On/Off, PWM & 0-10 VDC Globe Valve Actuators
Specifications subject to change without notice. | USA 110526 | Page 1 of 4
DESCRIPTION
MVX / MVR
Electro-thermal, bidirectional, zone globe valve actuators with normallyopen or normally-closed fail-safe control providing completely silent,
maintenance-free operation. Available with on/off, pulse width modulation
(PWM) or 0-10 VDC modulating control signal input. Compatible with
VSX (2-way) and VMX (3-way) ½” and ¾” zone globe valve bodies.
APPLICATION
For the actuation of chilled and hot water valves on fan coil units, reheating
of variable air volume (VAV) or variable volume & temperature (VVT) boxes,
base boards, and other A/C units. The silent operation and dampened
response of these electro-thermal actuators make them superior for spaces
with low ambient noise and gradual heating/cooling load changes.
MVX
MVR
FEATURES
•
•
•
•
•
• Pop-on, direct-coupled,
tool-less installation
• On/Off or PWM
• 0-10 VDC
• 24 VAC or 110...230 VAC
Power
Input Signal
Spring return: NO or NC
Optional aux. switch
Compact size, noiseless
Maintenance free
Two-year warranty
Aux.
Switch***
Spring
Return**
No
N.C.
No
Yes
No
Yes
N.O.
No
N.C.
On/Off or PWM*
24 VAC
On/Off
110...230 VAC
24 VAC
0-10 VDC, proportional
On/Off or PWM*
On/Off
24 VAC
110...230 VAC
On/Off or PWM*
24 VAC
On/Off
110...230 VAC
0-10 VDC, proportional
24 VAC
*
**
**
***
Part Numbers
MVX 41
MVX 21
MVX 57
MVR 24V
MVR 24MV
MVR 230V
MVR 230MV
MVX 42
MVX 22
MVX 52
certified
ISO 9000
MVX57/52
Valve
Compatibility
VSX / VMX ½” :
Cv 0.29, Cv 0.47,
Cv 0.7, Cv 1.16, Cv 1.87
VSX / VMX ¾” :
Cv 2.92
VSX / VMX ¾” :
Cv 4.67, Cv 7.00
PWM = Pulse Width Modulating
N.C. = Spring return normally closed position w/o power
N.O. = Spring return normally open position w/o power
Auxillary switch, SPST, 2(0.1) A, 250 VAC
SPECIFICATIONS
Control
Input signal
Electrical
Power supply
Frequency
Power consumption
Integral cable
Refer to table above
Refer to table above
50/60 Hz
Refer to table on page 2
6’ (MVX); 2’ (MVR)
Performance
Actuator type
Electro-thermal
(PTC thermistor heats thermostatic
element and moves piston/stem
downwards, valve spring moves
stem/piston upwards)
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
MVX / MVR
Specifications subject to change without notice. | USA 110526 | Page 2 of 4
SPECIFICATIONS
Performance (cont...)
Positioning force
- MVX, MVR
- MVX 22, 42, 52
Stroke time
Noise level
- actuating and
spring return
Environmental
Working temperature
Working humidity
Storage temperature
20.2 lbf (90 N) (Cv  2.92)
31.5 lbf (140 N) (Cv  4.67)
Refer to table and diagram on pg. 2
0 db (A), silent
36°F...122°F (2°C...50°C)
5...95% RH, non-condensing
14°F...140°F (-10°C...60°C)
Power Consumption
MVX 41
MVX 42
MVR24V
MVR24MV
Actuator
MVX 21
MVX 22
MVR230V
MVR230MV
MVX 57
MVX 52
24 VAC
Input power
110 VAC 230 VAC
On/Off or PWM 0-10 VDC
On/Off only
Control
Consumption
Operating
Inrush
1.8 VA
5.0 VA
1.8 VA
4.0 VA
1.8 VA
12.0 VA
1.8 VA
50.0 VA
Physical
Enclosure
- cover (top) material
- base material
- color
MVX 21/41
MVX 22/42
MVX 57
MVX 52
MVR.V
- protection
Fire retardant, UL94-V0
PA6
PP
Black
Blue
Black/clear
Blue/clear
Beige
NEMA 2 (IP 44),
conforms to IES 730-1 (93)/6.5.3
II (CEI 107-10)
Horizontal or vertical, avoid
actuator pointing downwards
- protection class
Mounting position
Wire Connection
-MVX series
-MVR series
6.5 ft (2.0 m)
2.1 ft (0.6 m)
color-coded appliance cable
21 AWG (0.35 mm2)
See table below
See table below
Wire size
Dimensions
Weight
Valve Body
Compatibilities
Valve Coupling
VSX, VMX valve series
Threaded, knurled ring nut,
tool-less, pop-on hand connection
ISO 9000 certified
CE
EMC 2004/108/CE directive,
EN 61010-1 standard
LVD 2006/95/CE directive,
EN 61010-1 standard
for MVX 21/22 actuators
Two-year material and
workmanship
Manufacturing
Listings/Approvals
Conformity
Actuator, full stem stroke time (approx.)
Cold start:
Actuator
Opening
Dead
MVX41/42
MVX57/52
MVR24V
MVX21/22
MVR230
Total
After powered on for:
> 5 min
> 30 min
Closing
Closing
Dead
Total
Dead
Warranty
Total
24
2 min 5 min 2 min 6 min 2 min 6 min
VAC 30 sec 50 sec 20 sec 30 sec 30 sec 40 sec
Outside Dimensions, Inch (mm)
110 1 min 6 min 1min
5 min
1min
5 min
VAC 40 sec 20 sec 20 sec 30 sec 20 sec 30 sec
A
B
Actuator
MVX 41/21/42/22 1.63 (41.5) 2.1 (52.0)
1.63 (41.5) 2.7 (68.0)
MVX 57/52
1.52 (38.5) 2.8 (70.0)
MVR
230 1min
3 min 2 min 6 min 2 min 6 min
VAC 20 sec 50 sec 20 sec 30 sec 30 sec 40 sec
Stroke
Opening/closing times
Open (valve stem down)
Closed
valve
stem up
lbs (kg)
0.37 (0.17)
0.44 (0.19)
0.31 (0.14)
A
A
A
NC
Power
Weight
On
Dead time
Dead time
Total opening time
Total closing time
B
B
B
Off
Time
MVX41/21/42/22
MVX57/52
MVR
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
MVX / MVR
Specifications subject to change without notice. | USA 110526 | Page 3 of 4
WIRING CONFIGURATION
The MVX and MVR are equipped with
one (1) color-coded pigtail cable
MVX 41
MVX 42
MVR 24V
On/off or pulse width
modulating control
MVX 41/42/21/22
MVX 24V/230V
blue (ble)
brown (brn)
ble
brn
ble
brn
Power
& Control
Line L1
Volts L2
MVR 24MV/230MV
24 VAC
Transformer
Power
& Control
blue (ble)
brown (brn)
black (blk)
black (blk)
Aux. Switch, SPST
250 VAC, 2(0.1) A
MVX 21
MVX 22
MVR 230V
On/Off control
MVX 57/52
white (wht)
brown (brn)
green (grn)
Common
< 24 VAC
< Control signal, 0-10 VDC
Line L1
Volts L2
MVX 52
MVX 57
Modulating control
110...230 VAC
com

wht
+
~
brn
Y
grn
(+)
(–)
Line L2
Control Signal
0-10 VDC
MVR 24MV
On/off or pulse width
modulating control
with auxillary switch
ble
Volts L1
brn blk
blk
24 VAC
Transformer
Line L1
Notes:
•
•
•
•
Volts L2
Wire connections on 2-wire actuators are interchangeable.
24 VAC
Transformer
Do not supply power to the actuator unless the
actuator has been coupled to the valve body
appropriately.
Auxillary Switch,
2.0(0.1) A,
250 VAC
Actuator will be damaged if 110...230 VAC is applied to
the 24 VAC actuator.
Be patient; it may take several minutes to stroke 100%
from a cold start.
(see the Actuator, full stem stroke time table on pg. 2)
Actuator stroke
direction,
valve position
MVX... MVX57/52
MVR...
On/Off 0-10 VDC On/Off Aux.
Switch
Valve stem moves...
SPST
Power/Control on
down
down
up
Valve ports A to AB
opens
opens
closes
up
up
down
closes
opens
Power/Control off
MVR 230MV
On/off control
with auxillary switch
Valve ports A to AB closes
contacts
open
contacts
close
ble
brn blk
blk
Line L1
Volts L2
110...230 VAC
Auxillary Switch,
2.0(0.1) A,
250 VAC
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
MVX / MVR
Specifications subject to change without notice. | USA 110526 | Page 4 of 4
MANUAL OVERRIDE
COUPLING TO THE VALVE BODY
VXC-CAP
Ensure the actuator piston/stem is lined up with the actuator
mounting neck. Screw
the actuator’s knurled
ring nut (M30 x 1.5 mm)
onto the threaded neck
portion of the valve body
by hand only.
Manual override cap
Screw the override cap
onto the threaded neck
portion of the valve body,
and stroke down the
valve stem into any partial
or fully open position.
•
Allowable mounting position
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
Download