8 7 6 5 1 3 4 D D ENPHASE AC INTERCONNECT CABLE 1 - BLACK - L1 2 - RED - L2 3 - BLUE - L3 4 - ORANGE - NEUTRAL GREEN - GROUND C C JUNCTION BOX METER TO METER OR AC DISTRIBUTION PANEL THE FIRST AC CONNECTOR IN EACH BRANCH CIRCUIT IS SUITABLE AS A DISCONNECTING MEANS THE AC LOAD CENTER BREAKER SHOULD BE OPENED PRIOR TO DISCONNECTING AC CONNECTORS B END CAP INSTALLED ON LAST CABLE CONNECTOR OF AC TRUNK CABLE PHASE B-C PHASE C-A PHASE A-B UP TO 15 D380s PER BRANCH CIRCUIT @ 208 VAC (Approx. 5700 WAC) B 1 - 3 POLE 20 AMP CIRCUIT BREAKER PER BRANCH CIRCUIT ENVOY INTERNET GATEWAY GROUND NEUTRAL 120 Vac POWER CABLE AC DISTRIBUTION PANEL OR SUB-PANEL A ETHERNET CONNECTION TO BROADBAND ROUTER A IMPORTANT: Make sure to measure the line-to-line and the line-to-neutral voltage of all service entrance conductors prior to installing any solar equipment. The voltages for the 208 Vac rated microinverters should be within the following ranges: line to line - 183 to 229 Vac, line to neutral - 106 to 132 Vac. 8 7 6 5 4 FIELD WIRING DIAGRAM 208 VAC THREE PHASE 3 2 1