230/460-3-60 POWER BY OTHERS 208Y/120-3-60 POWER BY OTHERS T1 This unit shall be installed and wired in accordance with ANSI/NFPA 70, National Electric Code, and all applicable Federal, State, and Local Codes. Failure to read and comply with this and other warnings may result in serious bodily injury or death, and/or property damage. L2 OL1 T2 L3 OL1 T3 MOTOR 2HP BRAKE D F JUNCTION BOX WITH LIMIT SWITCHES ON MAT LIFTER FRAME NEXT TO MOTOR 1/2" CONDUIT/SEALTITE 3#14 (T1, T2, T3) 7#16 (10, 12, 20, 22, 60, 61, & GRD) 8#16 FLAT CABLE BLK - 10 RED - 12 BLU - 20 ORG - 22 YEL - 60 BRN - 61 RED/BLK - SP FINAL BLU/BLK - SP CONNECTIONS (BY OTHERS) OL2 1T1 OL2 2T2 OL2 3T3 2 A 230V 1 A 460V UGLS R UP OFF X X FWD X MOTOR 2HP BRAKE D 120V KEYSWITCH NEUTRAL UP X LS-1 DOWN UP X DOWN UGLS DOWN 11 10 FUSED POWER SUPPLY (BY OTHERS) FUSE SIZE (DUAL-ELEMENT TIME-DELAY) 230-3-60 12 A 460-3-60 6A UGLS 30 12 U 22 LGLS 20 LGLS UGLS 12 LGLS 22 30 OL1 U FWD X REV 40 50 60 LS 1 OL1 LS-1 UPPER CONTACT PROXIMITY SWITCH 1 (EMERGENCY OVERTRAVEL)(TRIPPED IF LOADBAR IS TOO HIGH) UGLS UPPER GEARED LIMIT SWITCH (TRIPPED WHEN LOADBAR IS AT DESIRED UP POSITION) D FUSED POWER SUPPLY (BY OTHERS) FUSE SIZE (DUAL-ELEMENT TIME-DELAY) 208Y/120-3-60 10 AMP R - TERMINALS IN MAT LIFTER UNIT RAISE MAT LIFTER CONTROL ENCLOSURE (WALL MOUNTED) TO BE IN SIGHT OF, AND WITHIN 50FT OF MAT LIFTER CONDUIT OPENINGS BY OTHERS OFF LOWER - TERMINALS IN CONTROLS MOUNTED TO WALL - TERMINALS IN MAT LIFTER UNIT POWER FEED (BY OTHERS) (L1, L2, L3, NEUTRAL, GROUND) 208Y/120-3-60 POWER BY OTHERS DANGER Before installing, removing, inspecting, or performing any maintenance on this unit, the main switch shall be de-energized. Lock and tag the main switch in the de-energized position in accordance with ANSI Z244.1. 230/460-3-60 POWER BY OTHERS OL1 U L1 OL1 L2 OL1 L3 This unit shall be installed and wired in accordance with ANSI/NFPA 70, National Electric Code, and all applicable Federal, State, and Local Codes. FIELD WIRING PROVIDED BY OTHERS - TERMINALS IN CONTROLS MOUNTED TO WALL LS-1 UPPER CONTACT PROXIMITY SWITCH 1 (EMERGENCY OVERTRAVEL)(TRIPPED IF LOADBAR IS TOO HIGH) UGLS UPPER GEARED LIMIT SWITCH (TRIPPED WHEN LOADBAR IS AT DESIRED UP POSITION) LGLS LOWER GEARED LIMIT SWITCH (TRIPPED WHEN LOADBAR IS AT DESIRED LOWER POSITION) FIELD WIRING PROVIDED BY OTHERS REV 5 JUL 01 DP (ADDED 2ND TRVL MOTOR, CUSTOMER FUSES WERE 10A & 6A) LGLS LOWER GEARED LIMIT SWITCH (TRIPPED WHEN LOADBAR IS AT DESIRED LOWER POSITION) 1/2 CONDUIT BY OTHERS 4#14 (T1, T2, T3, GRD) 4#16 (10, 12, 20, 22) OL2 61 F D DN ADJUST UP ADJUST 11 10 REV POWER FEED (BY OTHERS) (L1, L2, L3, GROUND) DANGER Before installing, removing, inspecting, or performing any maintenance on this unit, the main switch shall be de-energized. Lock and tag the main switch in the de-energized position in accordance with ANSI Z244.1. 6.5 A 208V Failure to read and comply with this and other warnings may result in serious bodily injury or death, and/or property damage. LS-1 DOWN MAT LIFTER CONTROL ENCLOSURE (WALL MOUNTED) TO BE IN SIGHT OF, AND WITHIN 50FT OF MAT LIFTER CONDUIT OPENINGS BY OTHERS REV T3 MOTOR 1/2HP 115 V UP 1/2 CONDUIT BY OTHERS 6#14 (T1, T2, T3, 1T1, 1T2, 1T3) 6#16 (10, 12, 20, 22, 60, 61) RAISE T2 OL1 U X2 20 FWD NEUTRAL T1 OL1 L3 JUNCTION BOX WITH LIMIT SWITCHES ON MAT LIFTER FRAME NEXT TO MOTOR X1 KEYSWITCH OFF LOWER This unit shall be installed and wired in accordance with ANSI/NFPA 70, National Electric Code, and all applicable Federal, State, and Local Codes. OL1 L2 DN ADJUST J-BOX (BY OTHERS) MOUNTED ON TOP OF MONORAIL TRACTOR DRIVE L1 2 A 230V 1 A 460V LGLS LS 1 8#14 FLAT CABLE BLK - T1 RED - T2 BLU - T3 ORG - GRD YEL - SP BRN - 1T1 RED/BLK - 1T2 BLU/BLK - 1T3 DANGER Before installing, removing, inspecting, or performing any maintenance on this unit, the main switch shall be de-energized. Lock and tag the main switch in the de-energized position in accordance with ANSI Z244.1. MOTOR 1/2HP (SECOND MOTOR FOR SIDEWAYS TRAVELING UNIT ONLY) UP ADJUST T1 T2 T3 6.2 A 230V 3.1 A 460V MOTOR 2HP Failure to read and comply with this and other warnings may result in serious bodily injury or death, and/or property damage. BRAKE OL1 T1 L2 OL1 T2 L3 OL1 T3 U L1 This unit shall be installed and wired in accordance with ANSI/NFPA 70, National Electric Code, and all applicable Federal, State, and Local Codes. 6.5 A 208V MOTOR 2HP BRAKE D NEUTRAL D Failure to read and comply with this and other warnings may result in serious bodily injury or death, and/or property damage. KEYSWITCH X1 UP JUNCTION BOX WITH LIMIT SWITCHES ON MAT LIFTER FRAME NEXT TO MOTOR X X2 115 V 120V UGLS X DOWN 10 11 UGLS 12 30 U OL1 LGLS 22 DN ADJUST UP ADJUST D LS-1 UPPER CONTACT PROXIMITY SWITCH 1 (EMERGENCY OVERTRAVEL)(TRIPPED IF LOADBAR IS TOO HIGH) UGLS UPPER GEARED LIMIT SWITCH (TRIPPED WHEN LOADBAR IS AT DESIRED UP POSITION) FUSED POWER SUPPLY (BY OTHERS) FUSE SIZE (DUAL-ELEMENT TIME-DELAY) 230-3-60 10 A 460-3-60 5 A 3T3 2.2 A 208V (SECOND MOTOR FOR SIDEWAYS TRAVELING UNIT ONLY) NEUTRAL LGLS LOWER GEARED LIMIT SWITCH (TRIPPED WHEN LOADBAR IS AT DESIRED LOWER POSITION) FIELD WIRING PROVIDED BY OTHERS 4#14 SO CABLE BLK - 1T1 RED - 1T2 WHI - 1T3 GRN - GRD J-BOX (BY OTHERS) MOUNTED ON TOP OF MONORAIL 8#14 FLAT CABLE BLK - T1 RED - T2 BLU - T3 ORG - GRD YEL - SP BRN - 1T1 RED/BLK - 1T2 BLU/BLK - 1T3 UP X LS-1 DOWN UP X DOWN 11 10 20 1/2 CONDUIT BY OTHERS 6#14 (T1, T2, T3, 1T1, 1T2, 1T3) 6#16 (10, 12, 20, 22, 60, 61) TRACTOR DRIVE RAISE OFF LOWER FWD OFF - TERMINALS IN MAT LIFTER UNIT REVISED 5 JUL 01 DP OFF LOWER MAT LIFTER CONTROL ENCLOSURE (WALL MOUNTED) TO BE IN SIGHT OF, AND WITHIN 50FT OF MAT LIFTER CONDUIT OPENINGS BY OTHERS POWER FEED (BY OTHERS) (L1, L2, L3, GROUND) MOTOR 1/2HP LGLS FWD X LGLS UGLS 12 22 REVISED 11 MAY 01 DP REV MAT LIFTER CONTROL ENCLOSURE (WALL MOUNTED) TO BE IN SIGHT OF, AND WITHIN 50FT OF MAT LIFTER CONDUIT OPENINGS BY OTHERS POWER FEED (BY OTHERS) (L1, L2, L3, NEUTRAL, GROUND) FUSED POWER SUPPLY (BY OTHERS) FUSE SIZE (DUAL-ELEMENT TIME-DELAY) 208Y/120-3-60 12 A 30 U OL1 D REV FWD X REV 40 50 60 F 61 R - TERMINALS IN CONTROLS MOUNTED TO WALL RAISE 2.2 A 208V MOTOR 1/2HP LS 1 LS 1 1/2 CONDUIT BY OTHERS 3#14 (T1, T2, T3,) 4#16 (10, 12, 20, 22) 2T2 OL2 DN ADJUST UP ADJUST 1L1 20 LGLS 1T1 OL2 R KEYSWITCH UGLS OL2 LS-1 DOWN UP F JUNCTION BOX WITH LIMIT SWITCHES ON MAT LIFTER FRAME NEXT TO MOTOR 8#16 FLAT CABLE BLK - 10 1/2" CONDUIT/SEALTITE RED - 12 3#14 (T1, T2, T3) BLU - 20 7#16 (10, 12, 20, 22, ORG - 22 60, 61, & GRD) YEL - 60 BRN - 61 RED/BLK - SP FINAL BLU/BLK - SP CONNECTIONS (BY OTHERS) 6/10A 4#14 SO CABLE BLK - 1T1 RED - 1T2 WHI - 1T3 GRN - GRD 6.2 A 230V 3.1 A 460V 6/10A OL1 U L1 1L1 DANGER Before installing, removing, inspecting, or performing any maintenance on this unit, the main switch shall be de-energized. Lock and tag the main switch in the de-energized position in accordance with ANSI Z244.1. LS-1 UPPER CONTACT PROXIMITY SWITCH 1 (EMERGENCY OVERTRAVEL)(TRIPPED IF LOADBAR IS TOO HIGH) UGLS UPPER GEARED LIMIT SWITCH (TRIPPED WHEN LOADBAR IS AT DESIRED UP POSITION) LGLS LOWER GEARED LIMIT SWITCH (TRIPPED WHEN LOADBAR IS AT DESIRED LOWER POSITION) FIELD WIRING PROVIDED BY OTHERS - TERMINALS IN CONTROLS MOUNTED TO WALL - TERMINALS IN MAT LIFTER UNIT REV 5 JUL 01 DP (ADDED 2ND TRVL MOTOR, CUSTOMER FUSES WAS 12A) OL2