924, and meet or exceed requirements as established by the National Electrical Code Article 700 and Life Safety Code NFPA101. Specifications subject to change without notice. EM4.0 CUCBCL Pathway Lighting Products, Inc., P.O. Box 591, Old Saybrook, CT 06475-0591 voice: 800.342.0592 • fax: 800.207.0090 • www.pathwaylighting.com • e-mail: sales@pathwaylighting.com