Construction Automotive Industry INSTRUCTIONS FOR ZONE PUMP RELAY CONTROL ARTICLE NO. 281721-001 Fully fuse protected and with four standard "ice-cube" snap out relays, this junction box is feature rich with a priority switch for four zones. There is a convenient 24 VAC terminal available and a master/slave switch allowing for the ganging together of multiple boxes for control of up to 20 zones. External LED indicator ights indicate system power and zone pump operation. Three power port terminals are available and can receive plug-in cards, which can add additional features, such as post purge, priority protection and universal timer/pump exercise. Controls up to four zone pumps. Cold Start Boiler Application Tankless Coil Boiler Application (Alternative Wiring) For Cold Start Boiler Application Mode Operation: When the dip switch is set to NORMAL, the end switch relay will Operation: When any thermostat calls for heat, the appropriate circulating pump is be energized if any zone is in operation. When the switch is set to RESET, the end energized and the isolated end switch (X and X) will start the boiler. switch relay will only be energized if the priority zone is in operation, or through the operation of a plug-in reset control. For Tankless Coil Boiler Application (Alternative Wiring) Operation: When any thermostat calls for heat, the boiler will be enabled and Primary Pump Operation: When the dip switch is set to OFF, the primary circu- appropriate circulating pump is energized when the boiler temperature is above the lating pump output will energize when any zone calls for heat, except the priority set low limit and low limit (ZC) dip switch is set to on. zone. When the dip switch is set to ON, the primary circulating pump output will energize when any zone calls for heat. ZC and ZR Terminals: Connect terminal ZC to ZC terminal on the aquastat control. Connect ZR to ZR terminal on the aquastat control. Confirm polarity is Post Purge Operation: When the dip switch is set to ON, the priority zone output consistent between boiler aquastat and switching relay. will stay energized for 2 minutes after its thermostat or aquastat is satisfied, but not operate the boiler. WARNING: Power must originate from the boiler aquastat when using Alternative Wiring diagram. Failure to follow these wiring instructions may Priority Protection Operation: When the dip switch is set to on, and if the priority result in a secondary source of power being connected to the boiler that may zone calls continuously for more than one hour, power is returned to all the other activate it under certain circumstances, causing injury or death. zones, allowing each zone to function independently. Once the priority zone is satisfied, the control's auto-reset is activated and the priority zone is again allowed For Both Cold Start Boiler Application and Tankless Coil Boiler Application to have priority for up to one hour starting from when it calls next. (Alternative Wiring) Priority Operation: When the priority dip switch is set to ON and the priority zone Pump Exercise Operation: When the dip switch is set to on, the solid state timer is actuated, all other zones will stop operation until priority zone is satisfied. When cycles all the circulating pumps that are attached to the Expandable Switching not switched to priority, all zones will operate independently. Relay at the selected time interval. The time interval can be set for the pumps to run for either 30 seconds every 2 weeks or for 4 minutes every 24 hours. For updates to this publication, visit na.rehau.com/resourcecenter The information contained herein is believed to be reliable, but no representations, guarantees or warranties of any kind are made as to its accuracy, suitability for particular applications or the results to be obtained therefrom. Before using, the user will determine suitability of the information for the user’s intended use and shall assume all risk and liability in connection therewith. © 2012 REHAU www.rehau.com 855.627 10.12 Low Limit (ZC) Operation: When the dip switch is set to on and the boiler drops 120 VAC Connections (N is Neutral, H is Hot): below the set low limit (terminal ZC connected to boiler), all zone circulating pumps Power Input Connect 120 Volt AC power will stop. When the boiler rises above the set low limit, the zone circulating pumps Primary Primary Pump (optional) are allowed to operate. Zone 1-3 Circulator Zones Priority Zone 4 Priority Zone (if enabled) or Zone 4 End Switches (Dry Contacts): The main end switch closes when any zone N/C Zone 4 Normally closed terminals for the Priority Zone thermostat calls for heat and the mode switch is set to normal. The main end Will deactivate on a Priority Zone call. switch also closes when the mode switch is set to reset and a PC Series boiler reset power control is calling for heat. The priority end switch closes only when the This device complies with part 15 of the FCC Rules. Operation is subject to the priority zone thermostat or aquastat is calling for heat. following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that Expansion Connections: Set the expansion switch to MASTER on the switching may cause undesired operation. relay that has the designated priority zone or is utilizing the PC Series plug-in option. Set all other daisy chained controls to SLAVE. Using thermostat wire External Diagnostics: Externally visible lights show full functionality of the switch- (18-22 gauge) connect between terminals A, B, C on the master control to the ing relay. The green light should always be on, indicating that power is connected. corresponding A, B, C on the slave control(s). Controls may be daisy chained up to When the thermostat calls for heat, both the appropriate circulator and red indicat- 20 zoning panels using any combination of -EXP controls (120 zones if all are six ing light are energized. zone panels). Wiring connections must be made in accordance with all applicable electrical Thermostat Input (24 vac): codes. Use copper wire only. Recommendations for wiring: R - 12 to 18 gauge wire for 120 VAC connections (120 VAC wiring must have a Hot side of transformer. Connect to R on thermostat. W Switched R signal from thermostat. Connect to W on thermostat. C Common side of transformer. Connect to COM on thermostat (optional). - 14 to 22 gauge wire for thermostat connections NET Network terminals 1 and 2 are tied together for wiring convenience when - 14 to 22 gauge wire for 24 VAC source connections minimum temperature rating of 167°F (75°C) using communicating style thermostats (optional). WARNING: Failure to follow applicable electrical codes can result in Features: personal injury or death due to electrocution or shock and/or property - Front External Indicator Lights - Two Isolated End Switchs - Plug-In Power Port Cards - Expandable to 20 Zones - Ideal for Retrofitting - Simplified Wiring - Contractor-Friendly PC Board Layout - Primary Circulator Output - Universal Thermostat Compatibility - 100% Factory Tested - Compact Design - Fuse Protected - 24 Volt Power Input/Output Terminal - UL Approved damage due to fire. Dip Switch Settings - Expandable to 20 Zoning Panels SPECIFICATIONS Article No. 281721-001 Number of Zones 4 with priority Input Voltage 120/60/1 VAC Maximum Combined Load 20 amps Type 1 Enclosure W H D 10 3/4 in. 7 in. 2 3/4 in. All circulator relay connections, including ZC/ZR, are rated 1/3 hp (6 FLA, 36 LRA) at 120 VAC. End switch connections are rated 24 VAC, 1 amp. All thermostat connections supply a 24 VAC class 2 output. 2 Expandable Switching Relays Connected Together