Cooper B-Line Electrical Enclosures Catalog

advertisement
Climate Control Products
Air Conditioners
Type 12 Trimline Air-Cooled Panel-Mounted
Climate Control
KA4C7NP47R
Climate Control
KA4C4NP33L
KA4C2.0NP17L
Description
Innovations in technology have resulted in much denser
electronics packaging and smaller available panel sizes on
which to mount air conditioners. The TrimLine Series is the
response to these new packaging demands with the
Narrow 12” and 15” width panel mount air conditioners.
In addition to reducing the width of more traditional air
conditioner units, the TrimLine Series includes the
Condensate Evaporator, Low Temperature Control
(thermostat) and EMI/RFI Suppressor as standard
features.
The TrimLine Series consists of compact models in
2,000-2,500 BTU/H capacities, mid-size models, 33”
height, up to 4,000 BTU/H capacities and the full-size
models at 47” height up to 7,000 BTU/H. Each series of
models is designed with a minimum width to take up less
exterior cabinet space on the panel or door.
Integral to the TrimLine Series is the M/TAB (Mounting
Template and Assembly Bracket) system which makes
installing the TrimLine Series a simple and less timeconsuming task.
Outdoor or corrosive environments require weather
protection and/or special internal and external protective
coatings. For extreme ambient temperatures and/or
severely contaminated environments, the use of watercooled air conditioners is recommended.
Custom air conditioners can be designed and
manufactured to meet unique specifications. Contact
B-Line about modification and custom-design
capabilities.
Features
• All models UL/cUL Listed
• Tested and approved by UL for use with Type 12
enclosures
• UL/CSA ball bearing motor
• Filters
• Heavy duty steel with baked powder finish
• Exclusive M/TAB integral mounting system for quick,
easy installation
• Built-in Condensate Evaporator eliminates need for
draining normal condensate
• Thermostatic Control provides energy-efficient
operation and prevents over-cooling
• EMI/RFI Suppressor minimizes transient line spikes
during on/off cycling
• Six foot (minimum) SJT-3 wire power cord with plug
• Environmentally preferred CFC-Free R134a refrigerant
Discount Schedule: C2
Subclass: DT0
Notes: Data subject to change without notice. Consult factory for special requirements. Dimensions are in inches. Millimeters shown are for reference only.
376
Electrical Enclosures
Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com
Climate Control Products
Air Conditioners
Type 12 Trimline Air-Cooled Panel-Mounted
Climate Control
M/TAB Description
A highlight of the TrimLine Series is a new, revolutionary air
conditioner mounting system for cabinets and enclosures.
The M/TAB is standard on all TrimLine Air Conditioners.
This new integral system functions as a mounting template,
pre-installation hanger and final assembly bracket.
The M/TAB design simplifies the installation process by
eliminating the problem of handling flange-mounted air
conditioners. The solution is provided by following these
installation steps:
1) Use the M/TAB to drill holes for mounting and bolting
to the cabinet
2) Cut out the Supply and Return Air openings
3) Hang the air conditioner on the M/TAB
4) Secure the Air Conditioner to the M/TAB.
The M/TAB also allows for the quick removal and
transportation of the air conditioner, separate from the
equipment, for servicing or change to a different capacity
air conditioner or to a same-size heat exchanger.
Features
TrimLine Accessories & Options
•
•
•
•
•
•
•
•
•
•
•
•
Low Air Detectors
Cooling Effect Detector
Filter Recoating Adhesive
Filters for replacement
Internal corrosion resistant coatings
Lifting Eyes
Low Ambient Kit
Short Cycle Protector
Special materials or external finishes
Special motors, line cords or connectors
Weather Protection Kit
High capacity condensate evaporator
Discount Schedule: C2
Subclass: DT0
NP17 Series
Thermostat
Adjustment
Access
12.13
(308mm)
Climate Control
• No exposed rails or mounting flanges; aesthetically
pleasing while conserving cabinet space
• Ease of installation and one-piece design reduce
mounting errors and allows installer to operate selfsufficiently
• Functions as a pre-installation hanger and final assembly
bracket
• Installation is totally outside the cabinet; no clumsy
mounting from inside the cabinet
In order to use TrimLine Air Conditioners, including M/TAB,
to replace standard or other manufacturers’ units on
existing cabinets, a special Adapter M/TAB with
appropriate bolt holes and cutouts can be supplied.
M/TAB
Technical Data
Catalog
Number
BTU/H
Capacity
95/95 Rating
BTU/H
Ambient Temp F
(max./min.)
Volts
Hz
Running
Amps
Weight
KA4C2.0NP17L
2000
1420
125/50
115/100
60/50
6.7/6.5
59
K2A4C2.0NP17L
2000
1420
125/50
230/200
60/50
4.3
59
(lbs.)
17.50
(444mm)
9.00
Performance
KA4C2.0NP17L
Cooling Capacity (BTU/H)
(228mm)
12.25
(311mm)
(1) Filtered condenser air inlet (ambient air in)
(2) Condenser outlet (warm ambient air out)
(3) Warm air return from enclosure
(4) Cool air outlet to enclosure
12.25
Ambient Temperature (°F)
Operation within shaded area not recommended
(6) 1/4”-20 Weld Nuts
M/TAB
(311mm)
0.50
9.00
filter
(228mm)
Mounting Plan
11.25
(13mm)
6.13
0.50
(286mm)
3.13
(79mm)
(156mm)
(13mm)
0.38
(10mm)
typ.
6” Min.
5.00
(1.83m)
(127mm)
Power Cord
4.13
(105mm) 17.50
(444mm)
17.50
(444mm)
8.13
6.38
(206mm)
Weld nuts supplied for alternate mounting method to
maintain NEMA 12. Mounting Plans furnished on request.
12.13
0.38 (10mm) O.D.
condensate drain
(308mm)
0.38
(10mm) (8) .312 (10mm)
Dia. Holes
(162mm)
5.75
(146mm)
0.88
0.38 (22mm)
(10mm)
Notes: Data subject to change without notice. Consult factory for special requirements. Dimensions are in inches. Millimeters shown are for reference only.
377
Electrical Enclosures
Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com
Climate Control Products
Air Conditioners
Type 12 Trimline Air-Cooled Panel-Mounted
Climate Control
NP33 Series
Technical Data
Catalog
Number
BTU/H
Capacity
95/95 Rating
BTU/H
Ambient Temp F
(max./min.)
Volts
Hz
Running
Amps
Weight
KA4C4NP33L
4000
2680
125/50
115/100
60/50
12.8
90
K2A4C4NP33L
4000
2680
120/50
230/200
60/50
5.5
90
(lbs.)
12.50
(317mm)
Performance
M/TAB
Climate Control
Cooling Capacity (BTU/H)
KA4C4NP33L
Thermostat
Adjustment
Access
32.88
(835mm)
Ambient Temperature (°F)
9.50
Operation within shaded area not recommended
(241mm)
(1) Filtered condenser air inlet (ambient air in)
(2) Condenser outlet (warm ambient air out)
(3) Warm air return from enclosure
(4) Cool air outlet to enclosure
Mounting Plan
12.38
6” Min.
(314mm)
(1.83m)
Power Cord
M/TAB
9.50
Optional
(241mm)
0.94
(24mm)
10.50
(267mm)
9.00
(228mm)
Filter
(8) .312 (10mm)
Dia. Holes
32.88
32.88
(835mm)
(835mm)
8.00
19.63
(203mm)
(498mm)
typ.
7.69
(195mm)
0.38 (10mm) O.D.
Condensate Drain
9.13
12.50
Optional
Condensate Drain
Locations
(314mm)
0.56
(14mm)
(232mm)
2.75
11.19
(70mm)
(284mm)
0.38
(10mm)
Notes: Data subject to change without notice. Consult factory for special requirements. Dimensions are in inches. Millimeters shown are for reference only.
378
Electrical Enclosures
Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com
Climate Control Products
Air Conditioners
Type 12 Trimline Air-Cooled Panel-Mounted (cont.)
Climate Control
NP47 Series
Technical Data
Catalog
Number
BTU/H
Capacity
95/95 Rating
BTU/H
Ambient Temp F
(max./min.)
Volts
Hz
Running
Amps
Weight
KA4C7NP47R
7000
4750
125/50
115/100
60/50
16.5
150
K2A4C7NP47L
7000
4750
125/50
230/200
60/50
8.6
150
(lbs.)
15.12
(384mm)
Performance
Cooling Capacity (BTU/H)
KA4C7NP47R
47.18
(1198mm)
Climate Control
Ambient Temperature (°F)
Operation within shaded area not recommended
12.22
(310mm)
(1) Filtered condenser air inlet (ambient air in)
(2) Condenser outlet (warm ambient air out)
(3) Warm air return from enclosure
(4) Cool air outlet to enclosure
15.12
1.12
(384mm)
(28mm)
12.22
12.39
(310mm)
Mounting Plan
(315mm)
Power
Switch
10.50
2.25
1.08
7.80
(27mm)
(198mm)
Power
Cord
(267mm)
(57mm)
11.88
12.16
(302mm)
(309mm)
typ.
6.92
10.25
Mounting
Hooks
typ.
Filters
(27mm)
typ.
(1198mm)
(176mm)
1.06
(260mm)
47.18
33.65
12.89
(327mm)
29.29
7.00
(855mm)
(744mm)
(178mm)
typ.
0.43
12.80
7.00
(11mm)
1.10
(178mm)
10.85
(275mm)
typ.
typ.
(178mm)
(108mm)
typ.
typ.
1.36
(34mm)
(325mm)
1.16
(29mm)
0.34
(8mm)
1.75
(44mm)
13.31
0.84
typ.
(2) places typ.
(5) places
3.05
1.30
(338mm) (33mm) (77mm)
(21mm)
0.50
12.80
(77mm)
4.26
(325mm)
(28mm)
typ.
(221mm) 8.38
(213mm)
Drain
3.05
7.02
8.71
Drain
(12) .312 (10mm)
Dia. Holes
(13mm)
8.54
1.89
(217mm)
(48mm)
12.02
1.31
(305mm)
(33mm)
Notes: Data subject to change without notice. Consult factory for special requirements. Dimensions are in inches. Millimeters shown are for reference only.
379
Electrical Enclosures
Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com