Scientific Research Journal (SCIRJ), Volume III, Issue IX, September 2015 ISSN 2201-2796 1 Evaluation of Percentage Wasted Power in Electrical Loads with Constructed Power Factor Correction Equipment Afolabi O.M Department of Physics & Electronics Adekunle Ajasin University Akungba Akoko Nigeria Abstract- Fixed capacitive low power factor correction measurements was done to calculate percentage wasted power. The output of the nine operational amplifier voltage comparator controlled stabilizer was connected to a fixed CBB61; 450V 2uF AC run capacitor unto which each load was connected and computation of apparent power, power factor and percentage wasted power were made. It was found that very high percentage of required real power was wasted when power factor was uncorrected in electrical appliances studied. 52% of power was wasted in three laptops combination that reduced to 8.6% after CPF compare to 36.5% when 3 loads comprising of a laptop, printer and electric fan was used that was reduced to 3.3%. Minimum power was wasted in Philips Elance 3100, Electric iron with 32.3% when the power factor was uncorrected and 3.2% when power factor was corrected. IndexTerms—Electrical Power, loads, Percentage Wasted Power, Required. Power factor, I. INTRODUCTION Electrical distribution is in the form of a low frequency high voltage and low current to save cost incurred in conducting and insulating materials; to reduced overheating of cables and for ease of transformation from high to low voltage required at the consumer points. Alternating current systems supply two forms of energy: Real energy measured in kilowatt hours (kWh) which is converted into mechanical work, heat, light, etc and Reactive energy needed to generate magnetic fields by inductive circuits (transformers, motors, cables, refrigerators, inverters discharge lamps (with magnetic ballasts) etc.), Schneider Electric, 2008, Sugawara et al., 2007. In industries, Low power factor results when inactive motors are operated at less than full load. This often occurs in cycle processes occurring in circular saws, mills, conveyors, compressors, Grinders and punch presses, www.eaton.com, 2014. Low power factor is easily corrected by adding, in parallel to load, a capacitive reactance that acts in opposite sign as the load’s inductive reactance. Low power factor input in distribution systems causes power losses in transmission and distribution systems by heating the conductors, ON Semiconductor 2007. The combination of inductive reactance in transmission and distribution systems and that of consumer loads produces the worst possible conditions of low power factor. Power factor correction capacitors reduce the (inductive) reactive current in upstream conductors, thereby reducing or eliminating voltage drops (electroschematics, 2015; fairchildsemi, 2015). By improving the power factor of a load supplied from a transformer, (a) the current or power through the transformer will be reduced, thereby allowing more load to be added (it is cheaper to improve the power of transformer than to replace it with a bigger one), (b) the excess bill or penalties for excessive consumption of reactive power is reduced because the apparent power kVA demand, on which standing charges are usually based is reduced, (c ) the size of the cables supplying the local distribution boards is reduced and the cables have additional capacity for possible load increases, (c) heat losses in cables, transformers and loads will be reduced and they will have longer lifespan. From the power triangle (Fig.1) the bigger the reactive power component, the higher is the power factor of the circuit kVAR = kVAsinθ……………………………….…1 but kW kVA = ………………………………….…………2 Cos θ kWSinθ kVA = = kWtanθ……………………………….3 Cos θ The lower the power factor (cosθ ) the more the apparent power(kVA) or electrical bill. kVA2 = kW2 + kVAR2………….…………………4 For an electrical appliance with the power factor corrected, the apparent power is reduced since real power (kW) is fixed then the reactive power is reduced hence apparent power is affected by the reactive power (see equation 4). www.scirj.org © 2015, Scientific Research Journal Scientific Research Journal (SCIRJ), Volume III, Issue IX, September 2015 ISSN 2201-2796 2 kW π2 kVAR2 π1 kVA2 kVA1 kVAR1 Fig. 1: Increase in kVA2,kVAR2 and ππ due to induction sources A constructed stabilized power factor corrected and current voltage measuring equipment with ability to measure input voltage and output voltage and current (see Fig. 2) was used for 2uF 400V output port VO GND VI R9 2 15k R11 C4 100uF U1:A 10k V AC Volts 3 8 AMMETER D4 +88.8 RV1 3 1 2 Q1 R5 BD139 10k R1 4 96% TRAN-2P2S D1 10k LM393 50k 7 Q2 R6 BD139 10k R2 4 37% 6 10k LM393 50k D2 QUAZ-SH-105D 1 2 50% RL3 1nF 3 BD139 10k 10k 4 10k Q7 5 7 10k 6 Q4 R8 BD139 4 R4 L1 10k LM393 D5 3 1 D6 5 BD139 7 50% 6 RL2 L2 1nF Q6 R18 BD139 10k R13 10k 4 10k D8 LM393 50k DIODE 8 U5:B RV7 5 7 6 Q8 R19 BD139 10k R16 4 50k C6 DIODE 8 RV6 Q9 R10 4 10k U4:B 1 LM393 BD139 R12 LM393 50k 50% 10k 1mH 10k 8 R20 QUAZ-SH-105D Q5 R17 4 37% 2 U6:A 2 RL1 1nF 8 RV5 QUAZ-SH-105D C5 DIODE U4:A 3 1nF 10k 50k RL5 C3 DIODE U2:B RV4 50% 4 D3 LM393 50k BD139 R14 LM393 R3 8 R15 2 Q3 R7 8 3 1 51% C7 L3 1nF 8 RV3 DIODE C2 DIODE U2:A D7 1nF 8 5 U5:A C1 DIODE U1:B RV2 70% VOLTMETER +88.8 AC Amps +88.8 AC Amps 7812 TR1 1k +88.8 AC Volts U3 1 DIODE ADE AMMETER II. MATERIAL AND METHOD VOLTMETER the data collection in eleven electrical loads. The output of the stabilizer is connected to a CBB61; 450V 2uF AC run capacitor unto which each load was connected and computation of apparent power, power factor and percentage wasted power with and without the correction was done. LM393 10k Fig. 2 Stabilized power factor measuring circuit www.scirj.org © 2015, Scientific Research Journal C8 RL4 1nF QUAZ-SH-105D L4 Scientific Research Journal (SCIRJ), Volume III, Issue IX, September 2015 ISSN 2201-2796 3 III. RESULT AND DISCUSSION Tables 1 and 2 show the measurement of voltage and current for corrected power factor (CPF) and uncorrected power factor (UPF). The voltages and current in uncorrected power factor are higher than when they are corrected; this resulted in more apparent power (see Tables 3) Table 1: Stabilized Output Voltage and Load Current without Power Factor Correction S/N LOAD INPUT VOLTAGE (V) STABILIZED OUTPUT VOLTAGE (V) 250.0 LOAD CURRENT (A) 4.80 1 Sharp air conditioner 230 2 Haier thermocool refrigerator HRF250DX 230.0 245.0 2.00 3 Hand hair dryer 230.0 245.0 5.00 4 Electric iron 225.0 245.0 10.80 5 Electric clipper 230.0 240.0 0.06 6 Electric stove 230.0 240.0 5.80 7 Electric fan 18” century product 230.0 240.0 0.60 8 Hp pavilion DV600 and Acer V5series laptops 230.0 240.0 0.80 9 Hp pavilion DV600, Hp 630 and Acer laptops 230.0 240.0 1.40 Acer laptop V5series, hp printer P1102 and Century fan 18” 230.0 245.0 4.40 230.0 240.0 6.00 10 11 Battery charger Table 2: Stabilized Output Voltage and Load Current with Power Factor Correction. S/N LOAD 1 Sharp air conditioner 2 Haier thermocool HRF250DX INPUT VOLTAGE (V) refrigerator STABILIZED OUTPUT VOLTAGE(V) LOAD CURRENT (A) 230.0 240.0 4.20 230.0 240.0 1.60 3 Hand hair dryer 230.0 240.0 4.00 4 Electric iron 230.0 240.0 8.60 5 Electric clipper 230.0 240.0 0.05 www.scirj.org © 2015, Scientific Research Journal Scientific Research Journal (SCIRJ), Volume III, Issue IX, September 2015 ISSN 2201-2796 6 Electric stove 230.0 240.0 4.40 7 Electric Century fan 18” 230.0 240.0 0.50 230.0 240.0 0.60 230.0 240.0 1.00 230.0 240.0 3.40 230.0 240.0 4.40 8 9 10 4 Hp pavilion DV600 and Acer V5series laptops Hp pavilion DV600, Hp 630 and Acer laptops Acer laptop V5series, hp printer P1102 and Century fan 18” 11 Battery charger Table 3: Loads’ Real Power and Computed Apparent Power for CPF and UPF S/N STABILIZED AND CORRECTED POWER FACTOR APPARENT POWER (VA) 1008.0 STABILIZED AND UNCORRECTED POWER FACTOR APPARENT POWER (VA) 1200.0 Sharp air conditioner 900 2 Haier thermocool refrigerator HRF250DX 360 384.0 490.0 3 Hand hair dryer (Bestside RCE 2300) 900 960.0 1225.0 4 Electric iron (Philips Elance 3100) 2000 2064.0 2646.0 5 Electric clipper (Kinsclip NC-222) 10 12.0 14.40 6 Electric stove 1000 1056.0 1392.0 7 Electric fan 18” century product 100 120.0 144.0 131 144.0 192.0 221 240.0 336.0 790 816.0 1078.0 1000 1056.0 1440.0 9 11 REAL POWER (W) 1 8 10 LOAD Hp pavilion DV600 and Acer V5series laptops Hp pavilion DV600, Hp 630 and Acer laptops Acer laptop V5series, hp printer P1102 and Century fan 18” Battery charger www.scirj.org © 2015, Scientific Research Journal Scientific Research Journal (SCIRJ), Volume III, Issue IX, September 2015 ISSN 2201-2796 5 Table 4: Percentage Wasted Power for Corrected and Uncorrected Power factor S/N LOAD WAS TED POWER WITH NO PFC (VA) WAS TED POWER WITH PFC (VA) PERCENTA GE WASTED POWER WITH NO PFC (%) PERCENTA GE WASTED POWER WITH PFC (%) 1 Sharp air conditioner 300 108 33.3 12 2 Haier thermocool refrigerator HRF250DX Hand hair dryer (Bestside RCE 2300) 130 24 36.1 6.7 325 60 36.1 6.7 4 Electric iron (Philips Elance 3100) 646 64 32.3 3.2 5 Electric clipper (Kinsclip NC-222) 4.4 2 44 20 6 Electric stove 392 56 39.2 5.6 7 Electric fan 18” century product Hp pavilion DV600 and Acer V5series laptops Hp pavilion DV600, Hp 630 and Acer laptops 44 20 44 20 61 13 46.6 9.9 115 19 52.0 8.6 3 8 9 www.scirj.org © 2015, Scientific Research Journal Scientific Research Journal (SCIRJ), Volume III, Issue IX, September 2015 ISSN 2201-2796 6 10 Acer laptop V5series, hp printer P1102 and Century fan 18” 288 26 36.5 3.3 11 Battery charger 440 56 44 5.6 Table 4 and Figure 3 show that very high percentage of required real power is wasted when power factor is uncorrected. 52% of power is wasted in three laptops combination that reduced to 8.6% after CPF compare to 36.5% when 3 loads comprising of a laptop, printer and electric fan was used that was reduced to 3.3% and 46.6% that reduced to 9.9% after CPF when two laptops, Hp pavilion DV600 and Acer V5series laptops were used. Minimum power was wasted in Philips Elance 3100, Electric iron with 32.3% when the power factor was uncorrected and 3.2% when power factor was corrected. The highest wasted power after correction of power factor is in Century 18” Electric fan and Kinsclip NC-222 Electric clipper with similar 20% wasted power and corresponding 44% uncorrected wasted power. 60 50 40 PERCENTAGE WASTED POWER WITH NO PFC (%) 30 PERCENTAGE WASTED POWER WITH PFC (%) 20 10 0 1 2 3 4 5 6 7 8 9 10 11 Fig. 3: Percentage wasted power in electrical loads IV. CONCLUSION REFERENCES A stabilized power factor corrected and current voltage measuring equipment useful to evaluate power factor was designed and constructed. It was found that more voltage and current were consumed when power factor was not corrected resulting in more percentage of real power being wasted. The corrected power factor reduced the apparent power needed for the loads to operate this will reduce electrical power wasted as heat with lower electrical bill, reactive power penalties and a longer lasting electrical distribution system and consumer appliances. [1] ON Semiconductor, 2007. Power Factor Correction Handbook (PDF). [2] Schneider Electric - Electrical installation guide 2008 Power factor correction and harmonic ο¬ltering. [3] Sugawara, I.; Suzuki, Y.; Takeuchi, A.; Teshima, T. (19–23 Oct 1997), "Experimental studies on active and passive PFC circuits", INTELEC 97, 19th International Telecommunications Energy Conference, pp. 571–78, doi:10.1109/INTLEC.1997.646051. [4] www.eaton.com,2014. Power factor correction: a guide for the plant engineer www.scirj.org © 2015, Scientific Research Journal Scientific Research Journal (SCIRJ), Volume III, Issue IX, September 2015 ISSN 2201-2796 Technical Data SA02607001E. [5] www.electroschematics.com/5726/power-factor-correction/ accessed August 2015. 7 [6] www.fairchildsemi.com, 2004. Application Note 42047 Power Factor Correction (PFC) Basics www.scirj.org © 2015, Scientific Research Journal