ETM 1 including brass immersion sleeve, nickel

advertisement
Operating instructions, mounting & installation
ETM 1 including brass immersion sleeve, nickel-plated Screw-in temperature measuring transducer, calibrateable
ETM 2 including stainless steel immersion sleeve Screw-in temperature measuring transducer, calibrateable
KTM 1 ncluding mounting flange Duct ⁄ air duct temperature measuring transducer, calibrateable
S+S REGELTECHNIK GMBH | KLINGENHOFSTR. 11 | 90411 NUREMBERG | GERMANY |
PHONE +49(0)911 ⁄ 51947-0 | FAX +49(0)911 ⁄ 51947-70 | www.S p lusS.eu | mail@SplusS.eu
Industry-oriented solutions – Complete control technology from one source!
ETM 1 including brass immersion sleeve, nickel-plated ETM 2 including stainless steel immersion sleeve
Screw-in temperature measuring transducer calibrateable, with active output
APPLICATION:
Calibrateable screw-in temperature measuring transducer with enclosure made of impact-resistant
plastic and straight protective tube for the detection of temperatures in liquid or gaseous media. For
aggressive media, stainless steel immersion sleeves shall be used. Applications in piping systems, in
heating technology, in storage tanks, in district heating compact stations, in hot and coldwater systems, in oil and lubricant circulation systems, in mechanical, apparatus and plant engineering as well
as in the entire industrial sector.
TECHNICAL DATA:
Power supply:................................... 24 V DC
ETM 1
Sensor:.............................................. Pt100, DIN EN 60751, class B
Measuring range:.. ........................... see table
Ambient temperature:.................... measuring transducer - 30...+ 70 °C
Connection type:.............................. 2- or 3-wire connection
Process connection:.. ...................... screwed socket with ½“ pipe thread Immersion sleeve:............................ ETM 1: brass, nickel-plated, ½“ pipe thread, wrench size 22 mm, Ø = 8 mm ETM 2: stainless steel, 1.4571, V4A, ½“ pipe thread, wrench size 27 mm, Ø = 8 mm
Protective tube:............................... stainless steel, 1.4571, V4A, Ø = 6 mm
Connecting head:............................. plastic, material polyamide, 30 % glass-globe-reinforced, with quick-locking screws, colour pure white (similar RAL 9010)
Dimensions:...................................... 72 x 64 x 39.4 mm
Cable union:...................................... M 16, including strain relief
Max. pressure:
ETM 1 brass immersion sleeves 10 bar ETM 2 stainless steel immersion sleeves 40 bar
Electrical connection:.. .................... 0.14 - 1.5 mm² via terminal screws on circuit board
Humidity:........................................... < 95 % r. H., non-precipitating air
ETM 2
Protection class:.. ............................ III (according to EN 60 730)
Protection type:............................... IP 65 (according to IEC 529)
Standards:........................................ CE conformity, electromagnetic compatibility according to EN 61 326 + A1 + A2, EMC directive 89 ⁄ 336 ⁄ EWG low-voltage directive 73 ⁄ 23 ⁄ EWG
Optional:............................................ 8-digit display, cutout 36 x14 mm (W x H), for displaying actual temperature Connecting diagram Whithout display
Output: 0 -10 V Connecting diagram Without display
Output: 4...20 mA
Connecting diagram Output: 0 -10 V With display
Connecting diagram Output: 4...20 mA
With display
ETM xx with display
ETM 1 ETM 2
Dimensional drawing
▲ ETM 2 ▲ ETM 1
Type ⁄ WG1
Output
50 mm
100 mm
150 mm
200 mm
250 mm
300 mm
ETM 1 - I
4...20 mA
•
•
•
•
•
•
ETM 1 - U
0 -10 V
•
•
•
•
•
•
ETM 1xx - Display Extra charge see pricelist
Other ranges upon request: e.g. TB1 (- 50 ...+ 50 °C), TB10; (- 20 ...+150 °C), and others upon request
Please indicate with your order:
Measuring range (TB…) and length of protective sleeve e.g. ETM 1 - U, TB 10 (- 20 ...+ 150 °C), 150 mm; ETM 1 - I, TB 3 (0 ...+100 °C), 300 mm
Type ⁄ WG1
Ausgang
50 mm
100 mm
150 mm
200 mm
250 mm
300 mm
ETM 2 - I
4...20 mA
•
•
•
•
•
•
ETM 2 - U
0 -10 V
•
•
•
•
•
•
ETM 2xx - Display Extra charge see pricelist
Other ranges upon request: e.g. TB1 (- 50 ...+ 50 °C), TB10; (- 20 ...+ 150 °C), and others upon request
Please indicate with your order:
Measuring range (TB…) and length of protective sleeve e.g. ETM 2 - U, TB 10 (- 20 ...+150 °C), 150 mm; ETM 2 - I, TB 3 (0 ...+100 °C), 300 mm
KTM 1 including mounting flange
Duct ⁄ air duct temperature measuring transducer calibrateable, with active output
KTM 1
APPLICATION:
Calibrateable duct temperature measuring transducer with connecting head made of impact­r esistant plastic and mounting flange. It is used for the detection of temperatures in gaseous media, e.g. in ventilation and air conditioning ducts.
TECHNICAL DATA:
Power supply:................................... 24 V DC
Sensor:.............................................. Pt100, DIN EN 60751, class B
Measuring range:.. ........................... TB3 (0...+ 100 °C)
Ambient temperature:.................... measuring transducer - 30...+ 70 °C
Connection type:.............................. 2- or 3-wire connection
Protective tube:............................... stainless steel, 1.4571, V4A, Ø = 6 mm, optional perorated, dimensions see table
Connecting head:............................. plastic, material polyamide, 30 % glass-globe-reinforced, with quick-locking screws, colour pure white (similar RAL 9010)
Dimensions:...................................... 72 x 64 x 39.4 mm
Cable union:...................................... M 16, including strain relief
Electrical connection:.. .................... 0.14 - 1.5 mm² via terminal screws on circuit board
Process connection:.. ...................... by mounting flange (included in the scope of delivery), plastic, (galvanised steel optional)
Humidity:........................................... < 95 % r. H., non-precipitating air
Protection class:.. ............................ III (according to EN 60 730)
Protection type:............................... IP 65 (according to IEC 529)
Standards:........................................ CE conformity, electromagnetic compatibility according to EN 61 326 + A1 + A2, EMC directive 89 ⁄ 336 ⁄ EWG low-voltage directive 73 ⁄ 23 ⁄ EWG
Optional:............................................ 8-digit display, cutout 36 x14 mm (W x H), for displaying actual temperature
Connecting diagram Without display
Output: 0 -10 V Connecting diagram Without display
Output: 4...20 mA
Connecting diagram Output: 0 -10 V With display
Connecting diagram Output: 4...20 mA
With display
KTM 1 with display
KTM 1
Dimensional drawing
Type ⁄ WG1
Ausgang
50 mm
100 mm
150 mm
200 mm
250 mm
300 mm
KTM 1- I
4...20 mA
•
•
•
•
•
•
KTM 1- U
0 -10 V
•
•
•
•
•
•
KTM 1xx - DisplayExtra charge see pricelist
Other ranges upon request: e.g. TB1 (- 50...+ 50 °C), TB10; (- 20...+ 150 °C), or others upon request
Please indicate with your order:
Measuring range (TB…) and length of protective sleeve e.g. KTM 1 - U, TB 10 (- 20...+ 150 °C), 150 mm; KTM 1 - I, TB 3 (0...+100 °C), 300 mm
Technical data
Supply voltage:
Connection scheme
Individual operation
Connection scheme
Parallel operation
For operating voltage reverse polarity protection, a one-way rectifier or
­r everse polarity protection diode is integrated in this device variant. This­ ­internal one-way rectifier also allows operating 0 - 10 V devices on AC
supply voltage.
The output signal is to be tapped by a measuring instrument. Output voltage is measured here against zero potential (0 V) of the input voltage!
When this device is operated on DC supply voltage, the operating voltage
input UB+ is to be used for 15...36 V DC supply and UB– or GND for
ground wire!
When several devices are supplied by one 24 V AC voltage supply, it is to
be ensured that all ”positive“ operating voltage input terminals (+) of the
field devices are connected with each other and all ”negative“ operating
voltage input terminals (–) (= reference potential) are connected together (in-phase connection of field devices). All outputs of field devices
must be referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short-circuit would be caused by that device. The consequential short-circuit current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!
Connecting conditions
Connecting diagram Output: 0 -10 V Without display
Connecting diagram Output: 4...20 mA
Without display
The output voltage follows linear to the temperature signal applied at
the input terminals and generates a proportional output signal of
0 - 10 V. The voltage outputs are short-circuit proof against ground
wire. Applying voltage supply to the output terminals will destroy the
device.
Connecting diagram Output: 0 -10 V With display
Connecting diagram Output: 4...20 mA
With display
In case of the 4...20 mA measuring transducer, display and evaluating
elements are connected in series in the current loop. The measuring
transducer thereby limits the flowing current in variance of the input
signal. 4 mA are for the measuring transducer‘s internal current consumption. The apparent ohmic resistance can either be connected in
the plus or minus path of the measuring transducer. In case of an apparent ohmic resistance in the plus path, power supply and resistance
must not share one ground wire.
Technical data
Temperature measuring transducer calibrateable with active output Output:.. ............................................ 4...20 mA
Connection:.. ..................................... 2-wire connection
Auxiliary energy: .. ............................ 14...35 V DC, supplied from 4...20 mA loop
EMC :.................................................. according to EN 61 326: 1997 + A1: 1998 + A2: 2001
Measuring element:......................... see table
Operating temperature:.................. transmitter - 30...+ 70 °C
Apparent ohmic resistance:.. ......... Ra (Ohm) = (Ub-14 V) ⁄ 0.02 A
Linearisation:.................................... temperature linear according to DIN IEC 751
Linearity error:................................. ± 0.6 % of the set range
Zero point drift:.. .............................. 0.6 % ⁄ 10 K
Voltage drift:.. ................................... 0.6 % ⁄ 10 K
Auxiliary energy flow:..............................0.02 % ⁄ V
Output:............................................. 0 - 10 V
Connection:.. ..................................... 3-wire connection
Auxiliary energy: . ............................ 24 V DC ± 6 V,
EMC :.................................................. according to EN 61 326: 1997 + A1: 1998 + A2: 2001
Measuring element::.. ...................... see table
Operating temperature:.................. transmitter - 30...+ 70 °C
Apparent power of voltage
transformer:.. ................................... minimum load resistance 3 kOhm
Linearisation:.................................... temperature linear according to DIN IEC 751
Linearity error:................................. ± 0.6 % of the set range
Zero point drift:.. .............................. 0.6 % ⁄ 10 K
Voltage drift:.. ................................... 0.6 % ⁄ 10 K
Auxiliary energy flow:.. ..................... 0.02 % ⁄ V
Apparent ohmic resistance = Voltage supply – internal current consumption (7,5 V)
20mA
TEMPERATURE RANGES::
When selecting measuring transducer ranges, it is necessary to
ensure that the maximum temperatures permissible for
­sensor / enclosure are not exceeded.
(Ambient temperature for measuring transducer: - 30 ...+ 70 °C).
Standard ranges:
(stock items) TB 1
TB 2
TB 3
TB 10
- 50.......... + 50 °C 0.......... + 50 °C 0....... + 100 °C - 20....... + 150 °C
Special ranges:
TB 4
0....... + 200 °C TB 5
0....... + 300 °C TB 6
0....... + 400 °C TB 7
0....... + 500 °C TB 8
0....... + 600 °C TB 9
0....... + 700 °C TB 11
0....... + 150 °C
Other temperature ranges arbitrary!
Safety regulations:
These devices shall only be used for their intended purpose. Respective
safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed.
The buyer has to ensure adherence to the building and safety regu­lations
and has to avoid all dangers of any kind. We do not assume any ­warranty
for faults or damages arising or resulting from improper use of our
equipment or from non-observance of operating instructions. These
­instruments must be installed by authorised specialists only!
Preferably shielded cables should be used in order to prevent
d­ amages/errors. It is imperative to avoid laying parallel with currentcarrying lines. EMC directives must be adhered to.
Hinweise
TH
Installation scheme
Length of stainless steel protective tube (mm)
Length of Brass protective tube (mm)
Permissible approach velocities (flow rates) for crosswise approached protective tubes in water.
The protective tube is caused to vibrate by the
a­ pproaching flow.
If the specified approach velocity is exceeded even by a
marginal amount, a negative influence on the lifetime of
the protective tube may result (material fatigue).
Please observe the permissible approach ­velocities for
stainless steel protective tubes (see diagram TH-VA) as
well as for brass ­protective tubes (see diagramTH-ms).
Flow velocity (m/s)
Information for planning and installation
Gas discharges and pressure surge must be avoided as such have negative influence on ­lifetime
or damage protective tubes.
Devices are to be connected under dead-voltage condition. Devices must only be connected to safety extra-low voltage. Consequential damages
caused by a fault in this device are excluded from warranty or liability. Installation of these devices must only be realized by authorized qualified
personnel. The technical data and connecting conditions shown on the device labels and in the mounting and operating instructions delivered
together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms
of technical progress and continuous improvement of our products. In case of any modifications made by the user, all warranty claims are forfeited.
Operating this device close to other devices that do not comply with EMC directives may influence functionality. This device must not be used for
monitoring applications, which solely serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for
systems or machinery, or for any other similar safety-relevant purposes.
Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these ­instructions. Modifications of these records are not permitted. In case of a complaint, only complete devices returned in original packing will be accepted.
3Notes regarding mechanical mounting and attachment:
Before mounting, make sure the existing thermometer‘s technical parameters comply with the actual conditions at the place of utilization, in
particular in respect of:
- Measuring range - Permissible maximum pressure, flow velocity - Installation length, tube dimensions - Oscillations, vibrations, shocks are to be avoided (< 0.5 g)
© Copyright by S+S Regeltechnik GmbH · Reprints, in part or in total, are only permitted with the approval of S+S Regeltechnik GmbH.
1362 III ⁄ 07 
Mounting shall take place while observing all relevant regulations and standards applicable for the place of measurement (e.g. such as welding
instructions, etc.). Particularly the following shall be regarded:- VDE/VDI directive technical temperature ­measurements, measurement set-up
for temperature measurements.
- The EMC directives must be adhered to.
- It is imperative to avoid laying parallel with current-carrying lines.
- We recommend to use shielded cables with the shielding being attached at one side to the DDC / PLC.