Relay Interface

advertisement
Technical Datasheet
Relay Interface
The Vimpex Relay Interfaces are designed to provide a connection between external
equipment and alarm systems. Building Management Systems (BMS), security, fire and
smoke dampers and lift shutdown are just some of the applications for this device.
The unit is designed to be connected directly to the sounder circuit of the fire alarm
system. The relay automatically activates when an alarm is sounded. It can also be
connected directly to a fire alarm or security control panel outputs.
The double-pole relay provides two sets of NC and NO contacts that can switch up to 8
A each. An LED provides visual indication of relay activation. The unit fits a standard UK
electrical back box or can be provided with a back box for surface mounting.
Specification
Standards
Range:
12 V Series
24 V Series
+
Complies with EMC Directive (89/336EEC)
Nominal Voltage:
12 V dc
24 V dc
+
Low Voltage Directive (73/23/EEC)
Operational Current:
33 mA @ 12 V dc
18 mA @ 24 V dc
+
EN 50130:4 Alarm Systems
Drop Out Voltage:
2 V dc
3.5 V dc
Output Contact Rating: Double Pole-Change Over Contacts 230 V ac, 8 A max, 2000 VA
Contact Material:
Silver Alloy
-40 to +70 oC
Temperature Range:
Electrical Life:
100,000 operations at rated current
Part Numbers - Spares & Accessories
ANC0014:
ANC0017:
ANC0018:
ANC0019:
ANC0015:
ANC0016:
ANC0020:
ANC0021:
12VDC, 8A, White, Single Gang with Back Box
12VDC, 8A, White, Single Gang
12VDC, 8A, Red, Single Gang
12VDC, 8A, Red, Single Gang, with Back Box
24VDC, 8A, White, Single Gang with Back Box
24VDC, 8A, White, Single Gang
24VDC, 8A, Red, Single Gang
24VDC, 8A, Red, Single Gang, with Back Box
Contacts close
when sounder
circuit active
Spare
Contacts
NO - Normally
Open
C - Common
NC - Normally
Closed
Sounder
Circuit
Dimensions (mm)
86.0
60.0
Electrical Connection
23.0
EOL Resistor
86.0
28.0
Vimpex Limited
Star Lane, Great Wakering
Essex SS3 0PJ England
Tel: +44 (0) 1702 216999
Fax:+44 (0) 1702 216699
E-mail:sales@vimpex.co.uk
www.vimpex.co.uk
Assessed to ISO 9001
Cert/LPCB ref. 456
DS/RLYIF-TD/ISS 2
We reserve the right to change or amend any design or specification in line
with our policy of continuing development and improvement.
VIMPEX