Chapter 2:Transmission Lines ET302 S te s a n K u a sa Power station P e n g h a n ta r a n Transmission P e n g a g ih a n Distribution Figure 2.1 Transmission system in overhead line P eng gu na Consumer 2.1 Transmission system Transmission system was one large system linking generation station to users through distribution system. Transmission system supply large amount of energy of generator station to burden centres. Distribution system also will supply energy from transmission system and distribute to major substation and small substation to the consumer. Electricity can be supplied and distributed whether in alternating current (A.C) or direct current (DC). In practical, 3 phase 3 line system applies in transmission system meanwhile for 3 phase 4 line AC system applies in distribution system. Figure 2.1 show transmission system in overhead line. Important considerations in transmission line operation are referring to voltage and lost power fall which occurred on-line and also transmission line efficiency. Components such as R resistance, L inductance and C capacitance found in transmission line influence that circumstances. 2.2 Short Line Transmission line which possess long less than 60 kms and operating in voltage rate under 20 kV categorised as short line in transmission system. Refering to short distance and low operation voltage, then as a result of this on-line fitness is also small then capacitance effect can be neglected in this line system, such short line performance is depends on resistance and inductance found in transmission line. In real transmission line, resistance and inductance found all along that transmission line. But in line case short amount of obstruction and inductance lumped at one place or part. Page 17 Chapter 2:Transmission Lines 2.3 Resistance and Inductance in line ET302 Transmission line for electric circuit usually having a few parameter such as resistance, inductance and capacitance. This parameter is not same all along transmission line which affect to voltage regulation and also transmission line efficiency. This effect also depends on some transmission line length. 2.3.1 Series Resistance Conductor Several factors should be taken into consideration such as line length, diameter of the line, material and environmental temperature cross sectional area. Current flow in oppositional direction in its and this state is known as resistance. R resistance in ohm formed in this transmission line refering to long and diameter a conductor and can be stated as ; R= a ……(equation: 2.1) Where is resistance conductor. Resistance of the conductor ()is not only depends to material used by conductor but also depends to environmental temperature. Series resistance’s value found in line can be pointed through following equation:If 1 and 2 is resistance value which correlated with temperature value t1 and t2 then, 2 = 1[1 + (t1 - t2)] ……(equation: 2.2) Where is coefficient for material's temperature used to design conductor. Temperature coefficient’s value for resistance also not fixed but depends on beginning temperature. Temperature coefficient for resistance rendered as; = 0 / (1 + 0t1) ……(equation: 2.3) where 0 is a temperature coefficient for resistance when 0C Through equations which indicated can be concluded that resistance occur in transmission conductor are continuously started of transmission line until arrived to distribution line to users. Page 18 Chapter 2:Transmission Lines ET302 2.3.2 Inductance Conductor in transmission line system is not only have resistance even inductance also exist on that line. If we refer to Figure 2.2(a), shows two conductor single phase, note in separatist part both that conductor marking by distance, D. When current flow through this two conductor at any time-it will flow in opposite direction and further create field around both conductor. This pole will be permanently giving pressure between one by another like those portrayed on Figure 2.2(b). (see arrow of field movement). + - γ D - + γ D (b) (a) Figure 2.2: Magnetic force vein induced between two conductor Both conductor in figure 2.2(a) and 2.2(b), will form rectangle loop for each round through live flux current flow result in both conductor. When flux resultant this chain to that loop it will produce inductance. Although separatist distance between this conductor is large about 1 metres to 10 metres, because existence this compact flux number will form larger coil and influence inductance existence. Inductance existence in conductor for each round per metre ( when γ ≤ D ) provable through equation as follows; L D i loge 4 henry / meter ……(equation: 2.4) where, μ = permeability absolute medium. μi = permeability absolute conductor material. Page 19 Chapter 2:Transmission Lines ET302 2.4 Short Line circuit diagram R X I I Line Vm Vsn Load Neutral Figure 2.3 Single line circuit of short line Short transmission line could be identified briefly with draw a single line circuit. Some components found on this line could be used to make calculation to determine voltage efficiency and fall which occurred in short line transmission system. Figure 2.3 shows a short line single line circuit. Referring to figure 2.3, a few parameters could be identified namely, Vsn Vm I R X - Voltage in transmission end Voltage in recipient end Load current in R tailing Loop resistance () Loop inductance () Short Line Vector Diagram C IX Im kos m Vsn G H AA Vm IR B IX sin m Vm kos m sn m O Vm kos m D I F Figure 2.4 Short line vector diagram Page 20 Chapter 2:Transmission Lines ET302 A vector diagram for short line having relation with parameters found in short line individual line figure. In this case vector diagram follow can be drawn like Figure 2.2.4. Refering to Figure 2.4, a parameter identified as; OA OI AB BC OC Transmission end voltage , Vm Load Current, I effect of resistence drop at the line, IR effect of reactance drop at the line, IX Receiver end voltage, Vsn Refering to this parameter we could find end voltage transmision and further determine his power factor. Try the following solution:OC (OD DF ) 2 ( FB BC ) 2 and (V R os R IR) 2 (V R sin R IX ) 2 cos S OF V R cos R IR OC VS In fact, from this vector diagram, we will be able to determine VS and power factor, we also can determine regulation percent for a short line by referring to the parameter. Regulation percent voltage refering to Figure 2.4 can be written as. Regulation Percent = 2.5 IR cos R IX sin R x 100 VS ……(Equation: 2.5) Regulation Voltage Change with Load Power Factor In this condition, voltage drop are same in magnitude and phase but phase relationship with end voltage receiver and end voltage transmission are changed. A Voltage drop at end voltage receiver with increas of load for inductive case (power factor lagging) and increase with capacitance load (power factor leading). End voltage receiver not only depends to load but also in power factor. Regulation voltage changing at end voltage transmission for different power factor could be describe through locust figure such as Figure 2.4. Refering to Figure 2.5, AO vector show end voltage receiver (VR) at load state and OX line with angle ΦR, is load power factor with cos ΦR.Beside that OX line also showed current (I) load phase. AB line drew parallel to OX line having IR resistance's drop lR and vertical line BC drawn vertical to OX line having inductance’s drop IX. Page 21 Chapter 2:Transmission Lines ET302 Referring to figure 2.5, ABC is impedance triangle and CA is impedance drop total IZ line. While OC shows end voltage receiver phase (VS) and difference between VS and VR or ( OC - OA ) is voltage drop on-line and are also known as regulation end transmission. This regulation change able clearly seen if we see maximum regulasi in B point and empty regulasi in S point by referring to locust figure (Figure 2.5) through following equation :-. Regulation = IR cos θR + IX sin θR Regulation wiil be maximum when d ( regulation ) / d θ = 0 IR (-sin θ ) + IX ( cos θ ) = 0 atau Tan θ = X / R Transmission End Voltage, VS H F M Receiver End Voltage VR N E VS C G IX VR Φ ΦR O Φ IR A Power factor leading B X I IX O’ I D R VS VR K Power factor lagging Q P S Figure 2.5 Vm and Vsn Locus Page 22 Chapter 2:Transmission Lines ET302 2.6 Regulation per Unit When load at end receiver get power supply then will happen voltage drop effect from resistance and inductance in conductor. Hence voltage value at end receiver in Vm usually less compared end voltage transmission in Vsn. Different voltage drop in end receiver and end transmission stated as end transmission voltage percent known as regulation. Regulation per unit definable as voltage change in end receiver part when full load in halted, this will make voltage in transmission end equal to receiver end. This situation can be made to appear in form of similarity as follows: Regulation Percent = Vsn Vm x 100 Vm ……(Equation: 2.6) Where is Vsn is transmission end voltage and Vm receiver end voltage.As known regulation help to maintain voltage value in load terminal by setting limit ( 5% error voltage) by using suitable control equipment. 2.7 Transmission Efficiency When load given supply through transmission line will happen disappearance in conductor because of resistance and power effect sent in load transmission end line less than power supplied in end transmission. Transmission line efficiency found as power ratio received to power transmit or can be may be written as; Re ceived Power x 100 Transmit Power OutputPower = x 100 OutputPower PowerLosses Transmission Efficiency = T = Vm Im cos m x 100 ……(Equations: 2.7) VsnIsn cos sn Where is Vm, Im and cos m is voltage, current and receiver end power factor while Vsn, Isn dan cos sn is voltage, current and transmission end power factor. Page 23 Chapter 2:Transmission Lines 2.8 Regulation per Unit And Efficiency Calculation ET302 Voltage Regulation and transmission line visible with clearer through simple calculations examples like in this part. Example 2.1: A transmission line a capable phase power 1,100 kW to factory with a voltage 11 kV in power factor 0.8 lagging. This line have a resistance 2 and inductance coil 3 Get; i). Voltage at transmission end. ii). Regulation Percent. iii). Transmission Line Efficiency Solution : Given; Resistance, R = 2 Inductance, X = 3 Power , P = 1,100 kw Power factor m = 0.8 (mengekor) Receiver end voltage, Vm = 11,000 V Load Current, I = I= P x 1,000 Vm cos m 1,100 x 1,000 11,000 x 0.8 I = 125 A i). Value of transmission end voltage known, so that cos m = 0.8 sin m = 0.6 Vsn = (Vm cos m IR) 2 (Vm sin m IX ) 2 Vsn = (11,000 x0.8 125 x 2) 2 (11,000 x0.6 125 x 3) 2 Vsn = 11,426 V Page 24 Chapter 2:Transmission Lines ET302 ii). Regulation Voltage Unit. Vsn = 11,426 V Vm = 11,000 V Vsn Vm Regulation Percent = x 100 Vm 11,426 11,000 = x 100 11,000 = 3.873 % iii). Transmission Line Efficiency. Power Losses = I2 R = (125)2 x 2 = 31,250 atau 31.25 kw Transmission Power x 100 Re ceiving Power Transmission Efficiency = T = T 1100 x 1000 x 100 (1100 x 1000) + 31250 = 97.24% Example2.2: A transmission line three phase 11 kV owns resistance 1.5 and inductance 4 for each phase. Calculate regulation percent and efficiency line percent if total end receiver load, 5000 kVA in power factor 0.8 lagging and voltage supplied until last distance was 11 kV. Solution : Resistance for each conductor R = 1.5 Inductance for each conductor, X = 4.0 11,000 phase voltage at end of receiver, Vm = = 6,351 V 3 Transmission Load = 5,000 kVA Load power factor , kos m = 0.8 (lagging) Line Current, I = = Power in kVA x100 3 x Vm 5,000 x1,000 = 3 x 6,351 262.4 amp Transmission end voltage 262.43 for each A phase, Page 25 Chapter 2:Transmission Lines Vsn = Vm + IR cosm + IX sin m = 6,351+(262.43x1.5x0.8)+(262.43x4x0.6) = 7,295.8 V Transmission end voltage VSL = 3 x 7,295.8 = 12,637V So that, ET302 Vsn Vm x 100 Vm 12,637 11,000 = x 100 11,000 = 14.88 % Regulation Voltage Percent = and Transmission line efficiency = T = Output Power x 100 Output Power Power Losses 5000k x100 5000k + 103280.64 T = 97.98% MEDIUM AND LONG TRANSMISSION LINE 2.9 Introduction of Medium Line and Long Line Besides short line, medium line and long line also in transmission lines. As compared both this line with short line, effect of loss caused resistance and inductance in conductor were more numerous and large. With existence large lost power on-line medium and long thus it also also influence transmission line efficiency. As such voltage regulation should be done also is large to overcome loss in acceptance end transmission line. 2.9.1 Medium Line and Long Line Transmission line which possess line length between 60 to 150 kms and line voltage between 20 kV to 100 kV classified as medium line. If for line short capacitance effect deserted, in medium line capacitance effect taken. Transmission line which possess long exceeding 150 kms and voltage reach more 100 kV it classified as long line. As known each line influenced by resistance, capacitance, inductance and conductivity. Due to this from calculation aspect loss found in long line was enormous compared short and medium line. Page 26 Chapter 2:Transmission Lines ET302 2.9.2 Medium Line and Long Line circuit. Medium Line Circuit Referring to figure 2.6, a few parameters could be identified, Vsn Transmission end voltage Vm Receiver end voltage Isn Transmission end current Im Receiver end current Ic Capacitance current R Loop Capacitance () X Loop Inductance () C Capacitance (farad) ISn R X line Vsn Im IC C Vm load Neutral Figure 2.6 Medium line individual circuit Actually exist three way that can use to determine medium line individual line figure such as end condenser methods, T method and method . Figure 2.6 is method end condenser. This method crumple up capacitance in load end part. If in short line capacitance deserted, in medium line also capacitance taken into account this is because availability addition to voltage and length value line. Due to this regulation calculation in medium line will participate consider capacitance and leak reactants in line and its can be explained depends on value of receiving voltage. Refering to circuit in Figure 2.6, we would note line current (Isn) is total load current (Im) and also current recharging (Ic) for capacitance.Written as; Isn = Im + Ic ……(Equations: 2.8) If we write equation for current recharging for capacitance, Ic = jwCVm and Im load current = Im (cost θm - jsin θm) Page 27 Chapter 2:Transmission Lines We will find out Isn = Im cost θm - jIm Sin θm j, as such with this is found; ET302 equation Voltage drop in line = Isn ( R JX ) from this equation we will know voltage value found in transmission end as follows; Vsn = Vm + Isn (R + jX). ……(Equations: 2.9) Through this equation we can see how power flow occurring in line delivery system medium and further we be able to size his voltage regulation. Long Line Circuit A transmission line who sent out electricity power release heat due to conductor resistance. So long line act as a barrier. Transmission line also act as a inductance because every conductor are surrounded by a magnetic field in transmission line length. Long transmission line also acted as a its capacitor because conductor act as pelitic capacitor. Resistance, inductance and capacitance as a transmission line are dispensed uniform in line length, with magnetic field around conductor along with electric field created by different between that field. We could imagine that a transmission line contain thousands resistor, inductor and basis capacitor like those demonstrated at figure 2.7. ISn Vsn R/n X/n B/n Im G/n Vsn Load Figure 2.7 Long line individual circuit Refering to Figure 2.7, a few parameter could be identified in among them; Vsn Transmission end voltage Vm Receiver end voltage Isn Transmission end current Im Receiver end current Page 28 Chapter 2:Transmission Lines ET302 Apart from that several statements can be done refering to same circuit, i). Line are made up a few constant parameter namely resistance, inductance, capacitance and conductivity all along long transmission line distribution. ii). Resistance (R) and inductive reactance (X) is element on-line serial transmission iii). Capacitance string (B) and leaking conductivity (G) are element shunt, leaking conductivity also caused on-line lost power. It derives of insulation leak or corona effect in conductor. iv) Leakage current which flowed through shunt graduate is maximum in transmission end line and lesser continuously when headed for receiver end and finally become zero after arriving to receiver end of line. 2.10 Voltage Effects on Trasmission Efficiency. Transmission line efficiency is not only influenced by several constant occur in transmission line namely resistance, inductance and capacitance like already discussed before. However line efficiency also influenced by voltage value are brought by something corona line and effect in that line. In this part the effects will discuss briefly. 2.10.1 High Voltage Transmission ( 132 kV / 275 kV) Usually withdrawn electricity by one generator station is about 33 kV, 22 kV and 11 kV. Of that generator pass energy to a few transformer through span line on by various extension way such as ring system, radial system, network system etc. The generated voltage is step up to the wanted value such as 132 kV, 275 kV or 500 kV. This voltage purpose of raising was to reduce expenditure in large cable size usage because cable size used is based on enormity current which flowed. At the same time, transmission line efficiency can be increased. The situation explicable with double power (W) are sent through three phase transmission system which possess line voltage (E) and cost power factor kos , produce equations as follows Current Line I W 3 E kos …(Equations: 2.10) Let say : ι = Length of conductor line =Resistance of conductor material = current density A = Conductor cross section Page 29 Chapter 2:Transmission Lines ET302 line loss may be written as: 3I 2 R 3W E kos Line efficiency transmission line: 3 output 1 input E kos Voltage drop for each line: = IR = ι …………(Equations: 2.11) …(Equations: 2.12) ……(Equations: 2.13) Copper volume: =3ιA 3 W ……(Equations: 2.14) E kos Refering to this equation some assumptions could be made among them:Equation (2.11), giving picture that lost power are proportional inverse with E, also inversely proportional with power factor cost . Equation (2.12), show that efficiency increased transmission line by adding total voltage in line and power factor. Equation (2.13), resistance decrease at every line are fixed ( when and ι assumed fixed. Voltage regulation can be repaired because fall percentage voltage could be reduced with increasing value E. Copper volume of necessity for transmission line are proportional inverse with a voltage and system power hereby copper need dwindling. Can be concluded of this equation altogether, when voltage and power system value enhanced then this result would give efficiency in transmission line by conductor material saving also can be done and further reduce delivery cost with small cable size in long line. Due to this line capacity advancing by the increase of transmission line voltage. Undeniable that cost for transmission line and terminal equipment also rising with the increase of transmission line voltage but overall cost is proportional with delivery voltage. Moreover it will save cost in keeping with lost power reduction which occurred in transmission line. Effect of that, the delivery total cost decrease with the increase of transmission line voltage. Page 30 Chapter 2:Transmission Lines 2.10.1.1 Corona ET302 Corona was electrical discharge emerge around overhead line conductor, due to air flow where would disturb radio waves and creating lost power. In low voltage there was no change which occurred can be influenced by air condition around conductor. However when potential different and gradually increase, at one level, glow luminance (luminous glow) weak purple color will rise with hissing sound. This phenomenon is known as virtual corona and participated by gas production which has identified through system feature his smell. All situations such as hissing sound, purple radiation and gas production smelling known as corona. If conductor are homogeneous and smooth and similar state fixed all along conductor, in other circumstances rugged parts will issue brightness. If range in conductor not too big compared to diameter, arc may be might stand in for before glow luminance seem. This happened in keeping with statement where range in small conductor do not have time quite enabling glow luminance happened. In the case of a positive conductor DC system has a uniform warmth and brightness of the rising of the negative division. For AU system, according to the corona current is not sinusoidal. Corona, accompanied by loss of power, losing is caused by light, heat, noise and chemical reactions. Corona exists at small transmission line side effects of them; i). ii). Result in lost power that is during uncertain weather condition. Found voltage drop which not sinusoidal with current not corona sinusoidal, this situation cause little trouble of communication circuit as a result of electromagnetic and electrostatic induction. iii). Harmonic wave distortion which many especially in third hormonic, that exists in transmission line. Corona formation produce ozone gas with chemical reaction in conductor and creating corrosion Corona effect in transmission line like those above-mentioned of course undeniable especially for long transmission line i). conductor diameter (for example with ACSR). ii). Use more from one conductor for each phase, namely use bouquet conductor (bundle conductor) iii). Add more range in conductor hereby stress by magnetic static could be reduced and thereby corona effect also could be reduced. Page 31 Chapter 2:Transmission Lines ET302 OVERHEAD LINE INSULATOR 2.11 Principle and design and Overhead Line Overhead line distribution system usually involving a few key component namely wireline, insulation, tower post etc. However in chapter, insulator applies in overhead line distribution system will be discussed. This Insulator could be identified is based on design. 2.11.1 Overhead Line Insulators Conductor for distribution system overhead line is guaranteed his security with electric equipment assistance named insulator. This insulator then would not be have been leaks current to earth from conductor through this equipment. Due to this insulator play important role succeed distribution operand overhead line system. Figure 2.8 show either insulator form of equipment. Figure 2.8: Few insulator form overhead line A few important features and should be taken into consideration before insulator applies in installation any overhead line distribution system among them; i.). Physical strength: ability arrested suitable burden heavily something conductor. ii). Having high insulation resistance to prevent current leak to earth. iii). High resilience ratio of breach leap result voltage. iv). Material used to develop insulator was the type that does not permeable liquid or hollow and influenced by temperature changes. v). This process does not contain impurity and crack and impervious of liquid substance and gas of aerospace. Page 32 Chapter 2:Transmission Lines ET302 Overhead line insulator common use including pin insulator, suspension insulator, tension insulator and shackle insulator . In this chapter, only pin insulator, suspension and insulator insulator tension will be discused . Pin Insulator Pin insulator designs by having steel pin could be installed in post bar tower. This insulator have screw in pin part steel while conductor placing at this insulator top and bound with use wire aluminum soft with a couple coil. Pottery part kept apart from steel division with a kind of soft metal (timbre). Design this pin insulator visible in figure 2.9(a) for low voltage a pin insulator used is fair enough. For transmission line high voltage also stronger and large pin insulator utilized. Type pin insulator high voltage is different with insulator construction low voltage pin. Insulator construction high voltage pin comprising two or more ceramic layer simultaneous cement. Use a insulator unit pin fair enough for delivery system 33 kV if exceeded over in this voltage proportion two or more insulator arrangement pin used. However inside pin insulator use overhead line delivery system is not economy for voltage exceeding 80 kV. Figure 2.9(b) show schematic figure a pin insulator for overhead line. (a) Design Page 33 Chapter 2:Transmission Lines ET302 Conductor Binding Wire glazed porcelain Plumbed Shield Steel pin Tower Bar (b) Schematic Figure 2.9 Pin Insulator 2.11.3 Suspension Insulator Insulator installation suspension in dependent overhead line to voltage capacity under by conductor in line singles. Capacity expansion voltage at one line will participate increase number insulator installation suspension in that line. By transmission line and distribution as most handling exceeding 33 kV then sistam become bigger and distance between increased line far. This situation cause pin insulator have no capacity to keep this line system. Due to this to overcome this problem suspension insulator designs, insulator exact figure pin can be observed in Figure 2.10(a) Suspension Insulator suspend in different tower post bar with pin insulator placing at bar top. For type this insulator, conductor will be connected in insulator lower part suspension. As such we can add range in tower bar with conductor through insulator addition suspension arranged by network. Insulator increasing number suspension at one line are referring to line voltage capacity, weather condition, transmission line and size assembly type suspension insulator used. Page 34 Chapter 2:Transmission Lines ET302 Because this insulator is fitted by network then replacement any insulator could be made without change insulator entire network. Figure 2.9(b) show schematic form a suspension insulator Figure 2.10(a) Suspension Insulator Socket Cement Steel Cap Glass or Pottery Balls Steel Pin Figure 2.10(b) Suspension Insulator schematic Page 35 Chapter 2:Transmission Lines 2.11.4 Strain Insulator ET302 At one overhead line state having high tension, for example at end or hairpin at transmission line. For tension its low voltage line use shackle insulator. Whereas for line tension insulator high voltage tension used. Usually in insulator installation in transmission line two or more insulator used. Insulator disk tension fitted with horizontally different with suspension insulator will fitted with vertically. Process of tension insulator are same with suspension insulator, however height size of suspension insulator are exceeded tension insulator (Refer to Figure 2.11). Figure 2.11 : Tension Insulator Schematic tegangan Advantages and Disadvantages Overhead Line Insulator The advantages of suspension insulator compared pin insulator can be explained as follows; i). Suspension insulator is cheaper from his cost aspect for capacity line which exceeded 50 kV. ii). For each unit of suspension insulator type will designs by refer at low voltage capacity around 11kV . When used in high voltage capacity then enough with connect suspension insulator by serial, disk number used depends on voltage value in line. iii). If occur unanticipated damage in which points suspension insulator, just replace damaged disk only and no need replace insulator entire network that suspension. iv). Suspension insulator is more flexible assembled on in line. Insulator connection tension in tower bar is ease to turn to any direction. v). Pin insulator suitable to be fitted in low post compared suspension insulator. Page 36 Chapter 2:Transmission Lines ET302 Disadvantages of suspension insulator compared pin insulator can be explained as follows; i) Suspension insulator no suitable to be fitted in low tower post. ii) Suspension insulator need high and strong post and this increase cost delivery. iii). Damaged at pin insulator difficult to be detected as compared suspension insulator. iv). Limited pin insulator capacity only in voltage below 80 kV. v). Suspension insulator need wide column between conductor compared pin insulator. Tests Conducted on Overhead Line Insulator Overhead line insulator are important instrument to achieve electricity transmission process and distribution at some area. Due to this suitable and safe insulator selection should be taken into consideration, so that damage in line does not happen. Ensure insulators are used at well off overhead line several tests should be done before its used or being marketed. Test shouls be done before used and marketed are:(a). Design test (Test emerge arc or flashover) (b). Performance test (c). Habit test (a). Design test Design test done to ensure electric performance and mechanical insulator to several trial condition such as test emerge dry arc, test emerge wet arc and test emerge contamination arc. Insulator test of methods listed this commonly made to three insulator randomly chosen. This insulator will be tested either fulfilling standard or on the other hand. i. Test Emerge Dry Arc Voltage emerge arc is voltage cause insulator surface breach insulate, allow current flow through insulator face from conductor to supporter bar. A insulator fixing with a safe minimum voltage imposed at insulator. This minimum voltage is dependent to insulator type and size. In tests emerge this dry arc, a net and dry insulator assembled on a supporter. A voltage with power frequency system imposed in that insulator. This voltage will increase by way staggered until minimum voltage for insulator under test. This minimum voltage need to be given in insulator within not less than 30 seconds . If emerge arc does not happen in that period, insulator is good. Voltage raised again by way gradually until flashover happened within 10 seconds. Lightning overvoltage being recorded. This process is repeated as much as four times. Average voltage Page 37 Chapter 2:Transmission Lines ET302 of flashover could not less than minimum voltage of past dry lightning that is fixed. ii. Test Emerge Wet Arc This test equal to test (a) except under synthetic rain which possess resistance and temperature that is fixed. Angle and speed rate synthetic rain water decline also in fix. In this time, insulator should arrested lower minimum voltage of test (a) long 30 seconds at least without emerge arc. iii. Test Emerge Contamination Arc This test equal to test (b) except involving contamination with fog, salt, smoke, dust or chemical. Usually, lightning overvoltage is ½ value than tests (b). (b). Performance Test Performance test is another test used to determine the overhead line insulators are safe (to meet required standards). Among the tests involved dalan performance test is; i. Broken Test Insulate Breakdown tests carried out on 3% per cent of the total insulation produced. To test the dielectric insulation. Insulation may be able to withstand extreme lightning events have suffered, but it must be replaced if it had been breakdown. For insulation design, flash past should occur at voltages less than voltage breakdown. At the time of testing, the insulation shall be immersed in a clean insulating oil to prevent flash past. The value of the test voltage is raised slowly and the insulation must be able to withstand 1.3 times the voltage dry flash past without breakdown. ii. Pulse Test. Previous voltage lightning pulses obtained by using a signal pulse as in Figure 2.11. Page 38 Chapter 2:Transmission Lines ET302 Magnitude Leading Wave Lagging Wave Time Figure 2.12: test wave form pulse Pulse Ratio iii. Pulse Overvoltage Lighting overvoltage power frequency Mechanical Test A insulator network suspend tested by one tension 1.2 times double maximum load usually and type insulator pin tested with moment bentokan 2.5 times double maximum burden usually. After the test, dry lightning overvoltage test required again give ensure be provided change in lightning overvoltage. iv. Temperature Test The insulator is immersed in rotation in water barrels temperature 70 degrees celsius and 7 degrees celsius. Overall immersion number is six times, invariably take one hour long. The insulator then dried and flash test dry implemented. v. Porosity Test This is glaze test in pottery insulator. The insulator is weighed in dry state then it immersed in water and under pressure long 24 hours. After that the insulator is issued, his face dried. Difference between both the reading show the pottery deep water result gelis imperfect. (c). Habit Test Habit test are involving high voltage and test test corrosion which conducted on all insulator. For test insulator erosion and rustiness usually divulge to copper solution of sulphate in temperature 15.6 celcius in time a minute. After one minute insulator tested will in transferred and then polished and Page 39 Chapter 2:Transmission Lines ET302 cleaned and then disclosed again to copper solution of sulphate. Ianya done repeatedly up to four times. After that checked to be sure there were no any rustiness and metal cleave to insulator tested. High voltage test committed against pin insulator, where it overturned and placed inside water which hit keparas insulator neck. Water also placed in hole spindle. Then high voltage are supplied in 5 minutes time. After going through this test should good insulator will not suffer damage. INSULATOR NETWORK OVERHEAD LINE 2.12 Introduction Insulator Network Overhead Line After we learn a few insulator form overhead line and also tests which operate on insulator. We have obtain description a little bit insulator need for delivery system overhead line However also need we know that insulator are used at overhead line namely suspension insulator (Figure 1.13), having different voltage distribution within one network.This potential difference would cause network inefficiency insulation happened when occurence of interference (lightning) on overhead line. Although that kecepan this can be repaired with a couple method which will in discuss further dalan this input. Figure 2.13 Insulator installation suspension in overhead line 2.12.1 Potential Distribution in Network Insulator Overhead line which operates in high voltage capacity using some disk number (suspension insulator) connected by serial. Connection these disks by serial overall known as network insulator. Each suspension insulator having metal installation own and each metal installation for per unit this having relative fitness on metal installation to different units. For network Page 40 Chapter 2:Transmission Lines ET302 this insulator mutual capacitance are referring between metal installation insulator per unit suspension. Shunt fitness or air fitness also refering to each metal installation between insulator unit suspension with tower post to earth. Because availability faggot voltage in insulator network suspension when dihidupkan, cause unequal voltage division at every insulator will happen. Potential difference voltage found in insulator network is different, for insulator near network with conductor having voltage percentage value high compared near insulator with tower post. This situation cause voltage division no linear in this network insulator. Situation explicable refer solution in Figure 2.14 (a) and (b). I1 V1 C1 A V2 E i1 I2 V1 C1 B V1 C A V2 C i2 E B V1 + V2 V3 C C C1 i3 V1 + V2 + V3 Figure a V3 I3 I4 Figure b Figure 2.14 Process (a)and equivalent circuit (b) for insulator network Refering to Figure 2.14, known; C : Mutual capacitance C1 : Shunt fitness or air fitness V1 : Voltage negotiate first suspension insulator unit (near to tower post) V2 : Voltage negotiate second suspension insulator unit. V3 : Voltage negotiate third suspension insulator unit (near to conductor) E : Voltage between conductor and earth. Take K = C1 / C or C1 = KC Page 41 Chapter 2:Transmission Lines ET302 Use law kirchhoff in node A we find out:- I2 = CV2 = CV2 = CV2 = V2 = V2 = C1 = KC I1 + i1 CV1 + C1V1 CV1 + KCV1 C(V1 + KV1) (V1 + KV1) V1(1 + K) ……………… Get V1 By using law kirchhoff in node B we find out:I3 = I2 + i2 CV3 = CV2 + C1( V1 + V2) …………..…..Voltage negotiate C1 air's fitness from tower post to insulator unit to two = ( V1+ V2) …… figure above and note CV3 = CV2 + KC( V1 + V2) CV3 = C[V2 + K ( V1 + V2)] know V2 = V1 (1 + K) V3 = [V2 + K( V1 + V2)] V3 = [KV1 + V2(1 + K)] V3 = [KV1 + V1 (1 + K) (1 + K)] V3 = V1 [K + (1 + K) (1 + K)] ……………….Simplified. V3 = V1 (K + 1 + 2 K + K²) V3 = V1 (1 + 3 K + K²) …...…………..Get V1 Voltage between tower conductor and post (to earth) :E = V 1 + V2 + V3 E = V1 + V1(1 + K) + V1 (1 + 3 K + K²) E = V1 ( 3 + 4K + K2 ) From this equation is found :V1 = E / ( 3 + 4K + K2 ) …..{Equations: 2.16) After getting V1 value further obtain V2 value and V3. Of in this retrieval we will see bezaupaya voltage negotiate each this network insulator. Example 2.3: A network to four insulator used to hang up a 33kV conductor, three overhead line phase. Kapasitan air or shunt between every cap and tower was one tenth (1/10) from each fitness unit. Calculate voltage hinder each insulator. Solution : Page 42 Chapter 2:Transmission Lines ET302 Given: E = 33kV K = C1/C = 1/10 = 0.1 With use equation were obtained of 8.1 we know; V2 = V1(1 + K) V3 = V1 (1 + 3 K + K²) For equation V4 voltage hinder fourth insulator, available with method used just like in 8.1 and found as; V4 = V1 (1 + 6K + 5K2 + K3) So that V2 = V1(1 + K) V2 = V1(1 +0.1) V2 = 1.1V1 V3 = V1 (1 + 3 K + K²) V3 = V1(1+ 3(0.1) +(0.1)2) V3 = 1.31V1 V4 = V1 (1 + 6K + 5K2 + K3) V4 = V1(1+ 6(0.1) + 5(0.1)2 + (0.1)3) V4 = 1.651V1 Voltage between tower conductor and post (to earth) :E = V 1 + V2 + V3 + V4 E = V1 + 1.1V1 + 1.31V1 + 1.651V1 E = 5.061V1 and E= 33000 3 = 19050V So that; V1 = E / 5.061 V1 = 19050 / 5.061 V1 = 3764.7V By including V1 value in V2 ,V3 equation, and V4, from this equation is found :V2 = 1.1V1 V2 = 1.1(3764.7) V2 = 4141.2V V3 = 1.31V1 Page 43 Chapter 2:Transmission Lines ET302 V3 = 1.31(3764.7) V3 = 4931.8V V4 = 1.651V1 V4 = 1.651(3764.7) V4 = 6215.5V Refering to voltage values negotiate insulation per unit found V4 voltage's value obstruct fourth insulator in insulation network (near to conductor) was high compared V1 voltage's value in near insulator with tower post namely first insulator. 2.12.2 Network Efficiency Because availability unequal voltage division at every network insulator are used at overhead line what when occurence of interrupt or ganguan lightning result. Namely voltage negotiate near insulator with higher conductor and decrease until to near insulator with tower post. Then will reduce efficiency in insulation network used. Network efficiency also influenced by insulator number suspension applies in a network. Apart from that depend also to fitness ratio air (capacitance between tower unit and post) with mutual capacitance (capacitance between unit) at one network. Network efficiency for use overhead line definable as; Network Efficiency = Or can be writen as, Network Efficiency = Voltage Hinder Network x 100% n x Voltage Hinder Insulator near to conductor E x 100% nVT …..{Equations: 2.17) Where; E = Voltan hinder network n = number of insulator arranged by serial in network insulator VT = Voltage Hinder Insulator near to conductor Example 2.4: A network to four insulators used to hang up a 33kV conductor, three overhead line phase. Kapasitan air or shunt between every cap and tower was one tenth (1/10) from each fitness unit. Calculate insulator efficiency this network.. Solution : Page 44 Chapter 2:Transmission Lines ET302 By using answer achieved of example 2.3 namely; V4 = 6215.5V (Voltage Hinder Insulator near to conductor) Given; 33000 E= = 19053V 3 n= 4 So that; Network efficiency = E x 100% nVT = 19053 4 x 6215.5 = 76.6% x 100% 2.12.3 Repairing Potential Distribution in Network Insulator Although found potentisal inside voltage a insulator system network which reduces insulator efficiency network for overhead line. This problem could be overcome and repair by variety way among them extend tower bar, capacitance grading, shielding static and use guard ring. In this input only two ways would discuss to improve efficiency in network insulator namely cross arm and guard ring (a) Cross-arm Cross arm mean increase bar distance serves to suspend network insulator of tower post. Through this method network efficiency can be increased. If referring to example 2.3, to get network efficiency is obviously namely by adding bar distance from tower post will participate reduce K value (capacitor ratio). When K value reduced namely lower of 0.1 then will increase insulator efficiency network. However this method is on to high and large tower post only because for post small tower had no enough capacity to support long bar weight and also network insulator. Figure 2.15 show schematic for cross arm method Tower Bar D D = Bar length Conductor Figure 2.15 Cross arm schematic Page 45 Chapter 2:Transmission Lines (b) ET302 guard ring Ring way obstruction can be done with use static shield. This static shield assembled on end lower part insulator unit connected by using joining of metal in suspension insulator and then connects to line conductor. Guard ring which functions as curtain for per unit, reduce earth capacitance and create capacitance between insulator line and cap. Capacitance value is big in nearby unit part with guard ring and this will reduce voltage fall negotiate insulator per unit network. Through this way same voltage distribution negotiates per unit is impossible obtained in practically. However it could be considered to increase decently possible network efficiency. This guard ring method visible like figure 2.16(a). Tower post I1 Tower Post C i1 C 1 Arc Horn C1 C1 Obstruction Ring i2 i3 I2 C I3 Conductor Ix Cx Iy C y Iz C z V2 V3 Obstruction Ring (b) Equivalent circuit (a) Construction Figure 2.16 : C V1 Guard ring Refering to figure 2.16(b), a guard ring were installed in conductor part Page 46 Chapter 2:Transmission Lines ET302 so that level voltage voltage be equivalent. In this situation capacitanc current i1, i2 and i3 become equal capacitance current conductor to Ix pin, Iy and Iz. as such voltage value insulation per unit is the same namely V1 = V2 = V3 = V. Supposing Cx, Cy and Cz is capacitance obstruction need to be same voltage division; Through solution with method used kirchhoff law at every node we will achieve; At point A, At point C, C1V = Cx3V C1V = Cx3V Cx = C1 / 3 C13V = CzV C13V = CzV Cz = 3C1 At point B, C12V = Cy 2V C1V = Cy 2V Cy = C1 Page 47