Doc: TSI 075 Rev: 1 Date: 10/30/07 Page: 1 of 10 TSr SERIES Surge Protective Device Installation & Operation Manual THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 www.ThorSystems.us Sales@ThorSystems.us Ph 804.355.1100 Fax 804.355.8900 TSrc/TSri SERIES INSTALLATION & OPERATION Doc: TSI-075 Rev: 1 Date: 10/30/07 Page: 2 of 10 Quick Reference - Electrician Installation Information WARNING! Failure to confirm voltage can result in serious damage, injury, or even death. 1. Confirm Voltage. Confirm the voltage of the Surge Protective Device (SPD) device matches the utility voltage. (Reference Section I, System Identification Labels.) Should the Utility Voltage not match the SPD voltage, DO NOT INSTALL THE SPD – CONTACT YOUR LOCAL SALES REPRESENTATIVE OR THOR SYSTEMS, INC. 2. Neutral-Ground Bond Confirmation. If the SPD is connected to a Split Phase, 3 Phase WYE, or 3 Phase High-Leg Delta Transformer supplied source, confirm the Neutral and Ground have a bonding jumper in place. Note: If the X-0 bond is not in place, do NOT install SPD. I. 3. Mounting Location Recommendations. Mount the SPD in a location that ensures the conductors are as short and straight as possible. 4. Wire Size: #6AWG is recommended. 5. Safety Ground. Per NEC Article 250, ground the TVSS device to the nearest NEC-approved grounding electrode. A mechanical lug is provided and labeled as “Ground.” 6. Form C Contacts: Models that include a Form C Contact need to have the wires enter the SPD through a knockout other than the power wire knockout. Keep a minimum of two inches (2”) separation between the Form C wires and the power wires. SYSTEM IDENTIFICATION LABELS Voltage Code Voltage A. B. UL Label. All SPDs have a UL label affixed. This label includes the proper UL marks as well as the UL assigned Voltage Performance Ratings (VPR). It also provides the Model Number and Voltage Rating of the SPD. Prior to installation, verification of the voltage MUST be confirmed. You must confirm that the voltage and service configuration of the SPD match the voltage and service configuration of the distribution equipment the SPD will be connected to. TSri300Ss 3Y2 P201 208/120Vac, 3Ø Wye MCOV 150 kA/Mode 150 In(kA) 10 L-N L-G N-G L-L VPR (6kV/3kA): 600 600 600 1500 FACILITY EMI FILTER Mfg. Date: 06-29-07 Serial #: 062907-01 AIC Label. All THOR SYSTEMS’Series TSri and TSrc models have a 100kAIC rating up to 480Vac. Every SPD is labeled with an AIC label as shown here. Per NEC Article 285 Section 6, prior to installation the fault current coordination between the utility service and the SPD to be installed must be confirmed. The AIC rating of the SPD must be equal to (or greater than) the AIC rating of the distribution equipment supplying the installation. C. Model Voltage Suitable For Use on a Circuit Capable of Deliverying Not More Than 100k rms symmetrical Amps, at 480 Volts Maximum. Electrical Diagram Label. An electrical diagram label is affixed to each SPD. Should the utility electrical configuration not match the SPD electrical diagram label, DO NOT INSTALL THE SPD –CONTACT YOUR LOCAL SALES REPRESENTATIVE OR THOR SYSTEMS, INC. THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 www.ThorSystems.us Sales@ThorSystems.us Ph 804.355.1100 Fax 804.355.8900 TSrc/TSri SERIES INSTALLATION & OPERATION Doc: TSI-075 Rev: 1 Date: 10/30/07 Page: 3 of 10 WARNING! Failure to confirm electrical diagram can result in serious damage, injury, or even death. II. SYSTEM VOLTAGE CONFIGURATIONS THOR SYSTEMS, INC. offers SPDs in various voltage configurations. As illustrated on the UL Label on the previous page, each model number contains a three (3) digit code representing the voltage specific to that model. The table below lists the various three (3) digit codes and respective voltage configurations. An electrical diagram for each code is pictured at the bottom of this page. Sample Model number: TSri150Ts XXX M101. (XXX represents the voltage code; replace the XXX with the appropriate code to complete the model number): TSri150Ts 3Y2 M101 = 208/120Vac Three Phase WYE, 3L, N & G THOR SYSTEMS, INC. Voltage Code Table Voltage Code Voltage Configuration Ref. Diagram L1 (AØ) L2 (BØ) Wire Color Code L3 (CØ) Neutral Ground Green 2S1 240/120Vac Single (Split) Phase A Black Red N/A White 2S2 240Vac Single Phase B Black Red N/A N/A Green 2S4 480Vac Single Phase B Brown Orange N/A N/A Green 3Y2 208/120Vac Three Phase WYE C Black Red Blue White Green 3Y4 480/277Vac Three Phase WYE C Brown Orange Yellow White Green 3D2 240Vac Three Phase Delta D Black Red Blue N/A Green 3D4 480Vac Three Phase Delta D Brown Orange Yellow N/A Green Black Red Blue White Green 3H (1) 240Vac High-Leg Delta E (2) (1) Insert a for AØ High-Leg; b for BØ High-Leg; c for CØ High-Leg (2) Diagram E below represents a CØ High-Leg Application as reference only. Confirm the correct High-Leg before installation. Diagram A G AØ N BØ Diagram B G To Critical Loads AØ BØ G AØ N BØ CØ To Critical Loads OCPD Recommended OCPD Recommended Verify Voltage Before Energizing! Diagram C Verify Voltage Before Energizing! Thor TVSS Device OCPD Recommended Thor TVSS Device Diagram E G CØ To Critical Loads AØ N Verify Voltage Before Energizing! To Critical Loads BØ OCPD Recommended THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 Verify Voltage Before Energizing! Thor TVSS Device Diagram D G AØ BØ CØ To Critical Loads OCPD Recommended Thor TVSS Device Verify Voltage Before Energizing! www.ThorSystems.us Sales@ThorSystems.us Thor TVSS Device Ph 804.355.1100 Fax 804.355.8900 TSrc/TSri SERIES INSTALLATION & OPERATION Doc: TSI-075 Rev: 1 Date: 10/30/07 Page: 4 of 10 WARNING! Failure to verify voltage can result in serious damage, injury, or even death. III. SYSTEM MOUNTING AND DIMENSIONS A. Mounting Location. Mount the TSr as close as possible to the load to be protected. To achieve maximum SPD system performance, position the SPD in a location which permits the conductors to be as short and as straight as possible. Wall mount the Surge Protective Device using 3/8-16” mounting hardware. B. System Dimensions/Knockout Location. The illustrations below show the physical dimensions and knockout entry locations for both the TSri (Industrial) and TSrc (Commercial) models. Punch the proper size hole in the SPD located closest to the knockout to be utilized in the electrical panel. Top Entry K.O. Location 1 14" 10.00" Top Entry K.O. Location 8.00" 1 4 6.00" 3.00" 1.00" Side Entry K.O. Location 1.00" 6 14" 8.00" Side Entry K.O. Location 1 4" 3.00" 1.00" 1 14 Input Wiring Termination Area 23 18" 20.00" Input Wiring Termination Area 17.00" 3.00" 16 12" 21 12" 18.00" 9 18" 14.50" 12.00" IV. 8 14" 14 12" 16.00" TSri Series TSrc Series (Industrial Model) Physical Dimensions (Commercial Model) Physical Dimensions SYSTEM POWER WIRING A. Insure that all power is removed before beginning installation. A qualified licensed electrician shall install all electrical connections. THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 www.ThorSystems.us Sales@ThorSystems.us Ph 804.355.1100 Fax 804.355.8900 TSrc/TSri SERIES INSTALLATION & OPERATION Doc: TSI-075 Rev: 1 Date: 10/30/07 Page: 5 of 10 WARNING! Improper wiring can result in serious damage, injury, or even death.. IV. SYSTEM POWER WIRING, CONTINUED B. Based upon the input option ordered, input terminals are provided inside the SPD for the lines (phases), Neutral (if used), Ground and Safety Ground connections. THOR SYSTEMS, INC. Input Termination Wire Range & Torque Tightening Specifications Input Type DIN RAIL Terminal Block Fused Disconnect Switch Surge Disconnect Switch Distribution Block V. VI. Wire Range #4 - #6AWG #4 - #6AWG #2 - #6AWG #2 - #6AWG Tightening Torque 18 - 22 In. Lbs. 22 – 31 In. Lbs. 50 In. Lbs. 80 In. Lbs. (For #2-#6AWG) C. Connect the phase wires to the input Terminal Block, Surge Disconnect Switch or Fused Disconnect Switch. The terminals are marked Line1 (AØ), Line2 (BØ), and Line3 (CØ). D. Connect the Ground to the terminal marked “Surge Ground.” E. Connect the Neutral (if used) to the terminal marked “Neutral.” F. Connect the Safety Ground to the terminal marked “Ground.” FORM C CONTROL WIRING A. Dry “Form C”Contacts are standard on TSri models and optional on the TSrc models. B. If the Form C is to be connected, a separate knockout must be punched in the enclosure to route the cable. NOTE: The Form C cable cannot enter the SPD enclosure with the power wires. The Form “C”contact accepts #16 - #26 AWG conductor and the contact ratings are 0.50A @ 30Vdc or 0.13A @ 150Vac. Keep a minimum of two inches (2”) separation between the Form C wires and the power wires. The Terminal Block torque rating is two (2) inch pounds. C. The Terminal Block is marked NC-C-NO for proper connection. POWER UP THE SYSTEM A. Apply power to the SPD. B. The surge protector is fully operational when the Green LEDs on the SPD are illuminated. C. The TSri (Industrial Models) should have three (3) illuminated Green LEDs on the front door display. The TSrc (Commercial Models) should have seven (7) illuminated Green LEDs visible through the enclosures CLEAR cover. If the Green LEDs are not illuminated or if any of the Red LEDs are illuminated, check to ensure power is applied to the SPD. THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 www.ThorSystems.us Sales@ThorSystems.us Ph 804.355.1100 Fax 804.355.8900 TSrc/TSri SERIES INSTALLATION & OPERATION Doc: TSI-075 Rev: 1 Date: 10/30/07 Page: 6 of 10 VI. POWER UP THE SYSTEM, CONTINUED D. VII. If the SPD is not operating properly, remove power to the SPD and contact your local Sales Representative or THOR SYSTEMS, INC. SYSTEM MONITORING TYPES Your surge protection SPD system will include one (1) of four (4) monitoring types. For proper monitoring operation, confirm the monitor comes on-line per the descriptions below: A. B. C. TSri (Industrial Series) - Type 1 Monitor, TSm110a 1. Features. LED Matrix & Audible Alarm 2. During Normal Operation. At the SPD initial power up, three (3) Green phase LEDs will illuminate in the Main Display Window of the display panel on the system’s front door. Inside the SPD, each replaceable module will have a Green LED illuminated. 3. After a Fault Condition. The respective Red LED of the failed module will illuminate in the Main Display Window. The Audible Alarm will sound. Inside the SPD, two (2) Yellow tabs will protrude from the protection mode element (TpMOV) that has failed. 4. See Section VIII for detailed operating instructions of the TSm110a Monitor. TSri (Industrial Series) - Type 2 Monitor, TSm110-sc (Optional) 1. Features. LED Matrix, Audible Alarm and Surge Counter 2. During Normal Operation. At the SPD initial power up, three (3) Green phase LEDs will illuminate in the Main Display Window of the Display panel on the system’s front door. Inside the SPD, each replaceable module will have a Green LED illuminated. The Surge Counter will power on and will read “0.” 3. After a Fault Condition. The respective Red LED of the failed module will illuminate in the Main Display Window. The Audible Alarm will sound. Inside the SPD, two (2) Yellow tabs will protrude from the protection mode element (TpMOV) that has failed. If the current magnitude was large enough, the Surge Counter may increment to the next number. 4. See Section VIII for detailed operating instructions of the TSm110a Monitor. TSrc (Commercial Series) - Type 1 Monitor, Surge Tile LEDs (Standard) 1. Features. Green LED and Red LEDs on each Replaceable Surge Tile 2. During Normal Operation. At the SPD initial power up, seven (7) Green module LEDs will illuminate, visible through a CLEAR, hinged enclosure cover. 3. After a Fault Condition. The respective Red LED of the failed module will illuminate. Two (2) Yellow tabs will protrude from the protection mode element (TpMOV) that has failed. THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 www.ThorSystems.us Sales@ThorSystems.us Ph 804.355.1100 Fax 804.355.8900 TSrc/TSri SERIES INSTALLATION & OPERATION Doc: TSI-075 Rev: 1 Date: 10/30/07 Page: 7 of 10 VII. SYSTEM MONITORING TYPES, CONTINUED D. TSrc, Commercial Series - Type 2 Monitor, TSm270a (Optional) 1. Features. Green and Red LEDs on each Replaceable Surge Tile, Audible Alarm, and Surge Counter with eight (8) Sensitivity Settings. 2. During Normal Operation. At the SPD initial power up, the Surge Counter will display the Sensitivity Setting, which is set at “3”by the factory. The Green STATUS LED is illuminated indicating the SPD has AC power and all of the protection modes are functional. Seven (7) Green Module LEDs will illuminate, visible through a CLEAR, hinged enclosure cover. The Yellow ENABLE LED is illuminated indicating the Audible Alarm will sound in the event of a fault condition. The Surge Counter will display “0000”or some 4-digit display representing the number of impulses the SPD has diverted 3. After a Fault Condition. The Red LED of the failed module will illuminate upon any protection mode loss. The Audible Alarm will sound (if the Alarm is enabled). The Red Fault Light will illuminate. The Surge Counter will flash “ALRM”until the Acknowledge ACK button is pushed. The respective Red LED of the failed module will illuminate. Two (2) Yellow tabs will protrude from the protection mode element (TpMOV) that has failed. 4. VIII. See Section IX for further operating instructions of the Type 2, TSm270a Monitor. SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 1, TSm110a A. Apply power to the TVSS system. (You may hear a quick, low volume alarm “chirp.”) B. Three (3) Green phase LEDs in the Main Display Window will illuminate. C. If you experience the failure of a Surge Tile: 1. The Yellow round ACTIVE SURGE LED will flash on and then off. 2. A Yellow ACTIVE SURGE LED in the Main Display Window will flash on and then off, representing the respective active Module. 3. The Audible Alarm will sound (see instructions below to silence alarm). THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 www.ThorSystems.us Sales@ThorSystems.us Ph 804.355.1100 Fax 804.355.8900 TSrc/TSri SERIES INSTALLATION & OPERATION Doc: TSI-075 Rev: 1 Date: 10/30/07 Page: 8 of 10 VIII. SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 1, TSm110a, CONTINUED 4. The red round FAULT ALARM LED will illuminate. 5. In the Main Display Window, the Red LED of the respective Module will illuminate. TYPE 1 MONITOR MAIN DISPLAY WINDOW Viewing Area for Module Status LEDs MODULE STATUS LEDs COLOR Green INDICATION______ Phase Voltage Present Yellow Yellow Active Surge Horn is Disabled Red Failed Module or Fuse SYSTEM LEDs SYSTEM STATUS COLOR = INDICATION Green = Power to system ACTIVE SURGE FAULT ALARM Yellow = Active Surge Red = Failed Module or Fuse PUSHBUTTONS FUNCTION ON ALARM ACK Turns Monitor Display On and off Silences alarm during a fault event HORN DISABLE Turns alarm off (no alarm will sound during a fault event) 6. 7. 8. THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 To silence the alarm: a. When the Alarm sounds, push the ALARM ACK button. b. When the ALARM ACK button is pushed, the Yellow HORN DISABLE LED in the Main Display Window will illuminate. Note: The Red LEDs will remain illuminated after the Alarm is silenced until the fault is cleared. To turn the monitoring display off: a. Push the ON pushbutton one time b. Push the ON pushbutton a second time to turn the display back on. To disable the Alarm: a. Push the HORN DISABLE pushbutton. This will prevent the Alarm from sounding during a fault event. b. The Yellow HORN DISABLE LED will illuminate in the Main Display Window. www.ThorSystems.us Sales@ThorSystems.us Ph 804.355.1100 Fax 804.355.8900 TSrc/TSri SERIES INSTALLATION & OPERATION Doc: TSI-075 Rev: 1 Date: 10/30/07 Page: 9 of 10 VIII. SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 1, TSm110a, CONTINUED 9. IX. To enable the Alarm: a. Push the HORN DISABLE pushbutton a second time b. The Yellow HORN DISABLE LED will go out in the Main Display Window. SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 2, TSm270a A. Indicating LEDs. The Green STATUS LED is used to indicate power is applied to the Surge Protective Device. The Red ALARM LED is used to indicate a loss of a protection mode within the unit. The Yellow ENABLE LED indicates the status of the Audible Alarm and, finally, the Yellow ACTIVE SURGE LED illuminates during an actual counted surge event. TYPE 2 MONITOR B. LED Display. The four (4) digit LED 5x7 dot matrix smart alpha-numeric display uses both alpha and numeric characters to count up to 27,000 impulse events. This is accomplished by converting the first character into a letter when the 10,000 impulse level is reached (example, A000). The letter is then incremented after each subsequent 1000 impulses for a total of 26,999 (example, Z999) counts. C. Membrane Switches D. 1. ON. Pressing the ON switch will power the monitor on and off, extinguishing all LEDs and the Display. Pressing the ON switch a second time will illuminate the LEDs and Display in the same configuration as before the monitor was turned off. Any impulses recorded on the Display will be stored in an EE prom and will be displayed again when the monitor is turned back on. 2. ACK. Pressing the ACK switch will silence the Audible Alarm in an alarm condition. If the Alarm condition has cleared, pressing the ACK switch again will reset the display to the normal condition. 3. ENABLE. Pressing the ENABLE switch enables and disables the Audible Alarm function on the SPD. The current status is indicated by the Yellow ENABLE LED. If the Yellow LED is illuminated, the Audible Alarm is enabled. If the Yellow LED is not illuminated, the Audible Alarm is disabled. 4. RESET. The RESET switch will reset the impulse counter back to zero. Due to the advantages of knowing the total number of impulses the unit has experienced in a diagnostic situation, the RESET switch requires additional inputs for a reset to be performed. Please contact THOR SYSTEMS’Customer Service, for these additional inputs. Sensitivity Settings. The TSm 270a monitor has the capability of adjusting the sensitivity of the count circuitry. Often due to the electrical environment at the installation, the counter can experience excessive events that are continuously incremented, or lower level events that do not trigger the counter. The Sensitivity Settings allow an adjustment of the circuit due to the electrical environment without requiring a hardware change. THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 www.ThorSystems.us Sales@ThorSystems.us Ph 804.355.1100 Fax 804.355.8900 TSrc/TSri SERIES INSTALLATION & OPERATION Doc: TSI-075 Rev: 1 Date: 10/30/07 Page: 10 of 10 IX. SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 2, TSm270a, CONTINUED To adjust the Sensitivity Setting, press and hold the ENABLE and ACK switches. After three (3) seconds, the LED display will change to the sensitivity screen [SEN?]. The question mark (?) will actually display the current sensitivity setting--factory set to “3”. Using the ON and RESET switches will increase and decrease the sensitivity setting. The lower the setting, the more sensitive the circuit becomes, the higher the setting the less sensitive the circuit is. Settings are provided from “1”to “8.” After the new level is selected, press the ACK switch. The monitor will return to normal operation and the sensitivity level will be displayed on any power-up function of the monitor. X. SURGE TILE REPLACEMENT A. Surge Tile Identification: The TSr Series allows for failed Surge Tiles to be replaced in the field by a qualified electrician. The Surge Tile voltage rating varies based on the system voltage. The Surge Tile is keyed and numerically color-coded to prevent the installation of an incorrect voltage Surge Tile. The table below identifies the numeric, color and key value of the Surge Tile per Voltage. THOR SYSTEMS, INC. Surge Tile Numeric, Color, & Key Values B. C. System Voltage (AC) Numeric Value Color Pin ID (Key Value) 240/120 Vac or 208/120 Vac 480/277 Vac 480 Vac 150 320 550 Purple Red Yellow I II X Surge Tile Removal 1. Unplug the 24AWG wire harness from the failed Surge Tile. 2. Using a 7/16”socket, remove the two (2) ¼-20 serrated washer head hex nuts that hold the Surge Tile to the bus structure. 3. If your Surge Protective Device has a dielectric paper between the Surge Tiles, be sure to keep the paper in place during the removal of the Surge Tile. 4. Remove the Surge Tile. Surge Tile Replacement 1. Verify the numeric value, color-coded label, and pin ID match the Surge Tile being replaced. 2. If your SPD has a dielectric paper between the Surge Tiles, be sure to keep the paper in place during installation of the Surge Tile. 3. Secure the Surge Tile with the two (2) ¼-20 serrated washer head hex nuts removed in Step B-2 above. 4. Replace the 24AWG wire harness that was unplugged in Step B-1 above. THOR SYSTEMS, INC. 3621 Saunders Avenue Richmond, VA 23227-4354 www.ThorSystems.us Sales@ThorSystems.us Ph 804.355.1100 Fax 804.355.8900