Electrical distribution systems
CAS 36
Ring Main Unit
2011 Catalogue
Table of Contents
2
Overview
General description
Scope of application
36 kV distribution market leaders
Top-level after sales service
Environment and certification
Quality
Switchboard range
Content of the standard unit
Main characteristics
Description
3
4
5
6
7
8
9
10
11
12
Functional units
Components
Accessories
Locking systems
Connections
13
15
18
19
Installation
Civil engineering
20
Decision diagram
CAS 36 range. Standard unit and options
22
PD0201
PE0202
Overview
General description
2I + 1Q
Schneider Electric CAS 36 type switchboards are devices with built-in SF6 breaking
and insulation, of compact architecture and small size.
All the switchgear and the busbar are housed in a single sealed stainless steel wraparound tank, filled with SF6 and sealed for life. Each CAS 36 switchboard includes
several line and/or protection functions in a single steel case filled with SF6.
Benefits of a tried and tested design:
bb CAS 36 switchboard:
vv Maximum safety for the operator:
-- Internal arc test in accordance with the IEC 62271-200 standard
-- Three-position switch for safe switching operations
-- Ensures effective circuit breaking in accordance with the IEC 62271-102 standard
-- There is no possibility of accessing live parts
bb Insensitive to environmental conditions:
vv Stainless steel tank sealed for life
vv Completely enclosed fuse compartment
vv Switchboard withstands temporary flooding
bb Manufactured in accordance with best standards and quality approaches:
vv Certified by various electricity utilities of several countries
vv Design and production are ISO 9001 certified
vv Applying best international quality practices
vv Benefits of more than 60 years' accumulated experience in the manufacture of
medium-voltage switchboards
bb Environmentally friendly:
vv Manufacturing accredited in accordance with the ISO 14001 standard
bb Plug & Play installation
vv Its compact design reduces work in the field to a minimum
vv Levelling and coupling of different switchboards are avoided
vv Easy mounting with four anchoring points
vv Ease of connector installation
vv Fast commissioning.
Fonctions
DE0203
They can be line input/output (I) or transformer protection (Q) functions, all
incorporated in the same steel tank:
bb Line (I) functions of In = 400 or 630 A, with switch-disconnector, to switch line
inputs and outputs.
bb Protection (Q) functions of In = 200 A, with combined fuse switches, for
transformer protection.
Both the line functions and the protection functions in all cases incorporate earthing
switches with making capacity (up to 50 kA peak).
Human safety
The CAS 36 switchboard ensures human safety through:
bb Locking systems to prevent faulty operations
bb Locking systems to prevent access to cable and fuse compartments
bb AFL and AFLR internal arc option
bb Clearly defined mimic panel display
bb Effective breaking
bb Prevention of busbar access
bb Voltage presence indicating systems.
3
Scope of application
Overview
CAS 36 switchboards bring together in a single steel case all the medium voltage
functions that allow network switching, as well as the connection, power supply and
protection of distribution transformers.
Each CAS 36 type compact unit, with SF6 insulation (busbars) is the basic device for
MV switching and protection, within MV/LV transformer centres and MV distribution
centres, for applications requiring high availability and minimal maintenance. This is
confirmed by more than 12,000 units installed and in operation worldwide.
DD0202T
Substation
4
36 kV distribution
market leaders
Overview
World leaders... and growing
The experience built up during more than 60 years in the design and manufacture of
medium- and high-voltage switchgear and controlgear has been put to good use for
the design and manufacture of the CAS 36 switchboards.
Schneider Electric has supplied medium-voltage switchboards for more than 60,000
disconnection and protection functions both for electricity utility applications and for
wind power applications.
Our leading customers in the 36 kV distribution market include:
bb Electrical utilities: IBERDROLA, ENDESA (Spain),
bb EDP (Portugal), SENELEC (Senegal), STEG (Tunisia), EVN (Vietnam), EDCO
(Jordan), NEC (Sudan), Australia.
bb Wind power applications: GAMESA, VESTAS, ACCIONA, NORDEX, SUZLON,
GENERAL ELECTRIC, etc.
Benefits of the CAS 36 range
bb Maximum availability: continuity of service
bb Small size
bb Maximum safety for personnel
bb Insensitivity to the environment: SF6 insulation
bb Certification: IEC
bb Tried and tested quality: ISO 9001:2000
bb Environmental protection: ISO 14001:2004
bb Ease of installation
bb Economy.
PE0501
PE0507
PE60327
PE60326
The choice of CAS 36 switchboards guarantees installation security, endorsed
by the experience of the world leader in the wind-power sector..
UK
Turkey
Vietnam
PE0502
DE57036
Spain
PE0505
PE0504
PE0506
PE0503
Tunisia
Senegal
Australia
Sudan
Thailand
5
Overview
Top-level after sales service
PE0601
bb Assistance for your projects
bb Certified high-quality labour force
bb Assistance for installation and commissioning
bb Training
bb Equipment replacement.
Virtual instruction manual
To facilitate installation and mounting, we have created a virtual instruction manual
so that our customers may train their work teams.
Courses in factory or in the transformer centre
PE60312
PE0602
Get to know the CAS 36 from its design, manufacture, handling and installation
through to its maintenance where you want:
bb In the factory
bb In your offices
bb At the switchboard installation location.
6
Overview
Environment and certification
Environment
A strict system of materials management,
established on the whole production
process, ensures product traceability
and no polluting element emissions.
Emission-free
Schneider Electric is a company deeply committed to environmental protection.
As part of this commitment, the CAS 36 switchboards have been designed to be
environmentally friendly.
The tanks' sealing properties enable the CAS 36 switchboards to be classified as
"pressure-sealed systems" in accordance with the established definition in
recommendations.
All the materials used, both conductors and insulants, can be identified and
separated easily.
At end of life, the CAS 36 switchboards can be treated and recycled and their
materials can be recovered in accordance with the requirements of European
legislation on the end of life of electrical and electronic products.
PE57356
Quality
PE57354
The environmental management system put in place by Schneider Electric has been
certified in compliance with the requirements of the ISO 14001:2004 standard.
International regulations
Design: Certification in accordance with IEC regulations
CAS 36 switchboards have been designed and certified in compliance with the
following standards, some of which are in the process of being updated:
bb Operating conditions and general information IEC 62271-1, IEC 62271-200
bb Disconnectors and earthing switches IEC 62271-102.
Manufacture: Rigorous, systematic checks
The quality system for the production and design of CAS 36 switchboards has been
certified in compliance with the requirements of the ISO 9001:2000 standard.
PE57357
During the manufacturing process, in order to check quality, each CAS 36 switchboard
is subjected to systematic routine checks.
DE56817
The results of all these checks are recorded and form part of the test certificate
available for each switchboard.
Stainless steel
83.73%
Epoxy resin
4.39%
Wood
4.24%
Copper
3.40%
Iron
2.29%
SF6
1.58%
Aluminium
0.20%
Other
0.17%
7
Overview
Quality
PE0801
Altitude
bb Below 1000 m
bb Above 1000 m and up to 1700 m, please consult us.
IEC 62271-200 (AC metal-enclosed switchgear and controlgear for rated voltages
above 1 kV and up to and including 52 kV).
bb Switch classification: PM class (metallic partition).
bb Loss of service continuity: class LSC2B for switches and disconnectors.
bb Internal arc classification: AFL and AFLR class, up to 20 kA 1 s (optional on
request).
Switch-disconnector
IEC 60265-1 (High-voltage switches for rated voltages above 1 kV and less than 52 kV)
bb Class E3/M1
vv 100 opening/closing cycles under load and 0.7 p.f.
vv 1000 mechanical opening/closing cycles.
Other applications
bb Switches combined with fuses: IEC 62271-105: Alternating current switch-fuse
combinations.
bb Earthing switches: IEC 62271-102: Alternating current disconnectors and earthing
switches.
8
Switchboard range
Overview
36 kV utility type compact layouts
CAS 36 (2I+1Q)
CAS 36 (3I)
CAS 36 (4I)
CAS 36 (2I+2Q)
CAS 36 (3I+1Q)
DE60644
CAS 36 (1I+1Q)
36 kV extendable type compact layouts
CAS 36 (2I+1Q-EXT)
CAS 36 (1I+1Q-EXT)
CAS 36 (3I+2Q)
CAS 36 (1I-EXT)
CAS 36 (1Q+EXT)
36 kV wind power type standardized compact layouts
CAS 36 (0I+1I+1Q)
CAS 36 (0I+1Q)
CAS 36 (0I+2I+1Q)
CAS 36 (0IT+1Q)
CAS 36 (0IDB+1Q)
9
Overview
Content of the standard unit
PE55611
Cladding
The hardness of the galvanized steel makes the compartment a nondeformable corrosion-resistant component.
Tank
The SF6 in the tank is at a pressure of 0.3 bar. It is sealed for life after filling.
Routine checks are performed throughout the production process to ensure
closing, and this gives it a service life of 30 years. Therefore, the CAS 36
requires no maintenance on live parts. The tank contains all the live parts.
All the switchgear and controlgear is located inside, together with the busbars
of the switchboard and the fuse compartment. The efficiency levels of the CAS
36 are consistent with the definition of "pressurized and sealed for life" in
accordance with IEC recommendations.
Sealed compartment of a CAS 36 2I + 2Q switchboard
The strength and reliability of the CAS 36 design mean that the occurrence of
failures in the switching equipment is unlikely.
However, in order to ensure human safety, the CAS 36 is manufactured to
withstand an internal arc having the power of a 16 kA short circuit during 1
second or 20 kA during 1 second without putting the operator in danger.
DD0403
The overpressure caused by an internal arc is limited by the opening of a
safety valve in the lower part of the tank, without any consequence for the front
part of the tank.
After type tests carried out for 16 kA /1 s and 20 kA /1 s, the device is in
conformance with the six criteria defined in Appendix AA of the IEC 60295
standard (IEC 62271-200).
The air-blast circuit breaker uses a blast of SF6 gas toward
the region of contact union as breaking technique. This air blast
occurs only as a result of the very high-speed movement of the
switch inside the gas tank, without supplying additional SF6.
10
Main characteristics
DD0301
Overview
Electrical characteristics
CAS 36 kV
Height
(A)
Width
(B)
Depth
(C)
Rated voltage
36 kV
Test voltage of short duration (1 min.) at 50 Hz
70 kV rms
Rated lightning impulse withstand voltage (1.2/50 μs)
170 kV peak
Rated current of busbars
400 A / 630 A
Rated line output current (I)
400 A / 630 A
Rated protection output current (Q)
200 A (1)
Permissible current of short duration (1 s rms value)
16/20 kA rated
Breaking capacity of switch-disconnectors (I or Q)
400 A / 630 A
Rated making capacity in short circuit
40/50 kA peak
Mechanical endurance of switch-disconnectors
1000 switching operations
Temperature of working environment
-15 ºC / +40 ºC
Insulation medium
SF6
Nominal relative gas pressure
0.3 bar
General degree of protection
IP-3X (as per UNE-EN 60529)
Gas tank degree of protection
IP-67 (as per UNE-EN 60529)
General degree of protection against impacts
IK-08
Regulations
Standard
International
MV cubicles
IEC 60298 (62271-200)
Disconnectors
IEC 60129 (62271-102)
Switches
IEC 60265-1
Stipulations
IEC 60694 (62271-1)
Switch-fuse combination
IEC 60420 (62271-105)
Dimensions and weight
400/630 type cubicle
Height
A (mm)
Width
B (mm)
Depth
C (mm)
Weight
(kg)
CAS 36 2I+1Q
1705
1050
1050
500
CAS 36 2I+2Q
1705
1200
1050
600
CAS 36 3I
1850
1050
1025
450
CAS 36 3I+1Q
2100
1200
1050
600
CAS 36 4I
1850
1200
1025
500
CAS 36 3I+2Q
1705
1700
1050
850
CAS 36 0I+1T+1Q
1705
600
1050
400
CAS 36 0IT+1Q
1705
925
1050
400
CAS 36 0I+2I+1Q
1705
1600
1050
800
CAS 36 1I+1Q
1705
600
1050
400
CAS 36 0IDB+1Q
1705
600
1285
400
CAS 36 0I+1Q
1705
1100
1050
500
CAS 36 2I+1Q EXT
1705
1100
1050
400
CAS 36 1I+1Q EXT
1705
650
1050
400
CAS 36 1I EXT
1705
650
1050
400
CAS 36 1Q EXT
1705
650
1050
400
(1) The permissible protective device output current will always be limited by the rating of the
fuse installed on the cubicle.
11
Description
2I + 1Q
Compact architecture
PD0201
Overview
14
4
11
12
6
5
7
PE55633
13
9
1
4
12
11
6
2
5
3
8
7
10
1 Sealed stainless steel tank filled with SF6
2 Electrolytic copper bars
3 3-position air-blast circuit breakers
4 Fuse compartment
5 Controls compartment
6 Actuation panel and mimic panel
7 Line connectors compartment
8 Screw-on line connectors (I)
9 Plug-in protective connectors (Q)
10 Safety valve (internal arc)
11 SF6 pressure indicator
12 Voltage presence detector, VPIS
13 Low-voltage compartment (optional)
12
CAS 36 switchboards are small devices manufactured in quantities from 1 unit
up to 4 functional units.
This single-piece unit with integral insulation comprises:
bb All the switchgear and the busbar housed in a single sealed stainless steel
wrap-around tank, filled with SF6 and sealed for life.
bb From one to four line compartments with connection interfaces for both the
network and the transformer.
bb One or two fuse compartments.
The efficiency levels of the CAS 36 are consistent with the definition of "pressurized
and sealed for life" in accordance with IEC recommendations.
Switch-disconnector
The electric arc is turned off using the SF6 air blast technique.
The picture shows a cross section of the CAS 36 2I+Q in which several
compartments and functions can be seen:
bb Function (I) located in the lower part of the CAS 36. For functions for more
than 2 lines, the third and fourth (3I & 4I) will be located at the top.
bb Function (Q) located in the upper part of the CAS 36.
Each I or Q function is equipped with a moving contact and two fixed contacts,
one for closing the switch and the other for earthing.
Components
Controls compartment
Actuation panel
PE1302
Functional units
It is provided with a mimic diagram on which the various positions of the moving
equipment can be viewed.
Here are located the various grooves in which must be inserted the operating lever to
actuate the switches and earthing switches.
It also contains the push buttons which act on the mechanisms operating the
protective switches (Q).
Controls compartment
This is the location of the mechanisms which transmit the operations to the various
switches and earthing switches.
PE1402
Cable connection compartments
Line functions (I)
bb Switch function: closing and opening by means of a lever (or optional power
system independent of the operator's force).
bb Earthing switch function: closing and opening by lever.
Protection function (Q)
bb Switch function: closing by means of a lever independent of the operator's force.
During the closing operation, energy is accumulated for opening. Opening
independent of the operator's force by means of a push button, a tripping coil or fuse
blowing.
bb Earthing switch function: closing and opening by lever. This function cannot be
power-operated.
Cable connection compartments (line functions)
They are separate for each function (I) and receive the three cable glands to which
should be connected each of the 3 set screw connectors for each line.
Access to each of these compartments is locked with earthing of the corresponding
line switch-disconnector (I).
As an additional safety measure, each line of each function has voltage presence
detectors.
Standard equipment of the cable compartment
bb A front closing panel
bb Cable fastening clamps
bb Cable earth connection
bb Integral locking which prevents access to the connection compartment when the
earthing switch is open.
bb Integral locking which prevents access to the switch when the panel of the
connection compartment is open.
Options:
bb Back of compartment for single-pole or three-pole cable (compulsory for
non-directional field connections)
bb Internal arc in line function up to 20 kA / 1 s
bb IP-3X closing on cables
bb Base.
13
Functional units
Components
Fuse replacement operation
Fuse compartments
PE1501
Each compartment contains three separate fuse holders, single-pole and plug-in,
which facilitate fuse replacement in the event of fuse blowing. The separate fuse
holders are completely sealed and the fuse compartments are therefore floodable.
In the case of the CAS 36, this compartment is fully immersed in the SF6
compartment, also forming part of the tank in which the rest of the switchgear and
busbars are housed. Opening of the access door is locked by earthing of the
corresponding protective switch-disconnector (Q), which earths the two ends of each
of the three fuses.
CF fuses: Basic characteristics and selection table
The fuses to be installed shall be in compliance with the UNE-EN 60282-1
recommendation. It is recommended to use CF fuses provided with a Schneider
Electric thermal striker (in accordance with DIN regulations), due to the low losses
through heat dissipation.
The following table shows the type of Fusarc CF fuse to use for each mains voltage
and for the power of the transformer to be protected. In the event of overloads of ≥ 20%
and/or ambient temperatures ≥ 40°C, please consult us. For the use of fuses of
another type or from another manufacturer, please consult us.
PE60313
Fusarc CF fuse range
Choice of Fusarc CF fuses in CAS 36 for protection of
transformers
In accordance with the IEC 60076-5:2000 standard:
Ucc (S ≤ 630 kVA) = 4%
Ucc (S > 630 kVA and ≤ 1250 = 5%
Ucc (S > 1250 kVA) = 6%
Permissible overloads of ≤ 20% and ambient temperature of < 40ºC.
Un (kV)
6
6.6
10
11
13.2
13.8
15
20
22
25
30
33
S (kVA)
25
50
75
100
125
160
200
250
315
400
12/6.3
12/16
12/25
12/25
12/31.5
12/40
12/40
12/50
12/63
12/80 (2) 12/100 (1) –
500
630
800
1000
1250
–
–
–
12/6.3
12/16
12/20
12/25
12/31.5
12/31.5
12/40
12/50
12/50
12/80
12/6.3
12/10
12/16
12/20
12/25
12/25
12/31.5
12/40
12/40
12/50
12/100 (2) –
–
–
–
12/63
12/80
12/100 (1) –
12/4
12/10
12/16
12/20
12/20
12/25
12/31.5
12/31.5
12/40
–
12/50
12/63
12/80
12/80 (1) –
–
24/4
24/6.3
24/10
24/16
24/20
24/25
24/25
24/31.5
24/4
24/6.3
24/10
24/16
24/20
24/20
24/25
24/31.5
24/31.5
24/40
24/50
24/63
24/63 (1) –
–
24/31.5
24/40
24/50
24/63
24/63 (1) –
24/4
24/6.3
24/10
24/16
24/16
24/20
24/25
–
24/25
24/31.5
24/40
24/40
24/50
24/63 (2) –
–
24/6.3
24/6.3
24/10
24/10
24/16
–
24/20
24/25
24/25
24/31.5
24/31.5
24/40
24/50
24/63
–
–
24/4
24/6.3
24/10
24/10
–
36/4
36/6.3
36/6.3
36/10
24/16
24/20
24/20
24/25
24/31.5
24/31.5
24/40
24/40
24/50 (2) 24/63 (1)
36/10
36/16
36/20
36/25
36/25
36/31.5
36/40
36/40
–
36/4
36/6.3
36/6.3
36/50 (1) 36/63 (1)
36/6.3
36/10
36/16
36/16
36/20
36/25
36/25
36/31.5
36/31.5
–
36/4
36/4
36/6.3
36/40
36/50 (1)
36/6.3
36/10
36/10
36/16
36/20
36/25
36/25
36/31.5
36/31.5
36/40
36/50 (1)
(1) No permissible overload.
(2) Permissible overloads < 10%..
DD0603
Replacing fuses
Ød
Ø45
Ø6
Product range
Fusarc
33
33
e
23
* To use 12 kV or 24 kV CF fuses you must buy adapters
designed specially for the CAS 36.
14
When the elimination of a fault involves the blowing of one (or two) fuses, often the
properties of the fuses which apparently remain intact are in fact weakened by the
action of the short circuit. Returning them to service in these circumstances would
entail a high risk of unwanted fuse blowing for very slight overcurrents. It is therefore
recommended to replace the 3 fuses in accordance with the IEC 60282-1 standard.
Rating
(Amp)
e
(mm)
d
(mm)
Weight
(kg)
CF-12
6.3-10-16-20-25
292
50.5
1.2
CF-12
31.5-40
292
50.5
1.2
CF-12
50-63-80-100
292
76
3.2
CF-24
6.3-10-16-20-25
442
50.5
1.7
CF-24
31.5-40
442
50.5
1.7
CF-24
50-63-80
442
76
4.5
CF-24
100
442
86
5.7
CF-36
6.3-10-16-20
537
50.5
1.9
CF-36
25
537
50.5
1.9
CF-36
31.5-40
537
76
5.4
CF-36
50-63
537
86
6.5
Accessories
Low-voltage compartment
Remote indications
PE60314
Functional units
Moreover, to be able to perform satisfactory remote control of the MV switchgear, it is
necessary to have in the control centre all the required information on the status of
the equipment to be remote controlled:
Switch-disconnector position (I or Q)
On any of the switch-disconnectors, both line (I) and protection (Q), auxiliary
contacts (2NO + 2NC) can be incorporated for remote indication of the position of the
switch-disconnector and the earthing switch.
Voltage presence by line function (I)
For each line function (I), a relay can be incorporated with local indication of voltage
presence on each phase and an auxiliary contact for remote indication.
PE1603
Voltage presence indicating system
Earth fault passage by line function (I)
For each line function (I), a relay can be incorporated with combined with a toroidal
sensor with local indication of earth fault passage and an auxiliary contact for remote
indication.
Voltage presence indicating system
There is a voltage indicator device in each function (protection line) which makes it
possible to check whether or not voltage is present on the wires.
PE56825
Phase concordance unit
Phase concordance unit
This unit is used to check phase concordance. It can be connected to any voltage
indicator.
Tripping coils
DD0803
Base
Together with each protection switch-disconnector (Q), we can supply shunt tripping
coils, 220 Vac, / 50/60 Hz, breaking consumption: 8 A (peak value). Switching time
70/80 ms. Other working voltages: 24 Vdc, 48 Vdc and 110 Vdc.
Base
The base (optional) increases the height (C) by 400 mm.
Front case
The front case DB (optional), for housing double terminals or surge arresters,
increases the depth (C) by 250 mm.
Indication of fuse blowing
DE57990FR
On option, the CAS 36 has in its protection function a contact which indicates
blowing of one of its fuses. It can be a mechanical or electrical indication.
Antiseismic guarantee
CAS 36 has passed antiseismic tests in accordance with the ETGI-1020 tests of
Ingendesa (Chile) and UNE-EN 60068-3-3.
15
Functional units
Accessories
T200I
Motor pack
PE1702
In the switch control unit is a space reserved for the gear motor which can be
installed in factory, but which the customer can also install on the site, with the
busbar or the cable energized and without dismounting the control unit.
bb A set of electrical locking systems prevents faulty operations. With the motor pack,
the CAS 36 fits in perfectly with a remote control system.
bb Only the line functions (I) can be motorized.
Easergy T200I is a "plug and play" device or a multifunction device which takes into
account all needs for supervision and remote monitoring of a CAS 36.
bb Acquisition of various types of information: switch position, fault detection, real
current values.
bb Transmission of opening/closing orders for the switch.
bb Exchange of information with the control centres.
Essential during power cuts on the network. Easergy T200I has tried and tested
reliability and availability and is capable of ensuring operation of the switch at all
times.
It is easy to configure and operate.
PE1704
PE1703
Easergy T200I: An interface designed for monitoring MV networks
Functional unit designed for MV networks
bb Easergy T200I is designed to be connected to a MV switch without any type of
special converter.
bb It plays a front-end monitoring role for local operations. It can be used to actuate
electrical mechanisms (local/remote switch) and displays information concerning the
switch's status.
bb It has an integrated fault detection system for MV networks (overcurrent and zero
sequence) with detection of set point values which can be configured channel by
channel (current value and fault current).
Local information and control
16
Monitoring and control
Functional units
Accessories
Flair 21D and 21DT
Fault passage indicator
PE56820
The new version of the Flair 21D, Flair 22D and Flair 23DV devices of the Easergy
range has a highly visible flashing LED and provides detailed information via the
digital display. An external lamp (optional) can indicate the passage of a fault current
without any need to enter the substation..
61021N
Functions
bb Phase-to-phase and phase-to-earth fault indication
bb Display of settings
bb Display of phase at fault
bb Display of the load current and the peak current and frequency
bb Combination of fault current passage indication and voltage detection functions
(Flair 23DV only).
Ease of use and reliability
bb Automatic settings on site
bb Fault indication by LED or external lamp
bb The lifetime of the Flair 22D battery is 15 years
bb Fault detection is more precise if the Flair 22D is connected to a VPIS-VO voltage
indicator
bb Mounting on RM6 possible in factory or else on site
bb Adaptation on site can be facilitated by using a split toroid, without having to
dismount the MV cables.
Characteristics
PE57784
PE57783
Easergy Flair 21D - 22D - 23DV
Flair 21D
Flair 22D
Flair 23DV
Fault detection
Earth fault
20 to 160 A
20 to 160 A
20 to 160 A
Phase fault
200 to 800 A
200 to 800 A
200 to 800 A
Fault acknowledgement with voltage
indication (VPIS-VO)
–
b
b
–
–
b
Automatic settings
b
b
b
Manual settings
b
b
b
4 digits
Voltage detection
Voltage presence/absence
PE57785
21D
22D
Settings
Display
23DV
Display
4 digits
4 digits
Load current
b
b
b
Peak current
b
b
b
Frequency
–
b
b
Phase at fault
b
b
b
Current resolution
1A
1A
1A
Precision
± 10 %
± 10 %
± 10 %
Power supply
Self-powering
b
b
b
Dual power supply:
–
b (Lithium
battery)
b (external)(*)
Minimum operating load current
2A
2A
0A
External lamp
b
b
b
Reset
b
b
b
SCADA output
b
b
b
Other
(*) 12-48 Vdc
Thanks to a lithium battery, the Flair 22D can be configured without load current (display of
settings, reset time delay > 4 h)
17
Locking systems
Mechanical locking by bolt
Mechanical locking by bolt
Free key
Captive key
1
Missing key
1
PE1801
Between protection function (Q), transformer and low voltage:
Line function locking systems
2
1
CAS-CAS (1 and 2)
2
1
Cross locking between two lines of CAS switchboard (switch of one line with the
earthing switch of another line and vice versa); these lines may belong to the same
switchboard or another switchboard.
Line switching (3)
Locking which prevents two switches of two lines of the same switchboard from
being closed at the same time. Free key, switch open.
P106935
Mechanical locking by key (optional)
Free key, earthing switch open (4)
Locking system which allows the
key to be removed when the
disconnector of the
533.943.295.407 - (R2) CAS/CAS
533.943.395.018 - (R7/C1 - E21)
line earthing switch is closed. 533.943.295.418 - (R2) CAS/SM6
(1 and 2)
(3)
Free key, switch open
manual line switching)
533.943.395.205
(4)
Free key, earthing switch closed
1
11
2
11
1
1
DD1801
Free key, switch open
Free key, earthing switch open
2
1
2
1
1
1
2
1
1
1
1
533.943.295.407 - (R2) CAS/CAS
533.943.295.418 - (R2) CAS/SM6
533.943.395.018 - (R7/C1 - E21)
51098379M0
+ 533.943.395.018
533.943.395.018
533.943.395.306
- (R7/C1 - E21)
(R8 / C4 - E24)
533.943.295.407
533.943.395.205- (R2) CAS/CAS
533.943.295.418 - (R2) CAS/SM6
2
1
2
1
2
533.943.295.429
533.943.395.205
51098379M0 (R6)
533.943.395.029
533.943.395.306
533.943.295.407 - (R2) CAS/CAS
533.943.295.418 - (R2) CAS/SM6
533.943.395.018 - (R7/C
Protection function locking systems
(6)
Free key, earthing switch closed
Free key, earthing switch open
2
1
2
1
1
1
1
2
1
2
Free key, earthing switch open
Free key, earthing switch closed
1
1
2
(7)
1
1
1
1
1
2
DD1801
(5)
1
1
1
1
1
1
533.943.295.429
51098379M0
533.943.395.029
+ 533.943.395.018
(R8 / C4 - E24)
533.943.295.429
533.943.395.117
533.943.295.407
533.943.395.018 - (R2)
(R7/C1
CAS/CAS
- E21)
533.943.295.418 - (R2) CAS/SM6
533.943.395.205
533.943.395.018 - (R7/C1 - E21)
533.943.395.205
533.943.395.306
533.943.395.306
51098379M0 (R6)
533.943.395.029
533.943.395.106
+ 533.943.395.018
51098379M0 (R6)
(R8 / C4 - E24)
2
51098379M0 + 533.943.395.018
(R8 / C4 - E24)
1
1
1
1
1
S
6
Functional units
18
1
1
533.943.395.117
533.943.295.429
Functional units
PE1303
Connector for the protection function
PE1401
Connection cable glands
Connections
General
bb The sections, contacts and dimensions of the CAS 36 connection cable glands are
those defined by the UNE-EN 50181 standard.
bb 100% of epoxy resin cable glands are subjected to industrial frequency dielectric
tests and partial discharge tests.
The cable glands convey the current between the outside and inside of the case
filled with SF6 gas and ensure insulation between the live conductors and frame
earth.
There are two types of cable glands, which are defined by their permissible rated
current of short duration:
bb Type B: 400 A, 16 kA 1 s and 40 kA peak (plug-in) for protection function.
bb Type C: 400-630 A, 20 kA 1 s and 50 kA peak (M16 screw-on) for line function.
How to define connection cable glands
Connection cable glands depend on specific criteria:
Installation:
bb Amperage of connected equipment: 400, 630 A
bb Permissible rated current of short duration in the switch function
bb Minimum length of phase expansion
bb Type of plug-in connector:
vv Plug-in: contact finger
vv Screw-on: threaded connection
bb Plug-in output connector: straight, elbow, Tee.
Installation:
bb Rated voltage of:
vv the cable
vv the network
bb Type of conductor:
vv Aluminium
vv Copper
bb Cross section in mm2
bb With insulant
bb Cable composition:
vv Single-pole
vv Three-pole
bb Type of insulator:
vv Dry
vv Impregnated paper (non-migrating)
bb Type of screen
bb Frame.
Table of connectors (CAS 400 A/16 kA)
Brand
EUROMOLD
(with screen)
PRYSMIAN
(with screen)
Cable gland
CAS 36 functions
Description of plug-in
connector
Elbow connector
400 A - 15 kA
"T" connector
M16 400 A - 28 kA
Elbow connector
400 A - 36 kV
"T" connector
M16 630 A
M16 630 A - 20 kA
Line (I)
Screw-on
400 A - 12.5 kA
Protection (Q)
Plug-in
Cable type
1-pole dry
Cross sections
M400LR
35-240 mm2
18/30 kV
35-240 mm2
18/30 kV
25-240 mm2
18/30 kV
25-240 mm2
18/30 kV
M400TB
PMA-4/400/36
PMA-5/400/36AC
Table of connectors (CAS 630 A/20 kA)
Brand
EUROMOLD
(with screen)
PRYSMIAN
(with screen)
Bushings
CAS 36 functions
Description of plug-in
connector
Elbow connector
400 A - 15 kA
"T" connector
M16 630 A - 28 kA
Elbow connector
400 A - 36 kV
"T" connector
M16 630 A
M16 630 A - 20 kA
Line (I)
Screw-on
400 A - 12.5 kA
Protection (Q)
Plug-in
Cable type
1-pole dry
Cross sections
M400LR
35-240 mm2
18/30 kV
400-630 mm2
18/30 kV
25-240 mm2
18/30 kV
25-240 mm2
18/30 kV
M440TB
PMA-4/400/36
PMA-5/400/36AC
19
Civil engineering
Installation
CAS 36
Cable channel
400
50
50
50
20
400
A
20
PE2001
25
PE2002
B
Cable channel
C
Dimensions A, B and C (min. 100 mm) as per the criterion:
radius of curvature = 15 times total cable diameter.
(*) Cable with 18/30 kV solid insulation in accordance with
the IEC standard.
30
B
540
30
(Min. 100 mm)
Switchboard type
CAS 36 2I+1Q
CAS 36 2I+2Q
CAS 36 3I
CAS 36 3I+1Q
CAS 36 4I
CAS 36 1I
CAS 36 0I+1Q
CAS 36 3I+2Q
CAS 36 0I-T+1Q
CAS 36 0I+1I+1Q
CAS 36 0I+2I+1Q
Dimension A (mm)
Dimension B (mm)
Dimension C (mm)
1050
1200
1050
1200
1200
600
600
1700
600
925
1600
1005
1005
980
1005
980
980
1005
1005
1005
1005
1005
100
100
100
100
100
100
100
100
100
100
100
PE55643
CAS 36 2I+1Q
PE55644
A
B
The cable fasteners can be placed
at various levels.
C
Dimensions A, B and C (minimum 100 mm) in accordance
with the following criterion: the radius of curvature shall be 15
times the total cable diameter.
(*) Cable with 18/30 kV solid insulation in according with the
IEC standard.
20
Cross section
(mm2)
50
70
95
120
150
185
240
Cable exit position
Dimension A (mm)
100
100
130
150
180
220
260
Dimension B (mm)
100
100
130
150
180
220
260
Dimension C (mm)
100
110
120
125
130
140
155
Civil works
Installation
CAS 36 2I+2Q
PE55646
PE55643
A
B
C
Cross section
(mm2)
50
70
95
120
150
185
240
Dimensions A, B and C (minimum 100 mm) in accordance
with the following criterion: The radius of curvature shall be
15 times the total cable diameter.
(*) Cable with 18/30 kV solid insulation in accordance with
the IEC standard.
Cable exit position
Dimension A (mm)
100
100
130
150
180
220
260
Dimension B (mm)
100
110
120
125
130
140
155
Dimension C (mm)
100
110
120
125
130
140
155
Dimension B (mm)
320
350
380
400
425
460
500
Dimension C (mm)
570
600
630
650
675
710
750
PE55641
PE55642
CAS 36 3I
A
B
C
Dimensions A, B and C (minimum 100 mm) in accordance
with the following criterion: The radius of curvature shall be
15 times the total cable diameter.
(*) Cable with 18/30 kV solid insulation in accordance with
the IEC standard.
Cross section
(mm2)
50
70
95
120
150
185
240
Cable exit position
Dimension A (mm)
320
350
380
400
425
460
500
21
CAS 36 range
Standard unit and options
Decision Diagram
Order No.
Date
Delivery time
Country
An
X
should be marked or the desired value filled in only once for each horizontal line.
X
The green boxes
Configuration of the standard switchboard
Basic configuration (one function per box,
entail no extra cost.
Quantity
1st
2nd
3rd
function
function
function
0I
I
Q
4th
function
fill in from right to left)
Example 0I+1I+1Q V
Working voltage of the device
< 6 kV
6-10 kV
10 - 20 kV
20 - 33 kV
Rated current – Current of short duration (1s) / peak current
400 A - 16 kA / 40 kA
630 A - 20 kA / 50 kA
Rated frequency
50 Hz
60 Hz
*
( )
Service altitude
< 1000 m
> 1000 m (up to 1700 m)
Line options [except 0I (T)]
Remote operation for line function (motor pack)
Includes motor pack and 48 Vdc auxiliary contacts
Switches, 2 NO - 2 NC and ISO Earth, 2 NO - 2 NC
Auxiliary contacts (fill in only where applicable and if the line motor
pack option is not chosen)
Switches, 2 NO - 2 NC and ISO Earth, 2 NO - 2 NC
Fault passage detectors
Flair 21D
Flair 21DT
Flair 22D
Flair 23D
48 V dc
125 V dc
200 A
600 A
2 x tor.+ hom..
2 x tor.+ hom..
Short-circuit current
setting
3 x tor.
3 x tor.
400 A
800 A
1 x hom.
Options of the Protection function
Auxiliary contacts
Switches, 2 NO - 2 NC and earthing switch 2 NO - 2 NC
Switch, 2 NO - 2 NC
Tripping coil
Indication of fuse blowing
Mechanical indication
Mechanical + electrical indication
(*) Please consult us
22
50 Hz
110 V dc
60 Hz
48 V dc
220 V ac
24 V dc
CAS 36 range
Standard unit and options
Decision Diagram
An
X
should be marked or the desired value filled in only once for each horizontal line.
X
The green boxes
Configuration of the standard switchboard
Basic configuration ((one function per box,
entail no extra cost.
Quantity
1st
2nd
3rd
function
function
function
0I
I
Q
4th
function
fill in from right to left)
Example V
Locking options
Access to lower front cables compartment
Possible only with ISO Earth, line function, closed
Access to fuse compartment
Possible only with earthing switch, protection function, closed
Key locking (look up available functions)
For lines 1I (except 0I)
INCOMPATIBLE WITH POWER OPERATION OF THE LINE
(1*) Type R2 (CAS-CAS) free key, open switch.
(2*) Type R2 (CAS-SM6) free key, open earthing switch.
(3*) (CAS-CAS) manual switching of the 2 lines
(4*) (CAS) (earthing switch closed, free key)
For protective devices
(5*) R7-C1-E21 (earthing switch closed, free key)
(6*) R6 (earthing switch open, free key)
(7*) R8-C4-E24 (R7-C1-E21+R6)
always provided by default
always provided by default
Other options
Double terminal case (possibility of double connector or surge arrester
Possible only for lower front cable compartments)
Protection against internal arc 20 kA 1s (lateral function 0I not included.
Not compatible with double connector option)
AFL
AFLR
IP3X closing
(Possible only for lower front cable compartments)
Option with seismic resistance
Packaging type
Land
Maritime
Maritime with crate
Accessories
Fusarc CF MV fuses
MV fuses Fusarc CF
Fuse adapter
H = 400 mm
rating (kV/A)
rating (kV/A)
rating (kV/A)
12 kV (292 mm)
24 kV (442 mm)
Quantity
Quantity
Quantity
Quantity
Quantity
* See drawings on page 18
23
35, rue Joseph Monier
CS 30323
F- 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com
AMTED304013EN
As standards, specifications and designs change from time to time, please ask for confirmation