Communications Infrastructure Standards Manual (CISM)

advertisement

CENTRAL NEW MEXICO

COMMUNITY COLLEGE

CNM

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design

Guidelines

Version #4.0 12 December 2007

Provided by:

CNM ITS Department

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines

Forward

Central New Mexico Community College (CNM) has developed this document to assist our valued consultants and designers by establishing a set of “ground rules” when planning and designing new or renovated spaces and cabling infrastructure within and between our facilities.

This includes how we expect you to design a standard CNM communications room including provisions for electrical, mechanical and telecommunications systems and architectural finishes.

The cabling infrastructure includes equipment racks, cable tray, conduit, outlets, cabling and termination panels and they are also included in this document. This document, when used in conjunction with the CNM Communications Infrastructure Standards Manual (CISM) and the

CNM Standard Drawings, should provide the key and relevant information necessary to properly design to our new standards.

Richard Mazon

Manager, Infrastructure Support

Information Technology Services

1

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines

1.

COMMUNICATIONS ROOMS

The following are general build-out requirements for Equipment Rooms (ER) and

Telecom Rooms (TR). The ER is considered the primary entrance facility into the building. This is where the entrance conduits will enter the building. This room may also serve as a TR.

Purpose : The room shall be dedicated to providing a secure environment to house communications equipment.

1.1.

Equipment Room: The contractor shall design the rooms using the following criteria.

1.1.1.

Size: The size of the room shall be a minimum of 15 feet by 20 feet

(inside dimension) for an ER, and 15 feet by 16 feet for TR’s. The ceiling deck height shall be a minimum of nine (9) feet. The shape must be rectangular with no columns, piping, or other obstacles anywhere in the open space. The ER should be located such that the TR’s stack on the floors directly above.

1.1.2.

Entrance Conduits: Entrance conduits that enter the building must extend up from the finished floor a minimum of 6 inches and be spaced no more than 8 inches apart from center to center. All entrance conduits shall be Trade Size 4.

1.1.3.

Air Conditioning: A cooling system that is independent of the primary building HVAC system may be required to meet the ER/TR cooling requirements. Air conditioning is required to provide continuous cooling

(365 days a year, 24 hours a day, 7 days a week), with the thermostat controls located in the ER/TR. Air conditioning shall maintain the temperature between 75 o and 80 o Fahrenheit, with relative humidity between 40% and 60% on the typical heat load of 20 KBTU/hr per rack for the equipment in the ER/TR Room. The HVAC system shall be on both normal and emergency power. Adequate drainage shall be provided for the water by-product from the A/C unit if a standalone unit is used.

Humidity and reheat control shall be provided as required. Air ventilation must be provided with filters able to remove airborne particles ten (10) microns or greater in size from the room. Actual BTU’s to be verified before final design.

2

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines

1.1.4.

Power Requirements: An independent, dedicated sub-panel will be installed in each ER/TR and will be mounted on the wall opposite the door. The panel must be surface mounted to allow for additional conduit/circuits to be added as needed. The panel is dedicated to the equipment outlets and lighting within the space. No convenience outlets and any other non-telecom related equipment is to be powered from this panel. a) Sub-Panel: Provide one 120/208 VAC, 3-phase, 4-wire, 200 Amp, 30 spaces, surface-mounted electrical sub-panel equipped with breakers located in the room. The sub-panel must be sized to accommodate the current capacity plus 50% spare. The panel must be independently grounded. The breakers shall be rated as follows: i) 1 ea. - 3 pole, 208 VAC, 3 phase per rack. ii) 2 ea. - 20 Amp, 1 pole, 120 VAC, single phase circuit per rack. b) From the sub-panel, provide two (2) dedicated 20 Amp, single pole, 120

VAC, single phase circuit with 20 Amp breaker for each rack. The circuit junction box for the circuit shall be installed on the cable tray above the equipment rack position specified by the CNM ITS. Each circuit shall be wired with #10 AWG wire to facilitate higher voltage/amperage should that be necessary in the future. CNM ITS shall provide a floor plan for the

ER/TR indicating footprints for the equipment racks. c) From the sub-panel, provide one (1) 30 Amp, 208 VAC, 3 phase circuit with 30 amp breaker for each rack. The circuit junction boxes for all circuits shall be installed on the cable tray above the equipment racks, two feet apart. Circuit wires for each 30 Amp, 208 VAC circuit shall be terminated on a L6 receptacle mounted on an industrial raised cover. The industrial raised cover receptacle combination shall then be mounted on the dual gang box provided for each rack position. Each circuit shall be wired with #10 AWG wire to facilitate higher voltage/amperage should that be necessary in the future. CNM ITS shall provide a floor plan for the

ER/TR indicating footprints for the equipment racks. d) Provide a minimum of one 120 VAC, 20 Amp, duplex convenience outlets evenly spaced every four (4) feet on the walls of the ER. The outlets shall be located 18" above the finished floor. These convenience outlets and any other power receptacles for non-telecom use (security panels, AV

3

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines equipment, etc.) are NOT to be serviced from the sub-panel located in the communications room.

Detailed power requirements may vary per project but use this guidance for planning purposes.

1.1.5

Wall Covering: All walls shall be covered with A/C Grade plywood sheathing, 3/4" thick, 8’0” x 4’0” panels mounted vertically @6” A.F.F., painted with fire retardant paint to match wall color. If walls are not painted, plan on using off-white paint.

1.1.6

Floor Covering: The floor shall be covered with anti-static vinyl tiles.

Five (5) copper grounding tapes shall be distributed evenly beneath the vinyl flooring.

1.1.7

Earth Ground: The ER shall be equipped with a minimum ground bus of

#2 AWG bare copper wire bonded to the building frame and power ground, in accordance with the National Electrical Code (NEC). The

Earth Ground shall be Newton Instrument, Inc.’s Fig. 3056 or equivalent.

The power ground shall meet the Motorola R56 Standard for a Type B facility. The impedance to ground shall be 5 ohms or less. The grounding system shall be tied to the grounding loop system (also 5 ohms or less) provided for the communications tower, if applicable.

1.1.8

Lighting: Overhead fluorescent lighting shall be installed to illuminate a minimum of 100 foot-candles of light on a surface five (5) feet above the floor. The lighting fixture shall not be installed directly above the space reserved for the equipment racks. The light switch shall be located near the entry door. Emergency lighting will be provided within the space to facilitate egress.

SPECIAL NOTE:

In meeting the lighting requirements, DO NOT USE THE

ELECTRICAL SUB-PANEL SPECIFIED UNDER THE POWER

REQUIREMENTS . The lighting load shall be served by panels other than the one located in the ER/TR.

1.1.9

Door: The communications room door shall be sealed for dust proofing.

The door shall swing outward from the communications room. The door

4

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines lock shall be made for CNM ASSA key #APD and also be accessible using card swipe access.

1.1.10

Plenum Space: The ER shall be isolated from the plenum space.

1.1.11

Interface with Plenum Space: A number of 4” or 6” sleeves or cable tray shall be installed, if necessary, to interface the communications room with the plenum/non-plenum space outside the room.

1.1.12

Communications Room Interconnectivity: The ER, if not stacked together with TR’s, shall be interconnected with other communications rooms via cable tray or a number of 4” or 6” conduits. All conduits and cable trays shall be grounded. Coordinate with CNM ITS before considering a non-stacked scenario. a) Racks: 600 pounds per rack with footprint of 2' 0" by 2' 0".

**CNM ITS is to be notified if the estimated rack weight will exceed this value.

2.

CABLE TRAY AND CONDUIT

2.1

Horizontal Cable Distribution System: Standard 12, 18 or 24 inch wide(as appropriate) by 2, 4, or 6 inch deep trough aluminum cable tray shall be installed as horizontal cable raceway above the ceiling on each floor of the building, providing cable run down corridors, and interfacing the ladder cable tray inside the

ER and TR. Cable trays shall be bonded to the ground, in accordance with the

National Electrical Code (NEC).

1.1.13

Weight Requirements: The ER shall be capable of supporting a floor load created by the following equipment:

SPECIAL NOTE:

5

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines

Under no circumstances will any other type of cabling be installed within the cabletray other than telecommunications wiring approved for the use of voice/data networks unless pre-approved by CNM ITS. Furthermore, no cabling shall be attached to the cable tray system which includes trapeze hanger system supporting the tray. Removal costs will not be the responsibility of CNM.

2.2

Conduit For Horizontal Telephone and Data Cabling: A minimum of one inch

(1") diameter EMT conduit shall be provided from the cable tray to EACH office workstation outlet location and terminated on a dual gang, deep box. If modular furniture is installed in the offices, provide one (1) 1-1/2” conduit from the cable tray for every two (2) workstations for telephone and data cabling. The gang box for each workstation shall be located at 18" above the floor and covered with a face plate with eight (8) RJ-45 sockets. The use of 1.25” conduit will be used to all classroom outlets to double gang, deep boxes.

2.3

Entrance Conduits: For new construction plan for a minimum of 4-4” entrance conduits into each new building dedicated for telecommunications only. Each renovation project will require an inspection to determine the current, available entrance conduit capacity. If additional capacity is required, provide four (4) new

4” conduits for telecommunications only. Conduit quantities shown are minimums unless noted otherwise.

2.4

Conduit for Wall-mount Telephone: Provide one (1) each 1" conduit from the cable tray to each wall-mount telephone location. The conduit shall be terminated in a 4-S deep box, located at approximately 48" above the floor (U.N.O).

2.5

Cable Tray Inside ER, Telecom Rooms : Aluminum ladder type cable tray or ladder rack shall be provided for the ER, Telecom Rooms. The size of the cable tray or ladder rack shall be 12" wide by 4" deep (U.N.O.). The bottom of the cable tray shall be located at a height of 7'-6" above the finished floor. Power cable brackets shall be installed directly on the side of the cable tray evenly spaced above the rack. Cable trays shall be bonded to the ground, in accordance with the

National Electrical Code (NEC).

2.6

Vertical Risers : A minimum of one (1) 4” x 16” slot will be used for the vertical riser. For existing facilities, sleeves may be used upon approval by CNM ITS.

NOTES:

6

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines a. Conduit runs shall be no more than 150' without terminating point and the number of 90 o

bends on the conduit run shall be no more than two. b. If more bends are necessary, a pull-box shall be provided at designated locations selected by CNM ITS personnel. Conduits shall be provided with pull-wires and tagged as to the far-end location.

3.

CABLE AND CABLE TERMINATION HARDWARE

This section discusses the general requirements for the backbone and horizontal distribution systems. It is the desire of CNM ITS to use a single manufacturer capable of providing all cable and cable termination hardware and to ensure the complete, installed system is covered under a comprehensive 25 year system warranty on all future projects.

The warranty is to be formally issued by the manufacturer at the completion of the project. The installation contractor must be a manufacturer certified installation firm and must provide a minimum of a 2 year warranty covering workmanship performed at CNM facilities.

3.1

Backbone System : The backbone consists of the inter- and intrabuilding cabling for voice and data systems including fiber optic and high-pair copper cables.

These systems are terminated on designated hardware in the ER/TR.

3.1.1.

Backbone Fiber: Interbuilding (ER to ER) backbone fiber will consist of

48 strands laser optimized singlemode fiber. Intrabuilding (ER to TR, TR to TR)) backbone fiber will consist of a hybrid style bundle including 12 strands of laser optimized 50 micron multimode fiber and 6 strands of singlemode fiber.

3.1.2.

Fiber Termination: Fiber will terminate using SC style connectors on 6 port adapter plates in fiber housings in communications racks. SC style ports will be used on the adapter plates (U.N.O). Fiber jumpers will vary from ST, SC and LC and will usually be procured and installed by CNM

ITS. Fiber housings will be mounted at the top of the rack in all installations.

3.1.3.

Backbone Copper: The interbuilding backbone copper will be sized based on the size of the building being served. CNM ITS will provide the specific pair count required for the interbuilding connectivity. However, the intrabuilding copper riser will be sized to: Need + 100 pairs. Need is based on the actual count estimated for that floor plus an additional 100

7

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines pairs for buffer.

3.1.4.

Backbone Copper Termination: All interbuilding copper cable will terminate on multiple 100 pair protection blocks within the ER. From the protection blocks, a minimum of 100 pairs will be routed to a 48 port

Telco patch panel using amphenol connectivity. The riser cables will be routed up to the TR(s) and will terminate on 110 style termination blocks on the wall. A minimum of 100 pairs will be routed to a 48 port Telco patch panel using amphenol connectivity. If additional pairs are required, additional patch panels may be added.

3.2

Horizontal System

The horizontal system is composed of the ER/TR equipment rack or cabinet used to house the termination panels and wire management, the workstation outlet hardware including the faceplate and modular jacks, and the cable itself.

3.2.1 Equipment Rack: All racks will be full height, black equipment racks with predrilled EIA/TIA hole spacing. The rack must be modular to expand from a two post to a four post configuration. The rack must have an integral 6” channel as part of the frame.

3.2.2 Wire Management: All racks will be equipped with 4” x 6” vertical wire management installed back to back with solid covers to be installed on both sides of the rack. If multiple racks are ganged together, butt the frame of one rack up against the wire management of the adjoining rack.

Horizontal wire management will consist of 2 rack unit models with fingers and covers on the front and a mounting bar on the rear. Wire management on the plywood covered walls will use D-Ring style management with all rings mounted in straight lines.

3.2.3 Patch Panels: All horizontal cabling will terminate on patch panels in racks within the ER/TR. The patch panels will consist of 48 port, Category

6 rated panels with 110 style termination on the rear. The panels will alternate with the wire management in the rack.

3.2.4 Telco (Voice) Patch Panels : Dedicated patch panels for voice connectivity will consist of 48 port, Category 3 rated panels with RJ-45 ports on the front and amphenol connectors on the rear. Verify with CNM ITS to determine quantity of pairs to be terminated (1 or 2 pairs per port).

3.2.5 Horizontal Cabling: All cabling will be Blue, Category 6, Plenum-rated,

4-pair UTP cable regardless of Plenum environment . The quantity of

8

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines cables routed to each outlet is dependent on the type of outlet being served:

Office Outlet: 3 cables

Classroom Outlet: 4 cables

Wireless Outlet: 2 Cables

Wall Phone Outlet: 2 Cables (One left coiled in ceiling above)

3.2.6 Outlets: Each outlet will be equipped with the specified faceplate, inserts and color as shown in the table below

Office Outlet: 4-pos. Faceplate, three (3) Blue RJ-45 Inserts/One Blank

Classroom Outlet: 4-pos. Faceplate with three (4) Blue RJ-45 Inserts

Wireless Outlet: 2-pos. Faceplate with two (2) Blue RJ-45 Inserts

Wall Phone Outlet: 1-pos. Faceplate with One (1) Blue RJ-45 Insert

4.

OUTSIDE PLANT REQUIREMENTS

The following are general requirements for outside plant construction to be implemented on any new or renovation projects. No direct bury cabling is acceptable. As a general rule: All OSP cabling will be installed underground in conduit unless strictly unavoidable.

1.1.

Underground Conduit: Conduit systems shall adhere to TIA/EIA 569B standards, TIA/EIA 758 standards and shall accommodate the cabling requirements of TIA/EIA 568-B1, 568-B2 and 568 B-3 standards. Unless otherwise specified, all underground communications conduit shall be minimum 4 inch, schedule 40 PVC, buried a minimum of 24 inches, measured from the top of the conduit below finished grade. Warning tape is to be installed between 12”-

18” below the finished surface. All bends 45 degrees and larger shall be Rigid

Galvanized Steel (RGS) sweeps, 12 times the conduit diameter, or 48 inch radius, double wrapped with 10 mil PVC tape. Conduit ends shall be capped when work is in progress. RGS sweeps terminating in pull boxes shall be plugged. Mandrel testing of newly installed conduit systems is mandatory and to be witnessed by a member of CNM ITS staff. If the mandrel test fails, the Contractor shall repair or replace the affected conduit and re-test at no cost to CNM. All conduits not occupied by innerduct and tracer wire shall have an un-spliced, unknotted 2500 pound test (22 AWG) detectable mule tape installed and secured with 4 feet of slack at each pull box or termination point. Conduit must be installed in 20’ sections with no bends within 20’ of a manhole or handhole. Maximum linear

9

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines conduit run is limited to 600 feet between manholes and 300 feet for handholes.

Discount maximum length with 100’ deduction per 90 degree bend and no more than 180 degrees of accumulated bends in run.

1.2.

Tracer Wire: Tracer wire (also known as locating wire) is being used more frequently by utility companies. Tracer wire is buried alongside when PVC conduit and fiber optic lines are installed underground, to assist in locating them for service and repairs. Tracer wire is to be installed in every new conduit run and will terminate within each manhole/handhole. The tracer wire shall be 12 AWG with HDPE sheath. Recommend Copperhead Reinforced Tracer Wire or equivalent.

1.3.

Manholes/Handholes : Manholes must be sized to accommodate a minimum of 8 conduits per side with traffic rated cover. Handholes are limited to maximum number of 6 conduits per side with traffic rated cover. All cabling passing through manhole/handhole must be linear in/out of box (Type A) with no 90 degree turns executed in the box. All direction changes must occur in conduit outside the box.

All penetrations into the box must be properly sealed after pull rope is installed.

A drain shall be provided in the bottom of each manhole and this drain should be connected to the storm drainage system if possible. Otherwise, provisions shall be made to install the manhole on a base of 6" of crushed stone or gravel to facilitate the drainage if no connection to the storm system is available.

A 3/4" hole shall be drilled thru the floor, 4" from the wall and a 5/8" X 8' ground rod shall be driven thru the hole until a minimum of 4"/maximum of 6" of the rod is protruding into the manhole. The ground rod shall be driven in the ground before the top section of the manhole is installed. The ground rod shall then be attached to the copper bonding ribbon by way of a #6 solid copper ground wire.

1.4.

Aerial Installations – Pole to Pole, Pole to Building, Building to Building :

Cabling to be installed from pole to pole and pole to building will follow industry standard methods and techniques in regards to attachment and location on pole

(standard hierarchy from top to bottom is power (Primary), power (Secondary), telephone, CATV and special applications such as this). Minimum make-ready

(span droop) distances must be maintained to ensure vehicle/rail clearance is maintained. Pole access must first be approved by pole owner prior to any attachment being made. Proof of approval for each pole must be provided to

CNM ITS for review. Maximum distance between poles is 300 feet. Use of steel strand for attaching high-pair copper cable is required. Use of messenger style cable with integral steel strand in/on jacket is acceptable for fiber optic, coax or

10

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

Central New Mexico Community College

Information Technology Services (ITS)

Communications Systems Facility and

Cabling Infrastructure Design Guidelines twisted pair cables. Under no circumstances should any cable be installed without strain relief via messenger or steel strand.

Attachment to poles must use strain relief loop in cable to allow for expansion/contraction. Attachment to buildings may be roof mount or side mounted. For roof mounted applications use minimum 2-inch weatherhead and sleeve. Verify with CNM ITS the location of the penetration and then coordinate with CNM Facilities any roof warranty issues that may require the penetration to be performed by others. Under no circumstances will any penetrations to any building be performed without proper CNM ITS approval first. Attachment to the sides of buildings must use proper attachment technique. Penetration sleeve must be a minimum 2 inch sleeve angled downward from inside to outside to prevent rain/snow penetration. Cable must loop below lowest point of exterior sleeve before entering the sleeve. Sleeve must enter J-box w/cover on the interior before continuing into the ceiling/room space. Cable must transition from outside plant constructed cable to inside plant cable within 50 feet of penetration unless installed in conduit.

1.5.

Aerial Installations – Pole to Ground: Cabling that must transition from aerial to underground must have a service loop at the pole dead-end prior running down the pole. The cable should run down the pole on the opposite side of oncoming traffic when possible. The cabling must attach to the pole a minimum of every 24 inches using galvanized two hole straps and be run in a straight line down to the conduit stub up on the pole. The conduit must stub 12 inches above finished ground level. It is recommended to install a riser guard from the ground level to

~6 feet up the pole to prevent tampering. The guard should cover the conduit stub.

11

Use, duplication and/or distribution of this document and all other associated CNM ITS documents is prohibited without the express written approval by CNM ITS department or other preauthorized authority of CNM.

Version 4.0 12 Dec 2007

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS

PART 1 - GENERAL

1.1 SCOPE OF WORK

A.

A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of conduit sleeves as described on the Drawings and/or required by these specifications.

1.2

RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

H.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

I.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

J.

Division 27, Section 271543 Communications Faceplates and Connectors.

1.3

SUMMARY

A.

Section Includes:

1.

Communications equipment coordination and installation.

2.

Sleeves for pathways and cables.

3.

Sleeve seals.

4.

Grout.

5.

Common communications installation requirements.

1.4

A.

B.

GLOSSARY

ANSI American National Standards Institute

ASME American Society of Mechanical Engineers

COMMON WORK RESULTS FOR COMMUNICATIONS

Version 12DEC2007

270500 - 1

G.

H.

I.

C.

D.

E.

F.

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

ASTM American Society for Testing Materials

BFU Board of Fire Underwriters

BICSI Building Industry Consulting Services International

CSA Canadian Standards Association

DEC Department of Environmental Conservation

EIA Electronics Industry Association

EPDM: Ethylene-propylene-diene terpolymer rubber.

J.

K.

L.

FCC Federal Communications Commission

Q.

R.

S.

M.

N.

O.

P.

IEEE

ISD

NEC

Institute of Electrical and Electronics Engineers

Information Systems Division

ISO International Standards Organization

LB Electrical Elbow with accessible coverplate

National Electrical Code

T.

U.

V.

W.

X.

Y.

Z.

NESC National Electrical Safety Code

NFPA National Fire Protection Association

OSHA Occupational Safety and Health Administration

RUS

TIA

Rural Utility Service (formerly REA)

Telecommunications Industry Association

UFBC Uniform Fire Prevention and Building Code

UL Underwriter’s Laboratories, Inc.

1.2

A.

DEFINITIONS

Throughout the specifications, abbreviations may be used. The following are brief definitions of many of those abbreviations.

1.

Approved / Approval Written permission to use a material or system.

2.

As Called for Materials, equipment including the execution specified/shown in the Specifications.

COMMON WORK RESULTS FOR COMMUNICATIONS

Version 12DEC2007

270500 - 2

3.

Code Requirements

4.

Concealed

5.

Exposed

6.

Final Acceptance

7.

Furnish

8.

Furnished by Others

9.

Inspection

10.

Install

11.

Listed

12.

Or Approved Equal

13.

Owner's Representative

14.

Provide

15.

16.

Replace

17.

Review

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

Minimum requirements.

Work installed in pipe and duct shafts, chases or recesses, inside walls, above ceilings, in slabs or below grade.

Work not identified as concealed.

Owner acceptance of the project from Contractor upon certified by Owner’s Representative.

Supply and deliver to installation location.

Receive delivery at job site or where called for and install.

Visual observations by Owner or Owner’s Representative.

Mount and connect equipment and associated materials ready for use.

Refers to classification by a standards agency.

Approved equal or equivalent as determined by

Owner or Owner’s Representative.

Design professional or Consultant representing the Owner.

Furnish, install and connect ready for use. ment to new locations; then clean, test and install ready for use.

Remove and provide new item.

A general contractual conformance check of specified products.

1.5

SUBMITTALS

A.

Product Data: For sleeve seals.

1.6

COORDINATION

A.

Coordinate arrangement, mounting, and support of communications equipment:

COMMON WORK RESULTS FOR COMMUNICATIONS

Version 12DEC2007

270500 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.

2.

To provide for ease of disconnecting the equipment with minimum interference to other installations.

3.

To allow right of way for piping and conduit installed at required slope.

4.

So connecting pathways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.

B.

Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.

C.

Coordinate location of access panels and doors for communications items that are behind finished surfaces or otherwise concealed. Access doors and panels are specified in

Division 08 Section "Access Doors and Frames."

D.

Coordinate sleeve selection and application with selection and application of firestopping specified in Division 07 Section "Penetration Firestopping."."

PART 2 - PRODUCTS

2.1

SLEEVES FOR PATHWAYS AND CABLES

A.

Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.

B.

Sleeves for Rectangular Openings: Galvanized sheet steel.

1.

Minimum Metal Thickness: a.

For sleeve cross-section rectangle perimeter less than 50 inches (1270 mm) and no side more than 16 inches (400 mm), thickness shall be 0.052 inch (1.3 mm). b.

For sleeve cross-section rectangle perimeter equal to, or more than, 50 inches

(1270 mm) and 1 or more sides equal to, or more than, 16 inches (400 mm), thickness shall be 0.138 inch (3.5 mm).

2.2

SLEEVE SEALS

A.

Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and pathway or cable.

2.3

MANUFACTURERS

COMMON WORK RESULTS FOR COMMUNICATIONS

Version 12DEC2007

270500 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:

1.

Available Products: Subject to compliance with requirements, products that may be incorporated into the Work include, but are not limited to, products specified.

2.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.

3.

Sealing Elements: interlocking links shaped to fit surface of cable or conduit. Include type and number required for material and size of pathway or cable.

4.

Pressure Plates: Include two for each sealing element.

5.

Connecting Bolts and Nuts: Of length required to secure pressure plates to sealing elements. Include one for each sealing element.

2.4

GROUT

A.

Nonmetallic, Shrinkage-Resistant Grout: ASTM C 1107, factory-packaged, nonmetallic aggregate grout, noncorrosive, nonstaining, mixed with water to consistency suitable for application and a 30-minute working time.

2.4 FIRE STOPPING

A.

B.

C.

Fire stopping for openings through fire-rated and smoke-rated walls and floor assemblies shall be listed or classified by an approved independent testing laboratory for "Through-

Penetration Fire Stop Systems." The system shall meet the requirements of "Fire Tests of

Through-Penetration Fire Stops" designated ASTM E814.

Inside of all conduits, the fire stop system shall consist of dielectric, water resistant, nonhardening, permanently pliable/re-enterable putty along with the appropriate damming or backer materials (where required). The sealant must be capable of being removed and reinstalled and must adhere to all penetrants and common construction materials and shall be capable of allowing normal wire/cable movement without being displaced.

All conduit and sleeve openings used by the Contractor shall be waterproofed or fireproofed in compliance with State and Local Building and Fire Codes. Strict adherence to National,

State, and Local Fire Codes, particularly fire stopping will be required.

D.

The Contractor shall patch all openings remaining around and inside all conduit, sleeves and cable penetrations to maintain the integrity of any fire rated wall, ceiling, floor, etc. The fire stop system shall consist of a dielectric, water resistant, non-hardening, permanently pliable/re-enterable putty along with the appropriate damming materials (where required). The sealant must be capable of being removed and reinstalled and must adhere to all penetrants

COMMON WORK RESULTS FOR COMMUNICATIONS

Version 12DEC2007

270500 - 5

E.

F.

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) and common construction materials and shall be capable of allowing normal wire/cable movement without being displaced.

All building conduits and sleeves installed and/or used under this Specification shall be fire stopped, or re-fire stopped, upon cable placement through such passageways.

Manufacturer's recommended installation standards must be closely followed (i.e. minimum depth of material, use of ceramic fiber and installation procedures).

PART 3 - EXECUTION

3.1

COMMON REQUIREMENTS FOR COMMUNICATIONS INSTALLATION

A.

Comply with NECA 1.

B.

Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C.

Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.

D.

Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both communications equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

E.

Right of Way: Give to piping systems installed at a required slope.

3.2

SLEEVE INSTALLATION FOR COMMUNICATIONS PENETRATIONS

A.

Communications penetrations occur when pathways, cables, wireways, or cable trays penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.

B.

Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.

C.

Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.

D.

Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.

COMMON WORK RESULTS FOR COMMUNICATIONS

Version 12DEC2007

270500 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

E.

Cut sleeves to length for mounting flush with both surfaces of walls.

F.

Extend sleeves installed in floors 4 inches (100 mm) above finished floor level.

G.

Size pipe sleeves to provide 1/4-inch (6.4-mm) annular clear space between sleeve and pathway or cable, unless indicated otherwise.

H.

Seal space outside of sleeves with grout for penetrations of concrete and masonry

1.

Promptly pack grout solidly between sleeve and wall so no voids remain. Tool exposed surfaces smooth; protect grout while curing.

I.

Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and pathway or cable, using joint sealant appropriate for size, depth, and location of joint. Comply with requirements in Division 07 Section "Joint Sealants".

J.

Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pathway and cable penetrations. Install sleeves and seal pathway and cable penetration sleeves with firestop materials. Comply with requirements in Division 07

Section "Penetration Firestopping."

K.

Roof-Penetration Sleeves: Seal penetration of individual pathways and cables with flexible boot-type flashing units applied in coordination with roofing work. Prior to installation, verify existing warranty of roof with CNM ITS and Plant Facility personnel.

L.

Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel pipe sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch (25-mm) annular clear space between pipe and sleeve for installing mechanical sleeve seals. Ensure installed sleeve is sloped towards outside to prevent rain/snow water seepage through pipe.

M.

Underground, Exterior-Wall Penetrations: Install cast-iron pipe sleeves. Size sleeves to allow for 1-inch (25-mm) annular clear space between pathway or cable and sleeve for installing mechanical sleeve seals.

3.3

SLEEVE-SEAL INSTALLATION

A.

Install to seal exterior wall penetrations.

B.

Use type and number of sealing elements recommended by manufacturer for pathway or cable material and size. Position pathway or cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between pathway or cable and sleeve.

Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.

COMMON WORK RESULTS FOR COMMUNICATIONS

Version 12DEC2007

270500 - 7

3.4

A.

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

FIRESTOPPING

Fire stopping for Openings through Fire and Smoke Rated Wall and Floor Assemblies:

1.

2.

3.

4.

Provide materials and products listed. The system shall meet the requirements of "Fire Tests of Through-Penetration Fire Stops" designated ASTM E814. To be used inside all conduits and sleeves. Caulk on exterior of conduit penetration.

Provide fire stop system seals at all locations where conduit, fiber, cable trays, cables/wires and similar utilities pass through or penetrate fire rated wall or floor assembly. Provide fire stop seal between sleeve and wall for drywall construction. a)

The minimum required fire resistance ratings of the wall or floor assembly shall be maintained by the fire stop system. The installation shall provide an air and watertight seal.

The methods used shall incorporate qualities that permit the easy removal or addition of conduits or cables without drilling or use of special tools. The product shall adhere to itself to allow repairs to be made with the same material and permit the vibration, expansion and/or contraction of any items passing through the penetration without cracking, crumbling and resulting reduction in fire rating. Typical rating: floors - 3 hours b) c) corridor walls - 2 hours offices - ¾ hour

5.

d) smoke partitions - ¾ - 1 hour

Provide fire stop pillows for existing cable tray penetrations through firewalls.

END OF SECTION 270500

COMMON WORK RESULTS FOR COMMUNICATIONS

Version 12DEC2007

270500 - 8

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 270526 - GROUNDING AND BONDING FOR COMMUNICATION

SYSTEMS

PART 1 - GENERAL

1.1 SCOPE OF WORK

A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of grounding and bonding infrastructure as described on the Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

H.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

I.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

J.

Division 27, Section 271543 Communications Faceplates and Connectors.

1.3 SUBMITTALS

A.

Product Data: For features, ratings, and performance of each component specified.

B.

Shop Drawings:

1.

Component List: List manufacturer, part number, and quantity of each component.

1.4 GLOSSARY

A.

TBC (Telecommunications Bonding Conductor) - The bonding conductor installed from the building’s grounding electrode system to the TMGB. This bonding conductor shall be sized the same as the TBB.

GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Version 12DEC2007

270526 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

BC (Bonding Conductor) – Typical bonding conductor installed from any telecommunications grounding bus bar (TMGB or TGB) to telecommunications equipment and/or raceway.

C.

TBB (Telecommunications Bonding Backbone) – Continuous bonding conductor installed from the TMGB to the furthest telecommunications room. All TGBs shall attach to the

TBB.

D.

TMGB (Telecommunications Main Grounding Busbar) – The main telecommunications grounding bar located where the Outside Plant cables enter the telecommunications room.

E.

TGB (Telecommunications Grounding Busbar) – The telecommunications grounding bar located in every telecommunications room that does not contain the TMGB.

1.5 DEFINITIONS

A.

Throughout the specifications, abbreviations may be used. The following are brief definitions of many of those abbreviations.

1.

2.

Approved / Approval

As Called for

Written permission to use a material or system.

Materials, equipment including the execution specified/shown in the Specifications.

3.

4.

Code Requirements

Concealed

Minimum requirements.

Work installed in pipe and duct shafts, chases or recesses, inside walls, above ceilings, in slabs or below grade.

5.

6.

7.

8.

9.

10.

11.

12.

Exposed

Final Acceptance

Furnish

Furnished by Others

Inspection

Install

Listed

Or Approved Equal

Work not identified as concealed.

Owner acceptance of the project from Contractor upon certified by Owner’s Representative.

Supply and deliver to installation location.

Receive delivery at job site or where called for and install.

Visual observations by Owner or Owner’s

Representative.

Mount and connect equipment and associated materials ready for use.

Refers to classification by a standards agency.

Approved equal or equivalent as determined by

Owner or Owner’s Representative.

13.

Owner's Representative Design professional or Consultant representing the Owner.

14.

Provide Furnish, install and connect ready for use.

GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Version 12DEC2007

270526 - 2

15.

16.

17.

Relocate

Replace

Review

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

Disassemble, disconnect and transport equipment to new locations; then clean, test and install ready for use.

Remove and provide new item.

A general contractual conformance check of specified products.

PART 2: PRODUCTS

2.1 GROUNDING BUSBARS

All references to manufacturer should be considered as minimum performance criteria or other approved equal per submittal requirements in SOW may be submitted for CNM ITS approval.

A.

Telecommunications Main Grounding Busbar (TMGB)

1. Panduit #GB4B0612TPI-1 ground busbar with busbar insulators.

B.

Telecommunications Grounding Busbar (TGB)

1. Panduit #GB2B0312TPI-1 ground busbar with busbar insulators.

2.2 GROUNDING CONNECTIONS

A.

Grounding conductor terminations (lugs) shall be listed compression type, two hole, long barrel with window lug with a minimum of (2) crimps. Panduit #LCC6-14AW-L or equal. Crimp according to manufacturer’s recommendation.

B.

Grounding conductor terminations (HTAP) shall be listed compression type with a minimum of (2) crimps. Panduit HTAP kit #HTWC6-6-1 or equal. Crimp according to manufacturer’s recommendation.

2.3 BONDING CONDUCTORS

A. Cable Tray Bonding Conductor

1. Stranded green #6 AWG insulated bonding jumper (12” max) with appropriate lugs, or manufactured braided copper grounding jumper equal to B-Line #CAM-

GJ, T&B #BD12, OZ/Gedney type “FB” or Mono-Systems.

B. Equipment Frame Grounding Strip

1. Panduit #RGS134-1 Telecommunications Rack Grounding Strip.

C. Telecommunications Bonding Conductor (TBC)

1.

Green insulated copper bonding conductor, size as required by NEC.

2.

The TBC shall be, as a minimum, the same size as the TBB.

D. Telecommunications Bonding Backbone (TBB)

GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Version 12DEC2007

270526 - 3

1. Green insulated copper conductor, minimum size of No. 6 AWG. The TBB shall be sized at 2 kcmil per linear foot of conductor length up to a maximum size of

3/0 AWG. Insulation shall meet fire ratings of its pathway.

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

Table 1

Sizing of the TBB

TBB length (ft) TBB AWG Size

Less than 13 6

14-20 4

21-26

27-33

34-41

3

2

1

42-52

53-66

1/0

2/0

Greater than 66 3/0

PART 3: EXECUTION TELECOMMUNICATIONS INSTALLATION

Prior to performing any work on the building grounding system, CNM ITS requires that the building electrode system be verified to be properly grounded per NEC guidelines. Failure to verify the building grounding system may cause injury or death.

A. Installation of the TMGB

1.

Install the TMGB at the bottom of plywood backboard near the outside plant entrance conduits in the “BDF”.

2.

TMGB shall be installed so that the TBC for telecommunications is as short as possible and maintains a horizontal or downward path to the building’s grounding electrode system, where possible.

B. Installation of the TBC for Telecommunications

1.

TBC shall be installed in continuous 3/4” PVC conduit. Install in EMT conduit only if the path passes through a plenum area. EMT conduit must be bonded to the

TBC at both ends of the conduit.

2.

TBC shall maintain a horizontal or downward path from the TMGB to the building’s grounding electrode system. No bend shall form an included angle of more than 90 degrees or have a radius of less than 6”.

C. Installation of the TGB

1.

Install the TGB at the bottom of plywood backboard near the TBB.

GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Version 12DEC2007

270526 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

TGB shall be installed so that the bonding conductor connecting the TGB to the

TBB is as short as possible and maintains a horizontal or downward path to the

TBB.

3.

Install a stranded bonding conductor (same size as the TBB) from the TGB to the TBB. This wire shall be terminated on the TGB end with the Panduit twoholed compression type lug and terminated on the TBB end with the Panduit

HTAP kit.

D. Installation of the TBB

1.

Install Green insulated copper grounding conductor (refer to 2.3.D for conductor size) from the TMGB to the furthest telecommunications room.

2.

Conductors shall be installed in continuous 3/4” PVC conduit until it enters a telecommunications room. Where the TBB pathway passes through a plenum area, the installation of EMT conduit is required and must be bonded on each end to the

TBB.

3.

Each TBB shall be continuous to the furthest IDF.

4.

The end of the TBB shall be terminated on the TGB of the furthest telecommunications room.

5.

TBB shall maintain a horizontal or downward path to the TMGB. No bend shall form an included angle of more than 90 degrees or have a radius of less than 6”.

E. Grounding of Cable Tray

1.

Install Green #6 AWG bonding jumper (12” max) with Panduit #LCC6-14JAW-L two-hole lugs at each cable tray joint or install manufactured braided copper grounding jumper equal to B-Line #CAM-GJ, T&B #BD12, OZ/Gedney type

“FB” or Mono-Systems.

2.

Install Green #6 AWG grounding conductor with Panduit #LCC6-14JAW-L twohole lugs from side of cable tray down to TMGB or TGB. Maintain a horizontal or downward path from the cable tray to the TMGB or TGB. Drill and tap side of cable tray (for appropriate size bolt, ¼” x 20 min.), making sure that bolt does not extend into wire management part of tray.

F. Grounding of Equipment Frame

1.

Install Panduit #RGS134-1 Equipment Frame Grounding Strip on back side of all equipment frames. Maintain a horizontal or downward path of the bonding conductor from the Equipment Frame Grounding Strip to the TMGB or TGB.

No bend shall form an included angle of more than 90 degrees or have a radius of less than 6”. a.

Where only one equipment frame is located within a room, install a #6

AWG bonding conductor from the equipment frame grounding strip to the TMGB or TGB terminated with Panduit #LCC6-14JAW-L two-hole lugs. b.

Where multiple equipment frames are located within a room, install a bonding conductor (same size as the TBB) from the TMGB or TGB to

GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Version 12DEC2007

270526 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) the cable tray above the equipment frames. Route the bonding conductor horizontally on the “L” brackets of the cable tray. Install (1) #6 AWG green bonding conductor from each equipment frame grounding strip to the bonding conductor above the equipment frames. Attach the #6 AWG cable to the equipment frame grounding strip using Panduit #LCC6-

14JAW-L two-hole lugs. Attach opposite end of #6 AWG to the bonding conductor above the equipment frames using Panduit HTAP kit

#HTWC6-6-1 or equal.

2.

Install Chatsworth #11268-001 “L” brackets on cable tray for routing of the bonding conductors for equipment frame grounding. Install “L” bracket every 12”.

Fasten bonding conductor on each “L” bracket using wire ties.

G. Installation of Bonding Conductors

1.

Shall be routed so to minimize bends and length.

2.

Shall be a minimum of #6 AWG.

3.

Bonding Conductors shall maintain a horizontal or downward path to the TMGB or TGB. No bend shall form an included angle of more than 90 degrees or have a radius of less than 6”.

4.

Use Panduit HTAP kit to bond the TBB to the TMGB or TGB.

END OF SECTION 270526

GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Version 12DEC2007

270526 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 270528 - PATHWAYS FOR COMMUNICATIONS SYSTEMS

PART 1 - GENERAL

1.1 SCOPE OF WORK

A.

The work required under this section consists of providing conduits, boxes, raceways, etc., for telecommunications wiring included in this project. Telecommunications wiring includes cables for Data, Voice, Video, Audio, Security and future signal requirements.

B.

The location at which all new telecommunications wiring will terminate is called a Telecom

Outlet (TO). There are several styles of outlets: 1) New construction, 2) Existing construction typical, 3) Existing construction variations, 4) Telephone (Voice) only and 5) Data only.

C.

Furnish and install split channel raceway and outlet boxes as specified in the Drawings and as specified herein.

D.

Furnish and install conduit stubs in walls and floors for cable routes.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

H.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

I.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

J.

Division 27, Section 271543 Communications Faceplates and Connectors.

1.3 SUBMITTALS

A.

Product Data: For features, ratings, and performance of each component specified.

B.

Submit manufacturer’s instructions for storage, handling, protection, examination, preparation, operation, and installation of products. Include application conditions or limitations of use stipulated by any product testing agency. Submit for the following:

1.

Wall Boxes

2.

Raceway

3.

Conduit

4.

Conduit Bushings

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270528 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

C.

Shop Drawings:

1.

Component List: List manufacturer, part number, and quantity of each component.

2.

Include dimensioned plan and elevation views of equipment rooms, labeling each individual component. Show raceway assemblies, method of field assembly, workspace requirements, and access for cable connections.

PART 2 - PRODUCTS

2.1 TELECOM OUTLETS (TO)

A.

New construction TO consists of one (1) 4-11/16" square by 2-1/8" deep flush mounted box.

Each outlet box shall have a EMT conduit stubbed above the drop ceiling or extended into the hallway cabletray. Conduits size is as follows:

Œ

Œ

Œ

For Outlets with 3 or less cables, use a 1” EMT conduit

For Outlets with 3-6 cables, use a 1.25” EMT conduit

For all other sizes, calculate fill ratio at 40% for proper sized conduit

B.

Existing surface-mounted construction TO typically consists of surface-mounted Wiremold raceway including base, cover, end fitting, entrance end fitting, and (2) 1" EMT conduits stubbed out top of entrance end fitting to above ceiling or out to nearest hallway distribution system. Size of the raceway is site dependent based on number of conductors to be installed.

C.

The intent of the installation of the TOs which consist of the Wiremold raceway is as follows:

1.

Where ceilings are accessible, the raceway and entrance end fitting shall extend above the ceiling and the conduits installed above the ceiling in the room to the nearest hallway distribution system.

2.

Where ceilings are partially accessible, or if the Drawings and/or Specifications indicate installation of access panels, the raceway shall extend above the ceiling and the conduits installed above the ceiling in the room to the nearest hallway distribution system.

3.

Where ceilings are inaccessible or no ceilings exist, the raceway shall extend up as close to the ceiling as practical to allow installation of conduits as high as possible to the nearest hallway distribution system.

2.2 HORIZONTAL DISTRIBUTION SYSTEMS

A.

Conduit System (Renovations only, where conduit exists)

1.

Provide conduits secured to wall above corridor ceilings as shown on the Drawings or as specified herein for installation of telecommunications cables. Any exposed conduit

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270528 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) shall be painted except conduit above suspended ceilings or in mechanical, electrical or telecommunication rooms. Color to match that of surface installed upon or as directed by CNM ITS. Coordinate with CNM ITS prior to painting.

2.

Corridor conduits shall be 4" EMT, furnished in 10 foot lengths wherever possible, with no sharp edges, reamed as necessary, evenly supported at two locations per 10 foot section spacing. Conduits shall be sized and quantified to account for handling cables in all TO conduits at 40% fill back to the TR and/or ER rooms. Verify size with

CNM ITS prior to installation. Bushings and/or connectors on ends of EMT are required.

3.

All conduits shall be installed stacked and attached to walls unless conditions exist which prohibit this type of installation. When this condition exists, mount conduits side-by-side supported with 3/8” rod attached to building structure utilizing unistrut channel to form a trapeze. Double nut the top and bottom at the unistrut. Utilize conduit clamp to secure conduits to unistrut.

4.

Provide measured pull line in each conduit rated at 1200 lbs. minimum. Increments must be in 12” steps.

5.

Grounding of conduits is not required per NEC #250-33, Exception No. 2.

6.

Provide restorable fire stops inside and around conduits as recommended by UL1479 or ASTM E814 for all conduits penetrating fire-rated construction. Fire rated construction to be verified with CNM ITS. See Section 270500 for more firestopping information.

B.

Corridor Cable Tray System

1.

Complete wall mounted or suspended aluminum cable tray system and necessary accessories shall be provided as shown on plans. Install entire cable tray system in accordance with manufacturer’s minimum installation practices and all local governing codes.

2.

Coordinate installation of cable tray with other trades to allow a minimum of 12” above, 12” in front, and 12” below of clearance from piping, conduits, ductwork, etc.

Allowance must be provided for access to the tray with reasonable room to work.

Obstructions to the tray must be minimized and cannot block more than 6 feet of the tray at any point in the run.

3.

Submittal drawings, in the form of 8 ½”x 11” catalog cut sheets, shall be provided for the following items: cable tray, fittings, accessories and load data.

4.

Cable tray shall not be loaded beyond 60% of manufacturer’s recommended load capacity.

5.

Install wall mounted cable tray on both sides of hallway as shown on drawings and where applicable.

6.

Where a new cable tray distribution system encounters a wall, install sufficient 4”

EMT sleeves through the wall so cabling does not exceed 20% fill.

7.

Where cable tray is exposed below ceiling, install the appropriate solid bottom inserts to conceal cables.

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270528 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

8.

Install cable tray dropouts where large quantities of cables exit the distribution system.

9.

Cable tray must be sized to facilitate sufficient growth capacity for migration cable plant to coexist in same tray as existing cable plant, wherever possible.

10.

Manufacturer of cable tray in corridors and telecom rooms shall be: a. Mono-Systems, Inc. b. B-Line Systems, Inc. c. Hubbell d. or approved alternate per submittal requirements in contract SOW.

C.

Telecommunication Room Cable Tray System

1.

TR cable tray shall completely wrap all walls within the room. Cable tray shall extend over all equipment frames.

2.

Cable tray shall be a minimum width of 2” high x 12” wide. Cable tray may be sized upwards if fill ratio requirements need to be met based on cable quantities.

3.

Manufacturer of tubular ladder type cable tray in telecommunication rooms shall be

Homaco or Chatsworth.

4.

Cable tray shall be 12 inch cable runway. Fabricated of 3/8-inch x 1-1/2-inch x .065inch wall rectangular steel tubing, 1/2-inch x 3/8-inch x 1-1/2-inch

5.

Rectangular steel tubing cross members welded at 12-inch intervals. Finish in gray enamel. Homaco, Inc., Part Number TR10-12 or equivalent. a.

12-inch Wall Angle Assembly Kit – Homaco, Inc., Part Number P12840H or equivalent. b.

3-inch Channel Rack–To-Runway Mounting Plate - Homaco., Part Number

JP0912 or equivalent. c.

End Closing Tube - Homaco Inc., Part Number P413512HT or equivalent. d.

Corner Clamp - Homaco Inc., Part Number P403473H or equivalent (2 required per End Closing Tube to complete assembly).

2.3 STATION CONDUITS

A station conduit is defined as a conduit that originates at the TO and rises within the walls or is exposed from Wiremold raceway and extends up into the drop ceiling or over to the hallway distribution system.

A.

Provide station conduits from TOs to above the drop ceiling or extend over to the hallway distribution systems consisting of 1” EMT minimum or appropriate size as shown on the

Drawings or as specified herein for installation of telecommunications cables.

B.

Provide an insulating press fit bushing on all telecommunications conduits including interconnecting nipples and stub to distribution system. To prevent conflicts with other cables or conduits to cable tray, the conduit shall be stubbed not less than 6" above or below conduit/cable tray center line. Where space permits, every effort shall be made to

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270528 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) bend station conduits down such that the flow of installed cables promotes the minimum length back to the TR and the least amount of bends in the cables. Bushings must be rated to be used in an environmental air handling space (Plenum).

1.

Manufacturer of insulating bushing on all telecommunication conduits shall be

Arlington or approved alternate equal.

C.

Provide measured pull line in 12” increments in each empty conduit to hallway distribution system.

D.

Indelibly mark station conduit at hallway distribution end with Room # that conduit serves.

E.

The use of 90 degree electrical pulling elbows is prohibited.

F.

Do not include more than two 90 degree bends between pulling points when installing station conduit runs. If the path of the station conduits requires more than 180 degrees of total bends, installation of an appropriate sized junction box is required. See section 2.4 for junction box requirements.

G.

Place an appropriate sized junction box in each individual station conduit run that exceeds

100 feet in length.

H.

The use of a third bend in a conduit is only acceptable if:

1.

The total conduit run is reduced by 15%.

2.

The conduit size is increased to the next trade size.

3.

One of the bends is located within 12” of the cable feed end.

2.4 JUNCTION BOX REQUIRMENTS FOR STATION CONDUITS

A.

If the station conduit route exceeds the 180 degree of total bends limitation, an appropriate sized junction box is required within a straight section of the conduit run.

B.

Each station conduit run requires a separate junction box. The sharing of a junction box by multiple conduits is prohibited.

C.

A junction box shall not be used in place of a bend. All junction boxes in station conduit paths shall be installed within a straight section of the conduit run.

2.5 SERVICE ENTRANCE CONDUITS

A.

Minimum of (4) 4” IMC conduits shall be installed from the nearest utility tunnel on outside of the building as shown on the Drawings. Consult with CNM ITS on required telecommunication service to determine additional conduit requirements. Terminate entrance conduits entering ER rooms from below grade to extend 4" above finished floor.

Location of entrance conduits shall be within 12” of room corners.

B.

Terminate entrance conduits entering ER rooms from above ceiling height to extend 4" below finished ceiling or 12” above cable tray.

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270528 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

C.

Terminate entrance conduits entering an ER rooms from below ceiling height to extend 4" into the room.

D.

Entrance conduits shall be continuous into the building and to the ER. Securely fasten all entrance conduits to the building to withstand any cable placing operation. Do not include more than two 90 degree bends between pulling points when installing entrance conduits.

E.

On exterior wall penetrations, seal both sides of the wall around outside of conduit with hydraulic cement to prevent water from entering the building. Seal the inside of the conduit on both sides with conduit plugs, water plugs, or duct sealer to prevent water, vapors, or gases from entering the building.

2.6 PATHWAY REQUIRMENTS FOR ENTRANCE CONDUITS

A.

If the entrance conduits exceeds the 180 degree of total bends limitation, an appropriate sized junction box, manhole, or handhole is required.

B.

As-built drawings of entrance conduit path required to be submitted to CNM ITS before covered with soil.

2.7 RISER CONDUITS

Riser conduits shall only be used when noted on the Construction Documents for special applications only. Riser conduits are not required as a general rule for the riser system. However, when required:

A.

Minimum of (2) 4” conduits shall be installed between the ER room and each TR room as shown on the Drawings.

B.

Conduits entering ER and TR rooms shall be reamed or bushed and terminated not more than 4" from entrance wall and within 12” of room corners.

C.

Conduits entering ER and TR rooms from below floor shall be terminated not more than

4" above finished floor.

D.

Conduits for riser cables shall be continuous and separate from all other conduit or enclosed raceway systems. Do not include more than two 90 degree bends between pulling points when installing riser conduits. Where junction boxes are required, locate in accessible areas, such as above suspended ceilings in hallways.

E.

Conduits shall not be less than 4" trade size and be equipped with a measured pull line at

12” increments rated at a minimum 1200 pound test.

F.

Provide restorable fire stops inside and around conduits as recommended by UL1479 or

ASTM E814 for all conduits penetrating fire-rated construction. Fire-rated construction to be verified with CNM ITS.

G.

Provide an insulating press fit bushing on all telecommunications riser conduits. Bushings must be rated to be used in an environmental air handling space (Plenum).

1.

Manufacturer of insulating bushing on all telecommunication conduits shall be

Arlington or equal.

H.

Riser conduits shall not be used for the distribution of horizontal cables.

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270528 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.8 FIRE STOPS

A.

In all buildings, floor/ceiling assemblies, stairs, and elevator penetrations must be sealed with a 2-hour fire stop assembly at a minimum, unless otherwise noted.

B.

Contact CNM ITS to identify walls which are fire-rated construction. Walls must be sealed with a 2-hour fire stop assembly at a minimum.

C.

Communication pathways requiring fire stopping shall utilize removable/re-usable fire stopping putties for ease of Moves, Adds, and Changes.

D.

All fire stopping penetrations shall conform to the recommended practices listed in

UL1479 or ASTM.

PART 3: EXECUTION

3.1 GENERAL REQUIREMENTS

A.

The intention of the telecommunications conduits is to provide a route between ER and

TR rooms, routes from the TRs throughout building floors to hallways, and routes from hallway distribution systems into rooms to individual TOs for telecommunications cabling.

B.

Installation of new pathways shall not interfere with existing pathways in such a way that installation of new cables within the existing pathway is made more difficult.

END OF SECTION 270528

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270528 - 7

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 270543 - UNDERGROUND DUCTS AND RACEWAYS FOR

COMMUNICATIONS SYSTEMS

PART 1: GENERAL

1.1 WORK REQUIRED:

A.

The work required under this Section consists of providing all primary, secondary, telecommunications/data underground ducts and raceways, including manholes and handholes, for the project as shown on Drawings and/or as specified herein.

1.2 RELATED SECTIONS

A.

Division 31, Section 310000 – Earthwork (excavation, backfill, compaction, etc.)

B.

Division 02, Section 020000 – Site Improvements (concrete work, blacktop, etc.)

C.

Division 26, Section 260533 – Raceways and Fittings

D.

Division 27, Section 270500 – Common Work Results for Communications

E.

Division 27, Section 271102 – Main Equipment Room and Entrance Facilities

1.3 SUBMITTALS

A.

Product Data: For features, ratings, and performance of each component specified.

B.

Submit manufacturer’s instructions for storage, handling, protection, examination, preparation, operation, and installation of products. Include application conditions or limitations of use stipulated by any product testing agency. Submit for the following:

1.

Conduit

C.

Shop Drawings:

1.

Component List: List manufacturer, part number, and quantity of each component.

2.

Include dimensioned plan and elevation views of trench details and building penetrations, labeling each individual component.

PART 2: PRODUCTS

2.1 GENERAL:

1.

All ducts/raceways:

UNDERGROUND DUCTS AND RACEWAYS FROM COMMUNICATION S

SYSTEMS

Version 12DEC2007

270543 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

The number, size, raceway duct material and arrangement shall be as indicated on

Drawings and/or as specified herein.

2.

May be non-metallic (PVC) or galvanized heavywall (GMC) conduit (as outlined in items

B and C below) and indicated on Drawings and/or as specified herein.

3.

Shall be capped with manufactured caps (Duct Plugs) when installation is temporarily discontinued.

4.

Shall be checked by pulling a round wood or steel test mandrel, sized for each duct from both directions to remove obstructions. a.

Mandrel for 5” duct shall be a minimum of 4.69” outside diameter. b.

Mandrel for 4” duct shall be a minimum of 3.75” outside diameter. c.

Mandrel for 3” duct shall be a minimum of 2.81” outside diameter. d.

Mandrel for 2.5” duct shall be a minimum of 2.19” outside diameter. e.

Mandrel for 2” duct shall be a minimum of 1.88” outside diameter.

5.

Shall be cleaned by passing a wire brush mandrel and/or rubber duct swab (or approved alternative) of appropriate size back and forth until all foreign materials and water are removed.

6.

Shall be encased by a concrete envelope in road crossings or heavy traffic areas only, minimum 3” cover on all sides or flowable backfill as specified on the drawings.

7.

Shall be installed using long radius sweeps to minimize pulling tensions, unless otherwise noted on Drawings or in specifications. No more than 180 degrees of total bends in any one section of conduit.

8.

Shall be 4" nominal trade size, unless specifically noted otherwise.

9.

Shall be installed with minimum of 3" fall per 100' run toward manholes and away from buildings.

10.

Provide measured pull line in each conduit rated at 1200 lbs. minimum. Increments must be in 12” steps.

11.

Shall be approved for correct formations before tying to prevent ducts from floating when concrete is poured.

12.

Provide a minimum of 12” separation between electric power and telecommunications/data ducts.

13.

A minimum of 2’-6” bury depth (measured from concrete encasement to finished grade) is required. Exceptions may be granted to avoid interference’s with approval of CNM ITS.

B.

Non-metallic Raceways:

1.

Carlon PVC Type DB with concrete encasement.

2.

Plastic duct to meet NEMA TC-6 standards.

3.

Plastic duct with straight couplings and appropriate cement. Couplings to be staggered horizontally and vertically.

4.

Used for all raceways except where rigid conduit is required.

5.

Complete with threaded adapter when attached to rigid conduit.

6.

Protected from deformation during stockpiling.

UNDERGROUND DUCTS AND RACEWAYS FROM COMMUNICATION S

SYSTEMS

Version 12DEC2007

270543 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

7.

Perfectly circular in shape. Other configurations will not be permitted.

8.

Have joints made with materials provided by, and installed per manufacturer's directions.

Comply with manufacturers requirements for bending and cutting.

9.

Have joints covered with Scotch #88 tape as temporary concrete seal.

10.

Provide with end bells flush with inside wall of manhole or vault.

C.

Rigid Heavy Wall Conduit:

1.

As specified in Section 260533 - Raceways and Fittings.

2.

Used within excavated portion of building, including any areas where building excavation has been backfilled.

3.

Extended 20' minimum from building into undisturbed earth.

4.

Used for all ells stubbed "in," or "out" or concrete bases for electrical equipment.

5.

Used in areas of extended backfill, requiring maximum strength against shear.

6.

Used where crossing under tunnel.

D.

Concrete Envelope:

1.

Size where shown on drawings, with raceways receiving not less than 3" concrete cover all around and 1-1/2" between raceways.

2.

Provided with support piers to undisturbed soil where necessary for permanent bearing.

3.

3000 psi, class 2, concrete ready mix per ASTM-94.

4.

Provided with fine sand cover for initial curing except where waived by CNM ITS.

5.

Rebar reinforcement is required where duct banks will cross roadways.

E.

Backfill:

1.

Per Section Earthwork (excavation, backfill, compaction, etc.).

2.2 TELECOMMUNICATIONS/DATA MANHOLES:

A.

Manholes shall be as follows:

1.

Provided by Electrical or Telecommunications Contractor as described in the drawings and as specified herein.

2.

Be reinforced precast concrete, 4500 psi and designed for truck loading.

3.

Be 10 ft. long x 6 ft. wide x 7 ft. high inside dimensions, unless otherwise specified on the

Drawings and/or as specified herein.

4.

Be provided with pulling irons opposite each duct bank.

5.

Be complete with bonding jumper to reinforcing steel in each section. a.

Pre-cast manholes have reinforcing steel bonded together and do not require an additional ground rod. Install a bonding ribbon horizontally around the top of the manhole and attached to all cable racks and hardware. Continue installation vertically between bonding clamps so both top and bottom halves are bonded together on each side. The bonding ribbon will be used to bond and ground all splice cases and hardware placed within the manhole.

6.

Be complete with cable racks, arms, and insulators, for proper cable support.

UNDERGROUND DUCTS AND RACEWAYS FROM COMMUNICATION S

SYSTEMS

Version 12DEC2007

270543 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

7.

All manhole hardware shall have hot dipped galvanized finish.

8.

Provide heavy-duty, cast-iron, frame and cover with nominal 36” opening as NEENAH

#R-1640-D or approved equal, with pick holes. Lid to be lettered "Communications".

9.

Provide 6" and 12" grade ring riser castings as required to elevate cover to approximately

1” above finished grade. Internal diameter of grade rings to be not less than internal diameter of manhole cover frame. Verify with manufacturer on availability. Custom grade rings are acceptable upon prior approval of CNM ITS. Cast-iron adjusting rings, Neenah

#R-1979 series or equal may be used to trim final elevations.

10.

Set on leveled undisturbed earth with minimum 3” granular fill under entire manhole before setting. If earth is disturbed during excavation, properly compact soil and provide

3" concrete leveling pad under entire manhole before setting. Backfill around manholes per NMDOT specifications for Manhole, Inlet and Catch Basins.

11.

Manhole ladders are required for these manholes, unless otherwise noted on Drawings and/or as specified herein.

12.

Provide a 14 inch sump.

13.

Manhole shall be Type “J” with offset opening, duct entrances as shown on Drawings with properly placed precast knockouts, duct terminators.

14.

Tinned copper bonding ribbon equivalent to .0510 x .3750 EPT shall be bonded to all cable racks within the manholes.

2.3 CABLE SUPPORTS: (MANHOLES)

A.

Supports for Communications manholes shall be as follows:

1.

Channel steel type equal to Chance #1126 with hooks and #P-1120 insulators.

2.

Provide #L-1100 hook lock clips as required.

2.4 PULL PITS

A.

Pull Pits shall be as follows:

1.

Provided by Electrical or Telecommunications Contractor as described on the drawings and/or as specified herein.

2.

Be reinforced concrete, 4500 psi and designed for truck loading.

3.

Be 4' x 4' x 6' high inside dimensions.

4.

Be provided with pulling irons opposite each duct opening.

5.

Be complete with bonding jumper to reinforcing steel in each Section.

6.

Manhole Cover shall be NEENAH #R-1640-D, with pickhole, lid lettered

"COMMUNICATIONS".

7.

Provide 6" and 12" grade ring riser castings as required to bring lid up to proper grade, and NEENAH #R-1979 rings for final adjustments. Internal diameter of grade rings to be not less than internal diameter of manhole cover frame.

8.

Set on leveled undisturbed earth with minimum 3” granular fill under entire manhole before setting. If earth is disturbed during excavation, properly compact soil and provide

3" concrete leveling pad under entire manhole before setting.

UNDERGROUND DUCTS AND RACEWAYS FROM COMMUNICATION S

SYSTEMS

Version 12DEC2007

270543 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

9.

Support Cables in pull pits with galvanized #P1000 unistrut and #P-1753/4 porcelain cable saddles.

2.5 CONDUIT

A.

Conduit shall be a nonmetallic flexible raceway manufactured from High Density

Polyethylene (HDPE) for use in underground applications. It shall be a smooth walled interior and exterior configuration with wall construction of SDR 13.5. Each conduit shall have a onehalf inch pre-lubricated, woven, 1130lb. minimum polyester tape made from low friction, high abrasion resistant yarns placed within the conduit and secured at each end. Tape shall be printed with sequential footage markings for accurate measurements.

1.

Carlon 2” smooth-walled HDPE conduit, part #A13C9N7AXXC or equivalent as specified on the drawings.

2.

Carlon 1-1/4” smooth-walled HDPE conduit, part #A6C9N7AXXC or equivalent as specified on the drawings.

3.

Carlon 1” smooth-walled HDPE conduit, part #A5C9N7AXXC or equivalent as specified on the drawings.

B.

Toneable conduit shall be manufactured as indicated above but also include a copper conductor within the wall of the duct to be used for locating the buried conduit. Conduit shall be black.

1.

Carlon 2” smooth-walled toneable HDPE conduit, part #A13C9G7AXXC or equivalent.

2.

Carlon 1-1/4” smooth-walled toneable HDPE conduit, part #A6C9G7AXXC or equivalent.

3.

Carlon 1” smooth-walled toneable HDPE conduit, part #A5C9G7AXXC or equivalent.

2.6 CONDUIT COUPLERS

A.

Aluminum threaded conduit couplers to be used to join two segments of smooth walled conduit together. Non metallic couplers are not acceptable. Toneable conduit shall be coupled per the Manufacturer’s instructions to maintain continuity of copper conductor.

1.

Carlon 2” threaded aluminum coupler, part #P200 or equivalent.

2.

Carlon 1-1/4” threaded aluminum coupler, part #P125 or equivalent.

3.

Carlon 1” threaded aluminum coupler, part #P100 or equivalent.

4.

Contact CNM ITS Telecommunications Department when using toneable conduit.

2.7 DUCT PLUGS

A.

Conduit sealing plugs to be used to seal unused conduit.

1.

Carlon 2” blank duct plug, part #MAEPG5 or equivalent.

2.

Carlon 1-1/4” blank duct plug, part # MAEPG4 or equivalent.

3.

Carlon 1” blank duct plug, part # MAEPG2 or equivalent.

UNDERGROUND DUCTS AND RACEWAYS FROM COMMUNICATION S

SYSTEMS

Version 12DEC2007

270543 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.8 TELECOMMUNICATIONS/DATA HANDHOLES:

A.

Handhole enclosures shall be Quazite Pre-cast Polymer Concrete 30”W x 48”L x 24”D PG style (Stackable) assembly with no base or as specified on drawings. Quazite part

#PG3048BA24.

B.

Installation to be per the manufacturer’s specifications.

C.

Handhole cover shall be traffic rated, heavy duty Quazite Pre-cast Polymer Concrete complete with (2) bolts. Quazite part #PG3048HA00 with “Communications” labeling on the lid.

PART 3: EXECUTION

3.1 CABLE SUPPORTS:

A.

The cable supports described on the drawings or herein are intended to assist the Contractor in obtaining a satisfactory job and shall be altered to fit job conditions.

B.

In general, all cables in manholes shall be supported on 4'-0" maximum centers for straight runs, on each side of splices, and within 2'-0" of cable entrances to duct or termination.

3.2 EXCAVATION:

A.

Coordinated with other trades.

B.

Have elevations and arrangements verified on job.

C.

If soil conditions are such that because of the depth or any other reasons the trench/excavation cannot conform to the size of the duct bank, provide forms and bracing as required.

D.

Have grade stakes at 5' intervals in trench bottom.

E.

Have trench bottom filled to exact elevation with a 3" concrete grade pad prior to installation of ducts. Ducts are to be installed using 3" chairs and 1-1/2" separation to provide required cover. At Owner’s discretion or as directed on Drawings the 3" grade pad may be deleted.

F.

Contractor shall open entire length of trench and establish proper grades before beginning installation of any portion of connecting duct runs.

G.

Per Section 310000 - Earthwork and Section 020000 - Excavation, Backfill, Concrete,

Asphalt Repairs and Related Work.

H.

Depth of excavation shall be such that the required bury depths (top of concrete encasement) are met. Any deviation from required depths shall be approved by CNM ITS prior to installation.

3.3 CONCRETE ENVELOPE:

A.

Protected against freezing, etc., as required in General Construction Specification.

B.

Installed so no honeycombing occurs and be properly vibrated with small vibrator. Do not vibrate between ducts.

UNDERGROUND DUCTS AND RACEWAYS FROM COMMUNICATION S

SYSTEMS

Version 12DEC2007

270543 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

C.

Size where shown on drawings, with raceways receiving not less than 3" concrete cover all around and 1-1/2" between raceways.

D.

Concrete for the duct bank shall be placed in such a way that the duct bank will not be disturbed and that the sides of the trench do not crumble, using splash boards, proper placement, etc. The vertical drop of concrete from chute shall not exceed 30 inches.

E.

Concrete shall be poured continuous from manhole to manhole. No pours shall originate between manholes.

F.

Interval between base or intermediate spacers shall not exceed 8 feet with a minimum of two supports per length of duct.

G.

Make provisions, such as nylon ties, to prevent the ducts from floating when concrete is poured.

H.

Color top layer of concrete encasement by using “ORANGE” (for telecommunications) chalk dust while still wet.

3.4 REINFORCING:

A.

Shall be installed:

1.

Where noted on drawings and/or as specified herein.

2.

Where crossing trenches for other work.

3.

Where connected to buildings and manhole walls, anchored thereto with projecting re-bars provided by this Contractor.

4.

At joints between pours of concrete envelope.

5.

If continuous pour is impractical, provide (4) #4 reinforcing bars extending six feet (6’) into first and second pour.

6.

Where trenches cross roadways.

B.

Reinforcing shall be supported from bottom of trench at least one inch.

C.

Arranged to avoid contact between rods to prevent inductive heating of steel at reinforcing overlaps.

3.5 BACKFILL:

A.

Not be installed until after concrete has reached initial set.

B.

Per Section Earthwork (excavation, backfill, compaction, etc.).

C.

The Contractor will do all re-seeding and landscape repairs, unless specifically indicated on

Drawings and/or as specified herein.

D.

Backfill around manholes with select granular material free of broken pavement, rocks, frozen material, etc. Backfill in 6” layers and tamp each layer to ensure complete compaction, especially under pipes and conduit. Place backfill evenly on all sides of manhole to prevent racking. Backfilling should be completed on the same day the manhole is placed.

E.

In unpaved areas, the ground should be sloped away from the manhole frame and cover to provide proper drainage.

UNDERGROUND DUCTS AND RACEWAYS FROM COMMUNICATION S

SYSTEMS

Version 12DEC2007

270543 - 7

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

F.

Where the manhole is to be installed under a paved area, such as a parking lot, the surface of the paving should be graded slightly away from the manhole frame and cover.

G.

Where the manhole is to be installed under a concrete sidewalk, slab or pavement, expansion joint material shall be placed between the panel vault frame and concrete. A 2” minimum sand cushion shall be provided between the top surface of the manhole and the bottom of the concrete sidewalk, slab or pavement to prevent stress on the casting during freeze and thaw conditions.

H.

Restoration of the area where the manhole structure is installed shall meet the requirements of the Owner.

3.6 AS-BUILTS:

A.

Contractor shall provide as-built information to Owner prior to final payment for this work

B.

As-built information shall be in red-lined format on a copy of construction drawings. Indicate location of all underground routes, if different than original drawing.

C.

If construction drawings are not utilized, Contractor shall provide all telecommunications location information on an accurate scaled site plan.

D.

All as-builts will be marked with the proper XYZ coordinates at a minimum of every 20ft.

These coordinates shall be tied to the nearest CNM ITS benchmark and other permanent landmarks. Contact CNM ITS Department for the exact location of the benchmarks at least 48 hours prior to starting work.

END OF SECTION 270543

UNDERGROUND DUCTS AND RACEWAYS FROM COMMUNICATION S

SYSTEMS

Version 12DEC2007

270543 - 8

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 270553 – IDENTIFICATION FOR COMMUNICATION SYSTEMS

PART 1 - GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the labeling of the telecommunications infrastructure as described on the

Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

H.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

I.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

J.

Division 27, Section 271543 Communications Faceplates and Connectors.

1.3 SUBMITTALS

A.

Product Data: For features, ratings, and performance of each component specified.

B.

Submit manufacturer’s instructions for storage, handling, protection, examination, preparation, operation, and installation of products. Include application conditions or limitations of use stipulated by any product testing agency. Submit for the following:

1.

Wall Boxes

2.

Raceway

3.

Conduit

4.

Conduit Bushings

C.

Labeling Plan:

1.

Component List: List manufacturer, part number of each label to be used.

2.

Submit labeling plan for CNM ITS review and approval prior to commencing labeling.

IDENTIFICATION FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270553 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

PART 2 - PRODUCTS

2.1 LABELS

A.

Copper, Fiber, and Coax Riser Cable Labels in TRs

1. Brady part #WML-1231-292 or Panduit #LS7-75NL-1

B.

Copper, Fiber, and Coax Horizontal Cable Labels in TRs

1. Brady part #WML-317-292 or Panduit #LS7-75NL-1

C.

Copper, Fiber, and Coax Horizontal Cable Labels at the Workstation Outlet

1. Brady part #WML-317-292 or Panduit #LS7-75NL-1

D.

Telephone 110-Block Labels in TRs

1. Brady part #CL-111-619 or Panduit #LS7-38-1

E.

Faceplate Labels at the Workstation Outlet

1. Brady part #CL-111-619 or Panduit #LS7-38-1

F.

Patch Panel Labels in TRs

1. Brady part #CL-111-619 or Panduit #LS7-38-1

PART 3: EXECUTION

3.1 LABELING INSTALLATION

A.

Horizontal Cable Labeling:

1.

All horizontal cables shall be labeled with self-laminating marking tape, Brady ID-Pro labeler, Panduit LS7 labeler, or CNM ITS approved equal labeling system. Identification shall be shown on CNM Standard Drawings. a.

Place label on a visible part of cable within 12” of termination point for ease of identification after termination.

Size of letters and numbers shall be no less than 5/16” high by 1/8” wide.

This shall be visible by removing outlet cover plate. For rooms with multiple outlet locations, identification would begin with the first receptacle to the left of the main entrance to the room and continuing clockwise around the room. Size of letters and numbers shall be as indicated above. b.

At the ER and TR, the CATV cables shall be labeled at each end with the information indicating termination of the opposite end of the cables. This shall include Cable system, Room number, and cable number at opposite end. Place label on a visible part of cable 12” from end of cable for ease of identification after termination.

Size of letters and numbers shall be no less than 5/16” high by 1/8” wide.

IDENTIFICATION FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270553 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) c.

At the rooms, the CATV cables shall be labeled 4” from termination with the following: ER/TR TR Room # - TV Room # -Jack.

Size of letters and numbers shall be as indicated above.

B.

Copper Riser Cable Labeling:

1.

All riser cables shall be labeled with self-laminating marking tape, Brady IDPro labeler,

Panduit LS7 labeler, or IT Telecommunications approved equal labeling system.

Identification shall be as follows: a.

At the ER and TR, the copper riser cables shall be labeled at each end with the information indicating termination of the opposite end of the cables. This shall include building acronym and cable number and room location. Place label on a visible part of cable close to wiring block for ease of identification after termination.

Size of letters and numbers shall be no less than 5/16” high by 1/8” wide.

The cable label along with the pair count shall be labeled at each end of the wiring blocks.

C.

Fiber Riser Cable Labeling:

1.

All fiber optic riser cables shall be labeled at each end with the information indicating: 1)

Building, 2) Cable number, 3) “FO” indicating a fiber and opposite end of cable. “S” shall be used after the FO to indicate the use of single-mode fiber. Fiber type shall be labeled on the front of the fiber enclosure: SMF for single mode fiber; MMF for multimode fiber.

Verify cable number with CNM ITS before labeling.

D.

Copper Riser 110-Block Labeling:

1.

At the ER and TR, voice riser cables are terminated on their respective 110 blocks or patch panels per the Drawings. Label only 1st and last pairs on each row of 110 blocks.

Place cable number of riser cable on wiring block label in center of label.

E.

Coax Riser Labeling (CATV)

1.

At the ER and TR, CATV riser cables shall be labeled at each end with the information indicating termination of the opposite end of the cables.

F.

Horizontal 110-Block Labeling (Telephone):

1.

At the TR, voice horizontal cables are terminated on their respective S110 blocks, with pairs on the blocks labeled in ascending room number order. All horizontal cables from same room should be terminated in sequential order on S110 blocks. Single 4-pair cables will be labeled with a room location and a jack designation. e.g. 1113-1 = a single telephone jack in Room 1113.

IDENTIFICATION FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270553 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

Place label on jacket of cable within 3” of the wiring block.

G.

Horizontal Patch Panel Labeling (Data):

1.

At the TR, data horizontal cables are terminated on their respective patch panels, with jacks on the panels labeled in ascending room number order. All horizontal cables from same room should be terminated in sequential order at the patch panels.

H.

Faceplate Labeling:

At the rooms, the jacks will be labeled on the faceplates using the plastic insert to cover a printed identification tag with room number and proper jack designation as shown on the CNM Drawings.

END OF SECTION 270553

IDENTIFICATION FOR COMMUNICATIONS SYSTEMS

Version 12DEC2007

270553 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271101 - TELECOMMUNICATIONS ROOM AND SPACES

PART 1 - GENERAL

1.1

RELATED DOCUMENTS

A.

Drawings and general provisions of the Contract, including General and Supplementary

Conditions and other Division 01 Specification Sections, apply to this Section.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

H.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

I.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

J.

Division 27, Section 271543 Communications Faceplates and Connectors.

1.3

SUMMARY

A.

This Section includes minimum requirements for equipment, termination hardware, and cable installation in communication equipment rooms including, but not limited to:

1.

Floor mounted passive relay racks.

2.

Floor mounted active equipment relay racks.

3.

Wall mounted cabinets.

4.

Floor mounted cabinets.

5.

Cable management hardware.

6.

Ladder racks.

7.

Patch panels – Category 6

8.

Fiber optic SC-Duplex adapter panels, 6 adapters per panel.

9.

Fiber optic distribution unit 3U 48 port configuration – rack mounted.

10.

Plywood Backboards.

11.

110 system blocks.

12.

UTP cross connects.

13.

Grounding and bonding.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 1

1.4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

14.

Powerstrip Telecommunications Room active equipment relay rack.

15.

Powerstrip Telecommunications Room equipment cabinets.

16.

Optical fiber patch cords - multimode.

17.

Optical fiber patch cords – single mode.

18.

Category 6 patch cords.

19.

110 system patch cords – Category 6.

SUBMITTALS

A.

Product Data: For features, ratings, and performance of each component specified.

B.

Submit manufacturer’s instructions for storage, handling, protection, examination, preparation, operation, and installation of products. Include application conditions or limitations of use stipulated by any product testing agency. Submit for the following:

1.

Floor mounted relay racks.

2.

Wall mounted relay racks and brackets.

3.

Wall mounted cabinets.

4.

Floor mounted cabinets.

5.

Cable management hardware.

6.

Cable supports and ladder racks.

7.

Patch panels

8.

Fiber system blocks.

9.

Power strips.

10.

Patch cords.

C.

Shop Drawings:

1.

Component List: List manufacturer, part number, and quantity of each component.

2.

Include dimensioned plan and elevation views of equipment rooms, labeling each individual component. Show equipment rack assemblies, method of field assembly, workspace requirements, and access for cable connections.

1.5

QUALITY ASSURANCE

A.

Manufacturer Qualifications: ISO 9001 Certified, for components that are required to have submittals provided as part of this Section.

B.

Installer Qualifications:

1.

A firm currently engaged and which has been continuously engaged for the past 5 years in the installation of low voltage applications of type required for this Project,

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) and which is licensed in and has obtained or will obtain the necessary permits to perform telecommunications installations in jurisdiction where Project is located.

2.

Have a BICSI certified RCDD locally on staff

3.

Provide references of the type of installation provided in this specification.

4.

Have personnel knowledgeable in local, state, and national codes and the latest TIA

Telecommunications Standards and Manufacturer’s recommendations.

5.

Have personnel fluent in the use of AutoCAD version 2002 or later and possess and operate CAD software capable of producing .DWG or .DXF format.

C.

Source Limitations: Obtain units of the same type of equipment through one source from a single manufacturer.

D.

Product Options: Drawings indicate size, profiles, and dimensional requirements of equipment, accessories, and components and are based on the specific system indicated.

Refer to Division 01 Section “Product Requirements.”

1.

Do not modify intended aesthetic effects or performance, as judged solely by

Architect, except with Architect’s approval. If modifications are proposed, submit comprehensive explanatory data to Architect for review.

E.

Materials and labor shall comply with applicable requirements of following standards, using latest version of associated appendices and Technical Service Bulletins at the time of award of the Contract;

1.

EIA/TIA-568.

2.

EIA/TIA-569.

3.

EIA/TIA-606.

4.

EIA/TIA-607.

5.

Underwriter’s Laboratory.

6.

FCC (including CFR 47 and Part 68 – Subpart F).

7.

National Electric Code.

8.

Local and State Codes.

9.

ISO/I/EC 11801.

10.

IEC 1000-5-2.

11.

IEC 60603-7.

PART 2 - PRODUCTS

2.1

MANUFACTURERS

A.

In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Available Products: Subject to compliance with requirements, products that may be incorporated into the Work include, but are not limited to, products specified.

2.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.

2.2

FLOOR MOUNTED RELAY RACKS

A.

Physical Specifications:

1.

19 inch (482.6 mm) rack mounting space.

2.

84 inches (2134 mm) high.

3.

Lightweight, high strength aluminum construction.

4.

Black powder coat finish.

5.

15 inch (381 mm) deep base with 4 3/4 inch (19 mm) bolt down holes.

6.

EIA channel width of 3 inches (76 2 mm) , with #12-24 screw holes.

7.

Rack shall have double sided #12-24 tapped holes and EIA universal rack 5/8 inch (16 mm) to 5/8 inch (16 mm) – 1/2 inch (12.7 mm) standard hole pattern (compatible with

1-1/4 inch (32 mm) – 1/2 inch (12.7 mm) hole patterns).

B.

Approved Manufacturers:

1.

Hoffman

2.

APW

3.

Chatsworth Products Inc.

4.

Other approved equal submitted in advance as required in SOW

2.3

WALL MOUNTED CABINETS

A.

Physical Specifications:

1.

19 inch (482.6 mm) equipment mounting space.

2.

42 to 48 inches (1067 to 1219 mm) high.

3.

Universal mounting rails with 12/24 tapped holes.

4.

5/8 inch (16 mm) to 5/8 inch (16 mm) – 1/2 inch (12.7 mm) standard hole pattern.

5.

Black powder coat finish.

B.

Racks shall have:

1.

A 2 hinge design for front and rear access

2.

Louvered sides for ventilation

3.

Knockouts in top and bottom for cable access

4.

Both front and rear access shall be lockable

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

5.

Smoked Plexiglas Door

C.

Approved Manufacturers:

1.

Hoffman

2.

APW

3.

Chatsworth Products Inc.

4.

Other approved equal submitted in advance as required in SOW

2.4

FLOOR MOUNTED CABINET

A.

Physical Specifications:

1.

0.0556 inch (1.41 mm) thick steel construction.

2.

Capable of setting equipment mounting rails at 19 inches (483 mm).

3.

Nominal 84 by 24 by 40 inches (1956 by 610 by 1016 mm).

4.

Lockable smoked Plexiglas hinged door on front and steel hinged door in rear.

5.

Vented roof.

6.

Removable side panels.

7.

Leveling feet.

8.

Internal fan for non-raised floor areas only.

B.

Approved Manufacturers:

1.

Hoffman

2.

APW

3.

Chatsworth Products Inc.

4.

Other approved equal submitted in advance as required in SOW

2.5

CABLE MANAGEMENT FOR RELAY RACKS

A.

Cable management shall be black metal or plastic with integral wire retaining fingers.

B.

Vertical management panels shall have front and rear channels.

C.

Vertical cable management panels shall have removable front and back covers made of black metal.

D.

A horizontal crossover cable manager shall be provided as shown on Drawings for each relay rack, with minimum height of 1 rack units each.

E.

Approved Manufacturers:

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Panduit

2.

Hoffman

3.

Chatsworth Products Inc.

4.

Other approved equal submitted in advance as required in SOW

2.6

FIBER OPTIC SC-DUPLEX ADAPTER PANELS, 6 ADAPTERS PER PANEL

1.

Adapter shall support 6 adapters per panel and shall permit termination in increments of 6 strands of fiber.

2.

Adapter shall permit the installation of 2 SC type connectors to be installed, such that the 2 appear to function as one connector.

A.

Approved Manufacturers:

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

2.7

PATCH PANELS – CATEGORY 6

A.

Termination panels shall support appropriate Category 6 applications and facilitate crossconnection and inter-connection using modular patch cords.

B.

Sized to fit an EIA standard, 19-inch (482.6 mm) relay rack, or be capable of mounting to wall.

C.

Accommodate a minimum of 48 ports for each rack mount space, where 1 rack mount space is equal to 1.75 inches (44.5 mm).

D.

Have circuit boards tested in both directions as required by ANSI/TIA/EIA-568 and

ISO/IEC 11801.

E.

Have angle left and angle right modules to provide optimum cable management.

F.

Have removable 6 port modules to allow replacement in field.

G.

Have Category 6 jacks available in both T568A and T568B wiring schemes, with 110-style termination.

H.

Allow for minimum of 200 re-terminations without signal degradation below standards compliance limit.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

I.

Have modular ports compliant with FCC CFR 47 part 68 Subpart F and IEC 60603-7 with

50 microinches (0.0013 mm) of gold plating over nickel contacts or equivalent.

J.

Have plastic strip for physical protection of printed circuit board.

K.

Have port identification numbers on both the front and rear of panel.

L.

Provide clear label holders and white designation labels with panel, with optional color labels available.

M.

Be made by an ISO 9001 Certified Manufacturer.

N.

Electrical Specifications:

1.

Meet ANSI/TIA/EIA-568-B.2-1 Category 6 component specifications .

2.

Meet following requirements:

TIA/EIA-568-B.2-1 Category 6 Compliant; ISO/IEC 11801, 2nd ed. Category 6 Compliant

Return

Freq. Ins. ACR PSACR PSELFEXT

(MHz) (dB/100m)

Loss

(dB)

Loss

(dB) (dB) (dB) (dB) (dB)

Loss

(dB)

31.25 10.8 53.1 51.1 42.4 38.1 23.8

33.2 32.1 21.7

25.7 20.3

12.0 18.2

6.7 17.8

350 39.9 37.3 35.3 - - 20.1 17.1 17.3

400 42.9 36.5 34.5 - - 19.0 15.9 16.9

500 48.1 35.9 33.9 - - 16.9 13.9 16.3

550 50.7 34.8 33.6 - - 15.8 13.1 15.8

3.

Be UL verified for TIA/EIA Category 6 electrical performance.

4.

Steel frame with black powder coat finish in 24 and 48 port configurations.

5.

Have port identification numbers on both front and rear of panel.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 7

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

6.

Have mounting slots compatible with ANSI/EIA-310.

7.

Allow modular insert to accept 110-style patch plugs as means of termination.

8.

T-568B wired.

9.

Provide 48 port panels, unless otherwise noted.

10.

Density must accommodate maximum of 24 ports per single rack unit (1.75 inch

(44.5 mm)).

11.

Paired punch down sequence to allow pair twist within 1/2 inch (12.7 mm) of termination.

12.

Relay rack mounted.

13.

UL listed, compliant with FCC CFR47, Part 68 Subpart F and IEC 60603-7, with

50 microinches (0.0013 mm) of gold plating over nickel contacts, or equivalent.

14.

Allow use of 4 or 5 pair impact termination tool.

15.

Have port identification numbers on front and rear of panel.

16.

Provide port configurations and densities as indicated on Drawings.

17.

Provide rear cable management bar(s) as recommended by manufacturer.

18.

Shall be insulation displacement connector 110 style terminations.

19.

Provide EIA/TIA 606 compliant color-coded icons or color-coded designation label strips for all patch panels. Identify voice or data functionality as required.

O.

Approved Manufacturers:

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

2.8

FIBER OPTIC DISTRIBUTION UNIT 3U 48 PORT CONFIGURATION – RACK

MOUNTED

A.

All panels and trays (units) shall provide cross-connect, inter-connect, splicing capabilities and contain cable management for supporting and routing fiber cables and jumpers.

B.

Shall be available in 24 and 48 port configurations.

C.

Feature a front access design with hinged bulkhead plate.

D.

Use adapter plates that house 6 adapters SC-Duplex each.

E.

Use of MPO or MPT as alternative for approval

F.

Have blank adapter plates for future growth of fiber infrastructure.

G.

Have hinged removable front cover.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 8

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

H.

Have integrated vertical cableway on one side of panel.

I.

Be 19 inch (483 mm) rack mountable.

J.

Have storage and splicing options as part of product offering.

K.

Be made by ISO 9001 certified manufacturer.

L.

Provide port configurations and densities as indicated on Drawings.

M.

Approved Manufacturers:

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

2.9

BACKBOARDS

A.

Plywood backboards will be provided by others unless stated otherwise in the Contract

Documents and/or Drawings. All walls within a TR will be required to be covered with ¾”

AC rated plywood. Plywood may either be fire treated (stamp must remain visible if painted) or painted with two coats of fire retardant paint to match room color. Sheets must be installed lengthwise originating 6 inches above finished floor height.

2.10

DISTRIBUTION RINGS

A.

Provide open end distribution rings for wall mounted cross-connect fields above wall mounted blocks. Provide 2 rings per vertical row.

B.

Approved Manufacturers:

1.

Cooper B-Line

2.

Chatsworth

3.

Senior Industries

4.

Other approved equal submitted in advance as required in SOW

2.11

GROUNDING AND BONDING

A.

Materials: Comply with NFPA 70, TIA/EIA-607, and UL 467.

B.

See drawing package for additional requirements.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 9

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

C.

Comply with manufacturer’s grounding requirements.

2.12

TELECOMMUNICATIONS POWER STRIP

A.

Provide 2 power strips per cabinet.

B.

Shall have 1 dedicated 20 amp, 115 V circuit per strip.

C.

Shall be rack mounted.

D.

Shall be switched with rocker style switch per port.

E.

Shall provide minimum of 2 power strips per cabinet that contains active electronics, or as detailed on Drawings.

F.

Shall be surge suppressed.

G.

Shall have minimum of 6 outlets, transformer spaced where possible.

H.

Shall have a 15 foot (4 m) cord, minimum.

I.

Shall be UL listed and must meet UL 1363 and 1449 requirements.

J.

Approved Manufacturers:

1.

Wiremold

2.

Leviton

3.

TrippLite

4.

Other approved equal submitted in advance as required in SOW

2.13

OPTICAL FIBER PATCH CORDS – MULTIMODE

A.

Shall be available in standard lengths of 3, 6, 10, and 16.4 feet (1, 2, 3, and 5 meters), custom lengths shall also be available, and shall meet or exceed standards as defined in

ANSI/TIA/EIA-568 and ISO/IEC 11801.

B.

For existing environments utilize duplex optical fiber cable that is 62.5/125 micron multimode, OFNR riser grade, and meets the requirements of UL 1666. For new installation environments utilize 50/125 micron multimode fiber. Confirm with CNM ITS before purchasing cabling.

C.

Utilize optical fiber cable where the attenuation shall not exceed 3.5 dB/km at 850 nm wavelength or 1.0 dB/km at 1300 nm.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 10

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

D.

Cable Jacket Color:

1.

62.5/125: Orange.

2.

50/125: Aqua.

E.

Be equipped with SC type in accordance with TIA/EIA-568 and must include a ceramic ferrule.

F.

Have terminated connectors exhibit maximum insertion loss of 0.25 dB with average of 0.20 dB or better when tested at either 850 nm or 1300 nm wavelentths for 62/125 μ m.

G.

Have terminated connectors exhibit maximum insertion loss of 0.25 dB with average of 0.20 dB or better when tested at either 850 nm or 1300 nm wavelengths for 50/125

μ m.

H.

Have average return loss of 2.5 dB with minimum return loss of 2.0 dB at both 850 nm and

1300 nm.

I.

Be made by ISO 9001 certified manufacturer.

J.

Be UL 1666 approved.

K.

Shall be duplex fiber cable meeting or exceeding transmission characteristics of optical fiber horizontal cable.

L.

Connectors shall be duplex T568SC, as indicated on Drawings or equipment schedules.

M.

Following configurations may be required:

1.

SC type/SC type

2.

ST type/SC type

3.

ST Type/LC Type

4.

SC Type/LC Type

5.

ST Type/ST Type

6.

LC Type/LC Type

N.

Approved Manufacturers:

1.

Quiktron

2.

Commscope

3.

OCC

4.

Other approved equal submitted in advance as required in SOW

2.14

OPTICAL FIBER PATCH CORDS – SINGLE MODE

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 11

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

Available in standard lengths of 3, 6, 10, and 16.4 feet (1, 2, 3, and 5 meters), custom lengths shall also be available, and shall meet or exceed standards as defined in

ANSI/TIA/EIA-568 and ISO/IEC 11801.

B.

Be either simplex or duplex OFNR riser grade cable, with attenuation at wavelength 1310 nm being 1.0 dB/km and at wavelength 1550 nm 1.0 db/km.

C.

Jacket Color: Yellow.

D.

Connectors shall be SC type in accordance with TIA/EIA-568 and must include a ceramic ferrule.

E.

Terminated connectors shall exhibit a maximum insertion loss of 0.50 db with an average of

0.25 dB when tested at either 1310 nm or 1660 nm wavelengths for singlemode fiber.

F.

Have average return loss of 53 db with minimum return loss of 40 dB at both 1310 and 1550 nm.

G.

Be made by ISO 9002 certified manufacturer.

H.

Be UL 1666 approved.

I.

Approved Manufacturers:

1.

Quiktron

2.

Commscope

3.

OCC

4.

Other approved equal submitted in advance as required in SOW

2.15

CATEGORY 6 PATCH CORDS

A.

Shall be round, and consist of 8 insulated 24 AWG stranded copper conductors arranged in 4 color-coded twisted-pairs within flame-retardant jacket.

B.

Be equipped with modular 8-position plugs on both ends, wired straight through with standards compliant wiring.

C.

Use modular plugs, which exceed FCC CFR 47 Part 68 Subpart F and IEC 60603-7 specifications, and have 50 microinches (0.0013 mm) minimum of gold plating over nickel contacts.

D.

Be resistant to corrosion from humidity, extreme temperatures, and airborne contaminants.

E.

Utilize cable that exhibits power sum NEXT performance.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 12

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

F.

Be available in several colors with or without color strain relief boots providing snag-less design.

G.

Meet flex test requirements of 1000 cycles with boots and 100 cycles without boots.

H.

Be available in any custom length and standard lengths of 3, 5, 7, 10, 15, 20, and 25 feet (.9,

1.5, 2.1, 3, 4.6, 6.1, and 7.6 m).

I.

Be made by ISO 9001 certified manufacturer.

J.

Electrical Specifications:

1.

Input Impedance Without Averaging: 100 ohms plus or minus 15 percent from 1 to

100 MHz.

2.

One hundred percent transmission tested for performance up to 100 MHz.

Manufacturer shall guarantee cords are compatible with Category 6 links.

3.

Utilize cable that is UL verified (or equivalent) for TIA/EIA Category 6 electrical performance.

4.

UL listed 1863.

K.

Horizontal Workstation Colors:

1.

All horizontal cabling will consist of Plenum rated cable regardless of Plenum environment and will be Blue in color.

L.

Approved Manufacturers:

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

PART 3 - EXECUTION

3.1

FLOOR MOUNTED RELAY RACKS

A.

Anchor racks to floor using drop anchor with bolt to match diameter of mounting hole in base of rack.

B.

Provide vertical and horizontal cable as indicated on Drawings.

C.

Mount with minimum 36 inch (915 mm) clear access behind and in front of rack rows but maintain 48 inches between wall and rack.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 13

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

D.

Install equipment ground bus bar in rack for systems integrator or installer to ground equipment per grounding details on CNM ITS provided drawings. Ground rack equipment ground bus bar to room ground bus bar with #6 copper wire.

E.

Provide grounding, earthing, and bonding in accordance with applicable codes and regulations, with the requirements of IEC 1000-5-2, and ANSI/TIA/EIA-607.

3.2

WALL MOUNTED RELAY RACKS

A.

Secure racks to building structure with approved anchoring means for the type of wall being attached to. Always mount ¾” plywood backboard to wall first and then attach rack. Use full sheet of plywood attached to wall attached to a minimum of two separate studs. Paint plywood to match room color.

B.

Verify existing wall construction and submit proposed anchoring methods for CNM ITS approval.

C.

Provide vertical and horizontal cable management both front and rear wherever available.

D.

Must be lockable cabinet with matching keys.

3.3

CABLE MANAGEMENT

A.

Provide horizontal cable manager at top and bottom of each relay rack, with minimum height of two rack units each.

B.

Alternate patch panel and wire management starting from top of rack with wire manager on top.

C.

Provide 2 rear cable management bars and reusable Velcro-type hook and loop straps in each rear vertical channel. Reusable straps shall be of varying sizes, each allowing 50 percent spare future expansion, and of adequate quantity to secure cable bundles at least every 4 rack units.

D.

Secure cable managers, slack managers, support bars, and hook and loop straps per manufacturer’s recommendations.

3.4

CATEGORY 6 PATCH PANELS

A.

Install and label as recommended by manufacturer, per EIA/TIA 606A.

B.

Install rear cable management bars as recommended by manufacturer.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 14

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

3.5

OPTICAL FIBER PATCH PANELS

A.

Install as indicated on Drawings.

B.

Install blank adapter panels in positions not used at time of installation for fiber terminations.

3.6

CABLE SUPPORTS

A.

Provide “D” rings 24 inches (610 mm) on center for exposed wall mounted vertical

Category 6 cable runs.

B.

To maximum extent possible, horizontal wall runs shall be on wall mounted ladder racks.

Minimize horizontal wall mounted cable runs.

C.

Provide cable brackets 36 inches (914 mm) on center supported to building structure for cable runs not supported by cable tray.

3.7

BACKBOARDS

A.

Use full sheet of plywood attached to wall attached to a minimum of two separate studs.

Paint plywood to match room color. In telecom rooms, install plywood vertically on all four walls a minimum of 6 inches above finished floor and 6 inches away from all corners.

B.

Verify existing wall construction and submit proposed attachment methods for CNM ITS approval.

3.8

DISTRIBUTION RINGS

A.

Install distribution rings for cross-connect fields above all wall mounted blocks. Provide 2 rings per vertical row of blocks. Mount rings with 2 hex head screws per ring.

3.9

MISCELLANEOUS REQUIREMENTS

A.

Cables in Equipment Rooms shall be neatly “dressed out” and accessible.

B.

Provide service loops on cables terminated in Telecommunications Rooms as indicated on

Drawings.

C.

Firestop sleeves and conduit openings after cable installation is complete. See Section

270500 for more firestopping details.

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 15

3.10

GROUNDING AND BONDING

A.

See Section 270526 for Grounding Details

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

See drawing package for additional requirements.

C.

Comply with manufacturer’s grounding requirements.

END OF SECTION 271101

TELECOMMUNICATIONS ROOMS AND SPACES

Version 12DEC2007

271101 - 16

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271102 - MAIN EQUIPMENT ROOMS (ER) AND ENTRANCE

FACILITIES (EF)

PART 1 - GENERAL

1.1

RELATED DOCUMENTS

A.

Drawings and general provisions of the Contract, including General and Supplementary

Conditions and other Division 01 Specification Sections, apply to this Section.

1.2

SUMMARY

A.

This Section includes minimum requirements for equipment and materials at Main

Equipment Room (ER) and at Entrance Facility (EF) including, but not limited to:

1.

Racks and cabinets.

2.

Entrance facility terminals.

3.

Surge protection modules.

4.

Wall mounted distribution frames.

5.

Ladder racking.

6.

Grounding and bonding.

7.

Backboards.

8.

Frame mounted termination blocks.

9.

Frame mounted ring.

1.3

RELATED SECTIONS

A.

Division 27, Section 270500 – Common Work Results for Communications

B.

Division 27, Section 270526 – Grounding and Bonding for Communications Systems

C.

Division 27, Section 270543 – Underground Ducts and Raceway for Communications

Systems

D.

Division 27, Section 271100 – Communications Equipment Room Fittings

1.4

SUBMITTALS

A.

Product Data: Submit manufacturer’s instructions for storage, handling, protection, examination, preparation, operation, and installation of products. Include application conditions or limitations of use stipulated by any product testing agency. Submit for the following:

MAIN EQPT ROOMS AND ENTRANCE FACILITIES

Version 12DEC2007

271102 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Entrance facility terminals.

2.

Surge protection modules.

3.

Distribution frames.

4.

Steel ladder racking.

B.

Shop Drawings:

1.

Component List: List manufacturer, part number, and quantity of each component.

2.

Include dimensioned plan and elevation views of equipment rooms, labeling each individual component. Show equipment rack assemblies, method of field assembly, workspace requirements, and access for cable connections.

1.5

QUALITY ASSURANCE

A.

Source Limitations: Obtain units of the same type of equipment through one source from a single manufacturer.

1.6

EXTRA MATERIALS

A.

Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1.

Surge Protection Modules (10% of those installed)

2.

D-Rings (6 each)

3.

UTP Cross Connects: 1 Spool each Red/White, Blue/White

PART 2 - PRODUCTS

2.1

MANUFACTURERS

A.

In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:

1.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.

2.2

RACKS AND CABINETS

A.

Cabinets shall have vented sides and back panels.

MAIN EQPT ROOMS AND ENTRANCE FACILITIES

Version 12DEC2007

271102 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Cabinets shall be 24 inches (610 mm) wide, 36 inches (914 mm) deep and 88 inches

(2235 mm) high (Unless otherwise noted in Contract Documents or Drawings).

C.

Equip each cabinet with fan capable of providing 450 CFM (212.4 L/s) of air movement.

D.

Approved Manufacturers:

1.

Hoffman

2.

APW

3.

Chatsworth Products Inc.

4.

Other approved equal submitted in advance as required in SOW

2.3

ENTRANCE FACILITY TERMINALS

A.

Entrance facility terminal shall protect up to 100 lines (pairs).

B.

Dimensions shall be 4 inches (102 mm) wide by 24 inches (610 mm) high by 3-15/16 inches

(100 mm) deep.

C.

Input stub (tip) cable shall be #26 AWG shielded cable. Field verify actual stub length in field.

D.

Input stub shall serve as internal fuse link.

E.

Input stub shall be equipped with a heavy-duty strain relief and encapsulated cable connector.

F.

Output stub cable shall be #24 AWG shielded cable. Field verify actual stub length in field.

G.

Wall or frame mountable.

H.

Shall accommodate industry standard 5-pin protection modules.

I.

Plastic components shall meet or exceed specifications set forth in UL 497.

J.

Approved Manufacturers:

1.

Circa

2.

Porta System

3.

Reliable Marconi

4.

Other approved equal submitted in advance as required in SOW

2.4

SURGE PROTECTION MODULES

MAIN EQPT ROOMS AND ENTRANCE FACILITIES

Version 12DEC2007

271102 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

Five pin, 3 element gas type protection modules.

B.

Module shall provide true balanced operation.

C.

Over voltage on either side shall cause the entire tube to ionize to provide a simultaneous path to ground for both sides of the circuit.

D.

Shall be UL 497 listed.

E.

Ground pin shall be tin.

F.

Tip and Ring pins shall be gold alloy.

G.

Module Color: Black.

H.

Nominal DC breakdown shall be 350 V/ at 100 V/

μ sec.

I.

Impulse breakdown voltage shall be 700 A at 100 V/ μ sec and 150 A at 1KV/ μ sec.

J.

DC holding current shall be 135 V for less than 150 ms.

K.

Surge life (min. operations) shall be as follows:

1.

At 10 A, 10 x 1000

μ sec: Greater than 3000.

2.

At 100 A, 10 x 1000

μ sec: Greater than 300.

3.

At 10 kA, 8 x 20

μ sec: Greater than 10.

4.

At 20 kA, 8 x 20 μ sec: Greater than 1.

5.

At 65 Arms, 11 cycles, 130 A total: Greater than 1.

6.

At 10 Arms, 1 sec, 20 A total: Greater than 10.

L.

Capacitance shall be less than 1 pf for 1 Vrms at 1 Khz, 50 VDC.

M.

Insulation resistance shall be greater than 100 M ohms at 50 VDC.

N.

Fail safe operation shall be as follows:

1.

At 1.0 A: Less than 50 sec.

2.

At 5.0 A: Less than 15 sec.

3.

At 20 A: Less than 10 sec.

4.

At 60 A: Less than 3 sec.

O.

Current limiters shall be as follows:

1.

Hold Current (ma) at 20 C: 145.

2.

R min/max ohms: 3/6.

MAIN EQPT ROOMS AND ENTRANCE FACILITIES

Version 12DEC2007

271102 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

P.

Approved Manufacturers:

1.

Circa

2.

Porta System

3.

Reliable Marconi

4.

Other approved equal submitted in advance as required in SOW

2.5

RACK OR WALL MOUNTED DISTRIBUTION FRAMES

A.

300-Pair 110 Blocks.

B.

50-Pair 66 Blocks.

C.

Approved Manufacturers:

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

2.6

GROUNDING AND BONDING

A.

Materials: Comply with NFPA 70, TIA/EIA-607, and UL 467.

B.

See drawing package for additional requirements.

C.

Comply with manufacturer’s grounding requirements.

2.7

BACKBOARDS

A.

Plywood backboards will be provided by others unless stated otherwise in the Contract

Documents and/or Drawings. All walls within a TR will be required to be covered with ¾”

AC rated plywood. Plywood may either be fire treated (stamp must remain visible if painted) or painted with two coats of fire retardant paint to match room color. Sheets must be installed lengthwise originating 6 inches above finished floor height.

2.8

DISTRIBUTION RINGS

A.

Provide open end distribution rings for wall mounted cross-connect fields above wall mounted blocks. Provide 2 rings per vertical row.

MAIN EQPT ROOMS AND ENTRANCE FACILITIES

Version 12DEC2007

271102 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Approved Manufacturers:

1.

Cooper B-Line

2.

Chatsworth

3.

Senior Industries

4.

Other approved equal submitted in advance as required in SOW

PART 3 - EXECUTION

3.1

ENTRANCE FACILITY TERMINALS

A.

Shall be wall mounted.

B.

Field verify actual length required for input and output stubs.

C.

If scope of Work does not include splicing of tip cable to feed cable, provide clear labeling at splice end of tip cable referencing rack, row, and block information. Coordinate with

Owner.

D.

Terminate output stub to appropriate block on distribution frame. Coordinate with Owner.

E.

Install #6 AWG grounding wire as straight as possible from terminal to grounding bar.

3.2

SURGE PROTECTION MODULES

A.

Protect all pairs entering building.

3.3

LADDER RACKING

A.

Install ladder rack and associated mounting hardware in accordance with manufacturer’s written instructions and in a manner that will allow rack to support its maximum rated load.

B.

Secure ladder rack to relay rack when ladder rack and the top of the relay rack are at the same height and as additionally required by Drawings and by field conditions.

3.4

GROUNDING AND BONDING

A.

Comply with Division 27, Section 270526 Grounding and Bonding Communications

Systems

B.

See drawing package for additional requirements.

MAIN EQPT ROOMS AND ENTRANCE FACILITIES

Version 12DEC2007

271102 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

C.

Comply with manufacturer’s grounding requirements.

3.5

BACKBOARDS

A.

Use full sheet of plywood attached to wall attached to a minimum of two separate studs.

Paint plywood to match room color. In telecom rooms, install plywood vertically on all four walls a minimum of 6 inches above finished floor and 6 inches away from all corners.

B.

Verify existing wall construction and submit proposed attachment methods for CNM ITS approval.

END OF SECTION 271102

MAIN EQPT ROOMS AND ENTRANCE FACILITIES

Version 12DEC2007

271102 - 7

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271107 – TELECOMMUNICATIONS ROOM FINISHES

PART 1 - GENERAL

The Contractor is held responsible to be familiar with the provisions contained herein and with other

Sections of this Specification as applicable to the completion of the installation.

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, and materials unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of all telecommunications infrastructure as described on the Drawings and/or required by these specifications.

1.2 COMMUNICATION SECTIONS

A.

Division 27, Section 270526 Grounding and Bonding for Communication Systems.

B.

Division 27, Section 270528 Pathways for Communication Systems.

C.

Division 27, Section 270553 Identification for Communication Systems.

D.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

E.

Division 27, Section 271313 Communications Copper Backbone Cabling.

F.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

G.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

H.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

I.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

J.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

K.

Division 27, Section 271543 Communications Faceplates and Connectors.

1.3 INTENT OF DRAWINGS AND SPECIFICATIONS

A.

These Specifications, together with the Drawings accompanying them, are intended to depict the installation requirements necessary to support this Project. Contractor shall furnish materials shown and/or called for on the Drawings but not mentioned in the Specifications, or vice versa, that are necessary for the installation and support of communications cabling, whether or not specifically called for in both. In addition, Contractor shall provide incidental equipment and materials required for the completion of systems included in this contract whether or not specified or shown on the Drawings.

1.4 SUBMITTALS

A.

Product Data: For features, ratings, and performance of each component specified.

TELECOMMUNICATIONS ROOM FINISHES

Version 12DEC2007

271107 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Submit manufacturer’s instructions for storage, handling, protection, examination, preparation, operation, and installation of products. Include application conditions or limitations of use stipulated by any product testing agency. Submit for the following:

1.

Cable supports and ladder racks.

C.

Shop Drawings:

1. Component List: List manufacturer, part number, and quantity of each component.

Include dimensioned plan and elevation views of equipment rooms, labeling each individual component.

PART 2 - PRODUCTS

2.1 PRODUCT STANDARDS

A.

All materials shall conform with the current applicable industry standards including, but not limited to:

1.

NEMA (National Electrical Manufacturers' Association)

2.

ANSI (American National Standards Institute)

3.

ASTM (American Society for Testing and Materials)

4.

ICEA (Insulated Cable Engineers Association)

5.

IEEE (Institute of Electrical and Electronic Engineers)

6.

National Electrical Safety Code

B.

In addition, all Material shall be Underwriters Laboratories Listed unless otherwise indicated.

C.

All products must be new.

2.2 TELECOMMUNICATIONS ROOM PLYWOOD

A.

3/4” fire retardant plywood, grade A-C. If fire retardant plywood is not available, then a substitute of ¾” plywood, grade A-C painted with two coats of fire retardant paint is also acceptable. The backboards must be painted to match the room color but the fire rated stamp must be kept visible for inspection services.

2.3 TELECOMMUNICATIONS ROOM CABLE TRAY

A.

Approved Manufacturers:

1.

Hoffman

2.

Cooper B-Line

TELECOMMUNICATIONS ROOM FINISHES

Version 12DEC2007

271107 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

3.

Chatsworth Products Inc.

4.

Other approved equal submitted in advance as required in SOW

PART 3 - EXECUTION

3.1 TELECOMMUNICATIONS ROOM FINISHES

A.

New TR’s must be free from dust, dirt, and other foreign materials before the installation of any termination hardware or the termination of copper or fiber optic cables. The door to the telecommunication rooms must be permanently installed and closed during termination.

B.

Each Contractor shall be knowledgeable of work to be performed by other trades and take necessary steps to integrate and coordinate their work with other trades.

C.

The Contractor shall be responsible for furnishing all materials on the drawings or as specified herein for a complete telecommunications system.

D.

All surface raceway in new buildings must be approved in advance by CNM ITS.

E.

All telecommunications infrastructure shall be installed for optimal performance.

F.

All telecommunications infrastructure shall be installed for easy moves, adds, and changes in the future.

G.

All work performed in occupied spaces shall be in a manner that allows the owner to operate the existing facilities on a continuous basis.

H.

All anticipated/planned user outages, including wireless access points, shall be submitted to the CNM ITS for approval (10) ten working days before starting work.

3.2 BACKBOARDS

A.

Install 3/4” fire-retardant plywood vertically on all walls 6 inches above finished floor and 6 inches away from all corners.

B.

No mechanical/electrical equipment or conduits shall be installed on or across the plywood or impair the routing of telecommunication cables.

C.

Fire-retardant stamp to be visible or painted with appropriate fire retardant paint to match existing room color.

3.3 CABLE TRAY

A.

Install cable tray around entire perimeter of telecommunications room.

B.

Install cable tray above all equipment frames and attach to cable tray around perimeter of room.

C.

Install horizontal cable tray at 7’2” AFF. Contact CNM ITS if there are conflicts in mounting heights.

D.

Install additional horizontal and vertical sections of cable tray on walls where OSP cables, riser cables, and large bundles of horizontal cables route from conduits entering/exiting the room.

TELECOMMUNICATIONS ROOM FINISHES

Version 12DEC2007

271107 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

E.

Horizontal cable tray routed around perimeter of the ER room shall be installed in such a way that the route for future “unprotected” OSP cabling does not pass through, on, or in front of the cable tray containing “unprotected” UTP cabling.

3.4 ELECTRICAL OUTLETS

A.

Affix engraved plastic legend plates to all electrical outlet covers indicating circuit number and panel of origin.

B.

Electrical outlets designated for UPS units located behind equipment frames shall have engraved plastic legend plates indicating reading “UPS only” and contain the circuit number, and panel of origin.

C.

Electrical outlets designated for convenience use shall have engraved plastic legend plates indicating reading “Convenience Only” and contain the circuit number, and panel of origin.

Engraved label to match color of corresponding receptacle.

D.

Each circuit serving the telecommunication room shall have a critical circuit tag affixed adjacent to breaker/switch. Panel schedules/directories shall be labeled to indicate the outlets within the telecommunications room. A schedule and a room diagram must be posted within the ER/TR.

E.

A labeling scheme for electrical receptacles to ensure all outlets are labeled as to their panel, panel location, breaker, amps & volts can be found in Section 270553, Identification of

Communication Systems.

F.

A labeling scheme for the panels that indicates the receptacle location can be found in Section

270553, Identification of Communication Systems.

G.

Drawings may reflect additional outlets for future racks be extended and terminated on the ceiling above the racks.

H.

Outlets for other special systems (audio-visual, security, etc.) to be provided by others.

Service to these systems will NOT be run to the panel dedicated for telecommunications in the

ER/TR. They must be connected to a separate panel outside the room unless noted otherwise.

I.

For new construction and remodels locate the sub panel that feeds the ER/TR located within the ER/TR. Panel must accommodate current circuit capacity plus 50% growth.

J.

Distinguish between receptacles intended for essential data equipment (Equipment Outlets) and non-essential equipment (Convenience Outlets)

1.

Rack Equipment Outlets a.

Two duplex 20A, 120V receptacles mounted above each rack location in a single

4x4 box. Each duplex receptacle served by a dedicated 20A, 120V circuit independently grounded. b.

One 30A, 208V circuit with L6 receptacle mounted above each rack location in a single 4x4 box independently grounded. c.

A dedicated electrical conduit must be provided for each rack location. Circuits may share the same conduit for each rack location. Minimum Conduit size 1" (in case circuits need to be added)

TELECOMMUNICATIONS ROOM FINISHES

Version 12DEC2007

271107 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

Convenience Outlets: a.

Each wall shall be provisioned with a minimum of two duplex 20A, 120V receptacles mounted in a singlegang box with dedicated 3/4" conduit to panel.

Each duplex receptacle served by a dedicated 20A, 120V circuit independently grounded. Receptacle to be Gray in color with stainless steel cover.

END OF SECTION 271107

TELECOMMUNICATIONS ROOM FINISHES

Version 12DEC2007

271107 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271119 – COMMUNICATIONS TERMINATION BLOCKS AND

PATCH PANELS

PART 1 - GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of termination blocks and patch panels as described on the drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271313 Communications Copper Backbone Cabling.

D.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

E.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

F.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

G.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

H.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

I.

Division 27, Section 271543 Communications Faceplates and Connectors.

1.3 SUBMITTALS

A.

Product Data: For features, ratings, and performance of each component specified.

B.

Submit manufacturer’s instructions for storage, handling, protection, examination, preparation, operation, and installation of products. Include application conditions or limitations of use stipulated by any product testing agency. Submit for the following:

1.

110 Blocks.

2.

Patch Panels.

3.

Wall mount bracket.

4.

Wire management.

5.

Fiber Enclosures.

C.

Shop Drawings:

1.

Component List: List manufacturer, part number, and quantity of each component.

COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

Version 12DEC2007

271119 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

Include dimensioned plan and elevation views of equipment rooms, labeling each individual component. Show equipment rack assemblies, method of field assembly, workspace requirements, and access for cable connections.

1.3 QUALITY ASSURANCE

A.

Manufacturer Qualifications: ISO 9001 Certified, for components that are required to have submittals provided as part of this Section.

B.

Installer Qualifications:

1.

A firm currently engaged and which has been continuously engaged for the past 5 years in the installation of low voltage applications of type required for this Project, and which is licensed in and has obtained or will obtain the necessary permits to perform telecommunications installations in jurisdiction where Project is located.

2.

Have a BICSI certified RCDD locally on staff

3.

Provide references of the type of installation provided in this specification.

4.

Have personnel knowledgeable in local, state, and national codes and the latest TIA

Telecommunications Standards and Manufacturer’s recommendations.

5.

Have personnel fluent in the use of AutoCAD version 2002 or later and possess and operate CAD software capable of producing .DWG or .DXF format.

C.

Source Limitations: Obtain units of the same type of equipment through one source from a single manufacturer.

D.

Product Options: Drawings indicate size, profiles, and dimensional requirements of equipment, accessories, and components and are based on the specific system indicated.

Refer to Division 01 Section “Product Requirements.”

1.

Do not modify intended aesthetic effects or performance, as judged solely by

Architect, except with Architect’s approval. If modifications are proposed, submit comprehensive explanatory data to Architect for review.

E.

Materials and labor shall comply with applicable requirements of following standards, using latest version of associated appendices and Technical Service Bulletins at the time of award of the Contract;

1.

EIA/TIA-568.

2.

EIA/TIA-569.

3.

EIA/TIA-606.

4.

EIA/TIA-607.

5.

Underwriter’s Laboratory.

6.

FCC (including CFR 47 and Part 68 – Subpart F).

7.

National Electric Code.

COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

Version 12DEC2007

271119 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

8.

Local and State Codes.

9.

ISO/I/EC 11801.

10.

IEC 1000-5-2.

11.

IEC 60603-7.

PART 2 - PRODUCTS

2.1 110 BLOCKS

A.

110 Termination Blocks for Copper Riser Cables

1.

110 Block

2.

5-pair 110 Connecting Blocks

3.

Designation Label Holder

4.

110 Designation Labels

B.

110 Termination Blocks for Copper Horizontal Cables

1.

Field termination kit

2.

Field termination kit includes wiring block, (5) 4-pair connector blocks and (1) 5-pair connector block for each 25 pair wiring strip, and labels.

C.

Approved Manufacturers:

12.

Commscope

13.

Leviton

14.

Hubbell

15.

Other approved equal submitted in advance as required in SOW

2.2 PATCH PANELS

A.

Where Category 6 cabling is required:

1.

Category 6, T568B wired patch panel, with 48 ports.

B. Approved Manufacturers:

16.

Commscope

17.

Leviton

18.

Hubbell

19.

Other approved equal submitted in advance as required in SOW

COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

Version 12DEC2007

271119 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.3 WALL MOUNT BRACKET FOR PATCH PANELS

A.

Wall mounted bracket must be designed to work with manufacturer patch panel.

B.

Must be swing out style with reversible hinge

C.

Approved Manufacturers:

1.

Hoffman

2.

Cooper B-Line

3.

APW

4.

Other approved equal submitted in advance as required in SOW

2.4 WIRE MANAGEMENT FOR EQUIPMENT FRAMES

A.

Horizontal Wire Management for copper

1.

Provide 2U high horizontal wire management with covers.

B.

Vertical Wire Management for copper

1.

Provide 4” W x 6” D vertical wire management with covers on the front and back and on either side of each equipment rack.

2.

Bracket kit required for wire management between adjacent frames

C.

Horizontal Fiber Management Panel for fiber

1.

Provide 2U high horizontal wire management with covers.

D.

Approved Manufacturers:

1.

Panduit

2.

Cooper B-Line

3.

Chatsworth

4.

Other approved equal submitted in advance as required in SOW

2.5 FIBER ENCLOSURES

A.

Wall Mounted Fiber Enclosures

1.

Must accept 6 port adapters

B.

Frame Mounted Fiber Enclosures for Riser and Horizontal Fiber

1.

Must accept 6-port adapters

COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

Version 12DEC2007

271119 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

C. Approved Manufacturers:

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

PART 3: EXECUTION

3.1 110-BLOCK INSTALLATION

A.

The ER and TR shall contain wiring blocks as required to terminate all incoming pairs and all outgoing pairs to all TRs.

B.

Locate telephone wiring blocks on fire-treated plywood backboards as specified on the

Drawings or as specified herein.

C.

ER block labeling for riser cables shall designate the corresponding destination TR wiring block.

D.

ER/TR terminal boards shall be equipped with closed “D” rings for horizontal and vertical wire management as directed by CNM ITS.

E.

Horizontally separate 110 blocks 12” apart for horizontal cable by floor. Start 110 blocks 6” from the top of the backboard. In the ER, horizontally separate 110 blocks 12” away from entrance protectors. If entrance protectors are not installed, leave enough space as specified above (protector dimension= 14.75” width by 11” height).

F.

Horizontal cables shall enter new 110 blocks from the left side. Cables shall not be routed behind 110 blocks. In cases where existing cables have been routed behind the 110 blocks, contact CNM ITS before proceeding with new cable installation.

G.

Telecommunication rooms feeding multiple floors

1.

Install 110 blocks for each floor in a separate vertical row with each row separated 12” apart horizontally.

3.2 PATCH PANEL INSTALLATION

A.

Each ER/TR shall contain patch panels as required to terminate all pairs on its respective floor or floors served.

B.

Locate patch panels in 19” equipment frames as specified on the Drawings or as specified herein.

C.

Patch panels and wire management to be mounted in equipment frames no higher than 6’- 0”

A.F.F. and no lower than 3’-6” (42”) A.F.F.

D.

Alternate patch panels with horizontal wire management panels in equipment frame. CNM

ITS to furnish final layout sketch after final confirmed jack count is furnished by Contractor.

E.

Where additional equipment frames are required, separate the frames using one vertical cable manager.

COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

Version 12DEC2007

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

F.

Include vertical cable manager on both sides of equipment rack and on front and back.

G.

Patch panels for buildings with a TR too small for an equipment frame shall utilize wall mountable brackets to mount the horizontal wire management and patch panels.

3.3 FIBER PANEL INSTALLATION

A.

Wall Mounted Installations

1.

Mount fiber enclosures on the wall adjacent or next to equipment frame where applicable.

Verify WIC box use and location with CNM ITS unless otherwise shown on the drawings.

2.

Enclosures for multimode fiber to be complete with multimode SC connector panels.

3.

Enclosures for single-mode fiber to be complete with single-mode SC connector panels.

4.

Wall mounted fiber enclosure installations are only to be used when the telecommunications room does not have adequate space for an equipment frame.

B.

Equipment Frame Installations

1.

Install frame mounted fiber enclosures at the top of the equipment frames where applicable. Verify frame mounted fiber enclosure use and location with CNM ITS unless otherwise shown on the drawings.

2.

Install horizontal fiber management panel for every frame mounted fiber enclosure used.

Alternate fiber enclosure panels with the fiber management panels.

3.

Allow 8 inches at the top of the mountable portion of the ER equipment frame when OSP fiber has not yet been installed.

4.

Enclosures for multimode fiber to utilize 6-port duplex SC style MM panels per 12-strand multimode fiber. Enclosures for singlemode fiber to utilize 6-port duplex SC style SM panels per 12-strand single-mode fiber. Single-mode fiber to be installed on the left side of all panels while multimode fiber is to be installed on the right hand side of the panels.

Verify frame mounted fiber enclosure layout with CNM ITS unless otherwise shown on the drawings.

5.

In the TRs, install: a.

Horizontal fiber wire management at the top of the equipment frame. b.

Enclosures for multimode fiber to utilize 6-port duplex SC style MM panels per 12strand multimode fiber. Enclosures for single-mode fiber to utilize 6-port duplex SC style SM panels per 12-strand single-mode fiber. Single-mode fiber to be installed on the left side of all panels while multimode fiber is to be installed on the right hand side of the panels.

6.

Owner shall provide location for mounting enclosures if not shown on drawings.

7.

Typically, multimode fiber is terminated in enclosures in every telecommunications room.

Single-mode fiber is always terminated in a rack mounted panel in every telecommunications room unless an equipment frame is not present within the room.

END OF SECTION 271119

COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

Version 12DEC2007

271119 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271300 - COMMUNICATIONS BACKBONE CABLING

PART 1 - GENERAL

1.1

RELATED DOCUMENTS

A.

Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

1.2

SUMMARY

A.

Section Includes:

1.

Pathways.

2.

UTP cable.

3.

Multimode optical fiber cabling.

4.

Singlemode optical fiber cabling.

5.

Coaxial cable.

6.

Cable connecting hardware, patch panels, and cross-connects.

7.

Cabling identification products.

RELATED SECTIONS 1.3

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

H.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

I.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

J.

Division 27, Section 271543 Communications Faceplates and Connectors.

1.4

DEFINITIONS

A.

BICSI: Building Industry Consulting Service International.

B.

Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

C.

EMI: Electromagnetic interference.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 1

D.

IDC: Insulation displacement connector.

E.

LAN: Local area network.

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

F.

RCDD: Registered Communications Distribution Designer.

1.5

G.

UTP: Unshielded twisted pair.

BACKBONE CABLING DESCRIPTION

A.

Backbone cabling system shall provide interconnections between communications equipment rooms, main terminal space, and entrance facilities in the telecommunications cabling system structure. Cabling system consists of backbone cables, intermediate and main cross-connects, mechanical terminations, and patch cords or jumpers used for backbone-to-backbone cross-connection.

1.6

B.

Backbone cabling cross-connects may be located in communications equipment rooms or at entrance facilities. Bridged taps and splitters shall not be used as part of backbone cabling.

PERFORMANCE REQUIREMENTS

1.7

A.

General Performance: Backbone cabling system shall comply with transmission standards in TIA/EIA-568-B.1, when tested according to test procedures of this standard.

SUBMITTALS

A.

Product Data: For each type of product indicated.

1.

For coaxial cable, include the following installation data for each type used: a.

Nominal OD. b.

Minimum bending radius. c.

Maximum pulling tension.

B.

Shop Drawings:

1.

System Labeling Schedules: Electronic copy of labeling schedules, in software and format selected by Owner.

2.

System Labeling Schedules: Electronic copy of labeling schedules that are part of the cabling and asset identification system of the software.

3.

Cabling administration drawings and printouts.

4.

Wiring diagrams to show typical wiring schematics including the following: a.

Cross-connects. b.

Patch panels.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) c.

Patch cords.

5.

Cross-connects and patch panels. Detail mounting assemblies, and show elevations and physical relationship between the installed components.

6.

Cable tray layout, showing cable tray route to scale, with relationship between the tray and adjacent structural, electrical, and mechanical elements. Include the following: a.

Vertical and horizontal offsets and transitions. b.

Clearances for access above and to side of cable trays. c.

Vertical elevation of cable trays above the floor or bottom of ceiling structure. d.

Load calculations to show dead and live loads as not exceeding manufacturer's rating for tray and its support elements.

1.8

C.

Qualification Data: For qualified layout technician, installation supervisor, and field inspector.

QUALITY ASSURANCE

A.

Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff.

1.

Layout Responsibility: Preparation of Shop Drawings and Cabling Administration

Drawings and field testing program development by an RCDD.

2.

Installation Supervision: Installation shall be under the direct supervision of

Registered Technician, who shall be present at all times when Work of this Section is performed at Project site.

3.

Testing Supervisor: Currently certified by BICSI as an RCDD to supervise on-site testing.

B.

The Contractor shall be a Certified Cable Installer, with the capability of providing a manufacturer’s certification of not less than 25 years as a minimum, for the low-voltage cabling and associated termination equipment.

C.

Electrical Components, Devices, and Accessories: Listed and labeled as defined in

NFPA 70, by a qualified testing agency, and marked for intended location and application.

D.

Telecommunications Pathways and Spaces: Comply with TIA/EIA-569-A.

E.

Grounding: Comply with ANSI-J-STD-607-A.

1.9

DELIVERY, STORAGE, AND HANDLING

A.

Test cables upon receipt at Project site.

1.

Test optical fiber cable to determine the continuity of the strand end to end.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

Test optical fiber cable while on reels. Use an optical time domain reflectometer to verify the cable length and locate cable defects, splices, and connector, including the loss value of each. Retain test data and include the record in maintenance data.

3.

Test each pair of UTP cable for open and short circuits.

1.10

PROJECT CONDITIONS

A.

Environmental Limitations: Do not deliver or install cables and connecting materials until plumbing in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period.

1.11

COORDINATION

A.

Coordinate layout and installation of telecommunications pathways and cabling with

Owner's telecommunications and LAN equipment and service suppliers.

1.12

SOFTWARE

1.

Any software provided to CNM ITS is to be provided in the original packaging along with any instruction booklets.

2.

Software associated with test equipment used to open native files must be provided as a deliverable if the test results. No test results will be provided in hard copy unless stated otherwise.

3.

Software required to view contractor created drawings or sketches (AutoCAD, Visio, etc.) must be provided when the electronic files are submitted on CD or DVD. This applies to viewer software only such as VoloView, etc.

1.13

EXTRA MATERIALS

A.

Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1.

Patch-Panel Units: Equal to 10% of the installed type rounded up.

2.

Connecting Blocks: Equal to 10% of the installed type rounded up.

PART 2 - PRODUCTS

2.1

PATHWAYS

A.

General Requirements: Comply with TIA/EIA-569-A.

B.

Cable Support: NRTL labeled for support of Category 6 cabling, designed to prevent degradation of cable performance and pinch points that could damage cable.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Support brackets with cable tie slots for fastening Velcro ties to brackets.

2.

Spools, J-hooks, and D-rings.

3.

Straps and other devices.

C.

Cable Trays:

1.

Approved Manufacturers: a.

Cablofil b.

Cooper B-Line c.

Chatsworth Products Inc. d.

Other approved equal submitted in advance as required in SOW

2.

Cable Tray Material: Metal, suitable for indoors, and protected against corrosion. a.

Basket Cable Trays: Minimum dimensions given as 6 inches (150 mm) wide and

2 inches (50 mm) deep. Wire mesh spacing shall not exceed 2 by 4 inches (50 by 100 mm). b.

Trough Cable Trays: Minimum dimensions given as nominally 6 inches (150 mm) wide. c.

Ladder Cable Trays: Minimum dimensions given as nominally 12 inches (305 mm) wide, and a rung spacing of 12 inches (305 mm). d.

Channel Cable Trays: One-piece construction, minimum dimensions given as nominally 4 inches (100 mm) wide. Slot spacing shall not exceed 4-1/2 inches

(115 mm) o.c. e.

Solid-Bottom Cable Trays: One-piece construction, minimum dimensions given as nominally 12 inches (305 mm) wide. Provide without solid covers.

D.

Conduit and Boxes: Comply with requirements in Division 27, Section 270528 Pathways for Communication Systems and Section 270500 Common Work Results for

Communications Flexible metal conduit shall not be used.

1.

Outlet boxes shall be no smaller than 4 inches (100 mm) wide, 4 inches (100 mm) high, and 2-1/2 inches (64 mm) deep.

UTP CABLE 2.2

A.

Approved Manufacturers:

1.

Commscope

2.

Berktek

3.

Essex

4.

Other approved equal submitted in advance as required in SOW

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Description: 100-ohm, 25-pair UTP, covered with a thermoplastic jacket.

1.

Comply with ICEA S-90-661 for mechanical properties.

2.

Comply with TIA/EIA-568-B.1 for performance specifications.

3.

Comply with TIA/EIA-568-B.2, Category 6.

4.

Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70 for the following types: a.

Communications, Plenum Rated: Type CMP, complying with NFPA 262. b.

Multipurpose, Plenum Rated: Type MPP, complying with NFPA 262.

2.3

UTP CABLE HARDWARE

A.

Approved Manufacturers:

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

B.

General Requirements for Cable Connecting Hardware: Comply with TIA/EIA-568-B.2,

IDC type, with modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of same category or higher.

C.

Connecting Blocks: 110-style IDC for Category 6. Provide blocks for the number of cables terminated on the block, plus 25 percent spare. Integral with connector bodies, including plugs and jacks where indicated.

D.

Cross-Connect: Modular array of connecting blocks arranged to terminate building cables and permit interconnection between cables.

1.

Number of Terminals per Field. One for each conductor in assigned cables.

E.

Patch Panel: Modular panels housing multiple-numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables.

1.

Number of Jacks per Field: One for each four-pair conductor group of indicated cables, plus spares and blank positions adequate to suit specified expansion criteria.

2.4

F.

Jacks and Jack Assemblies: Modular, color-coded, eight-position modular receptacle units with integral IDC-type terminals.

CATEGORY 6 PATCH CORDS

A.

Shall be round, and consist of 8 insulated 24 AWG stranded copper conductors arranged in 4 color-coded twisted-pairs within flame-retardant jacket.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Be equipped with modular 8-position plugs on both ends, wired straight through with standards compliant wiring.

C.

Use modular plugs, which exceed FCC CFR 47 Part 68 Subpart F and IEC 60603-7 specifications, and have 50 microinches (0.0013 mm) minimum of gold plating over nickel contacts.

D.

Be resistant to corrosion from humidity, extreme temperatures, and airborne contaminants.

E.

Utilize cable that exhibits power sum NEXT performance.

F.

Be available in several colors with or without color strain relief boots providing snagless design.

G.

Meet flex test requirements of 1000 cycles with boot5s and 100 cycles without boots.

H.

Be available in any custom length and standard lengths of 3, 5, 7, 10, 15, 20, and 25 feet (.9,

1.5, 2.1, 3, 4.6, 6.1, and 7.6 m).

I.

Be made by ISO 9001 certified manufacturer.

J.

Electrical Specifications:

1.

Input Impedance Without Averaging: 100 ohms plus or minus 15 percent from 1 to

100 MHz.

2.

One hundred percent transmission tested for performance up to 100 MHz.

Manufacturer shall guarantee cords are compatible with Category 6 links.

3.

Utilize cable that is UL verified (or equivalent) for TIA/EIA proposed Category 6 electrical performance.

4.

UL listed 1863.

K.

Horizontal Workstation Colors:

1.

All horizontal cabling will consist of Plenum rated cable regardless of Plenum environment and will be Blue in color.

2.5

L.

Approved Manufacturers:

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

OPTICAL FIBER CABLE HARDWARE

A.

Approved Manufacturers:

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 7

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

B.

Cross-Connects and Patch Panels: Modular panels housing multiple-numbered, duplex cable connectors.

1.

Number of Connectors per Field: One for each fiber of cable or cables assigned to field, plus spares and blank positions adequate to suit specified expansion criteria.

C.

Cable Connecting Hardware:

1.

Comply with Optical Fiber Connector Intermateability Standards (FOCIS) specifications of TIA/EIA-604-2, TIA/EIA-604-3-A, and TIA/EIA-604-12. Comply with TIA/EIA-568-B.3.

2.

Quick-connect, simplex and duplex, Type SC, Type ST, Type LC, Type MT-RJ connectors. Insertion loss not more than 0.75 dB. Contact CNM ITS for required type of connector for the project.

2.6

OPTICAL FIBER PATCH CORDS – MULTIMODE

A.

Shall be available in standard lengths of 3.6, 10, and 16.4 feet (1, 3, and 5 meters), custom lengths shall also be available, and shall meet or exceed standards as defined in

ANSI/TIA/EIA-568 and ISO/IEC 11801.

B.

Utilize duplex optical fiber cable that is 62.5/125 or 50/125 micron multimode, OFNR riser grade, and meets the requirements of UL 1666.

C.

Utilize optical fiber cable where the attenuation shall not exceed 3.5 dB/km at 850 nm wavelength or 1.0 dB/km at 1300 nm.

D.

Cable Jacket Color:

1.

62.5/125: Orange.

2.

50/125: Aqua.

E.

Be equipped with SC type in accordance with TIA/EIA-568 and must include a ceramic ferrule.

F.

Have terminated connectors exhibit maximum insertion loss of 0.25 dB with average of 0.20 dB or better when tested at either 850 nm or 1300 nm wavelengths for 62/125 um.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 8

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

G.

Have terminated connectors exhibit maximum insertion loss of 0.25 dB with average of 0.20 dB or better when tested at either 850 nm or 1300 nm wavelengths for 50/125 um.

H.

Have average return loss of 2.5 dB with minimum return loss of 2.0 dB at both 850 nm and

1300 nm.

I.

Be made by ISO 9001 certified manufacturer.

J.

Be UL 1666 approved.

K.

Shall be duplex fiber cable meeting or exceeding transmission characteristics of optical fiber horizontal cable.

L.

Connectors shall be duplex T568SC, as indicated on Drawings or equipment schedules.

1.

Jacket Color: Orange.

M.

Following configurations may be required:

1.

SC type/SC type

2.

ST type/SC type

3.

ST Type/LC Type

4.

SC Type/LC Type

5.

ST Type/ST Type

6.

LC Type/LC Type

N.

Approved Manufacturers:

1.

Quiktron

2.

Commscope

3.

OCC

4.

Other approved equal submitted in advance as required in SOW

2.7

OPTICAL FIBER PATCH CORDS – SINGLE MODE

A.

Available in standard lengths of 3, 6, 10, and 16.4 feet (1, 2, 3, and 5 meters), custom lengths shall also be available, and shall meet or exceed standards as defined in

ANSI/TIA/EIA-568 and ISO/IEC 11801.

B.

Be either simplex or duplex OFNR riser grade cable, with attenuation at wavelength 1310 nm being 1.0 dB/km and at wavelength 1550 nm 1.0 db/km.

C.

Jacket Color: Yellow.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 9

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

D.

Connectors shall be SC type in accordance with TIA/EIA-568 and must include a ceramic ferrule.

E.

Terminated connectors shall exhibit a maximum insertion loss of 0.50 db with an average of

0.25 dB when tested at either 1310 nm or 1660 nm wavelengths for singlemode fiber.

F.

Have average return loss of 53 db with minimum return loss of 40 dB at both 1310 and 1550 nm.

G.

Be made by ISO 9002 certified manufacturer.

H.

Be UL 1666 approved.

I.

Approved Manufacturers:

1.

Quiktron

2.

Commscope

3.

OCC

4.

Other approved equal submitted in advance as required in SOW

2.8

COAXIAL CABLE

A.

Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1.

Belden

2.

Commscope

3.

General

4.

Other approved equal submitted in advance as required in SOW

B.

General Coaxial Cable Requirements: Broadband type, recommended by cable manufacturer specifically for broadband data transmission applications. Coaxial cable and accessories shall have 75-ohm nominal impedance with a return loss of 20 dB maximum from 7 to 806 MHz.

C.

RG-11/U: NFPA 70, Type CMP.

1.

No. 14 AWG, solid, copper-covered steel conductor.

2.

Gas-injected, foam-PE insulation.

3.

Double shielded with 100 percent aluminum polyester tape and 60 percent aluminum braid.

4.

Plenum rated.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 10

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

5.

Suitable for outdoor installations in ambient temperatures ranging from minus 40 to plus 85 deg C.

D.

RG59/U: NFPA 70, Type CMP.

1.

No. 20 AWG, solid, silver-plated, copper-covered steel conductor.

2.

Gas-injected, foam-PE insulation.

3.

Triple shielded with 100 percent aluminum polyester tape and 95 percent aluminum braid; covered by aluminum foil with grounding strip.

4.

Plenum Rated.

E.

RG-6/U: NFPA 70, Type CMP.

1.

No. 16 AWG, solid, copper-covered steel conductor; gas-injected, foam-PE insulation.

2.

Double shielded with 100 percent aluminum-foil shield and 60 percent aluminum braid.

3.

Plenum rated.

4.

Suitable for indoor installations.

F.

RG59/U: NFPA 70, Type CATV.

1.

No. 20 AWG, solid, copper-covered steel conductor; gas-injected, foam-PE insulation.

2.

Double shielded with 100 percent aluminum polyester tape and 40 percent aluminum braid.

3.

Plenum rated.

G.

RG59/U (Plenum Rated): NFPA 70, Type CMP.

1.

No. 20 AWG, solid, copper-covered steel conductor; foam fluorinated ethylene propylene insulation.

2.

Double shielded with 100 percent aluminum-foil shield and 65 percent aluminum braid.

3.

Plenum rated.

2.9

H.

NFPA and UL compliance, listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 1655 and with NFPA 70, "Radio and Television

Equipment" and "Community Antenna Television and Radio Distribution" Articles. Types are as follows:

1.

CATV Plenum Rated: Type CATVP, complying with NFPA 262.

COAXIAL CABLE HARDWARE

A.

Approved Manufacturers:

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 11

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Ideal

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

B.

Coaxial-Cable Connectors: Type BNC or ‘F’ Type, 75 ohms.

2.10

GROUNDING

A.

Comply with requirements in Division 26 Section "Grounding and Bonding for Electrical

Systems." for grounding conductors and connectors.

B.

Comply with ANSI-J-STD-607-A.

2.11

IDENTIFICATION PRODUCTS

A.

Comply with TIA/EIA-606-A and UL 969 for a system of labeling materials, including label stocks, laminating adhesives, and inks used by label printers.

2.12

SOURCE QUALITY CONTROL

A.

Testing Agency: Engage a qualified testing agency to evaluate cables.

B.

Factory test cables on reels according to TIA/EIA-568-B.1.

C.

Factory test UTP cables according to TIA/EIA-568-B.2.

D.

Factory test multimode optical fiber cables according to TIA/EIA-526-14-A and TIA/EIA-

568-B.3.

E.

Cable will be considered defective if it does not pass tests and inspections.

F.

Prepare test and inspection reports.

PART 3 - EXECUTION

3.1

ENTRANCE FACILITIES

3.2

A.

Coordinate backbone cabling with the protectors and demarcation point provided by communications service provider.

WIRING METHODS

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 12

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

Wiring Method: Install plenum cables in raceways and cable trays except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces, in attics, and in gypsum board partitions where unenclosed wiring method may be used. Conceal raceway and cables except in unfinished spaces.

1.

Install plenum cable in all spaces, including plenum and non-plenum ceilings or areas.

2.

Comply with requirements for raceways and boxes specified in Division 27.

B.

Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible.

C.

Wiring within Enclosures: Bundle and train cables within enclosures. Connect to terminal points with no excess and without exceeding manufacturer's limitations on bending radii.

Provide and use distribution spools.

3.3

INSTALLATION OF PATHWAYS

A.

Cable Trays: Comply with NEMA VE 2 and TIA/EIA-569-A.

B.

Comply with requirements for demarcation point, pathways, cabinets, and racks specified in

Division 27 Section "Communications Equipment Room Fittings." Drawings indicate general arrangement of pathways and fittings.

C.

Comply with TIA/EIA-569-A for pull-box sizing and length of conduit and number of bends between pull points.

D.

Comply with requirements in Division 27 for installation of conduits and wireways.

E.

Install manufactured conduit sweeps and long-radius elbows whenever possible.

F.

Pathway Installation in Communications Equipment Rooms:

1.

Position conduit ends adjacent to a corner on backboard where a single piece of plywood is installed, or in the corner of room where multiple sheets of plywood are installed around perimeter walls of room.

2.

Install cable trays to route cables if conduits cannot be located in these positions.

3.

Secure conduits to backboard when entering room from overhead.

4.

Extend conduits 4 inches (100 mm) above finished floor.

5.

Install metal conduits with grounding bushings and connect with grounding conductor to grounding system.

G.

Backboards: Install backboards with 96-inch (2440-mm) dimension vertical. Butt adjacent sheets tightly, and form smooth gap-free corners and joints.

3.4

INSTALLATION OF CABLES

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 13

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

Comply with NECA 1.

B.

General Requirements for Cabling:

1.

Comply with TIA/EIA-568-B.1.

2.

Comply with BICSI ITSIM, Ch. 6, "Cable Termination Practices."

3.

Install 110-style IDC termination hardware unless otherwise indicated.

4.

Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels.

5.

Cables may not be spliced. Secure and support cables at intervals not exceeding 30 inches (760 mm) and not more than 6 inches (150 mm) from cabinets, boxes, fittings, outlets, racks, frames, and terminals.

6.

Install support bars to restrain cables, to prevent straining connections, and to prevent bending cables to smaller radii than minimums recommended by manufacturer.

7.

Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI TDMM,

"Cabling Termination Practices" Chapter.

8.

Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable.

9.

Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not be used for heating.

10.

In the communications equipment room, install a 10-foot- (3-m-) long service loop on each end of cable.

11.

Pulling Cable: Comply with BICSI ITSIM, Ch. 4, "Pulling Cable." Monitor cable pull tensions.

C.

UTP Cable Installation:

1.

Comply with TIA/EIA-568-B.2.

2.

Do not untwist UTP cables more than 1/2 inch (12 mm) from the point of termination to maintain cable geometry.

D.

Optical Fiber Cable Installation:

1.

Comply with TIA/EIA-568-B.3.

2.

Cable may be terminated on connecting hardware that is rack or cabinet mounted.

E.

Open-Cable Installation:

1.

Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment.

2.

Suspend UTP cable not in a wireway or pathway, a minimum of 8 inches (200 mm) above ceilings by cable supports not more than 60 inches (1524 mm) apart.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 14

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

3.

Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items.

F.

Installation of Cable Routed Exposed under Raised Floors:

1.

Install plenum-rated cable only.

2.

Install cabling after the flooring system has been installed in raised floor areas.

3.

Coil cable 6 feet (1800 mm) long not less than 12 inches (300 mm) in diameter below each feed point.

G.

Outdoor Coaxial Cable Installation:

1.

Install outdoor connections in enclosures complying with NEMA 250, Type 4X.

Install corrosion-resistant connectors with properly designed O-rings to keep out moisture.

2.

Attach antenna lead-in cable to support structure at intervals not exceeding 36 inches

(915 mm).

H.

Group connecting hardware for cables into separate logical fields.

I.

Separation from EMI Sources:

1.

Comply with BICSI TDMM and TIA/EIA-569-A recommendations for separating unshielded copper voice and data communication cable from potential EMI sources, including electrical power lines and equipment.

2.

Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows: a.

Electrical Equipment Rating Less Than 2 kVA: A minimum of 5 inches (127 mm). b.

Electrical Equipment Rating between 2 and 5 kVA: A minimum of 12 inches

(300 mm). c.

Electrical Equipment Rating More Than 5 kVA: A minimum of 24 inches (610 mm).

3.

Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows: a.

Electrical Equipment Rating Less Than 2 kVA: A minimum of 2-1/2 inches (64 mm). b.

Electrical Equipment Rating between 2 and 5 kVA: A minimum of 6 inches

(150 mm). c.

Electrical Equipment Rating More Than 5 kVA: A minimum of 12 inches (300 mm).

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 15

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

4.

Separation between communications cables in grounded metallic raceways and power lines and electrical equipment located in grounded metallic conduits or enclosures shall be as follows: a.

Electrical Equipment Rating Less Than 2 kVA: No requirement. b.

Electrical Equipment Rating between 2 and 5 kVA: A minimum of 3 inches (76 mm). c.

Electrical Equipment Rating More Than 5 kVA: A minimum of 6 inches (150 mm).

5.

Separation between Communications Cables and Electrical Motors and Transformers,

5 kVA or HP and Larger: A minimum of 48 inches (1200 mm).

6.

Separation between Communications Cables and Fluorescent Fixtures: A minimum of

5 inches (127 mm).

3.5

FIRESTOPPING

A.

Comply with requirements in Division 27.

B.

Comply with BICSI TDMM, "Firestopping Systems" Article.

3.6

GROUNDING

A.

Install grounding according to BICSI

Protection" Chapter.

B.

Comply with ANSI-J-STD-607-A.

C.

Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall allowing at least 2-inch (50-mm) clearance behind the grounding bus bar. Connect grounding bus bar with a minimum No. 4 AWG grounding electrode conductor from grounding bus bar to suitable electrical building ground.

3.7

D.

Bond metallic equipment to the grounding bus bar, using not smaller than No. 6 AWG equipment grounding conductor.

IDENTIFICATION

A.

Identify system components, wiring, and cabling complying with TIA/EIA-606-A. Comply with requirements for identification specified in Division 26 Section "Identification for

Electrical Systems."

1.

Color-code cross-connect fields and apply colors to voice and data service backboards, connections, covers, and labels.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 16

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Comply with requirements in Division backboards. For fire-resistant plywood, do not paint over manufacturer's label.

C.

See Division 27 Section "Communications Horizontal Cabling" for additional identification requirements. See Evaluations for discussion about TIA/EIA standard as it applies to this

Section. Paint and label colors for equipment identification shall comply with TIA/EIA-606-

A.

D.

Comply with requirements in Division 27 Section "Communications Horizontal Cabling" for cable and asset management software.

E.

Cable Schedule: Install in a prominent location in each equipment room and wiring closet.

List incoming and outgoing cables and their designations, origins, and destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final comprehensive schedules for Project.

F.

Cabling Administration Drawings: Show building floor plans with cabling administrationpoint labeling. Identify labeling convention and show labels for telecommunications closets, terminal hardware and positions, horizontal cables, work areas and workstation terminal positions, grounding buses and pathways, and equipment grounding conductors.

G.

Cable and Wire Identification:

1.

Label each cable within 4 inches (100 mm) of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated.

2.

Each wire connected to building-mounted devices is not required to be numbered at device if color of wire is consistent with associated wire connected and numbered within panel or cabinet.

3.

Label each terminal strip and screw terminal in each cabinet, rack, or panel. a.

Individually number wiring conductors connected to terminal strips and identify each cable or wiring group being extended from a panel or cabinet to a buildingmounted device with name and number of particular device as shown. b.

Label each unit and field within distribution racks and frames.

4.

Identification within Connector Fields in Equipment Rooms and Wiring Closets:

Label each connector and each discrete unit of cable-terminating and connecting hardware. Where similar jacks and plugs are used for both voice and data communication cabling, use a different color for jacks and plugs of each service.

H.

Labels shall be preprinted or computer-printed type with printing area and font color that contrasts with cable jacket color but still complies with requirements in TIA/EIA 606-A, for the following:

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 17

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Cables use flexible vinyl or polyester that flexes as cables are bent.

FIELD QUALITY CONTROL 3.8

A.

Perform tests and inspections. Random testing will be performed by CNM ITS during the testing phase. A confidence factor must be demonstrated prior to system certification by manufacturer.

B.

Tests and Inspections:

1.

Visually inspect UTP and optical fiber jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments, and inspect cabling connections for compliance with TIA/EIA-568-B.1.

2.

Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.

3.

Test UTP copper cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks.

Test cables after termination but not cross-connection. a.

Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-

B.2. Perform tests with a tester that complies with performance requirements in

"Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.

4.

Optical Fiber Cable Tests: a.

Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-

B.1. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration. b.

Link End-to-End Attenuation Tests:

1) Horizontal and multimode backbone link measurements: Test at 850 or

1300 nm in 1 direction according to TIA/EIA-526-14-A, Method B, One

Reference Jumper.

2) Attenuation test results for backbone links shall be less than 2.0 dB.

Attenuation test results shall be less than that calculated according to equation in TIA/EIA-568-B.1.

C.

Data for each measurement shall be documented. Test results will be maintained in the test manufacturer native format and provided on CD only along with native reader software.

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 18

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

D.

Remove and replace cabling where test results indicate that they do not comply with specified requirements.

E.

End-to-end cabling will be considered defective if it does not pass tests and inspections.

F.

Prepare test and inspection reports.

END OF SECTION 271300

COMMUNICATIONS BACKBONE CABLING

Version 12DEC2007

271300 - 19

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271313 – COMMUNICATIONS COPPER BACKBONE CABLING

PART 1 - GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of copper backbone infrastructure as described on the Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270543 Underground Ducts and Raceways for Communication Systems.

C.

Division 27, Section 270553 Identification for Communication Systems.

D.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

1.3 COORDINATION

A.

Contractor shall coordinate the work specified in this Section with the work in other parts of the Contract document.

B.

Plans in general are diagrammatic. It is the full responsibility of the Contractor to be familiar with the location of equipment involved under the work of other trades to eliminate conflicts between the multipair copper cable installation and the work of other trades.

C.

All questions and issues with regard to coordination shall be directed to the CNM ITS.

1.4 SUBMITTALS

A.

All submittals for substitutions shall be made to the CNM ITS.

B.

The Contractor shall submit a Copper cable pulling plan for all multipair copper cables with a pair count of 25 pairs or greater, that includes, but is not limited to, the following:

1.

Each cable run and route.

2.

Date and duration of the pull.

3.

Pulling methodology and equipment setups.

4.

Pulling tension calculations for each pull in the run.

5.

Safety issues and precautions to be taken.

1.5 SUBSTITUTIONS

A.

Intent of Specifications:

COMMUNICATIONS COPPER BACKBONE CABLING

Version 12DEC2007

271313 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Where specified only by reference standards, select any product meeting standards by any manufacturer.

2.

Where specified by naming several products or manufacturers, select any product and manufacturer named that meets the specified requirements. Other products and manufacturers will not be considered.

3.

Where specified by naming one or more products or manufacturers, but indicating "or equivalent" after specified listing, the specified product is the preferred quality standard.

The Contractor may submit a request for another product for acceptance.

4.

Where specified by naming only one product and manufacturer: There is no option and no substitution will be allowed.

B.

Submit requests for substitutions within 10 days of contract award, or sooner if required to maintain the construction schedule.

C.

The Contractor must submit sufficient information to show that a proposed substitute is equivalent to the item specified. Acceptance of substitutions is at CNM ITS discretion: the

CNM ITS reserves the right to determine suitability of the substitute product and reject any and all materials submitted for substitution. All substitute products and materials must be approved for substitution by the CNM ITS in writing prior to installation. Products rejected or otherwise judged unsatisfactory by the CNM ITS will not be authorized for use in completing the Work. Any unapproved products discovered as part of the installation will be removed and replaced with CNM ITS specified and approved products at the Contractor’s expense.

D.

Project Drawings may be based on equipment configuration of a particular manufacturer. If a substitution is approved, the Contractor shall make changes needed to accommodate the substitution at no expense to CNM, including work under other divisions.

1.6 QUALITY ASSURANCE

A.

Verification: The CNM ITS will maintain inspection personnel on the job site. It is incumbent upon the Contractor to verify that the installation and material used has been inspected before it is enclosed within building features, or otherwise hidden from view. The Contractor shall bear costs associated with uncovering or exposing installations or features that have not been inspected.

B.

Equipment Qualifications: The Contractor is to use equipment and rigs designed for pulling, placement and termination of multipair copper cable; including reel trucks, mechanical mules, sheaves, shoes, anchors etc., and equipment for drilling masonry, installing anchors, etc., to install support and cable management hardware.

PART 2 – PRODUCTS

2.1 COPPER CABLE

A.

The cable shall be Bell Specification Filled Aluminum Polyethylene (ALPETH) Sheath cable with Dual Expanded Polyethylene (DEPIC) Insulated Conductors for aerial cabling.

SEALPIC is to be used for all underground cabling in conduit or direct buried applications.

B.

Cable construction shall be as follows:

COMMUNICATIONS COPPER BACKBONE CABLING

Version 12DEC2007

271313 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Conductor - Solid annealed copper in 24 AWG.

2.

Insulation - Dual expanded high density polyethylene (foam skin) with outer skin color coded in accordance with telephone industry standards.

3.

Twisted Pairs – Individual conductors twisted into pairs with varying twists and lay to minimize crosstalk, and specified color combinations to provide pair identification.

4.

Core Assembly – Assembled in units, each individually identified by color coded unit binders. Prior to the application of the outer sheath, and jacket, the core is completely filled with filling compound that resists moisture penetration.

5.

Filling compound – 80 degrees C. expanded thermal plastic rubber, compatible with most commercially available encapsulants. Cleaning of conductors is not required (CSI Flexgel or equivalent).

6.

Shielding System – Corrugated 8 mil electrically contiguous aluminum tape applied longitudinally with overlapped edges over the core wrap. A polyolefin based flooding compound is applied over the aluminum tape.

7.

Jacket – Black, linear low density, high molecular weight polyethylene.

8.

Identification and Length Marking – Manufacturer’s cable code pair size, manufacturing plant location, month and year of manufacture, sequential length markings and telephone handset symbol are imprinted onto jacket every two feet.

C.

Cable Electrical Performance Specifications

1.

Average Mutual Capacitance @ 23 +/- 2 degrees C (nF/mile) – 83 +/- 4.

2.

Capacitance Unbalance @ 23 +/- 2 degrees C.

D.

Maximum pair to pair (pf/kft) – 80; RMS – 25.

3.

Pair to Ground Maximum Capacitance, individual pair – 800;

E.

Cable average > 13 pair 175.

4.

DC Conductor Resistance @ 20 degrees C, individual maximum, (Ohms/kft): 27.3.

5.

Resistance Unbalance Maximum average:- 1.5 %, Maximum individual - 5.0%.

6.

Minimum Dielectric Strength (kV); conductor to conductor, 1 second – 3.0, 3 seconds to sheath – 10.

7.

Insulation Resistance (MegaOhm per mile) 100-550 VDC for 1 minute. – 1000.

8.

Attenuation (dB/kft) 20 degrees C, @ 772 kHz, Maximum average - 7.0.

9.

Equal Level Far End Crosstalk (ELFEXT) (dB/kft) @ 772 kHz, Minimum – Mean Power

Sum – 47; Worst Pair Power Sum – 43.

10.

Near End Crosstalk – (NEXT) (dB/kft) @772 kHz; Minimum; Mean Power Sum – 47;

Worst Pair Power Sum – 42.

E.

The Cable shall be Cable Systems International, 24 AWG Filled Alpeth or approved

Equivalent, Cable Code ANMA.

2.2 PROTECTOR PANELS

A.

Circa 1880 series-Type Multipair Protector Panel, with MS² connector input, 110 connector output, (no substitutions).

1.

25 Pair 110 Block Protector Panel – Circa Product #1880ENP1-25G.

COMMUNICATIONS COPPER BACKBONE CABLING

Version 12DEC2007

271313 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

50 Pair 110 Block Protector Panel – Circa Product #1880ENP1-50G.

3.

100 Pair 110 Block Protector Panel – Circa Product #1880ECP1-100G.

B.

Protector Modules – Circa #C3B1E Individual Protector Units.

1.

Circa #C3B1E, Color: Black, (Standard Service), 3-element gas, (no substitutions).

2.3 NODE CONNECTORS

A.

Corning C-388-100 (388-00243) Pair Connectors E/W 22 AWG stub shall be used on the frame at node location. Match connectors blocks, stub orientation, and stub length used at individual node location. (No substitutions.)

B.

Protector Modules – Lucent Individual Protector Units.

1.

Lucent Product Number 4B1-EW, Color: Black, (Standard Service) Comcode 104 401-

856. (No substitutions.)

2.5 SHIELD BOND CONNECTORS

A.

3M Scotchlok 4460 Series Shield Bond Connectors, or equivalent.

2.6 ENCAPSULANT

A.

3M High Gel Reenterable Encapsulant 3M Part Number 4442, or equivalent

2.7 BLOCKING COMPOUND

A.

3M Haplec Blocking Compound 3M Part Number 4408 or equivalent.

PART 3 - EXECUTION

3.1 CABLE INSTALLATION

A.

The Contractor shall submit the cable pulling plan to the CNM ITS prior to commencement of the operation.

B.

The route of multipair copper cable installation is as described herein or as shown on the

Drawings.

C.

When breaking out any multipair copper cable of 50 pairs or greater for splicing or termination, the binder groups shall have PIC color coded cable ties attached to the cable at the point of fanout from super groups for splicing, and at the point of fanout for termination on termination blocks.

D.

The Contractor shall ensure the cables are pulled into the ducts in a manner observing the bend radii and tension restrictions of the cable.

E.

The Contractor shall use appropriate shoes, guides, wheels and lubricants to prevent damage to the cable jacket and sheath during installation.

F.

Install shield bond connectors to the shields of all cables terminated at the Protector Panels.

G.

The Contractor shall apply an appropriate amount of damming compound over the end of filled copper cables in indoor or dry environments to prevent seepage of cable filling compounds where encapsulant will not be used.

COMMUNICATIONS COPPER BACKBONE CABLING

Version 12DEC2007

271313 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

H.

Prior to closure assembly in dry or indoor installations, all exposed cable pairs shall have the filling compound thoroughly cleaned off the cable insulation using appropriate cleaning solvents.

I.

All pairs spliced shall be tested and all splice-related faults cleared prior to sealing the closure assembly.

3.2 CABLE TESTING

A.

Individually test from both ends of the cable for continuity, power faults, and ground faults.

Correct all shorts, opens, crosses, bad terminations, foreign voltages, grounding problems, sheath continuity problems, etc..

B.

In addition, provide loop resistance measurements in ohms and dB loss at 1KHz and calculated dB loss at 8KHz and 256KHz on the first pair of each binder group..

C.

The CNM ITS is to be notified at least 24 hours prior to testing to allow observation at the

CNM ITS’s discretion. If the CNM ITS confirms his intention to observe, a reasonable starting time will be agreed upon. Should the CNM ITS not be present at the scheduled commencement time, the Contractor may begin testing as scheduled.

D.

All test results are to be recorded and turned over to the CNM ITS as a deliverable.

E.

CNM ITS to approve all test equipment prior to the start of testing. Proof of calibration is required.

3.3 CABLE AND TERMINATION PANEL LABELING

A.

Label the installed cables in accordance with the approved labeling plan and according to

CNM ITS’s instructions

END OF SECTION 271313

COMMUNICATIONS COPPER BACKBONE CABLING

Version 12DEC2007

271313 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 27131313 – COMMUNICATIONS COPPER CABLE SPLICING

AND TERMINATIONS

PART 1 - GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the performance of multipair copper cable splicing as described on the

Drawings and/or required by these specifications.

B.

Contractor shall provide hardware for the grounding and bonding of cable and closures and all associated hardware necessary for the routing and management of communication cable in the vicinity of splices.

1.2 COORDINATION

A.

Contractor shall coordinate the work specified in this Section with the work in other parts of the Contract document.

B.

Plans in general are diagrammatic. It is the full responsibility of the Contractor to be familiar with the location of equipment involved under the work of other trades to eliminate conflicts between the copper splicing and the work of other trades.

C.

All questions and issues with regard to coordination shall be directed to CNM ITS.

1.3 SUBMITTALS

A.

All submittals shall be made to CNM ITS.

B.

Shop drawings shall include manufacturer's printed information with each item. The information submitted shall include overall dimensions, weights, performance characteristics and manufactured specification. Shop drawings and Manufacturer's cut sheets where required,

1.4 STANDARDS FOR MATERIALS shall be submitted by the Contractor to CNM ITS for review prior to installation.

C.

Shop drawings and or manufacturers cut sheets and specification sheets shall be submitted for approval.

D.

Closure Supports, such as Threaded Rod and Channel Trapeze configurations to be fabricated on the jobsite if required.

A.

All materials shall conform with the current applicable industry standards including, but not limited to:

1.

NEMA (National Electrical Manufacturers' Association)

2.

ANSI (American National Standards Institute)

3.

ASTM (American Society for Testing and Materials)

COMMUNICATIONS COPPER CABLE SPLICING AND TERMINATIONS

Version 12DEC2007

27131313 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

4.

ICEA (Insulated Cable Engineers Association)

5.

IEEE (Institute of Electrical and Electronic Engineers)

6.

National Electrical Safety Code

B.

In addition, all Material shall be Underwriters Laboratories Listed unless otherwise indicated.

1.5 QUALITY ASSURANCE

A.

Verification: CNM ITS will maintain inspection personnel on the job site. It is incumbent upon the Contractor to verify that the installation and material used has been inspected before it is enclosed within building features, or otherwise hidden from view. The Contractor shall bear costs associated with uncovering or exposing installations or features that have not been inspected.

B.

Equipment Qualifications: The Contractor is to use equipment and rigs designed for splicing, preparation and drilling of closure end caps, drilling masonry, installing anchors, etc., to install the splice supports and cable management hardware.

PART 2 - PRODUCTS

2.1 SLICE CLOSURES

A.

The splice closure shall be designed to accommodate the number of cables to be spliced and allow either butt or through splices with an equal number of cables.

B.

The closure shall be a flame retardant closure with the following basic components:

1.

The Splice Cover shall be a two-piece reinforced fire resistant plastic or stainless steel cover with tongue and grove mating slots. The splice cover shall be closed with a snap catch clamping mechanism with reusable rubber seals, or stainless steel clamps.

2.

Flame Retardant End Caps shall provide the means of sealing the ends of the Splice Cover and securing the cable sheaths. The end caps shall contain a bonding stud for bonding the bonded shields within the closure to the ground bus.

3.

The splice closure shall be designed for multiple reentry.

C.

Encapsulant shall not be used in indoor splice closures. Encapsulant shall be used within splices installed within manholes or handholes as specified by CNM ITS.

D.

Splice closures shall be Preformed Stainless Steel, or approved equal.

E.

The Contractor shall use the tool kits and splice rigs recommended by the splice closure manufacturer for the splice closure provided.

2.2 COPPER CABLE SPLICE CONNECTORS

A.

The splice connector shall be a modular splicing system with the following features and specifications.

1.

The splice connector shall be compatible with 24 AWG PIC and DEPIC copper conductors, and 26 AWG protector fuse tails.

COMMUNICATIONS COPPER CABLE SPLICING AND TERMINATIONS

Version 12DEC2007

27131313 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

The splice connector shall be part of a modular system that includes: a.

Splice connectors. b.

Bridge connectors. c.

Half-tap connectors.

3.

The splice connector shall be dry for indoor application and use with 24 AWG PIC and DEPIC copper conductors, and 26 AWG protector fuse tails.

4.

The splice connector shall be filled for use in outdoor applications.

5.

The splice connector shall have a capacity of 25 pairs.

6.

The splice connector shall be constructed to allow multiple configurations based on a 2 or

3 piece standard assembly.

7.

The splice connector shall be 3M Micro Splice (MS2) 4000 Series Splicing Modules, as appropriate for the closure.

8.

For outside applications, the splice connector shall be 3M Micro Splice (MS2), gel-filled

4005 Series Splicing Modules, as appropriate for the closure.

2.3 MULTIPAIR COPPER CABLE IDENTIFICATION TIES

A.

The Contractor shall use color coded cable ties included within the Cable Marker Kit for identifying multi-pair copper cable binder groups within splice closures.

2.4 ENCAPSULANT

A.

The Contractor shall inject 3M High Gel Re-enterable Encapsulant in those closures specified by CNM ITS. 3M Part Number 4442.

2.5 DAMMING COMPOUND

A.

The Contractor shall apply damming compound over the end of filled copper cables once they are fanned out into splice closures intended for dry, indoor environments. 3M Haplec

Blocking Compound, 3M Part Number 4408, or equivalent.

2.6 BONDING CONNECTORS

A.

3M Scotchlok Bonding Connectors, 3M Part Number Series 4460 or equivalent, shall be used to bond multipair copper cable jackets to appropriate ground.

PART 3 - EXECUTION

3.1 CABLE SPLICING

A.

The Contractor shall configure splice closures for butt splices in manholes or confined spaces whenever possible. Large numbers of cables may require through splices, or where through splices are appropriate, such as within Utility Tunnels or large vaults.

COMMUNICATIONS COPPER CABLE SPLICING AND TERMINATIONS

Version 12DEC2007

27131313 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

The Closure shall be sized to ensure capacity for all pairs to be connectorized with appropriate splice modules, even if all pairs entering the closure are not to be spliced within the scope of this Project.

C.

All 25-pair binder groups within each cable entering the splice closure are to be connectorized with splice modules. The Contractor shall use the same type and manufacture of connectors for all pairs. Splice modules will be installed according to the manufacturer’s specifications.

D.

When breaking out any multipair copper cable of 50 pairs or greater for splicing or termination, the binder groups shall have color coded cable ties attached to the cable at the point of fanout from super groups for splicing, and at the point of fanout for termination on termination blocks.

E.

The Contractor shall ensure the cables to be spliced are routed into the closure in a manner observing the bend radii restrictions of the cables being spliced.

F.

Install shield bond connectors to the shields of all cables entering the closure and bond to the grounding lug of the closure prior to sealing the closure assembly.

G.

The splice shall be located in an area that will allow future access and reentry. Stagger or offset the splice closures when more than one closure is installed in parallel within Utility

Tunnels. Allow enough cable slack in all cables entering the closure to allow dismounting of the closure from its supports and to ensure convenient access or reentry.

H.

The Contractor shall apply an appropriate amount of damming compound over the end of filled copper cables in indoor or dry environments to prevent seepage of cable filling compounds where encapsulant will not be used.

I.

Prior to closure assembly in dry or indoor installations, all exposed cable pairs shall have the filling compound thoroughly cleaned off the cable insulation or sheath using appropriate cleaning solvents.

J.

All pairs spliced shall be tested in accordance with the Specifications, and all splice related faults cleared prior to sealing the closure assembly.

K.

Assemble the closure casing such that the hardware and fasteners are easily accessible without twisting or turning the cables.

L.

Splice closures shall be sealed to provide air- and water-tight integrity, and left unpressurized at the completion of the splices. Nitrogen gas shall be injected into the assembled closures and pressure tested to 6-10 psi.

M.

Splice Closure Mounting

1.

Within Manholes: Contractor shall mount assembled closures to cable hooks and manhole racking between 18 and 48 inches above the floor of the structure, measured from the bottom of the enclosure canister. Mount closures away from steps or hand holds to avoid the splice closure being used as a step for ascent or descent.

2.

Within Utility Tunnels and Vaults: Placement in existing cable trays, attachment to racking, or attachment to stranded messenger may be required. The Contractor shall coordinate the location for the splice and alternative mounting techniques with CNM ITS prior to cutting cables in preparation for splicing.

N.

A CNM ITS Technician shall be present during all splicing operations and inspect the splice before it is closed and pressurized.

3.2 SPLICE CLOSURE LABELING

COMMUNICATIONS COPPER CABLE SPLICING AND TERMINATIONS

Version 12DEC2007

27131313 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

Label the assembled closure in accordance with CNM ITS’s instructions.

END OF SECTION 27131313

COMMUNICATIONS COPPER CABLE SPLICING AND TERMINATIONS

Version 12DEC2007

27131313 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271323 – COMMUNICATIONS OPTICAL FIBER BACKBONE

CABLING

PART 1: GENERAL

1.1 SCOPE OF WORK

A.

The extent of the Interbuilding Fiber Optic Cabling Installation (The Project) will include the following as shown on the Drawings or as Specified herein:

B.

Installation, testing, labeling and documentation of new interbuilding fiber optic communication cable between buildings as specified herein and on the Drawings.

C.

The installation environment will include existing ERs, existing underground concrete encased duct, existing direct-buried conduit, existing utility tunnel pathways, as well as areas of CNM property which will require directional boring, and/or trenching to facilitate direct burial of cable and conduit to be completed by the Contractor. The Contractor shall not be responsible for the installation of concrete-encased ducts, or utility tunnels

D.

The Contractor shall be responsible for: placement of cable, attachment cable to support devices and underground structures, placement of conduit, metallic pullboxes (NEMA Type

3R), furnishing fiber optic splice closures and performance of splices, installation of termination hardware and enclosures, termination of individual fiber strands, labeling, testing and documentation of the work.

E.

The Contractor shall be responsible for the provision of grounding and bonding materials, duct plugs, and firestopping materials as appropriate. Other incidental hardware and appliances, necessary for the proper performance and operation of the communication cable system, which are consistent with the practices of underground cable installation, are to be provided by the Contractor at no additional charge to CNM ITS.

1.2 QUALITY ASSURANCE

A.

Manufacturer Qualifications: ISO 9001 Certified, for components that are required to have submittals provided as part of this Section.

B.

Installer Qualifications:

1.

A firm currently engaged and which has been continuously engaged for the past 5 years in the installation of low voltage applications of type required for this Project, and which is licensed in and has obtained or will obtain the necessary permits to perform telecommunications installations in jurisdiction where Project is located.

2.

Have a BICSI certified RCDD locally on staff

3.

Provide references of the type of installation provided in this specification.

4.

Have personnel knowledgeable in local, state, and national codes and the latest TIA

Telecommunications Standards and Manufacturer’s recommendations.

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

5.

Have personnel fluent in the use of AutoCAD version 2002 or later and possess and operate CAD software capable of producing .DWG or .DXF format.

C.

Source Limitations: Obtain units of the same type of equipment through one source from a single manufacturer.

D.

Product Options: Drawings indicate size, profiles, and dimensional requirements of equipment, accessories, and components and are based on the specific system indicated.

Refer to Division 01 Section “Product Requirements.”

1.

Do not modify intended aesthetic effects or performance, as judged solely by

Architect, except with Architect’s approval. If modifications are proposed, submit comprehensive explanatory data to Architect for review.

E.

Materials and labor shall comply with applicable requirements of following standards, using latest version of associated appendices and Technical Service Bulletins at the time of award of the Contract;

1.

EIA/TIA-568.

2.

EIA/TIA-569.

3.

EIA/TIA-606.

4.

EIA/TIA-607.

5.

Underwriter’s Laboratory.

6.

FCC (including CFR 47 and Part 68 – Subpart F).

7.

National Electric Code.

8.

Local and State Codes.

9.

ISO/I/EC 11801.

10.

IEC 1000-5-2.

11.

IEC 60603-7.

F.

Approved Manufacturers:

1.

Commscope

2.

General

3.

OCC

4.

Other approved equal submitted in advance as required in SOW

PART 2 - PRODUCTS

2.1 TELECOMMUNICATIONS INSTALLATION

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

General: The materials and products specified herein reflect the minimum acceptable standards of fabrication and manufacture. All materials and products supplied by the

Contractor and specified herein are to be new, unused, of first quality and in original packaging or shipping containers.

1.

All unused cables purchased for this project longer than 300ft will be surrendered to CNM

ITS.

B.

Outside Plant Fiber Optic Cable

1.

General: - The Project will require the installation of outside plant single-mode (SM) and/or multimode (MM) fiber optic cable in various outside plant environments. The cable types listed herein have been selected based on these environments and applications. a.

Optical Characteristics – Single-mode fiber optic cable

(1) 8.3

μ m/125

μ m single-mode optical fibers

(2) Attenuation:

0.35dB/km @ 1310 nm;

0.25dB/km @ 1550 nm

For example: 2200’ of 72 FO SMF was used on this project and a minimum order of

11,000’ was purchased…. The remaining 8,800’ of 72 FO SMF would be turned over to

CNM ITS. b.

Optical Characteristics – 62.5

μ m/125

μ m multimode optical cable

(1) Attenuation:

2.9 dB/km @ 850 nm;

0.6 dB/km @ 1300 nm

(2) Bandwidth: 160 MHz/km @ 850 nm 500 Mhz/km @ 1300 nm c.

Optical Characteristics – 50

μ m/125

μ m multimode optical cable

(1) Attenuation:

2.3 dB/km @ 850 nm;

0.6 dB/km @ 1300 nm d.

Bandwidth: 160 MHz/km @ 850 nm 500 Mhz/km @ 1300 nm e.

Mechanical Specifications

(1) Maximum tensile loading: Installation: 2700 N (600lb/ft) Long term installed: 890

N (200lb/ft)

(2) Operating Temperature: Storage: -40° to +70° C (-40° to +158° F) Long Term: -

40° to +70° C (-40° to +158° F)

(3) Minimum bend radius (12 and 48 strand armored fiber optic cable):

Loaded: 8.9 inches Installed: 6.0 inches

(4) Minimum bend radius (12 and 48 strand all-dielectric fiber optic cable):

Loaded: 7.0 inches Installed: 4.6 inches

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) f.

Mechanical Construction – armored fiber optic cable for direct-buried installation.

Construction shall conform to Corning ALTOS Double Sheath/Single Armor Cable or equivalent. (innermost to outermost components)

(1) Central dielectric member

(2) Water swellable yarn

(3) Buffer tubes/fibers

(4) Water swellable tape

(5) Dielectric strength members

(6) Ripcord

(7) Polyethylene inner jacket

(8) Water swellable tape

(9) Ripcord

(10) Corrugated steel tape armor

(11) Polyethylene outer jacket g.

Mechanical Construction – all dielectric fiber optic cable for installation within underground facilities. Construction shall conform to Corning ALTOS All Dielectric

Cable or equivalent. (innermost to outermost components)

(1) Central dielectric member

(2) Water swellable yarn

(3) Buffer tubes/fibers

(4) Water swellable tape

(5) Dielectric strength members

(6) Ripcord

(7) Polyethylene outer jacket h.

Mechanical Construction – all dielectric fiber optic cable for installation within buildings. Construction shall conform to either:

1.

Corning Freedom type Loose Tube Cable OFNR rated, UV-stabilized jacket or equivalent. (innermost to outermost components)

(1) Dielectric Central Member

(2) Water swellable yarn

(3) Buffer tubes/fibers

(4) Water swellable tape

(5) Dielectric strength members

(6) Ripcord

(7) UV-resistant, Flame Retardant Polyethylene outer jacket

2.

Corning Fan-Out type Tight Buffered Cable OFNR rated jacket, or equivalent.

(innermost to outermost components) for Intra-Building installations.

(1) Dielectric Central Member

(2) TBII Buffered Fiber

(3) Dielectric Strength Member

(4) Subunit jacket

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 4

(5) Dielectric Strength Member

(6) Ripcord

(7) Outer Sheath

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) i.

Fiber strand counts for each cable type as specified herein or on the Drawings.

(1) All dielectric fiber optic cable for installation within underground facilities.

(2) Armored fiber optic cable for direct-buried installation.

(3) All dielectric fiber optic cable for installation within buildings (Freedm)

(4) Tight buffered all dielectric MIC (All OFNP as required) fiber optic cable for installation within buildings. j.

Color codes for fiber optic cable

(1) Buffer tubes and individual strands shall be color coded as follows:

Number Color

1 Blue

2 Orange

3 Green

4 Brown

5 Slate

6 White

7 Red

8 Black

9 Yellow

10 Violet

11 Rose

12 Aqua

(2) Cable shall be assembled to ensure that no more than 12 fiber strands occupy each buffer tube.

C.

Fiber Optic Connectors

1.

For all fiber optic terminations, Type SC connectors, as specified in TIA/EIA 568A shall be used.

D.

Fiber Optic Splice Enclosures

1.

Fiber optic fusion splices shall be performed in underground facilities, therefore splice enclosures designed for use in an outside plant environment shall be used. Splice closures are to be configured for through splices only when distribution from splice is not required.

Where distribution is required from a splice closure, utilize splice closures with entrance

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) from one end only, when installing the 9.5”x 28.0” Coyote #800010884 splice enclosure

(or equivalent) or from both ends when installing the 8.5”x 22.0” Coyote #80805514 splice enclosure with (2) 6 port end plates. No encapsulant shall be injected into closures after splices are completed. a.

Preformed Coyote Fiber Optic Splice Closures Kits or equivalent, sized as required for the maximum fiber count within the splice case including distribution fibers.

(1) Preformed Splice Trays shall be used with Preformed Fiber Optic Splice Closures.

Splice only 24 fibers per splice tray (no exceptions, unless with written approval prior to installation).

(2) Preformed splice trays are to be labeled with a permanent black (Sharpie) marker on the front face of each splice tray indicating fiber count. b.

Support bracket kits for a Coyote Splice Case, sized as required for fiber count will support the splice case in maintenance holes, handholes and vaults.

E.

Innerduct

1.

Innerduct will be installed in specified ducts as indicated herein. Innerduct shall be smooth walled molded polyethylene and be of solid wall configuration. Each innerduct placed by the Contractor shall have a one-quarter inch polyethylene pull rope placed within the innerduct secured at each end. Innerduct will be available in multiple colors. a.

Carlon 1-1/4 inch Optic-Gard/PE solid wall innerduct. Carlon Part #A6C9N6NNNC or equivalent.

F.

Innerduct Couplers

1.

Aluminum threaded innerduct couplers to be used to join two segments of corrugated innerduct together. Non-metallic couplers are not acceptable. a.

Pyramid Innerduct Adapter 1-1/4 inches - Pyramid Part Number F09008 or equivalent. b.

Carlon Threaded Aluminum Couplings 1-1/4 inches – Carlon Part #BS1.660 or equivalent

G.

Duct Plugs

1.

Split Triplex Duct Sealing Plugs to be installed in 4-inch ducts containing Contractorinstalled 1-1/4 inch innerducts. a.

Jackmoon Triplex duct plugs - Jackmoon Part Number 40B167S or equivalent. b.

Carlon Triplex duct plugs – Carlon Part Number MATPG3 or equivalent.

2.

Innerduct Sealing Plugs to be used to seal used and unused innerducts. Used in conjunction with triplex duct sealing plugs. a.

Jackmoon Blank Duct Plug 1-1/4 inches – Jackmoon Part Number 12D148U or equivalent. b.

Jackmoon Fiber Optic Simplex Duct Plug 1-1/4 inches – Jackmoon Part Number

12S0XXSB or equivalent. Exact part number should be specified by Contractor upon materials order placement once exact cable diameters are known.

H.

Fiber Optic Cable Labels

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Plastic cable labels will be attached to all fiber optic cables using stainless steel straps as specified in Part 3.

I.

Cable Support – J-Type Pipe Hangers;

1.

B-Line Products Pipe Hanger, B-Line Products Part Number 3690-X, or equivalent, sized appropriately.

PART 3 - EXECUTION

3.1 TELECOMMUNICATIONS INSTALLATION

A.

General

1.

This Section describes the installation locations for the products and materials, as well as methods and CNM ITS Standards associated with the Telecommunications Installation portions of the Project. These Specifications, along with the Drawings and other CNM supplied specifications shall be followed during the course of the installation.

2.

The Contractor is instructed to coordinate his efforts with other tradesmen who may be working within the same vicinity to avoid conflict, lost time and potential injury. CNM

ITS will assist in coordination as requested or as required.

3.

The Contractor is to install all materials plumb, square and in a workman-like manner.

4.

The Contractor is required to supply all necessary tools, equipment, accessories, safety equipment, protective clothing, etc., as customary for the craft and necessary for the installation.

5.

The Contractor shall comply with all National, State, Local and CNM Codes and

Standards during the course of installation. Should any portion of these Specifications conflict with said Codes, the Contractor is to cease work on that particular aspect of the

Project and notify CNM ITS immediately.

B.

Field Conditions

1.

Fixed facility locations shown on the Drawings are based upon the latest design information available at the time this Specification was prepared. The Contractor shall conduct field inspections to determine the actual as-built locations of conduits, manholes, handholes and all other special facilities that affect the installation, prior to commencing the installation in any area.

C.

Cleaning

1.

Cleanliness. All ERs and underground structures to include utility tunnels, conduit and manhole systems, handholes and related fixtures shall be kept as clean as possible during installation. Labor required for any cleaning work shall be provided by the Contractor.

2.

Completion. ERs and underground structures to include utility tunnels, conduit and manhole systems, handholes and related fixtures, shall be thoroughly cleaned, flushed out, or blown out before the installation is offered to CNM ITS for acceptance.

3.

Temporary Work. Temporary labels, temporary protection and related items shall be removed and the entire installation left in a clean, usable condition.

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 7

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

4.

Attachments. Overhead beams, conduits, lighting fixtures and any other overhead structures shall be cleaned before installation racks, cabinets and cable tray. The purpose is to prevent dust and debris from falling on the electronic equipment beneath.

3.2 FIBER OPTIC INNERDUCT INSTALLATION

A.

Refer to the Project Drawings as applicable for routing.

B.

Duct/Conduit Preparation.

1.

All ducts and conduits intended for use as a pathway will be blown out with compressed air or brushed out to remove dirt, water, and other residue prior to cable and innerduct installation.

C.

Innerduct Installation

1.

Innerduct in utility tunnel shall be mounted on dedicated 6M strand messenger.

2.

The Contractor shall install 3 innerducts within select 4-inch conduits used for communication cable installed during this Project. Innerduct will be provided by the

Contractor as required, under the following conditions: a.

There is no existing innerduct installed in the conduit. b.

There is no existing cable installed in the conduit. c.

Multi-cell duct is not available as a pathway. d.

3 innerducts will be installed in any duct which is to hold any combination of: 1, 2 or 3 cables. e.

Innerduct will not be installed in any duct which does not carry cable installed in conjunction with this Work. f.

Innerduct is not to be installed within empty conduits slated for future use or expansion unless noted in SOW.

3.

Innerducts will be cut to allow approximately 12-24 inches of excess material to extend beyond the end of the duct.

4.

Innerducts are to be contiguous sections end to end. If it is absolutely necessary to splice innerduct together, use aluminum couplers as specified herein.

5.

Secure innerduct pull-ropes by cutting a slit into the excess duct and wedging the pullrope in the slit. Tie off excess slack around the duct.

6.

Install a triplex duct plug into each end of the duct used according to the manufacturer’s instructions.

7.

Install a simplex duct plug over the cable and secure the plug as instructed by the manufacturer.

8.

Install a blank plug in unused innerducts.

3.3 FIBER OPTIC CABLE INSTALLATION

A.

General - For cable installation within ductbanks: Cable is to be installed in CNM designated ducts. If field conditions prohibit the use of CNM ITS-designated duct, the Contractor is to select a duct for use and coordinate his selection prior to cable installation. If no innerduct is available, the Contractor is to install 3 innerducts into a single duct. If cable is already

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 8

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) installed within a duct without innerduct, new cable is to be pulled into the duct (also without innerduct) along with existing cables, provided that the new cable can be pulled without damage to itself or to other cables already in place.

B.

Description – Primary Fiber Optic Cable Backbone Route – As described herein and/or as shown on the Drawings.

C.

Fusion Splicing of Fiber Optic Cable

1.

Where required as part of the installation, the Contractor shall perform fusion splices of fiber cable.

2.

Prior to sealing spliced cables into a fiber optic splice enclosure, the Contractor shall perform a power meter test on each individual fiber. The attenuation measurement is to be compared to the link loss calculation for the segment in question. Measured attenuation through the splice is not to exceed 0.2 dB. Splices that exceed this level will be broken, respliced and retested by the Contractor until the minimum reading is attained.

3.

After performing the fusion splice, the splice technician shall examine each splice under a

100X power microscope. Splices with a “neck-down” (narrowing) effect, with an oversized bulge at the splice location, or which contain gas bubbles, dirt, or other aberrations shall not be acceptable.

4.

The spliced fibers are to be installed within a fiber optic splice tray according to the manufacturer’s specifications.

5.

The fiber optic splice closure will be sealed to be air-tight as specified by the manufacturer. Any encapsulant used shall be approved by CNM ITS before installation.

Installation would be only after testing and acceptance. Sealed closures are to be secured to the wall of the manhole using appropriate hardware.

D.

Installation of Fiber Optic Cable Within the ER

1.

Routing of cable and cable slack. Upon entering the ER, the fiber optic cable shall be routed to the termination location as shown on the drawings. At least 20 feet of slack cable shall be coiled maintaining a minimum of 2 times the minimum bend radius. The cable shall be secured to the ER wall or other specified location using Velcro cable wrap brackets. The end of the cable, exclusive of the coil of slack, shall be routed to the splice housing mounted within the equipment rack for furcation and termination. Leave a maximum of 6 feet of buffer tube in the fiber optic enclosures. Secure the cable to the wall or equipment frame using Velcro cable wraps.

E.

Furcation of Fiber Optic Cable

1.

Prior to termination, fiber optic cable strands will be furcated (fanned out) using the specified furcation kits and using the procedure specified by the manufacturer.

F.

Termination of Fiber Optic Cable

1.

Where specified, the Contractor shall terminate the individual fiber strands with SC-type connectors according to the manufacturer’s specifications.

2.

Upon final testing, mated-pair connector attenuation shall not exceed 0.75 dB. Connectors which exceed this level of attenuation shall be cut off and fibers re-terminated by the

Contractor.

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 9

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

3.

Terminated fibers shall be installed within a fiber termination panel mounted within an equipment rack, as specified on the Drawings.

G.

Installation of fiber in Maintenance Holes and Handholes

1.

Do not loop the fiber around the manhole or handhole unless specified in the SOW.

3.4 FIBER OPTIC CABLE TESTING

A.

Scope of Work - Work covered by this Paragraph shall consist of furnishing labor, equipment and supplies unless otherwise specified, and in performing the following operations recognized as necessary for the successful testing and verification of the installation of the

Fiber Optic cable plant described on the Drawings and required by these specifications. In addition, the Contractor shall: a.

Verify through Optical Time Dimension Reflectometer (OTDR) testing as well as visual inspection of manufacturers testing results, the quality of the fiber optic cable being installed. b.

Verify through power meter testing the attenuation of all point to point fiber optic strands. c.

Verify through OTDR testing the integrity of the point-to-point connections, the final installed connector-to-connector length of the fiber optic strands. d.

Verify through visual inspection of all fiber optic cable termination locations on

Drawings, the integrity of the workmanship and the operability of the fiber optic media.

B.

Contractor Responsibility: a.

The Contractor shall: a.

Coordinate a meeting with CNM IT personnel to discuss testing procedures, equipment, documentation, etc. to verify to the owner a complete understanding of requirements and schedule. b.

Complete quality control inspection and testing per this Specification. c.

Maintain fiber optic test technicians qualified to operate the test equipment (to be used) on the job site during testing. d.

Maintain test equipment in current calibration during testing operations. e.

Notify CNM ITS 48 hours in advance when work, technicians and equipment are prepared for Acceptance tests and inspections. Coordinate testing with CNM ITS beforehand to avoid delays in the Project schedule. f.

Maintain written record of tests pertinent for each fiber run and upon completion of testing, assemble and certify a final test report. g.

Maintain safety procedures and discipline when test equipment is emitting optical energy.

C.

Test Equipment

1.

Contractor will submit specification sheets for the test equipment to be utilized for CNM

ITS approval prior to commencement of testing.

2.

Calibration

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 10

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) a.

The Contractor is to ensure all test instruments are calibrated to provide measurements within stated accuracy. b.

Visible, dated calibration labels will be affixed to test instrumentation. Calibration will have been performed within 12 months of current testing operation. c.

The Contractor shall be prepared to present accurate records that indicate the calibration history of the equipment. The records should include the date and results of instruments calibrated or tested. d.

Test equipment is to be calibrated using a standard of higher accuracy than that of the instrument tested. Accuracy is to be directly traceable to the National Institute of

Standards and Technology.

D.

Acceptance Procedures: a.

Purpose: The following acceptance practices will be followed to ensure that should the incorrect products be received, should damage to the cable have occurred during shipping and handling; the Contractor can reorder replacement materials as soon after determination of the product’s unsuitability as possible to minimize the impact to the installation schedule. a.

The Contractor shall visually inspect fiber optic cable reels for damage upon receipt from the shipper. b.

Part numbers on cable reel shipping labels, bills of lading, invoices, etc., shall be compared to the original order. c.

Cable lengths should be verified. d.

The manufacturer’s OTDR measurement records received with the shipment shall be examined to ensure compliance with stated attenuation performance. The Contractor will accept and guarantee the OTDR and loss measurements provided with the cable or will make their own test before acceptance. The OTDR readings will be provided for all the fibers in each spool of fiber optic cable. Readings will be taken at the 850 nm, 1300 nm windows for multi mode fiber and 1310 nm, 1550 nm windows for single-mode fiber. e.

The Contractor will retain the manufacturer’s test data and provide it, along with all other specified test documentation to CNM ITS at the completion of the Project.

E.

Field Testing Procedures

1.

The following test procedures will be performed for all fiber optics cable installations. No variance can be obtained without written request to CNM ITS explaining the reasons for the request. Verbal approvals will not be accepted or provided.

2.

All readings will be taken end to end (SC to SC) in both directions on every fiber terminated at both ends, without exception.

3.

Fiber optic cable that is left un-terminated at both ends shall be tested using a launch cable and bare fiber adapter.

4.

CNM ITS is to be notified at least 48 hours prior to testing to allow 100% observation at

CNM’s discretion. If CNM ITS confirms his intention to observe, a reasonable starting time will be agreed upon. Should CNM ITS not be present at the scheduled commencement time, the Contractor may begin testing as scheduled.

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 11

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

F.

Optical Time Domain Reflectometer (OTDR) Testing

1.

After all terminations have been completed, tests will be conducted using an OTDR prior to testing with a power meter set (optical light source and optical meter). Contractor will test insertion loss of 850 nm and 1300 nm for Multimode cable; and at 1310 nm and 1550 nm wavelengths for Single-mode cable, for both directions through each connector pair using the OTDR. Use of an OTDR determines overall length and pinpoints loss locations along the segment being tested by indicating their distances from the source. The

Contractor will use the OTDR traces to assess the span attenuation that is necessary to evaluate the final acceptance tests utilizing the power meter test set(s). The power meter test measures overall attenuation of each span; this test also determines whether terminations are not within specified quality limits.

2.

OTDR Testing and the Span Loss Benchmark Calculation a.

Span Loss Benchmark Calculation. The estimated attenuation (loss) must be calculated for each fiber segment to determine a comparison value for the actual readings during the power meter test. This calculation is derived from the original reel tests performed at the time of cable acceptance. b.

In general, the OTDR traces must be interpreted to determine the length of each cable segment. Both ends of the span are terminated with an SC connector. In the following example the test is performed on multi mode fiber at 850nm. At the conclusion of the test, the trace for the span (end-to-end) is interpreted as follows:

Segment 1 is a fiber segment measured from termination to termination.

Distance of Segment 1 (per OTDR Trace)

Pre-Installation Attenuation Acceptance Test

Calculation: 125 meters x 0.0029 dB/meter

= 125 meters

2.90

= dB/km

= 0.36 dB

Calculated loss value for Segment 1:

Mated pair connector loss:

0.75 dB (per pair)* X 2

Maximum allowable loss for the span

=

=

=

=

0.36 dB

+ 1.50 dB

1.86 dB

1.86 dB

The Span Loss Benchmark Calculation for this span: 1.86 dB

The benchmark calculation for the span is to be compared with the reading taken on the span with the power meter in final acceptance testing.

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 12

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

3.

Power Meter Testing a.

All testing done with a light source and power meter shall be done such that the loss of any cables or connections used to interface the fiber to be tested to the instruments is measured and subtracted from the total loss of the fiber optic circuit. For testing the finished installation, the instrument(s) shall be "front ended" with SC connectors so that the testing includes the interface to the SC bulkheads in the fiber termination panels. b.

b. After termination of all the individual fibers, power meter readings will be taken.

The attenuation of readings must not be higher than the optimal attenuation loss. The optimal attenuation loss will be calculated using the manufacturer's factory certified fiber test reports (dB/km) converted to the actual installed lengths plus the attenuation losses for the SC connector of 0.75 dB per mated connector pair. The optimal attenuation losses shall be used for comparison with the end-to-end power loss test results prior to acceptance by CNM ITS. c.

c. If any reading is higher than 0.10 dB over the optimal attenuation loss, CNM ITS must be contacted for acceptance. If the loss is not acceptable, then the contractor must re-terminate the fiber to obtain acceptable loss levels. This will be done at the

Contractor's expense. Records of fiber loss must be maintained and provided for system acceptance by CNM ITS. d.

d. CNM ITS is to be notified at least 48 hours prior to testing to allow 100% observation at CNM ITS discretion. If CNM ITS confirms his intention to observe, a reasonable starting time will be agreed upon. Should CNM ITS not be present at the scheduled commencement time, the Contractor may begin testing as scheduled.

4.

Test Report Submittals a.

The Contractor shall submit test results on CD/DVD for review prior to CNM ITS acceptance of the Work. b.

Fiber optic cable test reports shall be delivered to CNM ITS for loss @ 1310nm and

1550nm for all single-mode fiber strands and 850nm and 1300nm for all multimode fiber strands. c.

Loss budget calculation shall be shown on the Fiber Optic Cable Test Report. d.

Substantial Completion will not be given without the final test results submitted and approved by CNM ITS.

3.6 AS-BUILT INFORMATION

A.

Contractor shall provide as-built information to CNM ITS to accompany all test result information.

B.

As-built information shall be in electronic format. Indicate location of all OSP routes, if different than original drawing, conduit configuration, cable type, cable labeling, and all additions and deletions pertaining to telecommunications.

3.7 SYSTEM WARRANTY

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 13

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

Contractor shall perform all labeling requirements and provide testing documentation for verification as described herein.

B.

Contractor shall submit cable records to reflect all moves, adds, and changes.

A.

Manufacturer shall provide a system performance warranty for the installed system.

C.

Contractor shall submit final paperwork for warranty to manufacturer and a copy to CNM ITS one week prior to the substantial completion date.

D.

Contractor must be a certified installer of installed cable plant and must be certified by manufacturer.

E.

Contractor must offer a 25-year extended warranty for the premises fiber cabling solution comprised of covered manufacturer products and must follow all warranty registration procedures set forth by manufacturer, including submitting all required materials to manufacturer for warranty certification.

F.

All installed equipment must conform to the manufacturer's official published specifications.

The warranty shall begin at the system acceptance date and remain in effect for a period of 25 years from that date. The contractor shall agree to repair, adjust, and/or replace (as determined by the CNM to be in its best interest) any defective equipment, materials, or other parts of the system at the contractor's sole cost. CNM will incur no costs for service or replacement of parts during the warranty period of 25 years. All third party warranties shall be passed through from contractor to CNM.

G.

Contractor shall warrant that the system will function as specified in the approved manufacturer's Technical Description Guide.

H.

Contractor shall warrant that the system shall accommodate traffic at the levels specified in all appropriate sections of the Request for Proposal.

END OF SECTION 271323

COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

Version 12DEC2007

271323 - 14

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271333 – COMMUNICATIONS COAXIAL BACKBONE CABLING

PART 1 - GENERAL

The Contractor is held responsible to be familiar with the provisions contained herein and with other

Sections of this Specification as applicable to the completion of the installation.

1.1 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

E.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

F.

Division 27, Section 271543 Communications Faceplates and Connectors.

1.2 SCOPE OF WORK

A.

The extent of the Interbuilding CATV Cabling Installation (The Project) will include the following as shown on the Drawings or as Specified herein:

B.

Installation, testing, labeling and documentation of new interbuilding CATV cable between buildings as specified herein and on the Drawings.

C.

The installation environment will include existing ERs, existing underground concrete encased duct, existing direct-buried conduit, existing utility tunnel pathways, as well as areas of Purdue University property which will require directional boring, and/or trenching to facilitate direct burial of cable and conduit to be completed by the Contractor. The Contractor shall not be responsible for the installation of concrete encased ducts, or utility tunnels.

D.

The Contractor shall be responsible for: placement of cable, attachment cable to support devices within the utility tunnel system and underground structures, placement of conduit, metallic pull boxes (NEMA Type 3R), furnishing CATV splice closures and performance of splices, installation of termination hardware and enclosures, termination of CATV cable, labeling, testing and documentation of the work.

E.

The Contractor shall be responsible for the provision of grounding and bonding materials, duct plugs, and fire-stopping materials as appropriate. Other incidental hardware and appliances necessary for the proper performance and operation of the communication cable system, which are consistent with the practices of underground cable installation, are to be provided by the Contractor at no additional charge to CNM ITS.

1.3 QUALITY ASSURANCE

A.

Verification: CNM ITS will maintain inspection personnel on the job site. It is incumbent upon the Contractor to verify that the installation and material used has hidden from view.

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

The Contractor shall bear costs associated with uncovering or exposing installations or features that have not been inspected.

1.4 SUBSTITUTIONS

A.

Intent of Specifications:

1.

Where specified only by reference standards, select any product meeting standards by any manufacturer.

2.

Where specified by naming several products or manufacturers, select any product and manufacturer named that meets the specified requirements. Other products and manufacturers will not be considered.

3.

Where specified by naming one or more products or manufacturers, but indicating "or equivalent" after specified listing, the specified product is the preferred quality standard.

The Contractor may submit a request for another product for acceptance.

4.

Where specified by naming only one product and manufacturer: There is no option and no substitution will be allowed.

B.

Submit requests for substitutions within 10 days of contract award, or sooner if required to maintain the construction schedule.

C.

The Contractor must submit sufficient information to show that a proposed substitute is equivalent to the item specified. Acceptance of substitutions is at Owner's discretion: CNM

ITS reserves the right to determine suitability of the substitute product and reject any and all materials submitted for substitution. All substitute products and materials must be approved for substitution by CNM ITS in writing prior to installation. Products rejected or otherwise judged unsatisfactory by CNM ITS will not be authorized for use in completing the Work.

Any unapproved products discovered as part of the installation will be removed and replaced with CNM ITS-specified and approved products at the Contractor’s expense.

D.

Project Drawings may be based on equipment configuration of a particular manufacturer. If a substitution is approved, the Contractor shall make changes needed to accommodate the substitution at no expense to CNM, including work under other divisions.

PART 2 - PRODUCTS

2.1 TELECOMMUNICATIONS INSTALLATION

A.

General: The materials and products specified herein reflect the minimum acceptable standards of fabrication and manufacture. All materials and products supplied by the

Contractor and specified herein are to be new, unused, of first quality and in original packaging or shipping containers.

B.

Outside Plant CATV Cable

1.

General: - The Project will require the installation of outside plant CATV cable in various outside plant environments. The cable types listed herein have been selected based on these environments and applications. a.

Electrical Characteristics – OSP CATV cable

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

(1) Capacitance 15.3 +/- 1.0 pf/ft

(2) Impedance 75 +/- 2 ohms

(3) Velocity of Propagation 87% b.

Maximum Copper Clad D.C. Resistance @ 68 degrees F

(1) Inner Conductor 1.35 ohms/1000ft

(2) Outer Conductor 0.37 ohms/1000ft

(3) Loop 1.72 ohms/1000ft c.

Attenuation @ 68 degrees F d.

Physical Dimensions – OSP CATV Cable

(1) Nominal Center Conductor Diameter .109 inches.

(2) Nominal Diameter Over Dielectric .450 inches.

(3) Nominal Diameter Over Outer Conductor .500 inches.

(4) Nominal Outer Conductor Thickness .024 inches.

(5) Nominal Diameter Over Flooded Jacket (JCASS) .570 inches.

(6) Diameter of Steel Messenger on Aerial Cable .109 inches. e.

Mechanical Construction - OSP CATV Cable

(1) Minimum Bend Radius of Jacketed Cable 6.0 inches.

(2) Minimum Bend Radius of Un-Jacketed Cable 6.5 inches.

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

(3) Maximum Pulling Tension 300 lbs.

(4) Minimum Breaking Strength of Messenger 1,800 lbs. f.

Mechanical Construction – OSP CATV Cable

(1) Polyethylene Jacket where jacketed cable required.

(2) Aluminum Outer Jacket.

(3) Dielectric Adhesive.

(4) Dielectric.

(5) Copper Center Conductor.

(6) Migra-Heal Flooding Compound where required.

C.

Approved Manufacturers:

1.

Commscope

2.

Belden

3.

General

4.

Other approved equal submitted in advance as required in SOW

D.

CATV Termination Connectors

1.

For OSP CATV terminations within the ER, use LRC part #BI500FFK3, “K” series, two piece cable to “F” female adapter bulkhead connector.

2.

For OSP CATV terminations within an amplifier, Use LRC part #EI500K3 “K” series, two piece PIN type connector. Coordinate with CNM IT Department before disturbing existing amplifiers.

E.

CATV Splice Connectors

1.

For OSP CATV splices, use LRC part #SI500K3, “K” series, two piece splice connectors.

F.

Termination within the Telecommunication Room (ER)

1.

All OSP CATV cables shall be terminated in the ER as described in Item 2.1, C.1.

2.

Install (1) Tru-Spec part #GRB-1HRLAR, 5-1500MHz, grounding block in the ER.

Coordinate termination location of the OSP CATV cable within the ER with a CNM IT

Representative.

3.

Install Belden Part #9116 RG-6 type cable, terminated on both ends with LRC Part # F56-

CHI as described in Section 271533, between the OSP CATV cable and the lightning arrester.

4.

Install Green #6 AWG insulated copper grounding conductor from the lightning arrestor to the ER ground bus bar.

G.

Innerduct

1.

Innerduct will be installed in specified ducts as indicated herein. Innerduct shall be either:

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) a.

Molded in orange polyethylene and be of smooth walled configuration. Each innerduct placed by the Contractor shall have a one-quarter inch polyethylene pull rope placed within the innerduct secured at each end.

(1) Carlon 1-1/4 inch Optic-Gard/PE corrugated innerduct. Carlon Part #AW4X1A or equivalent. b.

Flexible fabric type innerduct manufactured with pulling tape in all cells.

(1) TVC part #MXC-3456-XX in conduits 3” or larger.

(2) TVC part #MXC-2003 in 2” conduits.

H.

Innerduct Couplers

1.

Aluminum threaded innerduct couplers to be used to join two segments of smooth walled innerduct together. Non-metallic couplers are not acceptable. a.

Pyramid Innerduct Adapter 1-1/4 inches - Pyramid Part Number F09008 or equivalent. b.

Carlon Threaded Aluminum Couplings 1-1/4 inches – Carlon Part Number E142GT or equivalent

I.

Duct Plugs

1.

Split Triplex Duct Sealing Plugs to be installed in 4-inch ducts containing Contractorinstalled 1-1/4 inch innerducts. a.

Jackmoon Triplex duct plugs - Jackmoon Part Number 40B167S or equivalent. b.

Carlon Triplex duct plugs – Carlon Part Number MATPG3 or equivalent.

2.

Innerduct Sealing Plugs to be used to seal used and unused innerducts. Used in conjunction with triplex duct sealing plugs. a.

Jackmoon Blank Duct Plug 1-1/4 inches – Jackmoon Part Number 12D148U or equivalent. b.

Jackmoon Fiber Optic Simplex Duct Plug 1-1/4 inches – Jackmoon Part Number

12S0XXSB or equivalent. Exact part number should be specified by Contractor upon materials order placement once exact cable diameters are known.

J.

CATV Cable Labels

1.

Stainless steel cable labels will be attached to all CATV cables using stainless steel straps as specified in Part 3.

K.

Cable Support – J-Type Pipe Hangers;

1.

B-Line Products Pipe Hanger, B-Line Products Part Number 3690-X, or equivalent, sized appropriately.

PART 3 - EXECUTION

3.1 TELECOMMUNICATIONS INSTALLATION

A.

General

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

This Section describes the installation locations for the products and materials, as well as methods and Owner’s Standards associated with the Telecommunications Installation portions of the Project. These Specifications, along with the Drawings and other CNM

ITS-supplied specifications shall be followed during the course of the installation.

2.

The Contractor is instructed to coordinate his efforts with other tradesmen who may be working within the same vicinity to avoid conflict, lost time and potential injury. CNM

ITS will assist in coordination as requested or as required.

3.

The Contractor is to install all materials plumb, square and in a workman-like manner.

4.

The Contractor is required to supply all necessary tools, equipment, accessories, safety equipment, protective clothing, etc., as customary for the craft and necessary for the installation.

5.

The Contractor shall comply with all National, Indiana State, Local and CNM Codes and

Standards during the course of installation. Should any portion of these Specifications conflict with said Codes, the Contractor is to cease work on that particular aspect of the

Project and notify CNM ITS immediately.

B.

Field Conditions

1.

Fixed facility locations shown on the Drawings are based upon the latest design information available at the time this Specification was prepared. The Contractor shall conduct field inspections to determine the actual as-built affect the installation, prior to commencing the installation in any area.

C.

Cleaning

1.

Cleanliness. All ERs, Underground structures to include utility tunnels, conduit and manhole systems, handholes and related fixtures shall be kept as clean as possible during installation. Labor required for any cleaning work shall be provided by the Contractor.

2.

Completion. ERs and Underground structures to include utility tunnels, conduit and manhole systems, handholes and related fixtures, shall be thoroughly cleaned, flushed out, or blown out before the installation is offered to CNM ITS for acceptance.

3.

Temporary Work. Temporary labels, temporary protection and related items shall be removed and the entire installation left in a clean, usable condition.

3.2 CATV INNERDUCT INSTALLATION

A.

Refer to the Project Drawings as applicable for routing.

B.

Duct/Conduit Preparation.

1.

All ducts and conduits intended for use as a pathway will be blown out with compressed air or brushed out to remove dirt, water, and other residue prior to cable and innerduct installation.

C.

Innerduct Installation

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

The Contractor shall install 3 innerducts or equal capacity fabric innerducts within any of the 4-inch conduits used for communication cable installed during this Project. Innerduct will be provided by the Contractor as required, under the following conditions: a.

There is no existing innerduct installed in the conduit. b.

There is no existing cable installed in the conduit. c.

Multicell duct is not available as a pathway. d.

3 innerducts will be installed in any duct which is to hold any combination of: 1, 2 or 3 cables. e.

Innerduct will not be installed in any duct which does not carry cable installed in conjunction with this Work. f.

Innerduct is not to be installed within empty conduits slated for future use or expansion.

2.

Innerducts will be cut to allow approximately 6 inches of excess material to extend beyond the end of the duct.

3.

Innerducts are to be contiguous sections end to end. If it is absolutely necessary to splice innerduct together, use aluminum couplers as specified herein.

4.

Secure innerduct pullropes by cutting a slit into the excess duct and wedging the pullrope in the slit. Tie off excess slack around the duct.

5.

Install a triplex duct plug into each end of the duct used according to the manufacturer’s instructions.

6.

Install a simplex duct plug over the cable and secure the plug as instructed by the manufacturer.

7.

Install a blank plug in unused innerducts.

3.3 CATV CABLE INSTALLATION

A.

General - For cable installation within ductbanks: Cable is to be installed in Owner designated ducts. If field conditions prohibit the use of CNM ITS-designated duct, the Contractor is to select a duct for use and coordinate his selection prior to cable installation. If multicell duct is available, install one cable in each subduct. If no multicell duct is available, the Contractor is to install 3 innerducts into a single duct.

Three cables are to be installed within each innerduct. If cable is already installed within a duct without innerduct, new cable is to be pulled into the duct (also without innerduct) along with existing cables, provided that the new cable can be pulled without damage to itself or to other cables already in place.

B.

Description – Primary CATV Cable Backbone Route – As described herein and/or as shown on the Drawings.

C.

Splicing of CATV Cable

1.

Where required as part of the installation, the Contractor shall perform splices of CATV cable.

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 7

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

Where direct buried underground splices are required, install Canusa #CFTV-1300 selective adhesive filled heat shrink around the splice, extending 6 inches beyond the connectors on each end.

3.

Prior to sealing the splice(s) with the heat shrink, an Owner’s Representative from the

CNM IT Department shall inspect the splice.

4.

The CATV splice shall be sealed to be air and water tight as specified by the manufacturer.

D.

Installation of CATV Cable within the ER

1.

Routing of cable and cable slack. Upon entering the ER, the CATV cable shall be routed to the termination location as shown on the drawings or as directed by a CNM IT

Representative. The cable is to be secured to the ER wall or other specified location using cable ties or brackets. If cable ties are used, they shall be pulled snug, without deforming the jacket of the cable.

3.4 CATV CABLE INSTALLATION

A.

Scope of Work - Work covered by this Paragraph shall consist of furnishing labor, equipment and supplies unless otherwise specified, and in performing the following operations recognized as necessary for the successful testing and verification of the installation of the

CATV cable plant described on the Drawings and required by these specifications. In addition, the Contractor shall:

1.

Verify through continuity testing as well as visual inspection of the quality of the CATV cable being installed.

2.

Verify acceptable installed cable attenuation utilizing a spectrum analyzer and existing

CATV signal. Coordinate with Physical Facilities before connecting to the existing system.

3.

Verify through visual inspection of all CATV termination locations on drawings, the integrity of the workmanship and the operability of the CATV media.

B.

Contractor Responsibility:

1.

The Contractor shall: a.

Complete quality control inspection and testing per this Specification. b.

Notify CNM ITS when work, technicians and equipment are prepared for acceptance tests and inspections. Coordinate testing with CNM ITS beforehand to avoid delays in the Project schedule. c.

Maintain written record of tests pertinent for each CATV run and upon completion of testing, assemble and certify a final test report. Report to include attenuation values at specific frequencies as well as length measurements. d.

Maintain safety procedures and discipline when testing equipment that contains voltage.

C.

Test Equipment

1.

Contractor shall test the installed CATV cable utilizing a contractor furnished spectrum analyzer.

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 8

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

Contractor shall submit hand written documentation of the attenuation values at the following center frequencies:

D.

Acceptance Procedures:

1.

Purpose: The following acceptance practices will be followed to ensure that should the incorrect products be received, should damage to the cable have occurred during shipping and handling; the Contractor can reorder replacement materials as soon after determination of the product’s unsuitability as possible to minimize the impact to the installation schedule. a.

The Contractor shall visually inspect CATV cable reels for damage upon receipt from the shipper. b.

Part numbers on cable reel shipping labels, bills of lading, invoices, etc., shall be compared to the original order. c.

Cable lengths should be verified.

E.

Field Testing Procedures

1.

CNM ITS is to be notified at least 24 hours prior to testing to allow observation at CNM

ITS’s discretion. If CNM ITS confirms his intention to observe, a reasonable starting time will be agreed upon. Should CNM ITS not be present at the scheduled commencement time, the Contractor may begin testing as scheduled.

F.

Maximum Acceptable Attenuation Values

1.

Refer to 2.1.B.1.c for maximum acceptable attenuation values.

3.5 LABELING

A.

Each CATV Cable installed by the Contractor shall be labeled as follows:

1.

OSP CATV Cable Labeling Scheme a.

Labels will be stamped with machine generated markings, hand die stamping is not acceptable. b.

Labels are to be attached to the cable jackets with stainless steel straps. Labels straps will be cinched firmly enough to prevent slippage, but not tight enough to score, cut, or otherwise damage the cable jacket. c.

Place labels within 12 inches of each termination. Ensure labels are positioned to allow reading without twisting the cable.

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 9

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) d.

Place labels within 12 inches of each splice location.

END OF SECTION 271333

COMMUNICATIONS COAXIAL BACKBONE CABLING

Version 12DEC2007

271333 - 10

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271413 – COMMUNICATIONS COPPER RISER CABLING

PART 1: GENERAL

The Contractor is held responsible to be familiar with the provisions contained herein and with other

Sections of this Specification as applicable to the completion of the installation.

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of copper riser infrastructure as described on the Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271423 Communications Optical Fiber Riser Cabling.

H.

Division 27, Section 271433 Communications Coaxial Riser Cabling.

I.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

J.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

K.

Division 27, Section 271543 Communications Faceplates and Connectors.

PART 2 - PRODUCTS

2.1 COPPER RISER CABLING

A.

Riser Cable (Voice) - Provide riser cables from the ER to each TR as indicated on Drawings or as indicated herein.

1.

Riser cables shall consist of twenty-five, and/or fifty, and/or one hundred unshielded twisted pairs, 24 gauge, solid copper, S-R PVC insulated conductors, rated category 3, with overall gray PVC jacket, CMR rated.

2.2 UTP CABLE

A.

Approved Manufacturers:

1.

Commscope

COMMUNICATIONS COPPER RISER CABLING

Version 12DEC2007

271413 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

General

3.

Essex

4.

Other approved equal submitted in advance as required in SOW

PART 3: EXECUTION

3.1 TELECOMMUNICATIONS INSTALLATION

A.

General:

1.

This Section describes the installation locations for the products and materials, as well as methods and CNM ITS CISM Standards associated with the Telecommunications

Installation portions of the Project. These Specifications, along with the drawings and other CNM ITS supplied specifications shall be followed during the course of the installation.

2.

The Contractor is instructed to coordinate his efforts with the other tradesmen who may be working within the same vicinity to avoid conflict and lost time.

3.

The Contractor is required to supply all necessary tools, equipment, accessories, safety equipment, protective clothing, etc., as customary for the craft and necessary for the installation.

4.

The Contractor shall verify space requirements and locations with CNM ITS before starting cable installations and terminations.

5.

The Contractor shall verify the cable type and jacket rating required with a CNM ITS before starting riser cable installation.

6.

The Contractor shall verify existing cable fill in riser conduit before installation of additional cables so as not to exceed 40% cable fill. Contractor will be responsible for installation of additional riser conduit, where additional cables to be added will exceed the

40% cable fill.

3.2 RISER CONDUITS

A.

Provide a nylon pull cord in each empty conduit to facilitate future installation of cables.

B.

Communication pathways requiring fire stopping shall utilize removable/re-usable fire stopping putties for ease of Moves, Adds, and Changes.

C.

All fire stopping penetrations shall conform to the recommended practices listed in UL1479 or ASTM E814 and must be labeled with the UL1479 or ASTM E814 reference number, dated, and signed by the technician who installed the fire stopping material.

3.3 RISER COPPER CABLING

A.

The copper riser cabling will be terminated at the ER and TR’s on 110 type wiring blocks or on patch panels depending on what is shown on the Drawings.

COMMUNICATIONS COPPER RISER CABLING

Version 12DEC2007

271413 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Horizontal cabling shall be terminated such that wire pair twists are maintained as closely as possible to the point of mechanical termination.

C.

Maintain cable sheath to leading edge of connector block.

D.

Contractor is responsible to obtain and follow installation instructions for manufacturer products for correct termination and wire management of cables on respective products.

E.

CNM ITS to provide future cross-connect terminations to Campus switch.

3.4 WIRING COLOR CODES

A.

Wiring Color Code - Unshielded Data Riser Cable and telephone trunk cable. Note: Riser cables greater than 25 pair have same color code with different binder ribbon for each 25 pair group.

3.05 GENERAL CABLE INSTALLATION

COMMUNICATIONS COPPER RISER CABLING

Version 12DEC2007

271413 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

Cable bends shall not be greater than that recommended by the manufacturer of the cable.

B.

Care shall be taken so as not to damage cable during the installation process and that manufacturer’s pull tension specification is not exceeded.

C.

Provide a minimum 8’-0” and maximum 10’-0” of slack. Loop at the TRs to be contained in the cable tray. Smaller slack loops may be required at ER cabinets.

D.

Within TRs, cables shall be snugly wrapped using Velcro reusable cable ties, a minimum of every 3 feet for cable organization. Wire ties shall be tightened so as not to deform cable jackets and thus affect cable performance.

E.

Cable fill in riser conduits shall not exceed 40% cable fill.

F.

New TRs must be free from dust, dirt, and other foreign materials before the installation of any termination hardware or the termination of copper or fiber optic cables. The door to the telecommunication rooms must be installed and closed during termination.

3.6 CABLE TESTING

A.

A 100% verification by CNM ITS of all copper riser cable tests is required. Contractor shall notify the CNM ITS Representative before the start of testing. Contractor may request CNM

ITS to accompany them in the testing of cables to ensure proper information entry into the

Omniscanner.

B.

The vertical multiple pair copper riser cables shall be tested utilizing an Independent

Technologies, Inc. Test-All IV, Model ITC-302, Independent Technologies, Inc. Test- All 25, or CNM ITS Telecommunications approved equal, 4-pair or 25-pair communications and data network tester that enables the user to test 4-pair or 25-pair simultaneously. This should have attachments to enable direct testing of 110 wiring blocks. Contractor shall complete a riser cable summary form at the time of testing. The riser cable summary form shall contain a pass/fail indication along with other pertinent data regarding the cables tested. Testing required is 100%. Provide test results on CD/DVD to CNM ITS. CNM ITS has the option to perform 100% verification testing as part of acceptance of copper riser tests.

3.7 EQUIPMENT INSTALLATION AND CABLE TERMINATIONS

A.

All equipment shall be installed in a neat and workmanlike manner, arranged for convenient operation, testing and future maintenance.

B.

All paired cables shall be installed and terminated by technicians experienced in the termination of cables on connector blocks.

C.

The Contractor shall employ certified system installation technicians and have at least 5 years experience in the installation of similar and equivalent systems.

D.

The Contractor shall supply verification of experience, for this type of work, to the Architect for approval before performing any work.

3.8 AS-BUILT INFORMATION

COMMUNICATIONS COPPER RISER CABLING

Version 12DEC2007

271413 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

Contractor shall provide as-built information to CNM ITS to accompany all test result information.

B.

As-built information shall be in electronic format in AutoCAD version 2000. Indicate location of all riser conduit routes, distribution cable trays, junction boxes, and all additions and deletions pertaining to telecommunications. Include riser labeling next to all telecom symbols.

3.9 SYSTEM WARRANTY REQUIREMENTS

A.

Contractor shall perform all labeling requirements and provide testing documentation for verification as described herein.

B.

Contractor shall submit cable records to reflect all moves, adds, and changes.

C.

Manufacturer shall provide a system performance warranty for the installed system.

END OF SECTION 271413

COMMUNICATIONS COPPER RISER CABLING

Version 12DEC2007

271413 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271423 – COMMUNICATIONS OPTICAL FIBER RISER CABLING

PART 1 - GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of optic fiber riser infrastructure as described on the Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271413 Communications Copper Riser Cabling.

H.

Division 27, Section 271433 Communications Coaxial Riser Cabling.

I.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

J.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

K.

Division 27, Section 271543 Communications Faceplates and Connectors.

PART 2 - PRODUCTS

2.1 FIBER OPTIC RISER CABLING

A.

Multimode Fiber Optic Riser Cable (Data) - Provide backbone cables from the ER to each data TR as indicated on Drawings.

1.

General: a.

The optical fiber cable construction shall consist of 50/125 μ m multimode optical fibers, typically formed into groups of 6 or 12 fibers each. These groups and individual fibers shall be identifiable in accordance with ANSI/EIA/TIA-598. These groups consist of individually jacketed 900um tight buffered fiber strands around a dielectric central member with a flame-retardant outer jacket to form a protective sheath. b.

The function of optical fiber cables is to provide a compact, low loss, broad bandwidth transmission medium suitable for the transmission of voice, video, and high-speed data signals under adverse electrical and environmental conditions.

2.

Optical Specifications:

COMMUNICATIONS OPTICAL FIBER RISER CABLING

Version 12DEC2007

271423 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) a.

Attenuation:

(1) The maximum attenuation of each multimode optical fiber within a cable, when normalized to a length of 1 kilometer, shall conform with the following attenuation:

< 3.0 dB/km @ 850 nm

< 1.0 dB/km @ 1300 nm

(2) Attenuation values and method of determining attenuation of each fiber shall be provided by cable manufacture and supplied with cable. b.

Bandwidth:

Note: Bandwidth values and method of determining bandwidth of each fiber shall be provided by cable manufacture and supplied with cable. c.

Core Diameter: The core diameter shall be 50 +3 um. d.

Numerical Aperture: The numeric aperture (far-field radiation pattern) shall be .20 +

.02.

3.

Mechanical Specifications: a.

The minimum tensile force over the entire length of the fiber shall be equivalent to

35.1 kg/mm2 (50 kpsi).

4.

Environmental Requirements: a.

The cable shall be expected to operate and be stored under the following conditions:

(1) Storage temperature range: -60o C to +85o C

(2) Operating temperature range: -50o C to +70o C

5.

Each cable shall contain 12 strands unless noted otherwise.

6.

Cable shall be listed as OFNP in all areas of the building regardless of plenum environment..

COMMUNICATIONS OPTICAL FIBER RISER CABLING

Version 12DEC2007

271423 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Single-mode Fiber Optic Riser Cable (Data) - Provide backbone cables from the ER to each data TR as indicated on Drawings.

1.

General: a.

The optical fiber cable construction shall consist of 8/125

μ m singlemode optical fibers, typically formed into groups of 6 or 12 fibers each. These groups and individual fibers shall be identifiable in accordance with ANSI/EIA/TIA-92CAAA.

These groups consist of individually jacketed 900um tight buffered fiber strands around a dielectric central member with a flame-retardant outer jacket to form a protective sheath. b.

The function of optical fiber cables is to provide a compact, low loss, broad bandwidth transmission medium suitable for the transmission of voice, video and high-speed data signals under adverse electrical and environmental conditions.

2.

Optical Specifications: a.

Attenuation:

(1) The maximum attenuation of each single-mode optical fiber within a cable, when normalized to a length of 1 kilometer, shall conform with the following attenuation:

< 1 dB/km @ 1310 nm

< .75 dB/km @ 1550 nm

(2) Attenuation values and method of determining attenuation of each fiber shall be provided by cable manufacture and supplied with cable.

3.

Mechanical Specifications: a.

The minimum tensile force over the entire length of the fiber shall be equivalent to

35.1 kg/mm2 (50 kpsi).

4.

Environmental Requirements: a.

The cable shall be expected to operate and be stored under the following conditions:

(1) Storage temperature range: -60o C to +85o C

(2) Operating temperature range: -50o C to +70o C

5.

Each cable shall contain 12 strands.

6.

Cable shall be listed as OFNP.

A.

Approved Manufacturers:

1.

CommScope

2.

General

3.

OCC

COMMUNICATIONS OPTICAL FIBER RISER CABLING

Version 12DEC2007

271423 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

4.

Other approved equal submitted in advance as required in SOW

PART 3 - EXECUTION

3.1 TELECOMMUNICATIONS INSTALLATION

A.

General:

1.

This Section describes the installation locations for the products and materials, as well as methods and Owner’s Standards associated with the Telecommunications Installation portions of the Project. These Specifications, along with the drawings and other Owner supplied specifications shall be followed during the course of the installation.

2.

The Contractor is instructed to coordinate his efforts with the other tradesmen who may be working within the same vicinity to avoid conflict and lost time.

3.

The Contractor is required to supply all necessary tools, equipment, accessories, safety equipment, protective clothing, etc., as customary for the craft and necessary for the installation.

4.

The Contractor shall verify space requirements and locations with Owner before starting cable installations and terminations.

5.

The Contractor shall verify the cable type and jacket rating required with a CNM IT

Telecommunications Representative before starting riser cable installation.

6.

The Contractor shall verify existing cable fill in riser conduit before installation of additional cables so as not to exceed 40% cable fill. Contractor will be responsible for installation of additional riser conduit, where additional cables to be added will exceed the

40% cable fill.

3.2 RISER CONDUITS

A.

Provide a nylon pull cord in each empty conduit to facilitate future installation of cables.

B.

Communication pathways requiring fire stopping shall utilize removable/re-usable fire stopping putties for ease of Moves, Adds, and Changes.

C.

All fire stopping penetrations shall conform to the recommended practices listed in UL1479 or ASTM E814 and must be labeled with the UL1479 or ASTM E814 reference number, dated, and signed by the technician who installed the fire stopping material.

3.3 RISER FIBER OPTIC CABLING

A.

The fiber optic riser cabling will be terminated on either wall mountable fiber enclosures on in frame mountable fiber enclosures. Verify termination type and location with a CNM IT

Telecommunications Representative.

B.

Contractor is responsible to obtain and follow installation instructions for fiber products for correct termination and wire management of cables on respective products.

COMMUNICATIONS OPTICAL FIBER RISER CABLING

Version 12DEC2007

271423 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

C.

Owner to provide future cross-connect terminations to network equipment.

3.4 FIBER COLOR CODES

A.

Fiber Color Code –

Note: Riser cables greater than 12-strand have same color code with different colored tube for each 12-strand group. Tube colors use same color scheme.

3.5 GENERAL CABLE INSTALLATION

A.

Cable bends shall not be greater than that recommended by the manufacturer of the cable.

B.

Care shall be taken so as not to damage cable during the installation process and that manufacturer’s pull tension specification is not exceeded.

C.

Provide a minimum 8’-0” and maximum 10’-0” of slack. Loop at the TRs to be contained within the fiber enclosure.

D.

Within TRs, cables shall be snugly wrapped using Velcro reusable cable ties, a minimum of every 3’-0” for cable organization. Wire ties shall be tightened so as not to deform cable jackets and thus affect cable performance.

E.

Cable fill in riser conduits shall not exceed 40% cable fill.

F.

New TRs must be free from dust, dirt, and other foreign materials before the installation of any termination hardware or the termination of fiber optic cables. The door to the telecommunication rooms must be installed and closed during termination.

3.6 CABLE TESTING

COMMUNICATIONS OPTICAL FIBER RISER CABLING

Version 12DEC2007

271423 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

A 100% verification by CNM ITS of all fiber riser cable tests is required. Contractor shall notify the CNM ITS before the start of testing. Contractor may request CNM ITS to accompany them in the testing of cables to ensure proper operation of the light meter. If CNM

ITS accompany the Contractor on testing, verification shall not be performed. B. The fiber optic cables shall be tested utilizing a power meter and stabilized light source capable of testing at 850 nm and 1300 nm for multimode and 1310nm and 1550nm for single-mode.

Contractor shall complete a fiber optic post installation report at the time of testing containing meter readings at both 850 nm and 1300 nm for multimode and 1310nm and 1550nm for single-mode from both directions on each fiber, actual loss and other pertinent data regarding the cables tested, including model and serial number of test equipment, cable part #, installed fiber length, building span loss at 850 nm and 1300 nm for multimode and 1310nm and

1550nm for single-mode and date tested. The fiber optic post installation report shall be in a form substantially similar to 3.6 Attachment 1. Testing required is 100%. Provide test results on CD/DVD to Owner. Span loss calculations are required on the final test sheet for loss at

850 nm and 1300 nm for multimode and 1310nm and 1550nm for single-mode.

(D x L) + (C x # connectors)

D = Length; L = Loss; C = Connector loss (Max 0.75 dB)

1 ft. = .0003048 km.

Owner will perform 100% verification testing as part of acceptance of all fiber optic cable testing.

3.7 EQUIPMENT INSTALLATION AND CABLE TERMINATIONS

A.

All equipment shall be installed in a neat and workmanlike manner, arranged for convenient operation, testing and future maintenance.

B.

All fiber cables shall be installed and terminated by technicians experienced in the termination of fiber.

C.

The Contractor shall employ certified system installation technicians and have at least 5 years experience in the installation of similar and equivalent systems.

D.

The Contractor shall supply verification of experience, for this type of work, to the Architect for approval before performing any work.

3.8 AS-BUILT INFORMATION

A.

Contractor shall provide as-built information to Owner to accompany all test result information.

COMMUNICATIONS OPTICAL FIBER RISER CABLING

Version 12DEC2007

271423 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

As-built information shall be in electronic format in AutoCAD v. 2000. Indicate location of all riser conduit routes, distribution cable trays, junction boxes, and all additions and deletions pertaining to telecommunications. Include riser labeling next to all telecom symbols.

C.

If construction drawings are not utilized, Contractor shall provide all telecommunications location information on an accurate scaled floor plan.

3.9 SYSTEM WARRANTY REQUIREMENTS

A.

Contractor shall perform all labeling requirements and provide testing documentation for verification as described herein.

B.

Contractor shall submit cable records to reflect all moves, adds, and changes.

C.

Manufacturer shall provide a system performance warranty for the installed system.

END OF SECTION 27143

COMMUNICATIONS OPTICAL FIBER RISER CABLING

Version 12DEC2007

271423 - 7

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271433 – COMMUNICATIONS COAXIAL RISER CABLING

PART 1 - GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of coaxial riser infrastructure as described on the Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271413 Communications Copper Riser Cabling.

H.

Division 27, Section 271423 Communications Optical Fiber Riser Cabling.

I.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

J.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

K.

Division 27, Section 271543 Communications Faceplates and Connectors.

PART 2 - PRODUCTS

2.1 COAX RISER CABLING

A.

Riser Cables (CATV) - Provide CATV riser cables from the ER to each TR where CATV is to be distributed from.

1.

Riser cables shorter than 150ft shall be Type RG-6, 18 gauge, solid copper center conductor.

2.

Riser cables longer than 150ft shall be Type RG-11, 14 gauge, solid copper center conductor.

B.

Approved Manufacturers:

1.

CommScope

2.

General

COMMUNICATIONS COAXIAL RISER CABLING

Version 12DEC2007

271433 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

3.

Belden

4.

Other approved equal submitted in advance as required in SOW

PART 3 - EXECUTION

3.1 TELECOMMUNICATIONS INSTALLATION

A.

General:

1.

This Section describes the installation locations for the products and materials, as well as methods and CNM ITS CISM Standards associated with the Telecommunications

Installation portions of the Project. These Specifications, along with the drawings and other CNM ITS supplied specifications shall be followed during the course of the installation.

2.

The Contractor is instructed to coordinate his efforts with the other tradesmen who may be working within the same vicinity to avoid conflict and lost time.

3.

The Contractor is required to supply all necessary tools, equipment, accessories, safety equipment, protective clothing, etc., as customary for the craft and necessary for the installation.

4.

The Contractor shall verify space requirements and locations with CNM ITS before starting cable installations and terminations.

5.

The Contractor shall verify the cable type and jacket rating required with a CNM ITS before starting riser cable installation.

6.

The Contractor shall verify existing cable fill in riser conduit before installation of additional cables so as not to exceed 40% cable fill. Contractor will be responsible for installation of additional riser conduit, where additional cables to be added will exceed the

40% cable fill.

3.2 RISER CONDUITS

A.

Provide a nylon pull cord in each empty conduit to facilitate future installation of cables.

B.

Communication pathways requiring fire stopping shall utilize removable/re-usable fire stopping putties for ease of Moves, Adds, and Changes.

C.

All fire stopping penetrations shall conform to the recommended practices listed in UL1479 or ASTM E814 and must be labeled with the UL1479 or ASTM E814 reference number, dated, and signed by the technician who installed the fire stopping material.

3.3 RISER COAX CABLING

A.

The riser coax cabling will be terminated at the TR or ER on a wall designated by a CNM

ITS.

COMMUNICATIONS COAXIAL RISER CABLING

Version 12DEC2007

271433 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Contractor is responsible to obtain and follow installation instructions for manufacturer products for correct installation and termination of coax cables on respective products.

C.

CNM ITS to provide future taps, splitters, and amplifiers.

3.4 GENERAL CABLE INSTALLATION

A.

Cable bends shall not be greater than that recommended by the manufacturer of the cable.

B.

Care shall be taken so as not to damage cable during the installation process and that manufacturer’s pull tension specification is not exceeded.

C.

Provide a minimum 8’-0” and maximum 10’-0” of slack. Loop at the TRs to be contained in the cable tray.

D.

Within TRs, cables shall be snugly wrapped using Velcro reusable cable ties, a minimum of every 3’-0” for cable organization. Wire ties shall be tightened so as not to deform cable jackets and thus affect cable performance.

E.

Cable fill in station conduits, skeletal conduits, raceway, and cable tray shall not exceed 40% cable fill.

F.

New TRs must be free from dust, dirt, and other foreign materials before the installation of any termination hardware or the termination of copper or fiber optic cables. The door to the telecommunication rooms must be installed and closed during termination.

3.5 CABLE TESTING

A.

The vertical CATV riser cables shall be tested utilizing a Fluke OmniscannerII, Fluke 4000 series tester, or a Fluke DTX scanner. Test unit shall be set up using RG-6 or RG-11 cable selected, depending on type of cable used. Testing required is 100%. Contractor shall provide the information files via CD/DVD.

3.6 EQUIPMENT INSTALLATION AND CABLE TERMINATIONS

A.

All equipment shall be installed in a neat and workmanlike manner, arranged for convenient operation, testing and future maintenance.

B.

All coax cables shall be installed and terminated by technicians experienced in the termination of coax cables.

C.

The Contractor shall employ certified system installation technicians and have at least 5 years experience in the installation of similar and equivalent systems.

D.

The Contractor shall supply verification of experience, for this type of work, to the Architect for approval before performing any work.

3.7 AS-BUILT INFORMATION

A.

Contractor shall provide as-built information to CNM ITS to accompany all test result information.

COMMUNICATIONS COAXIAL RISER CABLING

Version 12DEC2007

271433 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

As-built information shall be in electronic format in AutoCAD version 2000. Indicate location of all riser conduit routes, distribution cable trays, junction boxes, and all additions and deletions pertaining to telecommunications. Include riser labeling next to all telecom symbols.

C.

If construction drawings are not utilized, Contractor shall provide all telecommunications location information on an accurate scaled floor plan.

3.8 SYSTEM WARRANTY REQUIREMENTS

A.

Contractor shall perform all labeling requirements and provide testing documentation for verification as described herein.

B.

Contractor shall submit cable records to reflect all moves, adds, and changes.

C.

Manufacturer shall provide a system performance warranty for the installed system.

END OF SECTION 271433

COMMUNICATIONS COAXIAL RISER CABLING

Version 12DEC2007

271433 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271500 - COMMUNICATIONS HORIZONTAL CABLING

PART 1 - GENERAL

1.1

RELATED DOCUMENTS

A.

Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

1.2

SUMMARY

A.

Section Includes:

1.

Pathways.

2.

UTP cabling.

3.

Multimode optical fiber cabling.

4.

Coaxial cable.

5.

Telecommunications Outlet assemblies.

6.

Cable connecting hardware, patch panels, and cross-connects.

7.

Telecommunications outlet/connectors.

8.

Cabling system identification products.

9.

Cable management system.

1.3

RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271313 Communications Copper Backbone Cabling.

D.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

E.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

F.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

G.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

H.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

I.

Division 27, Section 271543 Communications Faceplates and Connectors.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.4

DEFINITIONS

A.

Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

B.

BICSI: Building Industry Consulting Service International.

C.

Channel Cable Tray: A fabricated structure consisting of a one-piece, ventilated-bottom or solid-bottom channel.

D.

Consolidation Point: A location for interconnection between horizontal cables extending from building pathways and horizontal cables extending into furniture pathways.

E.

Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

F.

EMI: Electromagnetic interference.

G.

IDC: Insulation displacement connector.

H.

Ladder Cable Tray: A fabricated structure consisting of two longitudinal side rails connected by individual transverse members (rungs).

I.

LAN: Local area network.

J.

TO: Multiuser telecommunications outlet assembly, a grouping in one location of several telecommunications outlet/connectors.

K.

Outlet/Connectors: A connecting device in the work area on which horizontal cable or outlet cable terminates.

L.

RCDD: Registered Communications Distribution Designer.

M.

Solid-Bottom or Nonventilated Cable Tray: A fabricated structure consisting of longitudinal side rails and a bottom without ventilation openings.

N.

Trough or Ventilated Cable Tray: A fabricated structure consisting of longitudinal side rails and a bottom having openings for the passage of air.

O.

UTP: Unshielded twisted pair.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

HORIZONTAL CABLING DESCRIPTION 1.5

A.

Horizontal cable and its connecting hardware provide the means of transporting signals between the telecommunications outlet/connector and the horizontal cross-connect located in the communications equipment room. This cabling and its connecting hardware are called "permanent link," a term that is used in the testing protocols.

1.

TIA/EIA-568-B.1 requires that a minimum of two telecommunications outlet/connectors be installed for each work area. For CNM, the quantity of outlets will vary depending on the space to be occupied. Refer to Drawings for actual layout and quantities.

2.

Horizontal cabling shall contain no more that one transition point or consolidation point between the horizontal cross-connect and the telecommunications outlet/connector.

3.

Bridged taps and splices shall not be installed in the horizontal cabling.

4.

Splitters shall not be installed as part of the optical fiber cabling.

B.

A work area is approximately 100 sq. ft. (10 sq. m), and includes the components that extend from the telecommunications outlet/connectors to the station equipment.

C.

The maximum allowable horizontal cable length is 295 feet (90 m). This maximum allowable length does not include an allowance for the length of 16 feet (4.9 m) to the workstation equipment. The maximum allowable length does not include an allowance for the length of 16 feet (4.9 m) in the horizontal cross-connect.

1.6

PERFORMANCE REQUIREMENTS

A.

General Performance: Horizontal cabling system shall comply with transmission standards in TIA/EIA-568-B.1, when tested according to test procedures of this standard.

1.7

SUBMITTALS

A.

Product Data: For each type of product indicated.

1.

For coaxial cable, include the following installation data for each type used: a.

Nominal OD. b.

Minimum bending radius. c.

Maximum pulling tension.

B.

Shop Drawings:

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

System Labeling Schedules: Electronic copy of labeling schedules, in software and format selected by CNM.

2.

System Labeling Schedules: Electronic copy of labeling schedules that are part of the cabling and asset identification system of the software.

3.

Cabling administration drawings and printouts.

4.

Wiring diagrams to show typical wiring schematics, including the following: a.

Cross-connects. b.

Patch panels. c.

Patch cords.

5.

Cross-connects and patch panels. Detail mounting assemblies, and show elevations and physical relationship between the installed components.

6.

Cable tray layout, showing cable tray route to scale, with relationship between the tray and adjacent structural, electrical, and mechanical elements. Include the following: a.

Vertical and horizontal offsets and transitions. b.

Clearances for access above and to side of cable trays. c.

Vertical elevation of cable trays above the floor or bottom of ceiling structure. d.

Load calculations to show dead and live loads as not exceeding manufacturer's rating for tray and its support elements.

C.

Qualification Data: Technicians must be manufacturer certified on the system being installed.

D.

Source quality-control reports.

E.

Field quality-control reports.

F.

Maintenance Data: For splices and connectors to include in maintenance manuals.

1.8

QUALITY ASSURANCE

A.

Installer Qualifications: Cabling Installer must have personnel that are manufacturer certified on staff. Proof will be required.

1.

Layout Responsibility: Preparation of Shop Drawings by a BICSI certified RCDD on staff.

2.

Installation Supervision: Installation shall be under the direct supervision of a Lead

Technician, who shall be present at all times when Work of this Section is performed at Project site.

3.

Testing Supervisor: Must be properly trained on test equipment.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Manufacturer Warranty:

1.

System installed must be manufacturer certified with a system performance warranty of no less than 15 years.

C.

Electrical Components, Devices, and Accessories: Listed and labeled as defined in

NFPA 70, by a qualified testing agency, and marked for intended location and application.

D.

Telecommunications Pathways and Spaces: Comply with TIA/EIA-569-A.

E.

Grounding: Comply with ANSI-J-STD-607-A.

1.9

DELIVERY, STORAGE, AND HANDLING

A.

Test cables upon receipt at Project site.

1.

Test optical fiber cables to determine the continuity of the strand end to end.

2.

Test optical fiber cables while on reels. Use an optical time domain reflectometer to verify the cable length and locate cable defects, splices, and connector; including the loss value of each. Retain test data and include the record in maintenance data.

3.

Test each pair of UTP cable for open and short circuits.

1.10

PROJECT CONDITIONS

A.

Environmental Limitations: Do not deliver or install cables and connecting materials until plumbing work in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period.

B.

All equipment rooms included in this work must be cleaned from ceiling to floor prior to the installation activity being performed in the space.

1.11

COORDINATION

A.

Coordinate layout and installation of telecommunications pathways and cabling with

Owner's telecommunications and LAN equipment and service suppliers.

B.

Coordinate telecommunications outlet/connector locations with location of power receptacles at each work area.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.12

EXTRA MATERIALS

A.

Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1.

Patch-Panel Units: 10% of installed units rounded up.

2.

Connecting Blocks: 10% of installed units rounded up.

3.

Device Faceplates: 10% of installed units rounded up.

4.

Outlet Assemblies: 10% of installed units rounded up.

PART 2 - PRODUCTS

2.1

UTP CABLE

A.

Approved Manufacturers:

1.

CommScope

2.

Essex

3.

General

4.

Other approved equal submitted in advance as required in SOW

B.

Description: 100-ohm, 4-pair UTP covered with a blue jacket.

1.

Comply with ICEA S-90-661 for mechanical properties.

2.

Comply with TIA/EIA-568-B.1 for performance specifications.

3.

Comply with TIA/EIA-568-B.2, Category 6

4.

Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70 for the following types: a.

Communications, Plenum Rated Only: Type CMP

2.2

UTP CABLE HARDWARE

B.

Approved Manufacturers:

1.

CommScope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

General Requirements for Cable Connecting Hardware: Comply with TIA/EIA-568-B.2,

IDC type, with modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of same category or higher.

C.

Connecting Blocks: 110-style IDC for Category 6. Provide blocks for the number of cables terminated on the block, plus 25 percent spare. Integral with connector bodies, including plugs and jacks where indicated.

D.

Cross-Connect: Modular array of connecting blocks arranged to terminate building cables and permit interconnection between cables.

1.

Number of Terminals per Field: One for each conductor in assigned cables.

E.

Patch Panel: Modular panels housing multiple-numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables.

1.

Number of Jacks per Field: One for each four-pair UTP cable indicated.

F.

Jacks and Jack Assemblies: Modular, color-coded, eight-position modular receptacle units with integral IDC-type terminals.

2.3

OPTICAL FIBER CABLE

C.

Approved Manufacturers:

1.

CommScope

2.

General

3.

OCC

4.

Other approved equal submitted in advance as required in SOW

B.

Description: Multimode, 50/125-micrometer, 24-fiber, tight buffer, optical fiber cable.

1.

Comply with ICEA S-83-596 for mechanical properties.

2.

Comply with TIA/EIA-568-B.3 for performance specifications.

3.

Comply with TIA/EIA-492AAAA-B for detailed specifications.

4.

Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444, UL 1651, and NFPA 70 for the following types: a.

Plenum Rated, Nonconductive: Type OFNP, complying with NFPA 262.

5.

Maximum Attenuation: 3.5dB/km at 850 nm; 1.5dB/km at 1300 nm.

6.

Minimum Modal Bandwidth: 160 MHz-km at 850 nm; 500 MHz-km at 1300 nm.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 7

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

C.

Jacket:

1.

Jacket Color: Aqua for 50/125-micrometer cable.

2.

Cable cordage jacket, fiber, unit, and group color shall be according to TIA/EIA-598-

B.

3.

Imprinted with fiber count, fiber type, and aggregate length at regular intervals not to exceed 40 inches (1000 mm).

2.4

OPTICAL FIBER CABLE HARDWARE

D.

Approved Manufacturers:

1.

CommScope

2.

Hubbell

3.

3M

4.

Other approved equal submitted in advance as required in SOW

B.

Cross-Connects and Patch Panels: Modular panels housing multiple-numbered, duplex cable connectors.

1.

Number of Connectors per Field: One for each fiber of cable or cables assigned to field, plus spares and blank positions adequate to suit specified expansion criteria.

C.

Cable Connecting Hardware:

1.

Comply with Optical Fiber Connector Intermateability Standards (FOCIS) specifications of TIA/EIA-604-2, TIA/EIA-604-3-A, and TIA/EIA-604-12. Comply with TIA/EIA-568-B.3.

2.

Quick-connect, simplex and duplex, available in SC, ST, LC and MT-RJ style connectors. Insertion loss not more than 0.75 dB.

2.5

COAXIAL CABLE

A.

Approved Manufacturers:

1.

CommScope

2.

Belden

3.

General

4.

Other approved equal submitted in advance as required in SOW

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 8

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Cable Characteristics: Broadband type, recommended by cable manufacturer specifically for broadband data transmission applications. Coaxial cable and accessories shall have 75ohm nominal impedance with a return loss of 20 dB maximum from 7 to 806 MHz.

2.6

CONSOLIDATION POINTS

A.

Approved Manufacturers:

1.

CommScope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

B.

Description: Consolidation points shall comply with requirements for cable connecting hardware.

1.

Number of Terminals per Field: One for each conductor in assigned cables.

2.

Number of Connectors per Field: a.

One for each four-pair UTP cable indicated. b.

One for each four-pair conductor group of indicated cables, plus 25 percent spare positions.

2.7

TELECOMMUNICATIONS OUTLET ASSEMBLY (TO)

A.

Approved Manufacturers:

1.

CommScope

2.

Essex

3.

General

4.

Other approved equal submitted in advance as required in SOW

B.

Description: TO’s shall meet the requirements for cable connecting hardware.

1.

Number of Terminals per Field: One for each conductor in assigned cables.

2.

Number of Connectors per Field: a.

One for each four-pair UTP cable indicated. b.

One for each four-pair conductor group of indicated cables.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 9

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

TELECOMMUNICATIONS OUTLET/CONNECTORS 2.8

A.

Jacks: 100-ohm, balanced, twisted-pair connector; four-pair, eight-position modular.

Comply with TIA/EIA-568-B.1.

B.

Workstation Outlets: 3-port-connector assemblies mounted in single gang faceplate.

1.

Plastic Faceplate: High-impact plastic.

2.

Metal Faceplate for Wall phone: Stainless Steel.

3.

For use with snap-in jacks accommodating any combination of UTP, optical fiber, and coaxial work area cords. a.

Flush mounting jacks, positioning the cord at a 90-degree angle.

4.

Legend: Machine printed, in the field, using adhesive-tape label.

5.

Legend: Snap-in, clear-label covers and machine-printed paper inserts.

2.9

GROUNDING

A.

Comply with requirements in Division 270526 Section "Grounding and Bonding" for grounding conductors and connectors.

B.

Comply with ANSI-J-STD-607-A.

2.10

IDENTIFICATION PRODUCTS

A.

Comply with TIA/EIA-606-A and UL 969 for labeling materials, including label stocks, laminating adhesives, and inks used by label printers.

B.

Comply with requirements in Division 270553 Section "Identification for Communications

Systems."

2.11

SOURCE QUALITY CONTROL

A.

Factory test UTP and optical fiber cables on reels according to TIA/EIA-568-B.1.

B.

Factory test UTP cables according to TIA/EIA-568-B.2.

C.

Factory test multimode optical fiber cables according to TIA/EIA-526-14-A and TIA/EIA-

568-B.3.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 10

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

D.

Factory-sweep test coaxial cables at frequencies from 5 MHz to 1 GHz. Sweep test shall test the frequency response, or attenuation over frequency, of a cable by generating a voltage whose frequency is varied through the specified frequency range and graphing the results.

E.

Cable will be considered defective if it does not pass tests and inspections.

F.

Prepare test and inspection reports.

PART 3 - EXECUTION

3.1

ENTRANCE FACILITIES

A.

Coordinate backbone cabling with the protectors and demarcation point provided by communications service provider to ensure proper placement within room.

3.2

WIRING METHODS

A.

Wiring Method: Install cables in raceways and cable trays except within consoles, cabinets, desks, and counters. Conceal raceway and cables except in unfinished spaces.

1.

Install plenum cable in all spaces regardless of Plenum environment.

2.

Comply with requirements for raceways and boxes specified in Division 270528

Section.

B.

Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible.

C.

Wiring within Enclosures: Bundle and train cables to terminal points with no excess and without exceeding manufacturer's limitations on bending radii.

3.3

INSTALLATION OF PATHWAYS

A.

Cable Trays: Comply with NEMA VE 2 and TIA/EIA-569-A-7.

B.

Comply with requirements for demarcation point, pathways, cabinets, and racks specified in

Division 271101 Section. Drawings indicate general arrangement of pathways and fittings.

C.

Comply with TIA/EIA-569-A for pull-box sizing and length of conduit and number of bends between pull points.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 11

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

D.

Comply with requirements in Division 270528 Section for installation of conduits and wireways.

E.

Install manufactured conduit sweeps and long-radius elbows whenever possible.

F.

Pathway Installation in Communications Equipment Rooms:

1.

Position conduit ends adjacent to a corner on backboard where a single piece of plywood is installed, or in the corner of room where multiple sheets of plywood are installed around perimeter walls of room.

2.

Install cable trays to route cables if conduits cannot be located in these positions.

3.

Secure conduits to backboard when entering room from overhead.

4.

Extend conduits 4 inches (100 mm) above finished floor.

5.

Install metal conduits with grounding bushings and connect with grounding conductor to grounding system.

G.

Backboards: Install backboards with 96-inch (2440-mm) dimension vertical. Butt adjacent sheets tightly, and form smooth gap-free corners and joints.

3.4

INSTALLATION OF CABLES

A.

Comply with NECA 1.

B.

General Requirements for Cabling:

1.

Comply with TIA/EIA-568-B.1.

2.

Comply with BICSI ITSIM, Ch. 6, "Cable Termination Practices."

3.

Install 110-style IDC termination hardware unless otherwise indicated.

4.

TO shall not be used as a cross-connect point.

5.

Consolidation points may be used only for making a direct connection to telecommunications outlet/connectors: a.

Do not use consolidation point as a cross-connect point, as a patch connection, or for direct connection to workstation equipment. b.

Locate consolidation points for UTP at least 49 feet (15 communications equipment room.

6.

Terminate conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels.

7.

Cables may not be spliced. Secure and support cables at intervals not exceeding 30 inches (760 mm) and not more than 6 inches (150 mm) from cabinets, boxes, fittings,

8.

outlets, racks, frames, and terminals.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 12

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

9.

Bundle and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI TDMM,

"Cabling Termination Practices" Chapter. Install support bars and distribution spools.

10.

Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable.

11.

Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not be used for heating.

12.

In the communications equipment room, install a 10-foot- (3-m-) long service loop on each end of cable.

13.

Pulling Cable: Comply with BICSI TDMM, Ch. 4, "Pulling Cable" and manufacturer recommended practices. Monitor cable pull tensions.

C.

UTP Cable Installation:

1.

Comply with TIA/EIA-568-B.2.

2.

Do not untwist UTP cables more than 1/2 inch (12 mm) from the point of termination to maintain cable geometry.

D.

Optical Fiber Cable Installation:

1.

Comply with TIA/EIA-568-B.3.

2.

Cable may be terminated on connecting hardware that is rack or cabinet mounted.

E.

Open-Cable Installation:

1.

Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment.

2.

Suspend UTP cable not in a wireway or pathway a minimum of 8 inches (200 mm) above ceilings by cable supports not more than 60 inches (1524 mm) apart.

3.

Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items.

F.

Installation of Cable Routed Exposed under Raised Floors:

1.

Install plenum-rated cable only.

2.

Install cabling after the flooring system has been installed in raised floor areas.

3.

Coil cable 6 feet (1800 mm) long not less than 12 inches (300 mm) in diameter below each feed point.

G.

Group connecting hardware for cables into separate logical fields.

H.

Separation from EMI Sources:

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 13

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Comply with BICSI TDMM and TIA/EIA-569-A for separating unshielded copper voice and data communication cable from potential EMI sources, including electrical power lines and equipment.

2.

Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows: a.

Electrical Equipment Rating Less Than 2 kVA: A minimum of 5 inches (127 mm). b.

Electrical Equipment Rating between 2 and 5 kVA: A minimum of 12 inches

(300 mm). c.

Electrical Equipment Rating More Than 5 kVA: A minimum of 24 inches (610 mm).

3.

Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows: a.

Electrical Equipment Rating Less Than 2 kVA: A minimum of 2-1/2 inches (64 mm). b.

Electrical Equipment Rating between 2 and 5 kVA: A minimum of 6 inches

(150 mm). c.

Electrical Equipment Rating More Than 5 kVA: A minimum of 12 inches (300 mm).

4.

Separation between communications cables in grounded metallic raceways and power lines and electrical equipment located in grounded metallic conduits or enclosures shall be as follows: a.

Electrical Equipment Rating Less Than 2 kVA: No requirement. b.

Electrical Equipment Rating between 2 and 5 kVA: A minimum of 3 inches (76 mm). c.

Electrical Equipment Rating More Than 5 kVA: A minimum of 6 inches (150 mm).

5.

Separation between Communications Cables and Electrical Motors and Transformers,

5 kVA or HP and Larger: A minimum of 48 inches (1200 mm).

6.

Separation between Communications Cables and Fluorescent Fixtures: A minimum of

5 inches (127 mm).

3.5

FIRESTOPPING

A.

Comply with requirements in Division 07 Section "Penetration Firestopping."

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 14

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Comply with TIA/EIA-569-A, Annex A, "Firestopping."

C.

Comply with BICSI TDMM, "Firestopping Systems" Article.

D.

Approved Manufacturers:

1.

STI

2.

3M

3.

Nelson

4.

Other approved equal submitted in advance as required in SOW

3.6

GROUNDING

A.

Install grounding according to Division 270526 “Grounding and Bonding.”

B.

Comply with ANSI-J-STD-607-A.

C.

Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall allowing at least 2-inch (50-mm) clearance behind the grounding bus bar. Connect grounding bus bar with a minimum No. 4 AWG grounding electrode conductor from grounding bus bar to suitable electrical building ground.

D.

Bond metallic equipment to the grounding bus bar, using not smaller than No. 6 AWG equipment grounding conductor.

3.7

IDENTIFICATION

A.

Identify system components, wiring, and cabling complying with TIA/EIA-606-A. Comply with requirements for identification specified in Division 270553 Section "Identification for

Communications Systems."

1.

Color-code cross-connect fields. Apply colors to voice and data service backboards, connections, covers, and labels.

B.

Comply with requirements in Division backboards. For fire-resistant plywood, do not paint over manufacturer's label.

C.

Paint and label colors for equipment identification shall comply with TIA/EIA-606-A.

D.

Cable Schedule: Post in prominent location in each equipment room and wiring closet. List incoming and outgoing cables and their designations, origins, and destinations. Protect with

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 15

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) rigid frame and clear plastic cover. Furnish an electronic copy of final comprehensive schedules for Project.

E.

Cabling Administration Drawings: Show building floor plans with cabling administrationpoint labeling. Identify labeling convention and show labels for telecommunications closets, terminal hardware and positions, horizontal cables, work areas and workstation terminal positions, grounding buses and pathways, and equipment grounding conductors. Furnish electronic record of all drawings, in software and format selected by CNM ITS.

F.

Cable and Wire Identification:

1.

Label each cable within 4 inches (100 mm) of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated.

2.

Label each terminal strip and screw terminal in each cabinet, rack, or panel. a.

Individually number wiring conductors connected to terminal strips, and identify each cable or wiring group being extended from a panel or cabinet to a buildingmounted device shall be identified with name and number of particular device as shown. b.

Label each unit and field within distribution racks and frames.

3.

Identification within Connector Fields in Equipment Rooms and Wiring Closets:

Label each connector and each discrete unit of cable-terminating and connecting hardware.

4.

Uniquely identify and label work area cables extending from the TO to the work area.

These cables may not exceed the length stated on the TO label.

G.

Labels shall be preprinted or computer-printed type with printing area and font color that contrasts with cable jacket color but still complies with requirements in TIA/EIA-606-A.

1.

Cables use flexible vinyl or polyester that flex as cables are bent.

3.8

FIELD QUALITY CONTROL

A.

Perform tests and inspections.

B.

Tests and Inspections:

1.

Visually inspect UTP and optical fiber cable jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments, and inspect cabling connections for compliance with TIA/EIA-568-B.1.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 16

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

2.

Visually confirm Category 6 marking of outlets, cover plates, outlet/connectors, and patch panels.

3.

Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.

4.

Test UTP backbone copper cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not cross-connection. a.

Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-

B.2. Perform tests with a tester that complies with performance requirements in

"Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.

5.

Optical Fiber Cable Tests: a.

Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-

B.1. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration. b.

Link End-to-End Attenuation Tests:

1) Horizontal and multimode backbone link measurements: Test at 850 or

1300 nm in 1 direction according to TIA/EIA-526-14-A, Method B, One

Reference Jumper.

2) Attenuation test results for backbone links shall be less than 2.0 dB.

Attenuation test results shall be less than that calculated according to equation in TIA/EIA-568-B.1.

6.

UTP Performance Tests: a.

Test for each outlet and TO. Perform the following tests according to TIA/EIA-

568-B.1 and TIA/EIA-568-B.2:

1) Wire map.

2) Length (physical vs. electrical, and length requirements).

3) Insertion loss.

4) Near-end crosstalk (NEXT) loss.

5) Power sum near-end crosstalk (PSNEXT) loss.

6) Equal-level far-end crosstalk (ELFEXT).

7) Power sum equal-level far-end crosstalk (PSELFEXT).

8) Return loss.

9) Propagation delay.

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 17

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

10) Delay skew.

7.

Optical Fiber Cable Performance Tests: Perform optical fiber end-to-end link tests according to TIA/EIA-568-B.1 and TIA/EIA-568-B.3.

8.

Coaxial Cable Tests: Conduct tests according to Division 27 Section "Master Antenna

Television System."

C.

Document data for each measurement. All tests will be captured in tester native format and provided to CNM ITS in native format along with viewer on CD to view results. No hardcopies are required.

D.

End-to-end cabling will be considered defective if it does not pass tests and inspections.

E.

Prepare test and inspection reports.

END OF SECTION 271500

COMMUNICATIONS HORIZONTAL CABLING

Version 12DEC2007

271500 - 18

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271513 – COMMUNICATIONS COPPER HORIZONTAL CABLING

PART 1: GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of grounding and bonding infrastructure as described on the Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270543 Underground Ducts and Raceways for Communication Systems.

C.

Division 27, Section 270553 Identification for Communication Systems.

D.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

E.

Division 27, Section 271313 Communications Copper Backbone Cabling.

F.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

G.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

H.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

I.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

J.

Division 27, Section 271543 Communications Faceplates and Connectors.

PART 2 - PRODUCTS

2.1 GENERAL

A.

The materials and products specified herein reflect the minimum acceptable standards of fabrication and manufacture. All materials and products supplied by the Contractor and specified herein are to be new, unused, of first quality and in original packaging or shipping containers or as shown on drawings and described in Item 3.1.

B.

New buildings and major renovations will be treated differently than existing buildings.

Existing buildings will utilize Category 6 cabling and termination hardware for voice and data. New building construction and CNM ITS approved large-scale renovations will utilize

Category 6 cabling and termination hardware for voice and data. Contact CNM Information

Technology Telecommunications Department Representative for approval of cabling systems before installation.

2.2 HORIZONTAL UTP CABLING

A.

All buildings will utilize Category 6 cabling:

COMMUNICATIONS COPPER HORIZONTAL CABLING

Version 12DEC2007

271513 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Single 4-pair, Category 6, unshielded twisted pairs, 23 gauge, bare copper, polyethylene insulated conductors, with overall BLUE PVC flame retardant jacket, CMP rated.

B.

Approved Manufacturers:

1.

CommScope

2.

General

3.

Essex

4.

Other approved equal submitted in advance as required in SOW

PART 3 - EXECUTION

3.1 TELECOMMUNICATIONS INSTALLATION

A.

General:

1.

This Section describes the installation locations for the products and materials, as well as methods and CNM ITS CISM Standards associated with the Telecommunications

Installation portions of the Project. These Specifications, along with the drawings and other CNM ITS supplied specifications shall be followed during the course of the installation.

2.

The Contractor is required to be currently listed as a registered Certified Installer and provide personnel for telecommunications installations who are certified. See Warranty information 3.10.

3.

The Contractor is instructed to coordinate his efforts with the other tradesmen who may be working within the same vicinity to avoid conflict and lost time.

4.

The Contractor is required to supply all necessary tools, equipment, accessories, safety equipment, protective clothing, etc., as customary for the craft and necessary for the installation.

5.

The Contractor shall verify space requirements and locations with CNM ITS before starting cable installations and terminations.

6.

The Contractor shall verify the cable type and jacket rating required with CNM ITS before starting cable installation.

7.

The Contractor shall verify existing cable fill in conduit, raceway or cable tray system before installation of additional cables so as not to exceed 40% cable fill. Contractor will be responsible for installation of additional conduit, raceway or cable tray where additional cables to be added will exceed the 40% cable fill. See cable fill TABLE ON

Page 6.

3.2 CABLE TRAY, AND STATION CONDUITS

A.

Provide a nylon pull cord in each conduit to facilitate future installation of cables.

COMMUNICATIONS COPPER HORIZONTAL CABLING

Version 12DEC2007

271513 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

Provide nylon pull cord in each conduit and extended in raceway to openings for faceplates to facilitate future installation of cables in sections greater than 30 feet.

C.

Provide a nylon pull cord in each straight section of cable tray. Pull cord shall be continuous from each end of the straight section of tray.

3.3 HORIZONTAL COPPER CABLING

A.

The copper telephone horizontal cabling will be terminated at the TR or ER on RJ-45/110 type patch panels.

B.

The copper data horizontal cabling will be terminated at the TR or ER on patch panels as described herein. Where patch panels are mounted in equipment frames, equally distribute cables on each side, down the vertical wire management, and into the horizontal wire management so as not to exceed wire management fill.

C.

Horizontal cabling shall be terminated such that wire pair twists are maintained as closely as possible to the point of mechanical termination. (No greater than 0.5” for Category 6 cables.)

D.

Maximum strip length shall be 1.0” or less. Maintain cable sheath to leading edge of connector block.

E.

Contractor is responsible to obtain and follow installation instructions for manufacturer products for correct termination and wire management of cables on respective products.

F.

CNM ITS to provide future cross-connect terminations to Campus switch.

G.

Horizontal cables shall be terminated in the telecom room serving that floor unless otherwise noted. Exceptions would include telecom rooms serving multiple floors.

3.4 RELOCATION AND REMOVAL OF EXISTING TELECOM OUTLETS (TO)

A.

Where the relocation of existing TO’s is required and the new location will allow the existing cables to reach, the cables may be disconnected and removed back to the hallway or raceway system for installation into the new TO. Where existing cables will not reach, new cables shall be installed to the TR. The new TO location shall be relabeled. This installation requires a retest of the voice and data cables.

B.

Where the removal of existing TO’s is required, the contractor shall remove the TO raceway, conduits, and cables back to the exterior of the TR. Contractor shall notify CNM ITS

Representative at the time of removal. CNM ITS will remove all items within the TRs.

Removal of existing TO’s requires as-built information from the contractor. Contractors are to supply a copy of the construction floor plan indicating where the TO was removed and the labeling information on the TO.

C.

Wherever a TO is removed, a blank faceplate is to be installed to match the other outlets in the room. Provide a pull string in the vacant conduit for future pulls.

3.5 WIRING CONFIGURATION

A.

Wire all jacks according to ANSI/TIA/EIA T568-B configuration.

COMMUNICATIONS COPPER HORIZONTAL CABLING

Version 12DEC2007

271513 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

3.6 GENERAL CABLE INSTALLATION

A.

Cable lengths within boxes shall be adequate to permit installation and removal of device for inspection without damage to cable or connections (minimum of 12”).

B.

Cable bends shall not be greater than that recommended by the manufacturer of the cable.

C.

Care shall be taken so as not to damage cable during the installation process and that manufacturer’s pull tension specification is not exceeded.

D.

Route cables so that no horizontal cable exceeds 90 meters between TR termination and device jack termination. Contact CNM ITS Representative if this is not probable with TR location.

E.

Provide a minimum 8’-0” and maximum 10’-0” of slack. Loop at the TRs to be contained in the cable tray. Smaller slack loops may be required at ER cabinets.

F.

Within TRs, cables shall be snugly wrapped using Velcro reusable cable ties, a minimum of every 3’-0” for cable organization. Cable bundles should not exceed more than 25 cables in any run.

G.

Velcro cable ties and tie wraps shall not be used in cable trays and systems outside of the TR.

H.

Cable fill in station conduits, conduits, raceway, and cable tray shall not exceed 40% cable fill.

I.

New TRs must be free from dust, dirt, and other foreign materials from the ceiling to the floor before the installation of any termination hardware or the termination of copper or fiber optic cables. The door to the telecommunication rooms must be installed and closed during termination.

J.

Contractor is responsible for the protection of all telecommunications equipment in existing

Telecommunications Rooms (TR). Contractor shall contact the CNM ITS before starting any work in an existing TR that might cause dust and debris from harming network equipment.

3.7 CABLE TESTING

A.

Verification testing up to 20% of the installed plant may be performed by CNM personnel of all horizontal voice and data cable tests will be performed. Contractor shall notify the CNM

ITS before the start of testing. Contractor may request CNM personnel to accompany them in the testing of cables to ensure proper information entry into the Tester. If CNM personnel accompany the Contractor on testing, verification shall not be performed.

A.

The horizontal cabling consisting of single 4-pair cable runs shall be tested for Category 6 compliance utilizinga Fluke DTX series tester, or other approved tester, with specific test cords needed for the specific type of jacks used. Contact CNM ITSs Representative for proper test cord part numbers. Test unit shall be set up using: 1) Cat. 6 permanent link test, 2) actual cable # installed (e.g. CommScope #5EN5). Contractor shall provide downloaded files via CD/DVD and hard copy printout of cable certification reports for each jack. Fluke

Linkware software shall be set up to print certification reports in plain text format. Cable certification and summary reports shall be produced by downloading collected data information from the Fluke tester to a PC utilizing Fluke Linkware software. Testing required is 100%. Contractor shall provide the “.flw” files on CD/DVD. The file shall contain only the

COMMUNICATIONS COPPER HORIZONTAL CABLING

Version 12DEC2007

271513 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

“.flw” files for all tested locations. The disk shall contain individual files for each TR separated into data tests and tests. e.g. File name FS1106voice.flw contains all tests fed from

TR 1106. File name FS2106voice.flw contains all tests fed from TR 2106. CNM ITS will perform random verification testing as part of acceptance of all copper voice cable testing.

3.8 EQUIPMENT INSTALLATION AND CABLE TERMINATIONS

A.

All equipment shall be installed in a neat and professional manner, arranged for convenient operation, testing and future maintenance.

B.

All paired cables shall be installed and terminated by technicians experienced in the termination of cables on connector blocks.

C.

The Contractor shall employ certified system installation technicians and have at least 5 years experience in the installation of similar and equivalent systems.

D.

The Contractor shall supply verification of experience, for this type of work, to the Architect for approval before performing any work.

3.9 AS-BUILT INFORMATION

A.

Contractor shall provide as-built information to CNM ITS to accompany all test result information.

B.

As-built information shall be in electronic format in AutoCAD version 2000. Indicate location of all Outlets, and riser conduit routes, distribution cable trays, junction boxes, and all additions and deletions pertaining to telecommunications. Include correct Outlet labeling next to all telecom symbols.

C.

If construction drawings are not utilized, Contractor shall provide all telecommunications location information on an accurate scaled floor plan.

3.10 SYSTEM WARRANTY REQUIREMENTS

A.

Contractor shall perform all labeling requirements and provide testing documentation for verification as described herein.

B.

Contractor shall submit cable records to reflect all moves, adds, and changes.

C.

Contractor shall provide floor plans showing locations of all telecommunication outlets and spaces. See Item 3.9.

D.

Contractor shall perform these requirements for Category 6 permanent link configurations and submit to the hardware manufacturer such paperwork and test results as necessary to obtain the 25-year system performance guarantee to CNM ITS as defined by the cable and hardware manufacturers. The original 25-year system warranty shall be provided to CNM ITS prior to final payment for this work.

COMMUNICATIONS COPPER HORIZONTAL CABLING

Version 12DEC2007

271513 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

END OF SECTION 271513

COMMUNICATIONS COPPER HORIZONTAL CABLING

Version 12DEC2007

271513 - 6

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271523 – COMMUNICATIONS OPTICAL FIBER HORIZONTAL

CABLING

PART 1: GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of horizontal optical fiber infrastructure as described on the Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270543 Underground Ducts and Raceways for Communication Systems.

C.

Division 27, Section 270553 Identification for Communication Systems.

D.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

E.

Division 27, Section 271313 Communications Copper Backbone Cabling.

F.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

G.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

H.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

I.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

J.

Division 27, Section 271543 Communications Faceplates and Connectors.

PART 2 - PRODUCTS

2.1 FIBER CABLING

A.

Single-mode Fiber Optic Outlet Cable - Provide horizontal fiber optic cable from outlet through conduits to cable tray then through cable tray to TR or ER.

1.

Each single-mode fiber optic cable shall be a MIC type tight buffered fiber. Typical fiber outlets consist of a two-strand fan out type. Number of strands may vary depending on project.

B.

Multimode Fiber Optic Outlet Cable - Provide horizontal fiber optic cable from outlet through conduits to cable tray then through cable tray to TR or ER.

1.

Each multimode fiber optic cable shall be a MIC type tight buffered fiber. Typical fiber outlets consist of a two-strand fan out type fiber. Number of strands may vary depending on project.

2.2

MANUFACTURER

COMMUNICATIONS OPTICAL FIBER HORIZONTAL CABLING

Version 12DEC2007

271523 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

Approved Manufacturers:

1.

CommScope

2.

General

3.

OCC

4.

Other approved equal submitted in advance as required in SOW

PART 3 - EXECUTION

3.1 TELECOMMUNICATIONS INSTALLATION

A.

General:

1.

This Section describes the installation locations for the products and materials, as well as methods and CNM ITS CISM Standards associated with the Telecommunications

Installation portions of the Project. These Specifications, along with the drawings and other CNM ITS supplied specifications shall be followed during the course of the installation.

2.

The Contractor is instructed to coordinate his efforts with the other tradesmen who may be working within the same vicinity to avoid conflict and lost time.

3.

The Contractor is required to supply all necessary tools, equipment, accessories, safety equipment, protective clothing, etc., as customary for the craft and necessary for the installation.

4.

The Contractor shall verify space requirements and locations with CNM ITS before starting cable installations and terminations.

5.

The Contractor shall verify the cable type and jacket rating required with CNM ITS before starting fiber installation.

6.

The Contractor shall verify existing cable fill in conduit, raceway or cable tray system before installation of additional cables so as not to exceed 40% cable fill. Contractor will be responsible for installation of additional conduit, raceway or cable tray where additional cables to be added will exceed the 40% cable fill. See cable fill attachment, 3.1

Attachment #1.

3.2 EMPTY STATION CONDUITS

A.

Provide a nylon pull cord in each empty conduit to facilitate future installation of cables.

B.

Provide a nylon pull cord in each empty conduit and extended in raceway to openings for faceplates to facilitate future installation of cables.

3.03 HORIZONTAL FIBER CABLING

A.

The horizontal fiber cabling will be terminated at the TR or ER in a rack mountable enclosure.

B.

Contractor is responsible to obtain and follow manufacturer installation instructions for correct termination and fiber management of cables on respective products.

C.

CNM ITS to provide future cross terminations to network equipment.

COMMUNICATIONS OPTICAL FIBER HORIZONTAL CABLING

Version 12DEC2007

271523 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

3.5 FIBER COLOR CODES

A.

Fiber Color Code -

Number Color

1 Blue

2 Orange

3 Green

4 Brown

5 Slate

6 White

7 Red

8 Black

9 Yellow

10 Violet

11 Rose

12 Aqua

3.6 GENERAL FIBER INSTALLATION

A.

Cable lengths within boxes shall be adequate to permit installation and removal of device for inspection without damage to cable or connections (minimum of 12”).

B.

Cable bends shall not be greater than that recommended by the manufacturer of the cable.

C.

Care shall be taken so as not to damage cable during the installation process and that manufacturer’s pull tension specification is not exceeded.

D.

Route cables so that no horizontal cable exceeds 90 meters between TR termination and device jack termination. Contact CNM ITS if this is not probable with TR location.

E.

Provide a minimum 8’-0” and maximum 10’-0” of slack. Loop at the TRs to be contained within the fiber enclosure.

F.

Within TRs, cables shall be snugly wrapped using Velcro reusable cable ties, a minimum of every 3’-0” for cable organization. Velcro ties shall be tightened so as not to deform cable jackets and thus affect cable performance.

G.

Cable fill in station conduits, raceway, and cable tray shall not exceed 40% cable fill.

H.

New TRs must be free from dust, dirt, and other foreign materials before the installation of any termination hardware or the termination of copper or fiber optic cables. The door to the telecommunication rooms must be installed and closed during termination.

3.7 CABLE TESTING

COMMUNICATIONS OPTICAL FIBER HORIZONTAL CABLING

Version 12DEC2007

271523 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

A 100% verification by CNM ITS of all horizontal fiber cable tests will be performed.

Contractor shall notify the CNM ITS before the start of testing. Contractor may request CNM

ITS to accompany them in the testing of cables to ensure proper information entry into the

Omniscanner. If CNM personnel accompany the Contractor on testing, verification shall not be performed.

B.

The fiber optic cables shall be tested utilizing a power meter and stabilized light source capable of testing at 850 nm and 1300 nm for multimode and 1310nm and 1550nm for singlemode. Contractor shall complete a fiber optic post installation report at the time of testing containing meter readings at both 850 nm and 1300 nm for multimode and 1310nm and

1550nm for single-mode in one direction (TR to outlet) on each fiber, actual loss and other pertinent data regarding the cables tested, including model and serial number of test equipment, cable part #, installed fiber length, building span loss at 850 nm and 1300 nm for multimode and 1310nm and 1550nm for single-mode and date tested. The fiber optic post installation report shall be in a form substantially similar to 3.7 Attachment 1. Testing required is 100%. Place in a 3-ring binder, preceded by a tabbed divider and label as

“Horizontal Fiber”. Span loss calculations are required on the final test sheet for loss at 850 nm and 1300 nm for multimode and 1310nm and 1550nm for singlemode.

(D x L) + (C x # connectors)

D = Length; L = Loss; C = Connector loss (Max 0.75 dB)

1 ft. = .0003048 km.

CNM ITS will perform random verification testing as part of acceptance of all fiber optic cable testing.

3.8 EQUIPMENT INSTALLATION AND CABLE TERMINATIONS

A.

All equipment shall be installed in a neat and professional manner, arranged for convenient operation, testing and future maintenance.

B.

All fiber cables shall be installed and terminated by technicians experienced in the installation and termination of fiber cables.

C.

The Contractor shall employ certified system installation technicians and have at least 5 years experience in the installation of similar and equivalent systems.

D.

The Contractor shall supply verification of experience, for this type of work, to CNM for approval before performing any work.

3.9 AS-BUILT INFORMATION

A.

Contractor shall provide as-built information to CNM ITS to accompany all test result information.

COMMUNICATIONS OPTICAL FIBER HORIZONTAL CABLING

Version 12DEC2007

271523 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

B.

As-built information shall be in electronic format in AutoCAD Version 2000. Indicate location of all Outlets, distribution cable trays, junction boxes, and all additions and deletions pertaining to telecommunications. Include correct Outlet labeling next to all telecom symbols.

3.10 SYSTEM WARRANTY REQUIREMENTS

A.

Contractor shall perform all labeling requirements and provide testing documentation for verification as described herein.

B.

Contractor shall submit cable records to reflect all moves, adds, and changes.

C.

Contractor shall provide floor plans showing locations of all telecommunication outlets and spaces. See Item 3.9.

END OF SECTION 271523

COMMUNICATIONS OPTICAL FIBER HORIZONTAL CABLING

Version 12DEC2007

271523 - 5

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271533 – COMMUNICATIONS COAXIAL HORIZONTAL

CABLING

PART 1: GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of horizontal coax infrastructure as described on the Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270543 Underground Ducts and Raceways for Communication Systems.

C.

Division 27, Section 270553 Identification for Communication Systems.

D.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

E.

Division 27, Section 271313 Communications Copper Backbone Cabling.

F.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

G.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

H.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

I.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

J.

Division 27, Section 271543 Communications Faceplates and Connectors.

PART 2 - PRODUCTS

2.1 COAX CABLING

A.

Horizontal Cables (CATV) - Provide CATV cables from designated outlets in rooms through conduits to hallway to TR or ER.

1.

Each CATV cable shall be Type RG-6, 18 gauge, solid copper center conductor, quadshield,.

2.

Where plenum CATV cable is required use cable with overall natural Flamarrest jacket,

CMP rated.

B.

Approved Manufacturers:

1.

Commscope

2.

Belden

3.

General

4.

Other approved equal submitted in advance as required in SOW

COMMUNICATIONS COAXIAL HORIZONTAL CABLING

Version 12DEC2007

271533 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

PART 3 - EXECUTION

3.1 TELECOMMUNICATIONS INSTALLATION

A.

General:

1.

This Section describes the installation locations for the products and materials, as well as methods and CNM ITS’s Standards associated with the Telecommunications Installation portions of the Project. These Specifications, along with the drawings and other CNM ITS supplied specifications shall be followed during the course of the installation.

2.

The Contractor is instructed to coordinate his efforts with the other tradesmen who may be working within the same vicinity to avoid conflict and lost time.

3.

The Contractor is required to supply all necessary tools, equipment, accessories, safety equipment, protective clothing, etc., as customary for the craft and necessary for the installation.

4.

The Contractor shall verify space requirements and locations with CNM ITS before starting cable installations and terminations.

5.

The Contractor shall verify the cable type and jacket rating required with CNM ITS before starting coax installation.

6.

The Contractor shall verify existing cable fill in conduit, raceway or cable tray system before installation of additional cables so as not to exceed 40% cable fill. Contractor will be responsible for installation of additional conduit, raceway or cable tray where additional cables to be added will exceed the 40% cable fill. See cable fill attachment, 3.1

Attachment #1.

3.2 EMPTY STATION CONDUITS

A.

Provide a nylon pull cord in each empty conduit to facilitate future installation of cables.

B.

Provide a nylon pull cord in each empty conduit and extended in raceway to openings for faceplates to facilitate future installation of cables.

3.3 HORIZONTAL COAX CABLING

A.

The horizontal coax cabling will be terminated at the TR or ER on a wall designated by CNM

ITS.

B.

Contractor is responsible to obtain and follow manufacturer installation instructions for correct termination and coax management of cables on respective products.

C.

CNM ITS to provide future taps, splitters, and amplifiers.

3.4 GENERAL COAX INSTALLATION

A.

Cable lengths within boxes shall be adequate to permit installation and removal of device for inspection without damage to cable or connections (minimum of 6”).

B.

Cable bends shall not be greater than that recommended by the manufacturer of the cable.

COMMUNICATIONS COAXIAL HORIZONTAL CABLING

Version 12DEC2007

271533 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

C.

Care shall be taken so as not to damage cable during the installation process and that manufacturer’s pull tension specification is not exceeded.

D.

Route cables so that no horizontal cable exceeds 90 meters between TR termination and device jack termination. Contact CNM ITS if this is not probable with TR location.

E.

Provide a minimum 8’-0” and maximum 10’-0” of slack. Loop at the TRs to be contained in the cable tray.

F.

Within TRs, cables shall be snugly wrapped using Velcro reusable cable ties, a minimum of every 3’-0” for cable organization. Wire ties shall be tightened so as not to deform cable jackets and thus affect cable performance.

G.

Cable fill in station conduits, conduits, raceway, and cable tray shall not exceed 40% cable fill.

H.

New TRs must be free from dust, dirt, and other foreign materials before the installation of any termination hardware or the termination of copper or fiber optic cables. The door to the telecommunication rooms must be installed and closed during termination.

3.5 CABLE TESTING

A.

The CATV horizontal station cabling consisting of RG-6 shall be tested for length utilizing a

Fluke OmniscannerII, Fluke 4000 series tester, or Fluke DTX scanner. Test unit shall be set up using RG-6 cable selected. All tests shall be conducted at the opposite end from the

ER\TR. Contractor shall provide cable summary report for each CATV outlet similar to 3.5

Attachment 1. Testing required is 100%. Contractor shall provide the information files via email or printout. CNM ITS will perform random verification testing as part of acceptance of all CATV cable testing. Summary report shall have additional information on the sheet to indicate building and TR or ER.

.

3.6 EQUIPMENT INSTALLATION AND CABLE TERMINATIONS

A.

All equipment shall be installed in a neat and professional manner, arranged for convenient operation, testing and future maintenance.

B.

All coax cables shall be installed and terminated by technicians experienced in the installation and termination of coax cables.

C.

The Contractor shall employ certified system installation technicians and have at least 5 years experience in the installation of similar and equivalent systems.

D.

The Contractor shall supply verification of experience, for this type of work, to the Architect for approval before performing any work.

3.7 AS-BUILT INFORMATION

A.

Contractor shall provide as-built information to CNM ITS to accompany all test result information.

B.

As-built information shall be in electronic format in AutoCAD version 2000. Indicate location of all Outlets, riser conduit routes, distribution cable trays, junction boxes, and all

COMMUNICATIONS COAXIAL HORIZONTAL CABLING

Version 12DEC2007

271533 - 3

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM) additions and deletions pertaining to telecommunications. Include correct Outlet labeling next to all telecom symbols.

C.

If construction drawings are not utilized, Contractor shall provide all telecommunications location information on an accurate scaled floor plan.

3.8 SYSTEM WARRANTY REQUIREMENTS

A.

Contractor shall perform all labeling requirements and provide testing documentation for verification as described herein.

B.

Contractor shall submit cable records to reflect all moves, adds, and changes.

C.

Contractor shall provide floor plans showing locations of all telecommunication outlets and spaces. See Item 3.7.

END OF SECTION 271533

COMMUNICATIONS COAXIAL HORIZONTAL CABLING

Version 12DEC2007

271533 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

SECTION 271543 – FACEPLATES AND CONNECTORS

PART 1 - GENERAL

1.1 SCOPE OF WORK

A.

Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of faceplates and connectors as described on the Drawings and/or required by these specifications.

1.2 RELATED SECTIONS

A.

Division 27, Section 270528 Pathways for Communication Systems.

B.

Division 27, Section 270553 Identification for Communication Systems.

C.

Division 27, Section 271119 Communications Termination Blocks and Patch Panels.

D.

Division 27, Section 271313 Communications Copper Backbone Cabling.

E.

Division 27, Section 271323 Communications Optical Fiber Backbone Cabling.

F.

Division 27, Section 271333 Communications Coaxial Backbone Cabling.

G.

Division 27, Section 271513 Communications Copper Horizontal Cabling.

H.

Division 27, Section 271523 Communications Optical Fiber Horizontal Cabling.

I.

Division 27, Section 271533 Communications Coaxial Horizontal Cabling.

1.3 MANUFACTURERS

A.

Approved Manufacturers:

1.

Leviton

2.

Commscope Hubbell

3.

General

4.

Other approved equal submitted in advance as required in SOW

PART 2 - PRODUCTS

2.1 CONDUIT AND OUTLET BOXES

A.

See Section 270528 – Pathways for Communication Systems

2.2 TELECOMMUNICATIONS INSTALLATION

A.

General: The materials and products specified herein reflect the minimum acceptable standards of fabrication and manufacture. All materials and products supplied by the

COMMUNICATIONS FACEPLATES AND CONNECTORS

Version 12DEC2007

271543 - 1

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

Contractor and specified herein are to be new, unused, of first quality and in original packaging or shipping containers or as shown on drawings and described in Item 3.1.

B.

New buildings and major renovations will be treated differently than existing buildings.

Existing buildings will utilize Category 6 cabling and termination hardware for voice and data. New building construction and CNM ITS approved large-scale renovations will utilize

Category 6 cabling and termination hardware for all new cabling and termination hardware for data. Contact CNM ITS for approval of cabling systems before installation.

C.

Standard TO Outlet Configuration (New Construction or Renovation):

1.

Each installed TO shall consist of (3) Blue, Category 6, T568B wiring standard, 8 conductor jacks.

2.

Cover plate for the bottom or right outlet location shall be (1), Ivory, 2-gang, double opening wall plate with (4) blank modules in the openings.

3.

Cover plate for the top or left outlet location shall be (1), Ivory, 2-gang, double opening wall plate with (2) Flat, Ivory snap-in modules located in the top of the openings, (1) Flat,

Ivory snap-in modules located in the bottom left of the openings and (1) blank modules in the bottom of the openings.

D.

Wall Phone Outlet Device:

1.

Telephone device shall consist of (1) Stainless Steel wall plate, Category 6, T568B wiring standard, 8 conductor jack. Two cables will be run to this location but only one will be terminated in the box.

2.

Wall phone outlets shall utilize an Allen-Tel #AT630B-8, stainless steel phone plate.

E.

Data Only Outlet Device:

1.

Data device shall consist of: a.

(2) Category 6, T568B wiring standard, 8 conductor jacks, where Category 6 is required.

2.

Cover plate shall be (1) Ivory, single gang, single opening wall plate with (2) Blue snap-in modules in top opening, and (1) Ivory, blank fittings in bottom opening. See 2.2

Attachment #2 for jack configuration.

3.

When installing the faceplate horizontally, install the modules and jack as if it were mounted vertically.

F.

Fiber Only Outlet Device:

1.

Multimode fiber device shall consist of (1) Ivory, SC multimode fiber optic adapter module.

2.

Single-mode fiber device shall consist of (1) Ivory, SC single-mode fiber optic adapter module.

3.

Cover plate shall be (1) Ivory, single gang, single opening wall plate with (1) Ivory, sloped snap-in module in bottom opening, and (1) Ivory, blank fittings in top opening.

G.

Fiber Terminations

COMMUNICATIONS FACEPLATES AND CONNECTORS

Version 12DEC2007

271543 - 2

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

1.

Each multimode fiber shall be terminated with SC fiber optic connector.

2.

Each single-mode fiber shall be terminated with SC fiber optic connector.

H.

Existing Outlet Locations:

1.

Where new jacks are being installed in existing outlet locations, utilize Blue keystone jacks for voice and Category 6 data installations.

2.

Large renovations where Category 6 data is installed shall utilize new faceplates with new jacks.

I.

Outlet Locations in Divided Raceways

1.

Where jacks are being installed in a divided 4000 Wiremold raceway for telecommunications and power, utilize Wiremold #V4007C-1 one-gang device plates for the mounting of the Ivory, single gang, single opening wall plate. Electrical devices shall utilize a separate Wiremold #V4048B duplex receptacle device.

J.

CATV Terminations

1.

Type 6 (RG-6) Cable Installations a.

Terminate all RG-6 cable with LRC Part # F56-CHI. b.

Crimp connector using only .324 HEX type crimp tool.

2.

Type 11 (RG-11) Cable Installations a.

Terminate all RG-11 non-plenum cable with LRC Part # F11-QS. b.

Terminate all RG-11 plenum cable with LRC Part # PL11QS.

3.

CATV outlet within a Outlet shall utilize (1) F-type module.

PART 3 - EXECUTION TELECOMMUNICATIONS INSTALLATION

3.1 General:

A.

This Section describes the installation locations for the products and materials, as well as methods and Owner’s Standards associated with the Telecommunications Installation portions of the Project. These Specifications, along with the drawings and other Owner supplied specifications shall be followed during the course of the installation.

B.

The Contractor is instructed to coordinate his efforts with the other tradesmen who may be working within the same vicinity to avoid conflict and lost time.

C.

The Contractor is required to supply all necessary tools, equipment, accessories, safety equipment, protective clothing, etc., as customary for the craft and necessary for the installation.

D.

The Contractor shall verify space requirements and locations with CNM ITS before starting cable installations and terminations.

3.2 FACEPLATE INSTALLATION

COMMUNICATIONS FACEPLATES AND CONNECTORS

Version 12DEC2007

271543 - 3

1.

2.

3.

4.

5.

6.

7.

8.

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

The faceplate housing the UTP connector modules shall provide a symmetrically centered appearance for the modules.

The faceplate housing the UTP connector modules shall have no visible mounting screws.

It shall be possible to inspect and/or re-terminate the UTP cable at the outlet through front access at the faceplate.

The faceplate housing the UTP connector modules shall have aperture plugs to cover any unused openings in the faceplate.

The faceplate housing the UTP connector modules shall have an angle entry plate with recessed inserts for maximum protection of outgoing modular cords.

It shall be possible to install the UTP connector modules in wall-mounted single- and dual-gang electrical boxes, utility poles and modular furniture

(cubicle) access points using manufacturer-supplied faceplates and/or adapters.

The faceplate housing the UTP connector modules shall be available in the following finishes or colors: stainless steel, gray, almond, white, and black.

The faceplate housing the UTP connector modules shall have the option of being mounted on adapter boxes for surface mount installation.

9.

The faceplate housing the UTP connector modules shall have a labeling capability using built-in labeling windows, to facilitate outlet identification and ease network management.

10.

The faceplate housing the UTP connector modules shall accommodate up to a maximum of six modules in a single-gang form and up to a maximum of twelve modules in a dual-gang form.

11.

The faceplate housing the UTP connector modules shall provide flexibility in configuring multimedia workstation outlets that respond to present of future network needs such as audio, video, coaxial and optical fiber applications.

A.

Approved Manufacturers:

1.

Commscope

2.

Leviton

3.

Hubbell

4.

Other approved equal submitted in advance as required in SOW

3.3 EQUIPMENT INSTALLATION AND CABLE TERMINATIONS

COMMUNICATIONS FACEPLATES AND CONNECTORS

Version 12DEC2007

271543 - 4

CENTRAL NEW MEXICO COMMUNITY COLLEGE

COMMUNICATIONS INFRASTRUCTURE STANDARDS MANUAL (CISM)

A.

All equipment shall be installed in a neat and workmanlike manner, arranged for convenient operation, testing and future maintenance.

B.

All telecommunications cables, faceplates, and connectors shall be installed and terminated by technicians experienced in the installation and termination of telecommunications items listed herein.

C.

The Contractor shall employ certified system installation technicians and have at least 5 years experience in the installation of similar and equivalent systems.

D.

The Contractor shall supply verification of experience, for this type of work, to the Architect for approval before performing any work.

3.4 AS-BUILT INFORMATION

A.

Contractor shall provide as-built information to Owner to accompany all test result information.

B.

As-built information shall be in electronic format in AutoCAD version 2000. Indicate location of all Outlets, station and riser conduit routes, distribution cable trays, junction boxes, and all additions and deletions pertaining to telecommunications. Include correct

Outlet labeling next to all telecom symbols.

C.

If construction drawings are not utilized, Contractor shall provide all telecommunications location information on an accurate scaled floor plan.

3.5 SYSTEM WARRANTY REQUIREMENTS

A.

Contractor shall perform all labeling requirements and provide testing documentation for verification as described herein.

B.

Contractor shall submit cable records to reflect all moves, adds, and changes.

C.

Manufacturer shall provide a system performance warranty for the installed system.

END OF SECTION 271543

COMMUNICATIONS FACEPLATES AND CONNECTORS

Version 12DEC2007

271543 - 5

Central New Mexico

Community College

Central New Mexico

Community College

Central New Mexico

Community College

6" MIN

BOTH ENDS

24" MIN

LL WA

LL WA

Central New Mexico

Community College

Central New Mexico

Community College

Central New Mexico

Community College

Central New Mexico

Community College

(1) (1)

Central New Mexico

Community College

Central New Mexico

Community College

Central New Mexico

Community College

7

'-

0"

7

4" 3'-2"

5"

12"

4'-0"

2'-1" 6"

4'-0"

3'-6"

4'-0"

Central New Mexico

Community College

Central New Mexico

Community College

Download