PROPOSAL OF AN ADAPTIVE OVERCURRENT RELAY FOR 110 KV NETWORK09 IONUȚ CIPRIAN BORĂSCU 1 Key words: Network topology, Relays, Fault currents. Connection of many distributed generations (DG) has a major impact to the setting of numerical overcurrent relays since the power produced by wind power plants or photovoltaic power plants varies considerably. Therefore, in order to not exceed the limits of transportable power in certain sections, in the case of unavailability of a 110 kV line, territorial power dispatcher imposes operating regimes that have consequences to numerical overcurrent protections. Since power system is a dynamic system, changing the source impedance ratio (SIR), affects sensitivity, selectivity or in some cases can lead to the impossibility of starting the numerical overcurrent relay. Hence, in order to improve the functionality of a numerical overcurrent protection, under constant modification of the source behind the relay, the paper is proposing an adaptive overcurrent algorithm based on the phase to phase differential currents (PDC). As a result, the relay is sensitive to all types of phase to phase short circuits and the protection area is improved through the recognition of equivalent impedance source. 1. INTRODUCTION In 110 kV network, the overcurrent protection is used as backup protection in most of the cases. In the case of unavailability of the distance protection, the overcurrent protection can become a primary protection for a certain period of time [1]. Latest reviews in the field shows that it can remain as basic protection up to a few hours because it is dependent on the network topology changes and it cannot detect short circuits with high resistance fault. As is known, establishing the current setting threshold for conventional overcurrent protection cannot be achieved so easily because it raises a number of issues, like: number of operating schemes, radial or loop scheme, providing transportable power, setting the load current without affecting the sensitivity criterion, selective trip of the local overcurrent protection, fault resistance, etc.. Analysis of data provided by multi-function transient recorders for events that have occurred in the 110 kV network, have shown that, the changes in the source’s impedance and “Politehnica” University of Bucharest, 313 Splaiul Independenței, 060042, Bucharest, Romania, E-mail: borascu.ciprian@yahoo.com1 Rev. Roum. Sci. Techn. – Électrotechn. et Énerg., 60, 4, p. 376–386, Bucarest, 2015 2 Proposal of an adaptive overcurrent relay for 110 kV network 377 the limitation of the transmitted power, are two of the main reasons for which the setting of the overcurrent protection in 110 kV loop network is not used. The protection relay domain has made significant progress, mainly in order not to limit the transmitted power. Unlike the phase- to- phase overcurrent relays, the negative sequence overcurrent elements are not affected by the load current and it can be set below the load in order to operate faster and more sensitive [2]. On the other hand, the negative sequence overcurrent does not trip in the case of three phase short circuits because the only one sequence that occurs is the positive one. To prevent the changing of settings for numerical overcurrent protections every time a new power source appears in the 110 kV network, or to ensure the adequate protection zone, even when the dispatcher imposes modification of operating schemes due to the unavailability or revisions of the power system equipment, is necessary to use adaptive settings [3–6]. With the capabilities of the microprocessor-based devices, the operating parameters, in order to maintain optimal performance, are changing according to network conditions. The adaptive overcurrent proposed detects phase faults by measuring the phase to phase differential currents ( I AB , I BC , I CA ). The prospective short circuit current is detected in any conditions of the system. As a result this eliminates the need to establish a short circuit scenario in order to meet the maximum conditions [7]. Another advantage of this adaptive overcurrent logic is that it does not limit the transportable power, so it can be set under the load current level. 2. CHARACTERISTICS AND OPERATION OF THE NUMERICAL OVERCURRENT RELAYS BASED OF PHASE TO PHASE DIFFERENTIAL CURRENTS The three phase currents that flow through protective relay are I A , I B , I C , and the PDC and their amplitudes are defined as [8–10]: I AB = I A − I B I AB = I AB I BC = I B − I C I BC = I BC . I CA = I C − I A I CA = I CA (1) For two-phase fault, the equivalent circuit diagram of a transmission line with a single power source, with load conditions, is represented in Fig. 1. The overview diagram with load conditions is represented in Fig. 2. The sequence impedances from bus S to fault location are Zl1 = Z12 = Zl 3 , Z 'L = Z L − Zl . The balanced load impedances are Z 'load = Z 'load1 = Z 'load2 . E S represents the phase potential of the equivalent source. Ionuț Ciprian Borăscu 378 3 Fig. 1– Sequence impedances for double phase short circuit, considering a transmission line with a single power source, with load conditions. Fig. 2 – A 110 kV transmission line with a single power source, with load conditions. IAB = ES ⎡⎛ 3 3 ⎞ 3 Z 'L + Z 'load ⎤ , ⋅ ⎢⎜ + ⋅ j ⎟ − ⋅ ⎥ ZS + ZL ⎢⎣⎜⎝ 2 2 ⎟⎠ 2 ZS + Zl + Zload ⎥⎦ ⎛ I BC = ⎜ − j ⋅ 3 ⋅ ⎝ I AC = ES ⎞ ⎟, Z S + Zl ⎠ ES ⎡⎛ 3 3 ⎞ 3 Z 'L + Z 'load ⎤ , ⋅ ⎢⎜ − + ⋅ j ⎟ + ⋅ ⎥ ZS + Zl ⎢⎣⎜⎝ 2 2 ⎟⎠ 2 ZS + Zl + Zload ⎥⎦ where Zload = Z' L + Z'load . (2) (3) (4) 4 Proposal of an adaptive overcurrent relay for 110 kV network 379 Suppose that Z s = j ⋅ X S , Z L = RL + j ⋅ X L , Z load = j ⋅ X load . Equation (5) can be expressed as follows: I AB < 3 ⋅ I K (3) ; I BC = 3 ⋅ IK (3) ; I AC < 3 ⋅ IK (3) . (5) Technical regulations and the data provided by multi-function transient recorders from numerical relays confirm that in the case of two phase short circuits, for example, between phases B and C, the phase B current is equal and opposite to the phase C current and the current from phase A tends to 0 amp. Also, the ratio 3 between three phase short circuit and two phase short circuit is . In order to 2 identify the phase faults, in a 110 kV transmission line with a single source with load, the paper proposes the equation (6). The logic is to calculate the maximum absolute value of the phasors I AB , I BC , I CA , then it is checked that the absolute value of the phasor identified as maximum, is less or equal than 3 ⋅ I K (3) . max( I AB , I BC , I CA ) ≤ 3 ⋅ I K (3) , (6) where I K (3) = three phase short circuit current. Analyzing the equation (6) it can be deduced that the overcurrent detects phase faults by measuring the maximum of PDC and the trip command can be released when the maximum exceeds the setting. Therefore, the trip logic is: I op = K ⋅ E Sph ZS + ZL , max( I AB , I BC , I CA ) ≥ I op , (7) (8) where: K = reliability coefficient; E Sph = phase to phase potential of the equivalent source; Z S = equivalent source impedance; Z L = positive sequence impedance of the line. 3. ADAPTIVE IMPEDANCE RECOGNITION In order to extend the zone of protection, selectivity increased, trip criterion and coordination simplified, the adaptive impedance recognition represents a solution. Consider that before the fault the phase currents and the phase to phase voltages are: I AB (0) , I BC (0) , I AC (0) respectively U AB (t ) , U BC (t ) , U CA (t ) . The source impedance can be calculated as follows [8–10]: – for three phase faults ZS = − U BC (t ) − U BC (0) U (t ) − U CA (0) U (t ) − U AB (0) = − AB = − CA ; I BC (t ) − I BC (0) I AB (t ) − I AB (0) I CA (t ) − I CA (0) (9) Ionuț Ciprian Borăscu 380 5 – for phase to phase short circuit faults ZS = − U PPf (t ) − U PPf (0) I PPf (t ) − I PPf (0) , (10) where: U PPf = phase to phase voltage between the faulted phases; I PPf = phase to phase differential current between the faulted phases. In comparison with the three PDC, the highest magnitude is associated with the differential current between faulted phases and therefore the faulted loop can be selected. For a phase to phase short circuit (which involves phases A and B) the phases A and B are selected as faulted phase base, on operation criterion max( I AB , I BC , I CA ) = I AB . ESph = E AB (t ) = U AB (t ) + I AB (t ) ⋅ Z S ZS = − U AB (t ) − U AB (0) I AB (t ) − I AB (0) . (11) In these conditions, the expression for I op can be expressed as [8–10]: I op = K ⋅ I op = K ⋅ E Sph ZS + ZL U AB ( t ) ⋅ ( I A B ( t ) − I A B (0 ) ) - I A B ( t ) ⋅ (U A B ( t ) − U A B (0 ) ) . − (U A B ( t ) − U A B (0 ) ) + Z L ⋅ ( I A B ( t ) − I A B (0 )) (12) In order to avoid the malfunction of the adaptive overcurrent relay in the case of disconnection of power transformer (PT), the relay uses the fault currents or both fault currents and fault voltages. When the PT is disconnected, the protection scheme will use only the fault currents automatically. 4. PROTECTION ZONE OF THE NUMERICAL ADAPTIVE OVERCURRENT RELAY BASED ON PDC 4.1. WITHOUT REAL-TIME CALCULATION OF THE EQUIVALENT SOURCE IMPEDANCE For a classic instantaneous overcurrent relay, the I op is [8–10]: I op = K ⋅ ES , Z S min + Z L (13) 6 Proposal of an adaptive overcurrent relay for 110 kV network 381 where: I op represents the value of the pickup current. K represents the reliability coefficient. When the fault occurs on the position of m ⋅ Z L , the fault current is: IF = K f ⋅ ES ZS + m ⋅ ZL , (14) where I F represents the value of the fault current, K f represents the coefficient of the fault type. The zone of protection can be expressed as follows: m= K f ⋅ (Z S min + Z L ) − K ⋅ Z S K ⋅ ZL . (15) In the case that the real-time calculation of the equivalent source impedance is not possible, the equivalent source impedance is constant, I op' = I F ' , the zone of protection can be calculated from (16): Z + ZL − K ⋅ ZS m' = S min . K ⋅ ZL (16) Z S min + Z L − K ⋅ Z S m' = . m K ⋅ (Z S min + Z L ) − K ⋅ Z S (17) Then In equation (17) the coefficient of fault type can take the following values: K f = 1 – for three phase short circuit, then Kf = m' =1; m 3 m' 2 – for phase to phase short circuit, then . > 2 m 3 So, to all types of faults there is m' ≥ m . 4.2. WITH REAL-TIME CALCULATION OF THE EQUIVALENT SOURCE IMPEDANCE With real-time calculation of the equivalent impedance, I op'' = I F '' and the zone of protection can be calculated as follows: Ionuț Ciprian Borăscu 382 Z + (1 − K) ⋅ Z S . m'' = L K ⋅ ZL 7 (18) From equation (15) and (18) it can be derived: Z L + (1 − K) ⋅ Z S m'' . = m (K f ⋅ Z S min − K ⋅ Z S ) + K f ⋅ Z L (19) In equation (19), K f can take two values: – K f = 1 for three phase short circuit, then Z L + (1 − K) ⋅ Z S m'' = > 1; m (Z S min − K ⋅ Z S ) + Z L – Kf = (20) 3 for three phase short circuit, then 2 Z L + (1 − K) ⋅ Z S 2 m'' = > . m ⎛ 3 ⎞ 3 3 ⎜ ⋅ Z S min − K ⋅ Z S ⎟ + ⋅ ZL ⎜ 2 ⎟ 2 ⎝ ⎠ (21) From equations (20) and (21) it can be concluded that m'' ≥ m to all types of faults. m' < 1 denotes that the zone of protection of the numerical The ratio m'' adaptive overcurrent relay based on the PDC is larger than the traditional one. 5. SIMULATION In this paper I did a study in order to show the protection zones of the overcurrent relay based on the PDC and of classic instantaneous overcurrent relay (Figs. 3, 4). The phase to phase short circuits and three phase short circuits, were made on 100 % of a 110 kV radial transmission line ( Z L =1.88+3.96 ⋅ j [Ω]), considering different short circuit powers-source impedances, K and Kf. 8 Proposal of an adaptive overcurrent relay for 110 kV network Fig. 3 – The zone of protection considering K f = 3 / 2, 1 and K=1.1 . 383 384 Ionuț Ciprian Borăscu 9 Fig. 4 – The zone of protection considering K f = 3 / 2, 1 and K=1.5. 6. CONCLUSION Short circuits from established scenarios are an important reference for protection engineers. In reality the variable nature of the source impedance determined mainly by commissioning respectively by out of service of significant production capacity, significantly influence the selectivity and the speed of the overcurrent protections. Therefore, in order to eliminate errors generated by the changes of SIR or operating regimes, the paper proposes a numerical adaptive overcurrent relay based on phase to phase differential currents using real-time calculation of the equivalent impedance. 10 Proposal of an adaptive overcurrent relay for 110 kV network 385 Simulations that have been made show that the zone of protection of the numerical overcurrent relay, for all types of short circuit, it is improved significantly, using the adaptive impedance recognition. On the other hand, even if the communication path is not available, the proposed logic for numerical overcurrent relays is more sensitive in the case of phase to phase short circuits than the traditional one. Overall, compared with the classical overcurrent protection, the proposed scheme is sensitive to all types of short circuits and not influenced by the load current. The adaptive scheme provided in this paper can contribute to develop new adaptive algorithms for overcurrent relays. Important future approaches can treat adaptive algorithms for phase overcurrent protection within 110 kV loop network, so as for phase faults located on the protected line to allow the start of automatic reclosing from this protection. ACKNOWLEDGMENTS This work was co-funded by the European Social Fund through the Operational Programme Human Resources Development 2007-2013 (Contract number POSDRU/159/1.5/S/132395). Received on September 17, 2014 REFERENCES 1. Byung Chul Sung, Soo Hyoung Lee, Jung-Wook Park, Adaptive Protection Algorithm for Overcurrent Relay in Distribution System with DG, J. Electr. Eng. Technol., 8, 5, pp. 805–815, 2013. 2. Edmund O. Schweitzer, Mark W. Feltis, Ahmed F. Elneweihi, Improved sensitivity and security for distribution bus and feeder relays, WESCANEX 93, Communications, Computers and Power in the Modern Environment, Conference Proceedings, IEEE, Canada, 1993, pp. 337–339. 3. A.Y. Abdelaziz, H.E.A. Talaat, A.I. Nosseir, Ammar A. Hajjar, An adaptive scheme for optimal coordination of overcurrent relays, Electric Power Systems Research, 61, 1, pp. 1–9, 2002. 4. Andres Felipe Contreras C., Gustavo A. Ramos, Methodology and Design of an Adaptive Overcurrent Protection for Distribution Systems with DG, International Journal of Engineering & Technology, 12, 4, pp. 128–136, 2012. 5. M. Murali, P.Sharath Kumar, K, Vijetha, Adaptive Relaying of Radial Distribution System with Distributed Generation, International Journal of Electrical and Computer Engineering (IJECE), 3, 3, pp. 407–414, June 2013. 6. Han Yi, Hu Xuehao, Zhang Dongxia, A new adaptive current protection scheme of distribution networks with distributed generation, Sustainable Power Generation and Supply, Nanjing, 6–7 April 2009. 386 Ionuț Ciprian Borăscu 11 7. Herbert A. Fleck, Frank J. Mercede, Using Short-circuit Currents to Perform a Protective Device Coordination Study, IEEE Industry Application Magazine, 6, 1, pp. 43–52, 6 August 2002. 8. Chen Yanxia, Yin Xianggen, Zhang Zhe, Chen Deshu, The research of the overcurrent relays based on phase to phase differential current-adaptive setting and coordination, Transmission and Distribution Conference and Exposition, USA, 2003, pp. 250–255. 9. Y. Serizawa, H. Imamura, N. Sugaya, Experimental Examination of Wide-area Current Differential Backup Protection Employing Broadband Communication and Time Transfer Systems, IEEE Power Engineering Society Summer Meeting, Edmonton, Alta, 1999, pp. 1070–1075. 10. J. C. Tan, P. A. Crossley, I. Hall, J. Farrnell, P. Gale, Intelligent wide area back-up Protection and it’s role in enhancing transmission network reliability, Developments in Power System Protection, Seventh International Conference on (IEE), Amsterdam, 2001, pp. 446–449.