TSr SERIES Surge Protective Device

advertisement
Doc: TSI 075
Rev: 1
Date: 10/30/07
Page: 1 of 10
TSr SERIES
Surge Protective Device
Installation & Operation Manual
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
www.ThorSystems.us
Sales@ThorSystems.us
Ph 804.355.1100
Fax 804.355.8900
TSrc/TSri SERIES
INSTALLATION & OPERATION
Doc: TSI-075
Rev: 1
Date: 10/30/07
Page: 2 of 10
Quick Reference - Electrician Installation Information
WARNING!
Failure to confirm voltage can result in serious damage, injury, or even death.
1.
Confirm Voltage. Confirm the voltage of the Surge Protective Device (SPD) device matches the
utility voltage. (Reference Section I, System Identification Labels.) Should the Utility Voltage not
match the SPD voltage, DO NOT INSTALL THE SPD – CONTACT YOUR LOCAL SALES
REPRESENTATIVE OR THOR SYSTEMS, INC.
2. Neutral-Ground Bond Confirmation. If the SPD is connected to a Split Phase, 3 Phase WYE, or 3
Phase High-Leg Delta Transformer supplied source, confirm the Neutral and Ground have a
bonding jumper in place. Note: If the X-0 bond is not in place, do NOT install SPD.
I.
3.
Mounting Location Recommendations. Mount the SPD in a location that ensures the
conductors are as short and straight as possible.
4.
Wire Size: #6AWG is recommended.
5.
Safety Ground. Per NEC Article 250, ground the TVSS device to the nearest NEC-approved
grounding electrode. A mechanical lug is provided and labeled as “Ground.”
6.
Form C Contacts: Models that include a Form C Contact need to have the wires enter the SPD
through a knockout other than the power wire knockout. Keep a minimum of two inches (2”)
separation between the Form C wires and the power wires.
SYSTEM IDENTIFICATION LABELS
Voltage Code
Voltage
A.
B.
UL Label. All SPDs have a UL label affixed. This label includes the
proper UL marks as well as the UL assigned Voltage Performance
Ratings (VPR). It also provides the Model Number and Voltage Rating of
the SPD. Prior to installation, verification of the voltage MUST be
confirmed. You must confirm that the voltage and service configuration
of the SPD match the voltage and service configuration of the distribution
equipment the SPD will be connected to.
TSri300Ss 3Y2 P201
208/120Vac, 3Ø Wye
MCOV
150
kA/Mode
150
In(kA)
10
L-N L-G N-G L-L
VPR (6kV/3kA): 600 600 600 1500
FACILITY EMI FILTER
Mfg. Date: 06-29-07
Serial #: 062907-01
AIC Label. All THOR SYSTEMS’Series TSri and TSrc models have a 100kAIC rating up to
480Vac. Every SPD is labeled with an AIC label as shown here.
Per NEC Article 285 Section 6, prior to installation the fault current
coordination between the utility service and the SPD to be installed must
be confirmed. The AIC rating of the SPD must be equal to (or greater
than) the AIC rating of the distribution equipment supplying the
installation.
C.
Model
Voltage
Suitable For Use on a Circuit Capable
of Deliverying Not More Than
100k rms symmetrical Amps,
at 480 Volts Maximum.
Electrical Diagram Label. An electrical diagram label is affixed to each SPD. Should the utility
electrical configuration not match the SPD electrical diagram label, DO NOT INSTALL THE SPD
–CONTACT YOUR LOCAL SALES REPRESENTATIVE OR THOR SYSTEMS, INC.
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
www.ThorSystems.us
Sales@ThorSystems.us
Ph 804.355.1100
Fax 804.355.8900
TSrc/TSri SERIES
INSTALLATION & OPERATION
Doc: TSI-075
Rev: 1
Date: 10/30/07
Page: 3 of 10
WARNING!
Failure to confirm electrical diagram can result in serious damage, injury, or even death.
II.
SYSTEM VOLTAGE CONFIGURATIONS
THOR SYSTEMS, INC. offers SPDs in various voltage configurations. As illustrated on the UL Label on
the previous page, each model number contains a three (3) digit code representing the voltage specific to
that model. The table below lists the various three (3) digit codes and respective voltage configurations.
An electrical diagram for each code is pictured at the bottom of this page.
Sample Model number: TSri150Ts XXX M101. (XXX represents the voltage code; replace the XXX with
the appropriate code to complete the model number):
TSri150Ts 3Y2 M101 = 208/120Vac Three Phase WYE, 3L, N & G
THOR SYSTEMS, INC.
Voltage Code Table
Voltage
Code
Voltage
Configuration
Ref.
Diagram
L1 (AØ)
L2 (BØ)
Wire Color Code
L3 (CØ)
Neutral
Ground
Green
2S1
240/120Vac Single (Split) Phase
A
Black
Red
N/A
White
2S2
240Vac Single Phase
B
Black
Red
N/A
N/A
Green
2S4
480Vac Single Phase
B
Brown
Orange
N/A
N/A
Green
3Y2
208/120Vac Three Phase WYE
C
Black
Red
Blue
White
Green
3Y4
480/277Vac Three Phase WYE
C
Brown
Orange
Yellow
White
Green
3D2
240Vac Three Phase Delta
D
Black
Red
Blue
N/A
Green
3D4
480Vac Three Phase Delta
D
Brown
Orange
Yellow
N/A
Green
Black
Red
Blue
White
Green
3H
(1)
240Vac High-Leg Delta
E
(2)
(1)
Insert a for AØ High-Leg; b for BØ High-Leg; c for CØ High-Leg
(2)
Diagram E below represents a CØ High-Leg Application as reference only. Confirm the correct High-Leg before installation.
Diagram
A
G
AØ
N
BØ
Diagram
B
G
To
Critical
Loads
AØ
BØ
G
AØ
N
BØ
CØ
To
Critical
Loads
OCPD Recommended
OCPD Recommended
Verify Voltage
Before Energizing!
Diagram
C
Verify Voltage
Before Energizing!
Thor
TVSS
Device
OCPD Recommended
Thor
TVSS
Device
Diagram
E
G
CØ
To
Critical
Loads
AØ
N
Verify Voltage
Before Energizing!
To
Critical
Loads
BØ
OCPD Recommended
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
Verify Voltage
Before Energizing!
Thor
TVSS
Device
Diagram
D
G
AØ
BØ
CØ
To
Critical
Loads
OCPD Recommended
Thor
TVSS
Device
Verify Voltage
Before Energizing!
www.ThorSystems.us
Sales@ThorSystems.us
Thor
TVSS
Device
Ph 804.355.1100
Fax 804.355.8900
TSrc/TSri SERIES
INSTALLATION & OPERATION
Doc: TSI-075
Rev: 1
Date: 10/30/07
Page: 4 of 10
WARNING!
Failure to verify voltage can result in serious damage, injury, or even death.
III.
SYSTEM MOUNTING AND DIMENSIONS
A.
Mounting Location. Mount the TSr as close as possible to the load to be protected. To achieve
maximum SPD system performance, position the SPD in a location which permits the conductors to
be as short and as straight as possible. Wall mount the Surge Protective Device using 3/8-16”
mounting hardware.
B.
System Dimensions/Knockout Location. The illustrations below show the physical dimensions
and knockout entry locations for both the TSri (Industrial) and TSrc (Commercial) models. Punch
the proper size hole in the SPD located closest to the knockout to be utilized in the electrical panel.
Top Entry
K.O. Location
1 14"
10.00"
Top Entry
K.O. Location
8.00"
1 4
6.00"
3.00"
1.00"
Side Entry
K.O. Location
1.00"
6 14"
8.00"
Side Entry
K.O. Location
1
4"
3.00"
1.00"
1 14
Input Wiring
Termination Area
23 18"
20.00"
Input Wiring
Termination Area
17.00"
3.00"
16 12"
21 12"
18.00"
9 18"
14.50"
12.00"
IV.
8 14"
14 12"
16.00"
TSri Series
TSrc Series
(Industrial Model)
Physical Dimensions
(Commercial Model)
Physical Dimensions
SYSTEM POWER WIRING
A.
Insure that all power is removed before beginning installation. A qualified licensed electrician shall
install all electrical connections.
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
www.ThorSystems.us
Sales@ThorSystems.us
Ph 804.355.1100
Fax 804.355.8900
TSrc/TSri SERIES
INSTALLATION & OPERATION
Doc: TSI-075
Rev: 1
Date: 10/30/07
Page: 5 of 10
WARNING!
Improper wiring can result in serious damage, injury, or even death..
IV.
SYSTEM POWER WIRING, CONTINUED
B.
Based upon the input option ordered, input terminals are provided inside the SPD for the lines
(phases), Neutral (if used), Ground and Safety Ground connections.
THOR SYSTEMS, INC.
Input Termination Wire Range & Torque Tightening Specifications
Input
Type
DIN RAIL Terminal Block
Fused Disconnect Switch
Surge Disconnect Switch
Distribution Block
V.
VI.
Wire
Range
#4 - #6AWG
#4 - #6AWG
#2 - #6AWG
#2 - #6AWG
Tightening
Torque
18 - 22 In. Lbs.
22 – 31 In. Lbs.
50 In. Lbs.
80 In. Lbs. (For #2-#6AWG)
C.
Connect the phase wires to the input Terminal Block, Surge Disconnect Switch or Fused Disconnect
Switch. The terminals are marked Line1 (AØ), Line2 (BØ), and Line3 (CØ).
D.
Connect the Ground to the terminal marked “Surge Ground.”
E.
Connect the Neutral (if used) to the terminal marked “Neutral.”
F.
Connect the Safety Ground to the terminal marked “Ground.”
FORM C CONTROL WIRING
A.
Dry “Form C”Contacts are standard on TSri models and optional on the TSrc models.
B.
If the Form C is to be connected, a separate knockout must be punched in the enclosure to route the
cable. NOTE: The Form C cable cannot enter the SPD enclosure with the power wires. The Form
“C”contact accepts #16 - #26 AWG conductor and the contact ratings are 0.50A @ 30Vdc or 0.13A
@ 150Vac. Keep a minimum of two inches (2”) separation between the Form C wires and the
power wires. The Terminal Block torque rating is two (2) inch pounds.
C.
The Terminal Block is marked NC-C-NO for proper connection.
POWER UP THE SYSTEM
A.
Apply power to the SPD.
B.
The surge protector is fully operational when the Green LEDs on the SPD are illuminated.
C.
The TSri (Industrial Models) should have three (3) illuminated Green LEDs on the front door
display. The TSrc (Commercial Models) should have seven (7) illuminated Green LEDs visible
through the enclosures CLEAR cover. If the Green LEDs are not illuminated or if any of the Red
LEDs are illuminated, check to ensure power is applied to the SPD.
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
www.ThorSystems.us
Sales@ThorSystems.us
Ph 804.355.1100
Fax 804.355.8900
TSrc/TSri SERIES
INSTALLATION & OPERATION
Doc: TSI-075
Rev: 1
Date: 10/30/07
Page: 6 of 10
VI.
POWER UP THE SYSTEM, CONTINUED
D.
VII.
If the SPD is not operating properly, remove power to the SPD and contact your local Sales
Representative or THOR SYSTEMS, INC.
SYSTEM MONITORING TYPES
Your surge protection SPD system will include one (1) of four (4) monitoring types. For proper monitoring
operation, confirm the monitor comes on-line per the descriptions below:
A.
B.
C.
TSri (Industrial Series) - Type 1 Monitor, TSm110a
1.
Features. LED Matrix & Audible Alarm
2.
During Normal Operation. At the SPD initial power up, three (3) Green phase LEDs will
illuminate in the Main Display Window of the display panel on the system’s front door.
Inside the SPD, each replaceable module will have a Green LED illuminated.
3.
After a Fault Condition. The respective Red LED of the failed module will illuminate in the
Main Display Window. The Audible Alarm will sound. Inside the SPD, two (2) Yellow tabs
will protrude from the protection mode element (TpMOV) that has failed.
4.
See Section VIII for detailed operating instructions of the TSm110a Monitor.
TSri (Industrial Series) - Type 2 Monitor, TSm110-sc (Optional)
1.
Features. LED Matrix, Audible Alarm and Surge Counter
2.
During Normal Operation. At the SPD initial power up, three (3) Green phase LEDs will
illuminate in the Main Display Window of the Display panel on the system’s front door.
Inside the SPD, each replaceable module will have a Green LED illuminated. The Surge
Counter will power on and will read “0.”
3.
After a Fault Condition. The respective Red LED of the failed module will illuminate in the
Main Display Window. The Audible Alarm will sound. Inside the SPD, two (2) Yellow tabs
will protrude from the protection mode element (TpMOV) that has failed. If the current
magnitude was large enough, the Surge Counter may increment to the next number.
4.
See Section VIII for detailed operating instructions of the TSm110a Monitor.
TSrc (Commercial Series) - Type 1 Monitor, Surge Tile LEDs (Standard)
1.
Features. Green LED and Red LEDs on each Replaceable Surge Tile
2.
During Normal Operation. At the SPD initial power up, seven (7) Green module LEDs will
illuminate, visible through a CLEAR, hinged enclosure cover.
3.
After a Fault Condition. The respective Red LED of the failed module will illuminate. Two
(2) Yellow tabs will protrude from the protection mode element (TpMOV) that has failed.
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
www.ThorSystems.us
Sales@ThorSystems.us
Ph 804.355.1100
Fax 804.355.8900
TSrc/TSri SERIES
INSTALLATION & OPERATION
Doc: TSI-075
Rev: 1
Date: 10/30/07
Page: 7 of 10
VII.
SYSTEM MONITORING TYPES, CONTINUED
D.
TSrc, Commercial Series - Type 2 Monitor, TSm270a (Optional)
1.
Features. Green and Red LEDs on each Replaceable Surge Tile, Audible Alarm, and Surge
Counter with eight (8) Sensitivity Settings.
2.
During Normal Operation. At the SPD initial power up, the Surge Counter will display the
Sensitivity Setting, which is set at “3”by the factory.
The Green STATUS LED is illuminated indicating the SPD has AC power and all of the
protection modes are functional.
Seven (7) Green Module LEDs will illuminate, visible through a CLEAR, hinged enclosure
cover.
The Yellow ENABLE LED is illuminated indicating the Audible Alarm will sound in the
event of a fault condition.
The Surge Counter will display “0000”or some 4-digit display representing the number of
impulses the SPD has diverted
3.
After a Fault Condition. The Red LED of the failed module will illuminate upon any
protection mode loss.
The Audible Alarm will sound (if the Alarm is enabled).
The Red Fault Light will illuminate.
The Surge Counter will flash “ALRM”until the Acknowledge ACK button is pushed.
The respective Red LED of the failed module will illuminate. Two (2) Yellow tabs will
protrude from the protection mode element (TpMOV) that has failed.
4.
VIII.
See Section IX for further operating instructions of the Type 2, TSm270a Monitor.
SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 1, TSm110a
A.
Apply power to the TVSS system. (You may hear a quick, low volume alarm “chirp.”)
B.
Three (3) Green phase LEDs in the Main Display Window will illuminate.
C.
If you experience the failure of a Surge Tile:
1.
The Yellow round ACTIVE SURGE LED will flash on and then off.
2.
A Yellow ACTIVE SURGE LED in the Main Display Window will flash on and then off,
representing the respective active Module.
3.
The Audible Alarm will sound (see instructions below to silence alarm).
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
www.ThorSystems.us
Sales@ThorSystems.us
Ph 804.355.1100
Fax 804.355.8900
TSrc/TSri SERIES
INSTALLATION & OPERATION
Doc: TSI-075
Rev: 1
Date: 10/30/07
Page: 8 of 10
VIII.
SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 1, TSm110a, CONTINUED
4.
The red round FAULT ALARM LED will illuminate.
5.
In the Main Display Window, the Red LED of the respective Module will illuminate.
TYPE 1 MONITOR
MAIN DISPLAY WINDOW
Viewing Area for Module Status LEDs
MODULE STATUS LEDs
COLOR
Green
INDICATION______
Phase Voltage Present
Yellow
Yellow
Active Surge
Horn is Disabled
Red
Failed Module or Fuse
SYSTEM LEDs
SYSTEM STATUS
COLOR = INDICATION
Green = Power to system
ACTIVE SURGE
FAULT ALARM
Yellow = Active Surge
Red = Failed Module or Fuse
PUSHBUTTONS
FUNCTION
ON
ALARM ACK
Turns Monitor Display On and off
Silences alarm during a fault event
HORN DISABLE
Turns alarm off (no alarm will sound
during a fault event)
6.
7.
8.
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
To silence the alarm:
a.
When the Alarm sounds, push the ALARM ACK button.
b.
When the ALARM ACK button is pushed, the Yellow HORN DISABLE LED in the
Main Display Window will illuminate. Note: The Red LEDs will remain illuminated
after the Alarm is silenced until the fault is cleared.
To turn the monitoring display off:
a.
Push the ON pushbutton one time
b.
Push the ON pushbutton a second time to turn the display back on.
To disable the Alarm:
a.
Push the HORN DISABLE pushbutton. This will prevent the Alarm from sounding
during a fault event.
b.
The Yellow HORN DISABLE LED will illuminate in the Main Display Window.
www.ThorSystems.us
Sales@ThorSystems.us
Ph 804.355.1100
Fax 804.355.8900
TSrc/TSri SERIES
INSTALLATION & OPERATION
Doc: TSI-075
Rev: 1
Date: 10/30/07
Page: 9 of 10
VIII.
SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 1, TSm110a, CONTINUED
9.
IX.
To enable the Alarm:
a.
Push the HORN DISABLE pushbutton a second time
b.
The Yellow HORN DISABLE LED will go out in the Main Display Window.
SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 2, TSm270a
A.
Indicating LEDs. The Green STATUS LED is used to indicate power is applied to the Surge
Protective Device. The Red ALARM LED is used to indicate a loss of a protection mode within the
unit. The Yellow ENABLE LED indicates the status of the Audible Alarm and, finally, the Yellow
ACTIVE SURGE LED illuminates during an actual counted
surge event.
TYPE 2 MONITOR
B.
LED Display. The four (4) digit LED 5x7 dot matrix smart
alpha-numeric display uses both alpha and numeric characters
to count up to 27,000 impulse events. This is accomplished
by converting the first character into a letter when the 10,000
impulse level is reached (example, A000). The letter is then
incremented after each subsequent 1000 impulses for a total
of 26,999 (example, Z999) counts.
C.
Membrane Switches
D.
1.
ON. Pressing the ON switch will power the monitor
on and off, extinguishing all LEDs and the Display.
Pressing the ON switch a second time will illuminate
the LEDs and Display in the same configuration as
before the monitor was turned off. Any impulses
recorded on the Display will be stored in an EE prom
and will be displayed again when the monitor is turned
back on.
2.
ACK. Pressing the ACK switch will silence the
Audible Alarm in an alarm condition. If the Alarm condition has cleared, pressing the ACK
switch again will reset the display to the normal condition.
3.
ENABLE. Pressing the ENABLE switch enables and disables the Audible Alarm function
on the SPD. The current status is indicated by the Yellow ENABLE LED. If the Yellow
LED is illuminated, the Audible Alarm is enabled. If the Yellow LED is not illuminated, the
Audible Alarm is disabled.
4.
RESET. The RESET switch will reset the impulse counter back to zero. Due to the
advantages of knowing the total number of impulses the unit has experienced in a diagnostic
situation, the RESET switch requires additional inputs for a reset to be performed. Please
contact THOR SYSTEMS’Customer Service, for these additional inputs.
Sensitivity Settings. The TSm 270a monitor has the capability of adjusting the sensitivity of the count
circuitry. Often due to the electrical environment at the installation, the counter can experience excessive
events that are continuously incremented, or lower level events that do not trigger the counter. The
Sensitivity Settings allow an adjustment of the circuit due to the electrical environment without requiring
a hardware change.
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
www.ThorSystems.us
Sales@ThorSystems.us
Ph 804.355.1100
Fax 804.355.8900
TSrc/TSri SERIES
INSTALLATION & OPERATION
Doc: TSI-075
Rev: 1
Date: 10/30/07
Page: 10 of 10
IX.
SYSTEM MONITORING OPERATING INSTRUCTIONS –TYPE 2, TSm270a, CONTINUED
To adjust the Sensitivity Setting, press and hold the ENABLE and ACK switches. After three (3)
seconds, the LED display will change to the sensitivity screen [SEN?]. The question mark (?) will
actually display the current sensitivity setting--factory set to “3”.
Using the ON and RESET switches will increase and decrease the sensitivity setting. The lower the
setting, the more sensitive the circuit becomes, the higher the setting the less sensitive the circuit is.
Settings are provided from “1”to “8.” After the new level is selected, press the ACK switch. The
monitor will return to normal operation and the sensitivity level will be displayed on any power-up
function of the monitor.
X.
SURGE TILE REPLACEMENT
A.
Surge Tile Identification: The TSr Series allows for failed Surge Tiles to be replaced in the field
by a qualified electrician. The Surge Tile voltage rating varies based on the system voltage. The
Surge Tile is keyed and numerically color-coded to prevent the installation of an incorrect voltage
Surge Tile. The table below identifies the numeric, color and key value of the Surge Tile per
Voltage.
THOR SYSTEMS, INC.
Surge Tile Numeric, Color, & Key Values
B.
C.
System
Voltage (AC)
Numeric
Value
Color
Pin ID
(Key Value)
240/120 Vac or 208/120 Vac
480/277 Vac
480 Vac
150
320
550
Purple
Red
Yellow
I
II
X
Surge Tile Removal
1.
Unplug the 24AWG wire harness from the failed Surge Tile.
2.
Using a 7/16”socket, remove the two (2) ¼-20 serrated washer head hex nuts that hold the
Surge Tile to the bus structure.
3.
If your Surge Protective Device has a dielectric paper between the Surge Tiles, be sure to
keep the paper in place during the removal of the Surge Tile.
4.
Remove the Surge Tile.
Surge Tile Replacement
1.
Verify the numeric value, color-coded label, and pin ID match the Surge Tile being replaced.
2.
If your SPD has a dielectric paper between the Surge Tiles, be sure to keep the paper in place
during installation of the Surge Tile.
3.
Secure the Surge Tile with the two (2) ¼-20 serrated washer head hex nuts removed in Step
B-2 above.
4.
Replace the 24AWG wire harness that was unplugged in Step B-1 above.
THOR SYSTEMS, INC.
3621 Saunders Avenue
Richmond, VA 23227-4354
www.ThorSystems.us
Sales@ThorSystems.us
Ph 804.355.1100
Fax 804.355.8900
Download