On/Off, PWM & 0-10 VDC Globe Valve Actuators Specifications subject to change without notice. | USA 110526 | Page 1 of 4 DESCRIPTION MVX / MVR Electro-thermal, bidirectional, zone globe valve actuators with normallyopen or normally-closed fail-safe control providing completely silent, maintenance-free operation. Available with on/off, pulse width modulation (PWM) or 0-10 VDC modulating control signal input. Compatible with VSX (2-way) and VMX (3-way) ½” and ¾” zone globe valve bodies. APPLICATION For the actuation of chilled and hot water valves on fan coil units, reheating of variable air volume (VAV) or variable volume & temperature (VVT) boxes, base boards, and other A/C units. The silent operation and dampened response of these electro-thermal actuators make them superior for spaces with low ambient noise and gradual heating/cooling load changes. MVX MVR FEATURES • • • • • • Pop-on, direct-coupled, tool-less installation • On/Off or PWM • 0-10 VDC • 24 VAC or 110...230 VAC Power Input Signal Spring return: NO or NC Optional aux. switch Compact size, noiseless Maintenance free Two-year warranty Aux. Switch*** Spring Return** No N.C. No Yes No Yes N.O. No N.C. On/Off or PWM* 24 VAC On/Off 110...230 VAC 24 VAC 0-10 VDC, proportional On/Off or PWM* On/Off 24 VAC 110...230 VAC On/Off or PWM* 24 VAC On/Off 110...230 VAC 0-10 VDC, proportional 24 VAC * ** ** *** Part Numbers MVX 41 MVX 21 MVX 57 MVR 24V MVR 24MV MVR 230V MVR 230MV MVX 42 MVX 22 MVX 52 certified ISO 9000 MVX57/52 Valve Compatibility VSX / VMX ½” : Cv 0.29, Cv 0.47, Cv 0.7, Cv 1.16, Cv 1.87 VSX / VMX ¾” : Cv 2.92 VSX / VMX ¾” : Cv 4.67, Cv 7.00 PWM = Pulse Width Modulating N.C. = Spring return normally closed position w/o power N.O. = Spring return normally open position w/o power Auxillary switch, SPST, 2(0.1) A, 250 VAC SPECIFICATIONS Control Input signal Electrical Power supply Frequency Power consumption Integral cable Refer to table above Refer to table above 50/60 Hz Refer to table on page 2 6’ (MVX); 2’ (MVR) Performance Actuator type Electro-thermal (PTC thermistor heats thermostatic element and moves piston/stem downwards, valve spring moves stem/piston upwards) 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols MVX / MVR Specifications subject to change without notice. | USA 110526 | Page 2 of 4 SPECIFICATIONS Performance (cont...) Positioning force - MVX, MVR - MVX 22, 42, 52 Stroke time Noise level - actuating and spring return Environmental Working temperature Working humidity Storage temperature 20.2 lbf (90 N) (Cv 2.92) 31.5 lbf (140 N) (Cv 4.67) Refer to table and diagram on pg. 2 0 db (A), silent 36°F...122°F (2°C...50°C) 5...95% RH, non-condensing 14°F...140°F (-10°C...60°C) Power Consumption MVX 41 MVX 42 MVR24V MVR24MV Actuator MVX 21 MVX 22 MVR230V MVR230MV MVX 57 MVX 52 24 VAC Input power 110 VAC 230 VAC On/Off or PWM 0-10 VDC On/Off only Control Consumption Operating Inrush 1.8 VA 5.0 VA 1.8 VA 4.0 VA 1.8 VA 12.0 VA 1.8 VA 50.0 VA Physical Enclosure - cover (top) material - base material - color MVX 21/41 MVX 22/42 MVX 57 MVX 52 MVR.V - protection Fire retardant, UL94-V0 PA6 PP Black Blue Black/clear Blue/clear Beige NEMA 2 (IP 44), conforms to IES 730-1 (93)/6.5.3 II (CEI 107-10) Horizontal or vertical, avoid actuator pointing downwards - protection class Mounting position Wire Connection -MVX series -MVR series 6.5 ft (2.0 m) 2.1 ft (0.6 m) color-coded appliance cable 21 AWG (0.35 mm2) See table below See table below Wire size Dimensions Weight Valve Body Compatibilities Valve Coupling VSX, VMX valve series Threaded, knurled ring nut, tool-less, pop-on hand connection ISO 9000 certified CE EMC 2004/108/CE directive, EN 61010-1 standard LVD 2006/95/CE directive, EN 61010-1 standard for MVX 21/22 actuators Two-year material and workmanship Manufacturing Listings/Approvals Conformity Actuator, full stem stroke time (approx.) Cold start: Actuator Opening Dead MVX41/42 MVX57/52 MVR24V MVX21/22 MVR230 Total After powered on for: > 5 min > 30 min Closing Closing Dead Total Dead Warranty Total 24 2 min 5 min 2 min 6 min 2 min 6 min VAC 30 sec 50 sec 20 sec 30 sec 30 sec 40 sec Outside Dimensions, Inch (mm) 110 1 min 6 min 1min 5 min 1min 5 min VAC 40 sec 20 sec 20 sec 30 sec 20 sec 30 sec A B Actuator MVX 41/21/42/22 1.63 (41.5) 2.1 (52.0) 1.63 (41.5) 2.7 (68.0) MVX 57/52 1.52 (38.5) 2.8 (70.0) MVR 230 1min 3 min 2 min 6 min 2 min 6 min VAC 20 sec 50 sec 20 sec 30 sec 30 sec 40 sec Stroke Opening/closing times Open (valve stem down) Closed valve stem up lbs (kg) 0.37 (0.17) 0.44 (0.19) 0.31 (0.14) A A A NC Power Weight On Dead time Dead time Total opening time Total closing time B B B Off Time MVX41/21/42/22 MVX57/52 MVR 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols MVX / MVR Specifications subject to change without notice. | USA 110526 | Page 3 of 4 WIRING CONFIGURATION The MVX and MVR are equipped with one (1) color-coded pigtail cable MVX 41 MVX 42 MVR 24V On/off or pulse width modulating control MVX 41/42/21/22 MVX 24V/230V blue (ble) brown (brn) ble brn ble brn Power & Control Line L1 Volts L2 MVR 24MV/230MV 24 VAC Transformer Power & Control blue (ble) brown (brn) black (blk) black (blk) Aux. Switch, SPST 250 VAC, 2(0.1) A MVX 21 MVX 22 MVR 230V On/Off control MVX 57/52 white (wht) brown (brn) green (grn) Common < 24 VAC < Control signal, 0-10 VDC Line L1 Volts L2 MVX 52 MVX 57 Modulating control 110...230 VAC com wht + ~ brn Y grn (+) (–) Line L2 Control Signal 0-10 VDC MVR 24MV On/off or pulse width modulating control with auxillary switch ble Volts L1 brn blk blk 24 VAC Transformer Line L1 Notes: • • • • Volts L2 Wire connections on 2-wire actuators are interchangeable. 24 VAC Transformer Do not supply power to the actuator unless the actuator has been coupled to the valve body appropriately. Auxillary Switch, 2.0(0.1) A, 250 VAC Actuator will be damaged if 110...230 VAC is applied to the 24 VAC actuator. Be patient; it may take several minutes to stroke 100% from a cold start. (see the Actuator, full stem stroke time table on pg. 2) Actuator stroke direction, valve position MVX... MVX57/52 MVR... On/Off 0-10 VDC On/Off Aux. Switch Valve stem moves... SPST Power/Control on down down up Valve ports A to AB opens opens closes up up down closes opens Power/Control off MVR 230MV On/off control with auxillary switch Valve ports A to AB closes contacts open contacts close ble brn blk blk Line L1 Volts L2 110...230 VAC Auxillary Switch, 2.0(0.1) A, 250 VAC 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols MVX / MVR Specifications subject to change without notice. | USA 110526 | Page 4 of 4 MANUAL OVERRIDE COUPLING TO THE VALVE BODY VXC-CAP Ensure the actuator piston/stem is lined up with the actuator mounting neck. Screw the actuator’s knurled ring nut (M30 x 1.5 mm) onto the threaded neck portion of the valve body by hand only. Manual override cap Screw the override cap onto the threaded neck portion of the valve body, and stroke down the valve stem into any partial or fully open position. • Allowable mounting position 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols