BUILD RIGHT Tucking up downlights Manufacturers, suppliers, designers, electricians and insulation installers should all know how to maintain the thermal envelope around downlights. Do you? By Stephen Sargent, BRANZ Technical Writer I nsulation is often installed with a clearance distance around recessed downlights. The effect of heat loss from warm air rising into concealed ceiling spaces is often seen as far less important than possibly causing a deadly fire from insulation abutting a light fitting. If you want to improve your thermal efficiency by not having a gap between the insulation and fitting, BRANZ recommends using a CA or RA fitting. provided by manufacturers and designers ❚ if specified, fittings are sometimes substituted for a similar looking fitting during the supply/installation process. Electricians must ensure compliance What the requirements say This thinking goes against the requirements of the New Zealand Electrical Code of Practice (NZECP) 54: 2001 which states under 2.6 Thermal Insulation: ‘Recessed luminaires and any auxiliary equipment shall be constructed and installed so as not to compromise the thermal efficiency of buildings’. It also isn’t supported in that, historically, insulation products used in New Zealand have not typically supported combustion. The problem is further compounded because: ❚ there is a lack of detail about lighting available on the market and not all light fittings have been tested to NZECP 54 ❚ lights are often selected by the owners and sometimes specified relatively late in the construction process An electrician is bound under the requirements of their registration and selfcertification authorisation to ensure that NZECP 54 is complied with. For details refer to the Energy Safety Service website www. ess.govt.nz under ‘Rules and reports’, ‘Acts and regulations’, ‘Electricity Regulations 1997 bottom chord of ceiling trusses of rafter ❚ insulation is usually installed at a different time (by a different person) to the light fittings ❚ the relationship between the New Zealand Building Code (NZBC) Clause E9 Electricity and NZECP 54: 2001 is clearly defined, but misunderstood ceiling insulation (segment type) plasterboard ❚ light fitting types have historically not been required to be specified at the time of building consent approval by the Territorial Authority ❚ a wide variety of specialist and/or budget generic NZECP 54 Closed Abutted (CA) type recessed ceiling downlight, complete with integral transformer, allows insulation to be fitted tightly to light cover lights (both bulbs and fittings) are now Figure 1: Optimum layout to ensure NZBC Clause H1 compliance. 24 BUILD October/November 2006 ceiling battens and amendments’, and then specifically to ‘Regulations 69 Electrical safety and 69A Electrical installations’. Specify at consent stage Downlights should be specified at the time of building consent. The NZEPC 54 fitting rating needs to be indicated to ensure that the NZBC Clause H1 Energy efficiency is not compromised when downlights are installed in a ceiling. NZECP 54 gives guidance on ‘the selection of recessed luminaires and their installation requirements to ensure that the integrity of the building is maintained. This integrity includes building elements, thermal, acoustic, fire and moisture’. If you see a gap between the insulation and the fitting, and want to improve your thermal efficiency, BRANZ recommends using the correct fitting type. To allow close-butted insulation, the light fitting must be rated as either category Closed and Abutted (CA) or Restricted and Abutted (RA) – refer to the manufacturer’s installation instruction sheet. Typically use only CA fittings above moist areas like kitchens, laundries and bathrooms. Some DIY allowed The Acceptable Solution G9/AS1 allows members of the public to carry out some of their own electrical work. The Electricity Act, Regulations and relevant Codes of Practice are available on the Energy Safety building element above fitting (floor, roof) transformer T H S I insulation ceiling lining H = height clearance (HCB) to building element Halogen fitting - 200 mm min. Incandescent fitting - 50 mm min. or to manufacturer’s specification I = Thermal insulation clearance: Halogen fitting - 200 mm min. Incandescent fitting - 50 mm min. or to manufacturer’s specification (abutted, standard or specified) T = Recommended transformer clear from luminaire, to manufacturers’ instructions S = Side clearance (SCB) to building element: Halogen fitting - 200 mm min. Incandescent fitting - 50 mm min. or to manufacturer’s specification Clearance specified in NZECP 54 for untested light fittings in confined spaces. Insulation would be compromised in this installation. Figure 2: The clearances specified in NZECP 54 for untested light fittings in confined spaces. Insulation may be compromised in this installation. Service’s website www.ess.govt.nz. A good first reference for those considering altering wiring, A guide to doing your own electrical work safely and legally, is available on the website under ‘Safety information’ then ‘Electrical safety’. But remember, don’t remove the cover or do any wiring work behind the meter board. Electrical Workers Licensing Group The Electrical Workers Licensing Group was transferred to the Department of Building and Housing (DBH) on 1 September 2006. The Group provides registration and complaints assessment services to the Electrical Workers Registration Board, and was previously part of the Ministry of Economic Development. It is responsible for certifying the ongoing competency of the country’s 38,000 electrical and electronic workers. Nothing will change in the way electrical and electronic workers are registered. The same staff will be doing the job and the Group’s contact details will remain unchanged. The transfer is part of a suite of Government reforms to provide improved and integrated services to the building sector and the public, and to bring occupational licensing in the sector under one ‘roof’. Other occupations overseen by the DBH include chartered engineers, associate engineers and architects, as well as the establishment of 13 licensed building practitioner classes. The Plumbers, Gasfitters and Drainlayers Registration Board will transfer to the DBH in 2008. BUILD October/November 2006 25