SmartMod™ Infrastructure Solution 30 kW (N+1), Tier 2, 4 Racks with Containment Basic Floor Plan Hot Aisle Cold Aisle Distribution board w/ATS Liebert® CRV cooling unit Fire suppression Liebert APM UPS Roxtec entry ports Sliding door Liebert DCF server rack Condensing Units Monitoring cabinets ® ® SmartMod™ Intelligent, Integrated Infrastructure for the Data Center The SmartMod™ approach to infrastructure design leverages an intelligent, row-based solution that simplifies the installation and management of your modular data center, optimizing efficiency and reliability. By integrating UPS, power distribution, thermal management and control technologies, this solution offers industry best practices in data center design to deliver an infrastructure that is: n Efficient n Economical n Simplified Building Specifications IT Specifications Building Type Modular, prefab data center Racks (H x W x D) 2000 mm x 600 mm x 1100 mm Dimensions (H x W x D) 2.9 m x 2.3 m x 6.1 m Number of Racks 4 Floor Load 12-15 kN/m2 distributed Server Load 7.5 kW per rack Point Load 20 kN/m2 PDU Type Liebert® MPH, Liebert® MPX rack PDUs or basic Knürr® DI Strip Fire Rating F30 No. of PDUs 8 (2 per rack) Material S275 steel Doors (H x W) 2350 mm x 900 mm (single door) Power Specifications Paint Specification Incomer Rating 125 A, 400 VAC, 3-phase, 50 Hz Wall Insulation 0.4 W/m2K ATS 125 A, ASCO® ATS Foundation Pillars or continuous beam Redundancy N+1 Wind load 30 m/s UPS 30 kW, modular Life Span 20 years Backup 10 minutes backup @ 30 kW load Cabling Overhead cable trays for energy cables, LAN cables and optical cables C4 medium (ISO 12944-5) n Controllable This solution, designed to meet Uptime Institute® tier 2 requirements, is one example of how Smart Solutions from Emerson Network Power can help achieve efficiency and availability for small to medium data centers. This design optimizes capacity – to ensure you do not oversize a solution, yet are able to scale as IT requirements change. EN317DRA-30KWSMOD ® Thermal Management Specifications Heat Load 35 kW Redundancy Cooling Unit N+1 Liebert® CRV 035, in-row cooler No. of Units 2 Cooling Type Direct expansion (DX) Condenser Placement On roof or on ground Outdoor Conditions -20 °C to + 48 °C, 50% RH (Summer), 100% RH (Winter) Indoor Conditions 20 °C cold aisle, 37 °C hot aisle, 45% RH 1 30 kW SmartMod™ Infrastructure Solution Key Technologies Liebert® DCF Server Rack Performance Highlights SmartMod™ solutions with containment technologies result in a superior Power Usage Effectiveness (PUE) performance and substantial savings in installation, energy usage and space utilization. The PUE of a SmartMod™ solution is more than 15-25% lower on average than that of a conventionally designed data center with the same capacity. Data Center PUE Comparison PUE Calculation Easily separates hot and cold air, increasing return air temperature to cooling units 30+% efficiency improvement Increases space efficiency, improves airflow Easy to install with modular roof and door systems ® Liebert CRV In-row, up to 40 kW capacity Thermal Variable capacity digital scroll compressor Management continuously adjusts airflow to rack temperatures, using up to 35% less cooling energy EC fans use 10-30% less energy than average standard AC motor Easy to direct airflow with adjustable baffles Enable Liebert® CRV thermal management Liebert® iCOM Enviromental units to work together Controls Simplify unit, zone and room control Dynamically optimize the control of airflow and cooling within the row Rated up to 600 VAC, 30 to 4000 Amps ASCO® Power Transfer Switches Active synchronization of onsite generating unit to the utility source Programmable microprocessor controller with keypad and LCD display Reliable and field-proven solenoid operating mechanism ensures maximum performance ® Easy to scale with 30, 60, 90, 120, 150 kW Liebert APM UPS System modules and redundant in 30 kW power cores 96% operating efficiency Modular, longer lasting batteries reduce TCO while improving availability Sliding rails and anti-static floor Controls power at the receptacle level Liebert® MPH & MPX Managed Monitors power, temperature and Rack PDU humidity at the strip level Highly configurable and hot swappable Aisle Containment 3 2.8 2.6 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Percent of Utilized IT Capacity 35 °C Ambient 35 °C Ambient 18 °C Ambient 18 °C Ambient Total PUE of Contained Solution Total PUE of Contained Solution Total PUE of Contained Solution with Energy Logic Improvements Total PUE of Contained Solution with Energy Logic Improvements Notes: Liebert ® CRV inlet air temperature 24˚C. PUE is a measure of how efficiently a computer data center uses its power; specifically, how much of the power is actually used by the computing equipment (in contrast to cooling and other overhead). To learn more about Energy Logic read the Energy Logic 2.0 e-Book at: EmersonNetworkPower.com/en-EMEA/Latest-Thinking/Energy-Logic. 42U high optimized rack system 600 mm, 800 mm widths 1100 mm, 1200 mm depths Improved airflow for cooling efficiency Faster moves/adds/changes with tool-less accessories and sliding rails © Emerson Network Power, Energy Systems, North America, Inc. 2014. Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson™, Consider it Solved, Avocent®, Knürr®, Liebert® and SmartMod™ are service marks and trademarks of Emerson Electric Co. Any other product, brand, or company names or logos are the property of the respective owner. 2 Conventional Data Center PUE For more details, please contact your local Emerson Network Power SmartMod infrastructure specialist or email EnergySystems@Emerson.com. While every precaution has been taken to ensure accuracy and completeness herein, Emerson Electric Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice. EN317DRA-30KWSMOD