Operating instructions, mounting & installation ETM 1 including brass immersion sleeve, nickel-plated Screw-in temperature measuring transducer, calibrateable ETM 2 including stainless steel immersion sleeve Screw-in temperature measuring transducer, calibrateable KTM 1 ncluding mounting flange Duct ⁄ air duct temperature measuring transducer, calibrateable S+S REGELTECHNIK GMBH | KLINGENHOFSTR. 11 | 90411 NUREMBERG | GERMANY | PHONE +49(0)911 ⁄ 51947-0 | FAX +49(0)911 ⁄ 51947-70 | www.S p lusS.eu | mail@SplusS.eu Industry-oriented solutions – Complete control technology from one source! ETM 1 including brass immersion sleeve, nickel-plated ETM 2 including stainless steel immersion sleeve Screw-in temperature measuring transducer calibrateable, with active output APPLICATION: Calibrateable screw-in temperature measuring transducer with enclosure made of impact-resistant plastic and straight protective tube for the detection of temperatures in liquid or gaseous media. For aggressive media, stainless steel immersion sleeves shall be used. Applications in piping systems, in heating technology, in storage tanks, in district heating compact stations, in hot and coldwater systems, in oil and lubricant circulation systems, in mechanical, apparatus and plant engineering as well as in the entire industrial sector. TECHNICAL DATA: Power supply:................................... 24 V DC ETM 1 Sensor:.............................................. Pt100, DIN EN 60751, class B Measuring range:.. ........................... see table Ambient temperature:.................... measuring transducer - 30...+ 70 °C Connection type:.............................. 2- or 3-wire connection Process connection:.. ...................... screwed socket with ½“ pipe thread Immersion sleeve:............................ ETM 1: brass, nickel-plated, ½“ pipe thread, wrench size 22 mm, Ø = 8 mm ETM 2: stainless steel, 1.4571, V4A, ½“ pipe thread, wrench size 27 mm, Ø = 8 mm Protective tube:............................... stainless steel, 1.4571, V4A, Ø = 6 mm Connecting head:............................. plastic, material polyamide, 30 % glass-globe-reinforced, with quick-locking screws, colour pure white (similar RAL 9010) Dimensions:...................................... 72 x 64 x 39.4 mm Cable union:...................................... M 16, including strain relief Max. pressure: ETM 1 brass immersion sleeves 10 bar ETM 2 stainless steel immersion sleeves 40 bar Electrical connection:.. .................... 0.14 - 1.5 mm² via terminal screws on circuit board Humidity:........................................... < 95 % r. H., non-precipitating air ETM 2 Protection class:.. ............................ III (according to EN 60 730) Protection type:............................... IP 65 (according to IEC 529) Standards:........................................ CE conformity, electromagnetic compatibility according to EN 61 326 + A1 + A2, EMC directive 89 ⁄ 336 ⁄ EWG low-voltage directive 73 ⁄ 23 ⁄ EWG Optional:............................................ 8-digit display, cutout 36 x14 mm (W x H), for displaying actual temperature Connecting diagram Whithout display Output: 0 -10 V Connecting diagram Without display Output: 4...20 mA Connecting diagram Output: 0 -10 V With display Connecting diagram Output: 4...20 mA With display ETM xx with display ETM 1 ETM 2 Dimensional drawing ▲ ETM 2 ▲ ETM 1 Type ⁄ WG1 Output 50 mm 100 mm 150 mm 200 mm 250 mm 300 mm ETM 1 - I 4...20 mA • • • • • • ETM 1 - U 0 -10 V • • • • • • ETM 1xx - Display Extra charge see pricelist Other ranges upon request: e.g. TB1 (- 50 ...+ 50 °C), TB10; (- 20 ...+150 °C), and others upon request Please indicate with your order: Measuring range (TB…) and length of protective sleeve e.g. ETM 1 - U, TB 10 (- 20 ...+ 150 °C), 150 mm; ETM 1 - I, TB 3 (0 ...+100 °C), 300 mm Type ⁄ WG1 Ausgang 50 mm 100 mm 150 mm 200 mm 250 mm 300 mm ETM 2 - I 4...20 mA • • • • • • ETM 2 - U 0 -10 V • • • • • • ETM 2xx - Display Extra charge see pricelist Other ranges upon request: e.g. TB1 (- 50 ...+ 50 °C), TB10; (- 20 ...+ 150 °C), and others upon request Please indicate with your order: Measuring range (TB…) and length of protective sleeve e.g. ETM 2 - U, TB 10 (- 20 ...+150 °C), 150 mm; ETM 2 - I, TB 3 (0 ...+100 °C), 300 mm KTM 1 including mounting flange Duct ⁄ air duct temperature measuring transducer calibrateable, with active output KTM 1 APPLICATION: Calibrateable duct temperature measuring transducer with connecting head made of impact­r esistant plastic and mounting flange. It is used for the detection of temperatures in gaseous media, e.g. in ventilation and air conditioning ducts. TECHNICAL DATA: Power supply:................................... 24 V DC Sensor:.............................................. Pt100, DIN EN 60751, class B Measuring range:.. ........................... TB3 (0...+ 100 °C) Ambient temperature:.................... measuring transducer - 30...+ 70 °C Connection type:.............................. 2- or 3-wire connection Protective tube:............................... stainless steel, 1.4571, V4A, Ø = 6 mm, optional perorated, dimensions see table Connecting head:............................. plastic, material polyamide, 30 % glass-globe-reinforced, with quick-locking screws, colour pure white (similar RAL 9010) Dimensions:...................................... 72 x 64 x 39.4 mm Cable union:...................................... M 16, including strain relief Electrical connection:.. .................... 0.14 - 1.5 mm² via terminal screws on circuit board Process connection:.. ...................... by mounting flange (included in the scope of delivery), plastic, (galvanised steel optional) Humidity:........................................... < 95 % r. H., non-precipitating air Protection class:.. ............................ III (according to EN 60 730) Protection type:............................... IP 65 (according to IEC 529) Standards:........................................ CE conformity, electromagnetic compatibility according to EN 61 326 + A1 + A2, EMC directive 89 ⁄ 336 ⁄ EWG low-voltage directive 73 ⁄ 23 ⁄ EWG Optional:............................................ 8-digit display, cutout 36 x14 mm (W x H), for displaying actual temperature Connecting diagram Without display Output: 0 -10 V Connecting diagram Without display Output: 4...20 mA Connecting diagram Output: 0 -10 V With display Connecting diagram Output: 4...20 mA With display KTM 1 with display KTM 1 Dimensional drawing Type ⁄ WG1 Ausgang 50 mm 100 mm 150 mm 200 mm 250 mm 300 mm KTM 1- I 4...20 mA • • • • • • KTM 1- U 0 -10 V • • • • • • KTM 1xx - DisplayExtra charge see pricelist Other ranges upon request: e.g. TB1 (- 50...+ 50 °C), TB10; (- 20...+ 150 °C), or others upon request Please indicate with your order: Measuring range (TB…) and length of protective sleeve e.g. KTM 1 - U, TB 10 (- 20...+ 150 °C), 150 mm; KTM 1 - I, TB 3 (0...+100 °C), 300 mm Technical data Supply voltage: Connection scheme Individual operation Connection scheme Parallel operation For operating voltage reverse polarity protection, a one-way rectifier or ­r everse polarity protection diode is integrated in this device variant. This­ ­internal one-way rectifier also allows operating 0 - 10 V devices on AC supply voltage. The output signal is to be tapped by a measuring instrument. Output voltage is measured here against zero potential (0 V) of the input voltage! When this device is operated on DC supply voltage, the operating voltage input UB+ is to be used for 15...36 V DC supply and UB– or GND for ground wire! When several devices are supplied by one 24 V AC voltage supply, it is to be ensured that all ”positive“ operating voltage input terminals (+) of the field devices are connected with each other and all ”negative“ operating voltage input terminals (–) (= reference potential) are connected together (in-phase connection of field devices). All outputs of field devices must be referenced to the same potential! In case of reversed polarity at one field device, a supply voltage short-circuit would be caused by that device. The consequential short-circuit current flowing through this field device may cause damage to it. Therefore, pay attention to correct wiring! Connecting conditions Connecting diagram Output: 0 -10 V Without display Connecting diagram Output: 4...20 mA Without display The output voltage follows linear to the temperature signal applied at the input terminals and generates a proportional output signal of 0 - 10 V. The voltage outputs are short-circuit proof against ground wire. Applying voltage supply to the output terminals will destroy the device. Connecting diagram Output: 0 -10 V With display Connecting diagram Output: 4...20 mA With display In case of the 4...20 mA measuring transducer, display and evaluating elements are connected in series in the current loop. The measuring transducer thereby limits the flowing current in variance of the input signal. 4 mA are for the measuring transducer‘s internal current consumption. The apparent ohmic resistance can either be connected in the plus or minus path of the measuring transducer. In case of an apparent ohmic resistance in the plus path, power supply and resistance must not share one ground wire. Technical data Temperature measuring transducer calibrateable with active output Output:.. ............................................ 4...20 mA Connection:.. ..................................... 2-wire connection Auxiliary energy: .. ............................ 14...35 V DC, supplied from 4...20 mA loop EMC :.................................................. according to EN 61 326: 1997 + A1: 1998 + A2: 2001 Measuring element:......................... see table Operating temperature:.................. transmitter - 30...+ 70 °C Apparent ohmic resistance:.. ......... Ra (Ohm) = (Ub-14 V) ⁄ 0.02 A Linearisation:.................................... temperature linear according to DIN IEC 751 Linearity error:................................. ± 0.6 % of the set range Zero point drift:.. .............................. 0.6 % ⁄ 10 K Voltage drift:.. ................................... 0.6 % ⁄ 10 K Auxiliary energy flow:..............................0.02 % ⁄ V Output:............................................. 0 - 10 V Connection:.. ..................................... 3-wire connection Auxiliary energy: . ............................ 24 V DC ± 6 V, EMC :.................................................. according to EN 61 326: 1997 + A1: 1998 + A2: 2001 Measuring element::.. ...................... see table Operating temperature:.................. transmitter - 30...+ 70 °C Apparent power of voltage transformer:.. ................................... minimum load resistance 3 kOhm Linearisation:.................................... temperature linear according to DIN IEC 751 Linearity error:................................. ± 0.6 % of the set range Zero point drift:.. .............................. 0.6 % ⁄ 10 K Voltage drift:.. ................................... 0.6 % ⁄ 10 K Auxiliary energy flow:.. ..................... 0.02 % ⁄ V Apparent ohmic resistance = Voltage supply – internal current consumption (7,5 V) 20mA TEMPERATURE RANGES:: When selecting measuring transducer ranges, it is necessary to ensure that the maximum temperatures permissible for ­sensor / enclosure are not exceeded. (Ambient temperature for measuring transducer: - 30 ...+ 70 °C). Standard ranges: (stock items) TB 1 TB 2 TB 3 TB 10 - 50.......... + 50 °C 0.......... + 50 °C 0....... + 100 °C - 20....... + 150 °C Special ranges: TB 4 0....... + 200 °C TB 5 0....... + 300 °C TB 6 0....... + 400 °C TB 7 0....... + 500 °C TB 8 0....... + 600 °C TB 9 0....... + 700 °C TB 11 0....... + 150 °C Other temperature ranges arbitrary! Safety regulations: These devices shall only be used for their intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The buyer has to ensure adherence to the building and safety regu­lations and has to avoid all dangers of any kind. We do not assume any ­warranty for faults or damages arising or resulting from improper use of our equipment or from non-observance of operating instructions. These ­instruments must be installed by authorised specialists only! Preferably shielded cables should be used in order to prevent d­ amages/errors. It is imperative to avoid laying parallel with currentcarrying lines. EMC directives must be adhered to. Hinweise TH Installation scheme Length of stainless steel protective tube (mm) Length of Brass protective tube (mm) Permissible approach velocities (flow rates) for crosswise approached protective tubes in water. The protective tube is caused to vibrate by the a­ pproaching flow. If the specified approach velocity is exceeded even by a marginal amount, a negative influence on the lifetime of the protective tube may result (material fatigue). Please observe the permissible approach ­velocities for stainless steel protective tubes (see diagram TH-VA) as well as for brass ­protective tubes (see diagramTH-ms). Flow velocity (m/s) Information for planning and installation Gas discharges and pressure surge must be avoided as such have negative influence on ­lifetime or damage protective tubes. Devices are to be connected under dead-voltage condition. Devices must only be connected to safety extra-low voltage. Consequential damages caused by a fault in this device are excluded from warranty or liability. Installation of these devices must only be realized by authorized qualified personnel. The technical data and connecting conditions shown on the device labels and in the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products. In case of any modifications made by the user, all warranty claims are forfeited. Operating this device close to other devices that do not comply with EMC directives may influence functionality. This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes. Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these ­instructions. Modifications of these records are not permitted. In case of a complaint, only complete devices returned in original packing will be accepted. 3Notes regarding mechanical mounting and attachment: Before mounting, make sure the existing thermometer‘s technical parameters comply with the actual conditions at the place of utilization, in particular in respect of: - Measuring range - Permissible maximum pressure, flow velocity - Installation length, tube dimensions - Oscillations, vibrations, shocks are to be avoided (< 0.5 g) © Copyright by S+S Regeltechnik GmbH · Reprints, in part or in total, are only permitted with the approval of S+S Regeltechnik GmbH. 1362 III ⁄ 07 Mounting shall take place while observing all relevant regulations and standards applicable for the place of measurement (e.g. such as welding instructions, etc.). Particularly the following shall be regarded:- VDE/VDI directive technical temperature ­measurements, measurement set-up for temperature measurements. - The EMC directives must be adhered to. - It is imperative to avoid laying parallel with current-carrying lines. - We recommend to use shielded cables with the shielding being attached at one side to the DDC / PLC.