400VDC in Data & Telecom Centers 2013-09-05 Data Center Conference, Moscow Marek Szpek Business Development EMEA © Emerson Network Power AB 2012. All rights reserved throughout the world. The information in this document is the property of Emerson Network Power AB. Except as authorized by Emerson Network Power AB in a written document, those receiving this document shall keep all the information contained herein confidential, and shall protect the same from disclosure and dissemination to third parties. While every precaution has been taken to ensure accuracy and completeness in this document, Emerson Network Power AB assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. This information in this document is subject to change without notice. © 2013 Emerson Network Power Intellectual Property. All rights reserved Agenda Data Center Trends and Emerging Technologies Gains with 400V DC in Data Center and Telecom Center 400VDC pilot installations 400VDC Eco-system availability 400VDC power portfolio availability © 2013 Emerson Network Power Intellectual Property. All rights reserved Data Center Landscape Changing Different compute models available (enterprise, cloud, hyper-scale, co-location) Demands for data and connectivity increase daily Segmentation of computing applications Green data center operations objectives Customers have choices like never before © 2013 Emerson Network Power Intellectual Property. All rights reserved 3 Convergence Creating Choices VOICE DC POWER Traditional AC Traditional DC High-Voltage AC High-Voltage DC Eco-Mode Renewables DATA AC POWER Convergence creates several power choices © 2013 Emerson Network Power Intellectual Property. All rights reserved AC Power in Data Centers 30+ years of history Established ecosystem Highly reliable and efficient platform Will be a choice of many customers for years to come © 2013 Emerson Network Power Intellectual Property. All rights reserved 400V DC – widely discussed and considered in several applications Data Centers High availability, high efficiency and lower total costs thanks to a simple architecture Telecom sites Copper savings for telecom central offices lowers investment and installation costs Commercial buildings / Micro grids Easy integration of renewable energy sources with a common 400V DC bus © 2013 Emerson Network Power Intellectual Property. All rights reserved 400VDC drivers in Data Centers Higher availability vs. AC UPS > 6x, due to more simple architecture Increased overall efficiency, 8-12% (less conversion stages) Lower footprint, ≈ 30% More simple architecture - Data center loads are DC loads - Unnecessary conversions AC/DC, DC/AC are eliminated Easier integration with Renewable © 2013 Emerson Network Power Intellectual Property. All rights reserved Source: NTT-Facilities 400VDC drivers in Telecom (48V) Key driver Copper cable saving, 10x Long distance power feeding (50 x lower distribution losses) Similar architecture to 48V 2-4% higher overall efficiency © 2013 Emerson Network Power Intellectual Property. All rights reserved 400VDC drivers in Commercial Buildings and Micro Grids Energy sourcing becomes decentralized - Local “green” production is typically DC Connecting local sources to AC grid cost energy and money - Part of the “green” energy is lost in conversions before it reaches any “real” load - DC is converted to AC and back to DC Sharing DC bus by different sources is much simpler than AC grid - No phase/voltage balancing © 2013 Emerson Network Power Intellectual Property. All rights reserved Selection of 400VDC field trials Nextek 380V DC Syracuse University 380V DC UPN AB. 350V/380V DC Netpower Labs AB (several sites) 350V/380V DC Green.Ch 380V DC France Telecom 380V DC SAP 380V DC France Telecom 380V DC NTT Group (several sites) 380V/400V DC Intel 380V DC Univ. California 380V DC Other Japan Demos 300V/350V DC Clustered Systems 380V DC China Mobile 380V DC Duke Energy 380V DC North American Telecom 380V DC Telecom Data Center China Telecom 240V/380V DC European Telecom 380V DC Buildings / Microgrids Emerson power equipment © 2013 Emerson Network Power Intellectual Property. All rights reserved IBM Singapore 380V DC Vendor participants include: HP, IBM, EMC, Fujitsu, Hitachi, NEC 400V Eco-system Availability DC Power System DC Breaker Rack PDU Server Power Supply Connector Emerson ABB ServerTech* ABB Carling Netpower Schneider Delta* Nader API Hubbel Technologies Rong Feng / Delta* Delta Eltek* Siemens Fujitsu* Anderson Emerson* NEI – catalog products available Delta* HP – 2013 release of common slot power supply LiteOn* Fujitsu* IBM* – some X and Z series available today, new power available 2014 Juniper* – products in evaluation GE Supermicro* – 2 servers models available for trial Eaton *Pre-production products available Components Are Available for the 400V DC Ecosystem, but Supply Chain Is Still Maturing 11 © 2013 Emerson Network Power Intellectual Property. All rights reserved ICT Load HP 1200W 380VDC/12VDC common slot power supply - Common slot 1200W (100-240VAC, 48VDC, 380VDC) power unit for HP’s ”pizza” portfolio/switches, servers etc. - Highest efficiency, 94% with 380VDC interface - Commercially available Source :HP © 2013 Emerson Network Power Intellectual Property. All rights reserved IBM 380VDC server - New 400VDC power supplies for IBM blade servers planned for release 2014 Source: IBM © 2013 Emerson Network Power Intellectual Property. All rights reserved NEI 380VDC servers Source: NEI © 2013 Emerson Network Power Intellectual Property. All rights reserved Greenfield - Bulk: 400V DC Loads Redundancy Implementation Options Bus or cable Cable or bus cont’d A B A B 400V DC Output DC Distribution (Alt. 1) (N+1) 400V DC UPS N+m Rectifiers Internal Distribution B Side Battery Distribution Distribution 400V A Side B Side Equipment Racks (Alt. 2) (Opt, Alt. 2) Bus or cable Cable or bus cont’d A B Cable or bus cont’d 400V DC Power strips Bus or cable 400V DC (2N) 400V DC UPS N+m Rectifiers Internal Battery A Side 400V DC UPS N+m Rectifiers Internal Distribution A Side © 2013 Emerson Network Power Intellectual Property. All rights reserved Equipment Rack Distribution B Side Battery B Side Cable saving at transision from 48V to 400V & 400V/48V, 100kW load 48V Battery 400V Battery 10m 120kW/48V Power System 30m 120kW/400V Power System 1-3 x PDU 200 x 6-63A c.b. 400V 48V 1-3 x PDU 200 x 6-63A 5m 100kW/48V Telecom Eq. 100kW/48V Telecom Eq. 21kW-400V/48V Tot cable material saving ≈ 25 kEUR Distribution losses saving ≈ 1kW =1% 35 mm² market price 4.1 EUR/m, 150 mm²market price 19.2 EUR/m © 2013 Emerson Network Power Intellectual Property. All rights reserved Available today: NetSure™ 4015 30kW 400V Integrated System Standard system offering (1) output distribution sub-rack (1) power and controls sub-rack (2) battery trays (back-up 20kW7min) Integrated into 24U 19” IT rack HWD: 1200mm x 600mm x 1000mm © 2013 Emerson Network Power Intellectual Property. All rights reserved Under Development: Integrated 120kW cabinet module Output Distribution (400VDC) single section Controller Insulation Failure Detector Individual input c.b. to rectifiers AC Input Breakers Rectifiers 2x250A/400VAC (A+B) 360kW power system = 3x120kW © 2013 Emerson Network Power Intellectual Property. All rights reserved 400V information on Emerson WEB site http://www.EmersonNetworkPower.eu/400vdc © 2013 Emerson Network Power Intellectual Property. All rights reserved Remaining Hurdles for 400VDC Limited components across IT ecosystem Standards under development Lack of familiarity with the technology Installed base of knowledge & information These obstacles will be overcome with additional deployments © 2013 Emerson Network Power Intellectual Property. All rights reserved 20