Name, department/event, date ABB SACE Low Voltage Breakers for GenSet ATS devices, MCCBs, ACBs © ABB Group February 7, 2013 | Slide 1 ATS New Family What is ATS More Reliability More Safety More Intelligence ATS is the control unit of automatic transfer switching equipment applied to any installations requiring switching from the main power circuit to another to ensure the supply of loads. ABB presents the ATS family (ATS021, ATS022) that offers the most advanced and comprehensive solution in power continuity. © ABB Group February 7, 2013 | Slide 2 ATS New Family Devices ATS021 is the basic and complete device for automatic transfer switch ATS022 is the high-performance and versatile solution for automatic transfer switch Find out more at http://www05.abb.com/global/scot/scot209.nsf/veritydisplay /7bd38b33b95e3ca8c1257a6b0050e5c2/$file/1SDC007408 G0201.pdf © ABB Group February 7, 2013 | Slide 3 ATS New Family Technical Characteristics © ABB Group February 7, 2013 | Slide 4 ATS021 ATS022 Auxiliary Power Supply Not Required Not Required (24-110 Vdc is required only for Modbus dialogue and 16.6Hz system) Rated Voltage, Un Max 480 Vac Max 480 Vac Frequency, fn 50, 60 Hz 16.6, 50, 60, 400 Hz Operating temperature -20 … +60 oC -20 … +60 oC Dimensions(H*L*D) 96x144x170 mm 96x144x170 mm Scenarios Normal&Emergency – Generator start-up – No line priority Adjustable Gen. shut down As ATS021 plus Bus Tie and Priority Line selection Modbus RS485 Dialogue - Yes Display - Yes Molded Case Circuit Breaker Dedicated Product Tmax XT2, XT3 and XT4 for Generator Protection From 10 to 250 A Two interrupting ratings available Available with traditional thermomag trip unit or with electronic trip unit © ABB Group February 7, 2013 | Slide 5 Molded Case Circuit Breaker Dedicated Product TMG Thermomag Trip Unit Thermomagnetic release specific for Generator Protection Protection against short-circuit at 3 x In Protection against overload adjustable starting 0.7 x In © ABB Group February 7, 2013 | Slide 6 Molded Case Circuit Breaker Dedicated Product Ekp G-LS/I Electronic Trip Unit New electronic release specific for Generator Protection Test connector on the front of the release: easy testing & troubleshooting Protection against short-circuit with or without delayed trip from 1x In: Ithreshold=1…10 x In Protection against overload available in 2 curves © ABB Group February 7, 2013 | Slide 7 Molded Case Circuit Breakers: other aspects of interest Size 7 (up to 1600 A) of Tmax range can have a motor operator mounted inside the breaker, saving a lot of space Size 8 (up to 3200 A) of Tmax range is appreciated for its special Front Terminals All Tmax breakers provide the widest choice for connection terminals and for accessories (handles, motors, coils...) © ABB Group February 7, 2013 | Slide 8 Air Circuit Breakers Emax ACB: Perfect for GenSet protection, up to 6300A Emax Air Circuit breaker: extremely compact dimensions (with X1 frame being the smallest on the market), outstanding performances Reduced power losses Power, Energy measures available thanks to integrated CTs&VTs The most complete protection functions, from basics (overload, short-circuit) till advanced (Reverse Power, Dual setting…) © ABB Group February 7, 2013 | Slide 9 Air Circuit Breakers & Molded Case Circuit Breakers Common features Worldwide breakers (UL, IEC, CCC certifications) Possibility of wireless connection for testing/troubleshooting (for Tmax starting size 4) © ABB Group February 7, 2013 | Slide 10 © ABB Group February 7, 2013 | Slide 11