MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 SECTION 27 15 00 - COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.01 1.02 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. B. Specifications throughout all Divisions of the Project Manual are directly applicable to this Section, and this Section is directly applicable to them. SUMMARY A. Section Includes: 1. Horizontal Cabling Description. 2. Products. 3. Installation of Cables 1.03 REFERENCE STANDARDS A. 1.04 1.05 See Section 27 05 10 or 27 05 20. SCOPE OF WORK A. Add T-drawing numbers for Communication Design drawings B. Add scope of project. HORIZONTAL CABLING DESCRIPTION A. Horizontal cable and its connecting hardware provide the means of transporting signals between the telecommunications outlet/connector and the horizontal cross-connect located in the Telecommunication Room or Equipment Room. 1. Horizontal cabling shall contain no transition point or consolidation point between the horizontal cross-connect and the telecommunications outlet/connector. 2. Bridged taps and splices shall not be installed in the horizontal cabling. B. The maximum allowable horizontal cable length is 295 feet (90 m). This maximum allowable length does not include an allowance for the length of 16 feet (4.9 m) to the workstation equipment. The maximum allowable length does not include an allowance for the length of 16 feet (4.9 m) in the horizontal cross-connect. C. Color and cable type designations for UTP and F/UTP cable: 1. MD ANDERSON Owned Buildings: Data and Voice: UTP CAT6A, Blue 2. MD ANDERSON Leased Buildings: Data and Voice: UTP CAT6, Blue The University of Texas MD Anderson Cancer Center MS011210 COMMUNICATIONS HORIZONTAL CABLING 27 15 00 1 OF 8 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 3. Wireless Access Points (WAPS): CAT5E UTP, Orange 4. Kronos clocks and Omninotes: CAT5E UTP, Orange 5. Nurse Call System: Circulating loop between connections: CAT5e F/UTP, Purple 6. Nurse Call System: Dome light to patient room connections: CAT5e F/UTP, Green D. E. Color designation for UTP / F/UTP inserts: 1. Data, Voice, Security, Fire Alarm > White 2. PICIS > Green 3. Command Center > Purple 4. Physiological Monitoring > Blue 5. Anesthesiologist > Yellow 6. Refrigerator Monitoring > Red (Wall mount and modular furniture) Color designation for copper patch cords (defined per trade or service): 1. Data to the desktop: a. Network Services > Blue b. EMR > Yellow c. > Pink Hurricane Ride Out 2. WAPS, BAS, Patient Monitoring, Security > Blue with identifying label 3. Voice: a. Analog Line > Orange b. Digital Line > White c. > Red Special Circuit d. VoIP F. > White Color designation for fiber patch cords 1. Single Mode 8.3 micron > Yellow 2. Multi Mode 62.5 micron > Orange 3. Multi Mode 50 micron 1GB > Orange 4. Multi Mode 50 micron 10GB > Aqua The University of Texas MD Anderson Cancer Center MS011210 COMMUNICATIONS HORIZONTAL CABLING 27 15 00 2 OF 8 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 PART 2 - PRODUCTS 2.01 2.02 GENERAL A. All materials shall meet or exceed all applicable referenced standards, federal, state and local requirements, and conform to codes and ordinances of authorities having jurisdiction. B. Cables shall be terminated with connecting hardware of same category or higher. MANUFACTURER HORIZONTAL CABLING A. The system must be a manufacturer certified System. B. The following manufacturers are approved: 1. CAT6A UTP: Siemon 2. CAT6 UTP, CAT5e UTP, CAT5e F/UTP: Siemon, Berk-Tek, General Cable, Mohawk, Superior Essex (for cable only, not for other hardware) 2.03 UTP CABLE A. Data UTP Cable (Siemon part numbers are listed as reference of performance if other manufacturer is chosen and approved by Owner and Siemon): 1. Category 5E UTP a. Siemon #9C5R4-E2-02-RBA. Cat5E Non-Plenum, white. b. Siemon #9C5P4-E2-02-RBA. Cat5E Plenum, white. 2. Category 5E F/UTP a. Siemon #9A5R4-E1-09-R1A. Cat5E Non-Plenum, orange. b. Siemon #9A5P4-E1-09-R1A. Cat5E Plenum, orange. 3. Category 6 UTP a. Siemon #9C6R4-E3-06-RXA. Cat6 Non-Plenum, blue. b. Siemon #9C6P4-E3-06-RXA. Cat6 Plenum, blue. 4. Category 6A UTP a. Siemon #9C6R4-A5-06-R1A. Cat6A Non-Plenum, blue. b. Siemon #9C6P4-A5-06-R1A. Cat6A Plenum, blue. 2.04 UTP CABLE HARDWARE A. All icons on insert will show computer icon. B. Category 6A – Fixed wall locations and Modular Furniture 1. Siemon Faceplate– The University of Texas MD Anderson Cancer Center MS011210 COMMUNICATIONS HORIZONTAL CABLING 27 15 00 3 OF 8 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 a. White 1-port; Part Number 10GMX-FPS01-02 b. White 2-port; Part Number 10GMX-FPS02-02 c. White 4-port; Part Number 10GMX-FPD04-02 d. White 6-port; Part Number 10GMX-FPD06-02 e. White 8-port: Part Number 10GMX-FPD08-02 2. Siemon Connector - Part Number 10GMX-02. White, angled. 3. Siemon Blank – Part Number MX-BL-02. White. C. Category 6 – Fixed wall locations and Modular Furniture 1. Siemon Faceplate a. White, 1-port; Part Number MX-FP-S-01-02 b. White, 2-port; Part Number MX-FP-S-02-02 c. White, 3-port; Part Number MX-FP-S-03-02 d. White, 4-port; Part Number MX-FP-S-04-02 e. White, 6-port; Part Number MX-FP-S-06-02 f. White, 8-port; Part Number MX-FP-D-08-02 g. White, dual-gang 6-port; Part Number MX-FP-D-06-02 h. White, dual-gang 8-port; Part Number MX-FP-D-08-02 i. White, dual-gang 12-port; Part Number MX-FP-D-12-02 2. Siemon Connector - Part Number MX6-02. White, angled. 3. Siemon Blank – Part Number MX-BL-02. White. D. Category 5E – Fixed wall locations and Modular Furniture 1. Siemon Faceplate a. White, 1-port: Part Number MX-S-01-02 b. White, 2-port; Part Number MX-FP-S-02-02 c. White, 3-port; Part Number MX-FP-S-03-02 d. White 4-port; Part Number MX-FP-S-04-02 e. White, 6-port; Part Number MX-FP-S-06-02 f. White, dual-gang 6-port; Part Number MX-FP-D-06-02 g. White, dual-gang 8-port; Part Number MX-FP-D-08-02 The University of Texas MD Anderson Cancer Center MS011210 COMMUNICATIONS HORIZONTAL CABLING 27 15 00 4 OF 8 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 h. White, dual-gang 12-port; Part Number MX-FP-D-12-02 2. Siemon Connector - Part Number MX5-02. White, angled. 3. Siemon Blank – Part Number MX-BL-02. White. E. Laboratory & Ceiling locations. 1. Siemon Faceplate a. 1-port - Part Number MX-FP-S-01-SS-L b. 2-port - Part Number MX-FP-S-02-SS-L c. 3-port - Part Number MX-FP-03-SS-L d. 4-port - Part Number MX-FP-04-SS-L e. 6-port - Part Number MX-FP-06-SS-L 2. Siemon Blank – Part Number MX-BL-04, Gray. 3. For Category 6A applications, use MX-FP-03-SS-L with a single MX-BL-04 blank for a duplex outlet. Use MX-FP-06-SS-L with two MX-BL-04 blanks for a quad outlet. 4. Harsh Environment/Industrial locations. a. Category 5E 1) Siemon Connector – Part Number X5. 2) Siemon Faceplate a) 1-port - Part Number XFP-S-01-SS b) 2-port- Part Number XFP-S-02-SS c) 4-port- Part Number XFP-D-04-SS 3) Siemon Connector Cap – Part Number X-CAP. 4) Siemon Cord – Part Number XC5-XX, XX=length in feet b. Category 6 1) Siemon Connector – Part Number X6 2) Siemon Faceplate a) 1-port - Part Number XFP-S-01-SS b) 2-port; Part Number XFP-S-02-SS c) 4-port, Part Number XFP-D-04-SS 3) Siemon Connector Cap – Part Number X-CAP. The University of Texas MD Anderson Cancer Center MS011210 COMMUNICATIONS HORIZONTAL CABLING 27 15 00 5 OF 8 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 4) Siemon Cord – Part Number XC6-XX, XX=length in feet c. NEMA 4x Surface-mount Box 1) Siemon Surface-mount Box – Part Number X-IBOX-01 a) Part Number X-IBOX-02 b) Part Number X-IBOX-03 c) Part Number X-IBOX-04. 2) Siemon Bulkhead Connector – Part Number X5-X5S. F. In the communications rooms, horizontal voice and data cables will terminate on RJ45 Patch Panels. 1. Category 6A a. Siemon #Z6A-PNL-48K b. Siemon #Z6A-PLNA-24K (Angled) 2. Category 6 a. Siemon #HD6-48 3. Category 5E a. Siemon #HD5-48 G. For single wall phones: 1. Category 6: a. Siemon Faceplate – Part Number MX-WP-(K6)-SS 2. Category 5E: a. Siemon Faceplate – Part Number MX-WP-(K5)-SS PART 3 - EXECUTION 3.01 GENERAL A. Installation shall meet or exceed all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of authorities having jurisdiction. B. All installation shall be in accordance with manufacturer’s published recommendations. C. Horizontal UTP and F/UTP cable must be terminated using 8-conductor, 8-position connectors. The pin/pair assignment will be T568B. Use color matching icon. D. Install plenum cable in environmental air spaces, including plenum ceilings. E. Non-Plenum cable may only be used after a formal written approval by the Owner. The University of Texas MD Anderson Cancer Center MS011210 COMMUNICATIONS HORIZONTAL CABLING 27 15 00 6 OF 8 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 3.02 COORDINATION A. 3.03 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 Coordinate telecommunications outlet/connector locations with location of power receptacles at each work area with General Contractor/Owner. The telecommunications outlet/connector shall be close proximity to the power receptacles in each work area. INSTALLATION OF CABLES A. General Requirements for Cabling: 1. MUTOA shall not be used. 2. Terminate conductors; no cable shall contain un-terminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels. 3. Cables may not be spliced. Secure and support cables at intervals not exceeding 5 ft. and not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals. 4. Install lacing bars to restrain cables, to prevent straining connections consistently, and to prevent bending cables to smaller radii than minimums recommended by manufacturer. 5. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii. 6. Use Velcro tie wraps. 7. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable. 8. Cold-Weather Installation: Follow manufacturer specifications for installation and storage temperatures. Heat lamps shall not be used for heating. 9. Outlet boxes shall be assembled as follows: a. Depth: 3.26 inches. b. Height: 4.16 inches. c. B. Width: 3.51 inches. UTP / F/UTP Cable Installation: 1. Do not untwist UTP / F/UTP cables more than 1/2 inch from the point of termination to maintain cable geometry. C. Optical Fiber Cable Installation: 1. Cable may be terminated on connecting hardware that is rack or cabinet mounted. D. Open-Cable Installation: 1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment. The University of Texas MD Anderson Cancer Center MS011210 COMMUNICATIONS HORIZONTAL CABLING 27 15 00 7 OF 8 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 2. Suspend UTP cable independently from “Other Trades” and not in a wire way or pathway a minimum of 8 inches above ceilings by cable supports not more than 60 inches apart. 3. Cable shall not be run through or supported from structural members or in contact with pipes, ducts, or other potentially damaging items. E. Group connecting hardware for cables into separate logical fields. END OF SECTION 27 15 00 The University of Texas MD Anderson Cancer Center MS011210 COMMUNICATIONS HORIZONTAL CABLING 27 15 00 8 OF 8