RIB® Emergency Lighting and Power Equipment Relays with

advertisement
RIB® Emergency Lighting and Power Equipment
Relays with Remote Test Capability
IMPORTANT SAFEGUARD: INSULATE
UNUSED LEADS INDIVIDUALLY
When using electrical equipment, basic safety precautions should always be
followed including the following:
www.FunctionalDevices.com | 800.888.5538
UL924
Emergency Lighting and
Power Equipment
Bulletin B1179
393106B
33PE
ESRT
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. Do not use outdoors.
2. Do not mount near gas or electric heaters.
3. Equipment should be mounted in locations and at heights where it will not readily
be subjected to tampering by unauthorized personnel.
4. The use of accessory equipment not recommended by the manufacturer may
cause an unsafe condition.
5. Do not use equipment for other than intended use.
6. Servicing of this equipment should be performed by a qualified service personnel.
SAVE THESE INSTRUCTIONS.
Wireless Key Fob Transmitter
Remote Tester for Use with Radio Frequency-Enabled UL924 Emergency Bypass / Shunt Relays
Remote Testing of Emergency Lighting
Emergency
Emergency
Lighting
Lighting
ESRT
ESRT
ESR2401B-RF
ESR2402B-RF
Emergency
Emergency
Power
Power
Specifications
Battery:
Expected Battery Life:
Operate Time:
Dimensions:
Frequency:
Radio Certifications:
CR2032, 3V, Lithium
2 years
500 mS
2.30˝ x 1.40˝ x .50˝
315 MHz
FCC Part 15 (USA), IC (Canada)
Notes:
» Control one or more radio frequency-enabled ESR
relays with a single transmitter
» Typical transmission distance: Up to 50 feet indoors
Emergency
Emergency
Transfer
Transfer
Yel
Yel
SW
SW
Coil
Coil
Blu
Blu
Normal
Normal
Power
Power
RF-Enabled UL924 Relays
ESR2401B-RF, ESR2402B-RF, ESRE01C-RF, ESRE277C-RF
Turn wall switch (SW) to
OFF position
Press button on ESRT to turn
Emergency Lighting ON
Emergency Lighting will
remain ON for 7-10 seconds,
and then will turn OFF
RIB® Emergency Lighting and Power Equipment
Relays with Remote Test Capability
ESR2401B-RF
^
Wht/Blk
120 Vac
Blu
N/C
Wht/Blu
24 Vac/dc
Yel
Comm
ESRE01C-RF^
Blk
Utility 120 Vac
ESR2402B-RF
^
Wht/Brn
208-277 Vac
Blu
N/C
Wht/Blu
24 Vac/dc
Yel
Comm
COIL INPUT RATINGS
24 Vdc @ 50 mA max
30 Vdc @ 60 mA max
24 Vac @ 83 mA max
120 Vac @ 60 mA max
Org
N/O
Wht/Yel
Comm
CONTACT RATINGS
20 A Resistive, 277 Vac
20 A Ballast N/O, 120/277 Vac
10 A Ballast N/C, 120/277 Vac
10 A Tungsten N/O, 120 Vac
2 A Tungsten N/C, 120 Vac
1 HP, 120 Vac
2 HP, 277 Vac
770VA Pilot Duty, 120Vac
1110VA Pilot Duty, 277Vac
Wht/Yel
Comm
Blu
Switched Hot to Load
Yel
Emergency Hot
Wht
Utility Neutral
Gry
Emergency Neutral
CONTACT RATINGS
3 Amp Ballast @ 120/277 Vac
COIL INPUT RATINGS
120 Vac @ 50 mA max
Blk
Utility 277 Vac
Yel
Emergency Hot
Wht
Utility Neutral
Gry
Emergency Neutral
Example Wiring for ESR2402B-RF
Emergency
Lighting
Transfer
Switch
ESR2402B-RF
208-277 Vac
208-277 Vac
Emergency
Circuit
Breaker
Panel
Hot
Wht/Brn
Neutral
Wht/Yel
Light
Switch
Hot
Blu
Yel
Neutral
Emergency
Power
ie. Generator/
Battery Backup
UL924
Emergency Lighting and
Power Equipment
Blu
Switched Hot to Load
Prp
Switched
277 Vac
NOTES
^FOR SUPPLY CONNECTIONS USE #12AWG WIRES OR
LARGER RATED FOR AT LEAST 75°C(167°F).
Normal
Circuit
Breaker
Panel
COIL INPUT RATINGS
24 Vdc @ 50 mA max
30 Vdc @ 60 mA max
24 Vac @ 83 mA max
208-277 Vac @ 75 mA max
ESRE277C-RF^
Prp
Switched
120 Vac
Normal
Power
Org
N/O
CONTACT RATINGS
20 A Resistive, 277 Vac
20 A Ballast N/O, 120/277 Vac
10 A Ballast N/C, 120/277 Vac
10 A Tungsten N/O, 120 Vac
2 A Tungsten N/C, 120 Vac
1 HP, 120 Vac
2 HP, 277 Vac
770VA Pilot Duty, 120Vac
1110VA Pilot Duty, 277Vac
CONTACT RATINGS
3 Amp Ballast @ 120/277 Vac
COIL INPUT RATINGS
277 Vac @ 40 mA max