Appendix B: Electrical Assessment Brown County Library Central Branch – Building Assessment Lighting Controls Description The current lighting control system consists of circuit breakers in the main branch panels for each floor. By turning on each noted breaker, banks of lights come on throughout the main floor space as well as provide power to the lighting in the offices. Currently, either maintenance or security personnel are responsible for turning on and off all lighting in the facility. The offices also have local light switches that turn on and off the lighting. Only a few locations exist where occupancy sensors turn on and off the lighting. Recommendations The lighting control system as it exists today would not meet the current energy code. The energy code mandates that all lighting in a facility be automatically controlled such that lighting can be automatically turned off, either at a predetermined time or by a device such as an occupancy sensor. For a facility of this size and use, a low voltage control system may be more appropriate due to the large open spaces on the lower, first and second floors. A recommendation would be to provide a low voltage lighting controller on the main usage floors and provide occupancy sensors for other spaces throughout the facility. Emergency Lighting Controls Description The current Emergency lighting control system will energize lighting upon loss of building power, however, the emergency lighting in the stairwells will only be 'on' if the keyed switch in the main stairwell on the north face of the building is in the 'on' position, otherwise all stairwell lighting will be off. Recommendations The emergency lighting located in the stairwells should be unswitched and should operate during any kind of event requiring emergency lighting. This lighting should be taken off the keyed switch or be connected just ahead of the switch. An occupancy sensor could help to turn off lighting if this is a concern. Appendix B: Electrical Assessment Brown County Library Central Branch – Building Assessment Main Disconnect Switch on Main Service Description The main power disconnect switch for the building located on the incoming service switchboard in the buildings basement is in need of replacement. Due to the age of this device, it is no longer readily available from the manufacturer (Sq-D). The replacement of this disconnect switch is very important for several reasons; 1) Circuit Breaker may not operate properly when a fault occurs (may not open if experiencing a fault) 2) May not reset (close) after opening 3) May not protect against external fault which may be as high as 100,000 AIC Recommendations Due to the age of this equipment, the cost of replacing this device will be extreme. A cursory review of this scenario with the equipment manufacturer has suggested that a complete replacement of the main service switchboard, including all circuit breakers and main switch will be approximately the same as replacing just the main breaker. This equipment should be replaced. Exterior Emergency Lighting Description There are no exterior emergency lighting fixtures Recommendations This is a Life Safety concern. At the time this facility was constructed, the facility met the building code as it pertained to exterior emergency lighting. In today's code, a minimum of a two lamped emergency fixture is required at each required emergency exit for a building. Emergency Lighting Description Interior Emergency lighting does not meet code minimums of an average of 1 footcandle (fc) and a minimum of .1 fc along all paths of egress. Recommendations This is a Life Safety concern. Additional emergency lights should be located throughout the facility to provide the code mandated emergency lighting required to safely get library patrons and personnel safely out of the building. Key areas would be each of the office and workroom areas as well as Children’s, Popular Library, Reference, and second floor book areas. Appendix B: Electrical Assessment Brown County Library Central Branch – Building Assessment Rooftop Disconnect Switch Description Disconnect Switch on Exterior Rooftop Unit is rusted badly Recommendations The disconnect switch on the condensing unit located on the roof should be replaced. Branch Panels Description All building branch panels are manufactured by Square-D and come in various sizes due to the requirements of the loads each panel is serving. These panels are original to the building and are approaching 36 years of use. It was noted that these panels have not been through a preventative maintenance program (cleaning of panel board interior, checking breakers). Circuit breakers should be tested and cleaned periodically to insure proper operation. A panel board and it’s integral bus bars have a useful life of approximately 25 years and can last much longer (these are fixed pieces of metal which generally will not undergo any changes over time). However, the circuit breakers that are connected to the bus bars and protect the loads on a circuit have a useful life that can be much less. Circuit breakers life span is influenced by the stability of the electricity that flows through it, the amount of current the load is drawing, the heat generated on the circuit and whether or not the circuit breaker has previously tripped. Recommendations A building preventative maintenance plan should be created to include the cleaning and testing of the circuit breakers in each of the panel boards once every five years. A qualified Electrical Contractor or Testing Agency should be engaged to test and clean this equipment. Arc Fault Protection Description Flash Protection ratings are not identified on panels. This is a more recent addition to the National Electric Code (NEC) in 1999 and is now being enforced by Local Authorities Having Jurisdiction. Recommendations An Arc Flash Study involving all branch panels including the main service switchboard should be completed such that Arc Flash Hazard identification may be placed on each piece of electrical equipment. This identification will help any qualified or maintenance personnel review the potential hazards prior to working on these pieces of electrical equipment. These pieces of identification provide assistance in determining severity of potential exposure, planning safe work practices, and selecting personal protective equipment. Appendix B: Electrical Assessment Brown County Library Central Branch – Building Assessment Stairwell Exit Lighting Description Exit Lighting in the stairwells is not adequate. Recommendations In general, exit lighting in the stairwells is found on the floor exiting to grade. What has been provided in some instances is a luminescent sticker located on the exit door. A requirement of an exit sign is that it produces 5 footcandles of illumination 1 foot from its face. These luminescent signs do not provide this. Exit lighting if on other floors that do not exit to grade should clearly identify the path of egress. Data / Communications IDF Description The Intermediate Distribution Frame (IDF) currently located on the second floor, just out of main circulation is located in an area that is not secure. This equipment provides connections to the Libraries computers and telephones. Recommendations The IDF should be relocated to a room that is locked and is not open to the public. Elevators Description Elevators are not reliable - may stop working prior to letting passengers off at predetermined floor. The inconsistent operation of the elevators may be an effect of overheating of the elevator controllers. The elevator controllers are remotely located in the basement which can be accessed through the periodical storage location. The doors on each of the elevator controllers are currently left open to allow for circulation of air so that the equipment won't overheat. However, the heat in this room builds up and may contribute to the stoppage problems for the elevators. These elevators are very old. The elevator manufacturer has stated that the useful life of the elevators is 20 years. These elevators are nearing 37 years of operation. Recommendations Provide additional room make-up air to allow the equipment to operate within the temperature tolerance for the equipment. A comprehensive study by qualified elevator maintenance personnel should review the existing elevator configuration and provide recommendations based upon findings. These elevators are Dover (now Thyssen Krupp) elevators. The nearest Dover representative is located in Madison, WI. Option 1: Provide additional make up air into the elevator equipment room. Appendix B: Electrical Assessment Brown County Library Central Branch – Building Assessment Option 2: Replace the two elevator controllers with new control panels and connect to existing elevators. Option 3: Modify the existing staff/freight elevator to accept library patrons with disabilities. Interior Building Lighting Description The building lighting system incorporates a few different technologies. For nearly 70% of the lighting fixtures, 4 ft. T12 lamps are used in combination with energy saving ballasts. These lamp and ballast combinations are primarily found in the indirect lighting found between the double tees in the precast concrete structure. These fixtures provide a gentle illumination throughout the facility but utilize much more energy than what is necessary due to lamp and ballast technology from 20-30 years ago and the fact that the lighting is located inside of the double tees of the precast. T-12 U tube lamps are utilized in the fixtures of the corridors of the third floor. T8 FO32W lamps are used in the leased area on the third floor. On the second floor, in the offices and on the first floor in the primary circulation areas, it was noted that light fixtures used louvers that contain 1"x1"x1" parabolic louvers that direct the light from the lamps inside the fixtures straight down to the floor without allowing the light to spread out . This could be seen in our walkthrough's with a light meter. Directly below one of these paracube fixtures a reading was registered of 56 footcandles and two feet over a reading of 20 footcandles registered. Recommendations The building lighting systems should undergo a retrofit. At a minimum, lighting systems should be changed to incorporate T8 lighting technology with electronic ballasts (potentially 32W lamps or even 25W lamps with high performance electronic ballast). Color temperature of the lamps should be looked at which can allow for a space to look brighter (3500 degree Kelvin is an accepted standard, but 4200 degree Kelvin may make a space look brighter). Additionally, a study should be completed to determine a more efficient way to distribute lighting throughout the library. Recommendations to include lowering the existing light fixtures located inside each of the double tees or changing those fixtures all together and replace with a fixture that offers both up lighting and down lighting which allows some of the light to come out of the bottom of the fixture. Additionally, the paracube fixtures may be appropriate for some of the library spaces, but should be looked at for the main circulation area on the first floor and throughout the offices on the second floor. Appendix B: Electrical Assessment Brown County Library Central Branch – Building Assessment Lighting – Book Unloading Description The lighting levels in the book unloading area are not where they should be. Lighting ranging from 68 footcandles directly beneath the light fixture to below 7 footcandles along the room edges has been measured. For the work that takes place in this room, lighting levels need to be more consistent throughout the room (typically 35-50 footcandles). Recommendations Lighting in this space should be changed. A potential layout could be to have two 1x4 fixtures with two lamps each located 6 ft on center oriented in the north/south direction in this room. Lighting – Stack Areas Description Lighting levels in the book stack areas on the second floor are lower than industry standards. During our walkthrough on July 15, 2009 at 10:00pm, a light meter was used to measurement horizontal footcandles. Results were registered in the range of 4.6 - 22.4 footcandles in the low ceiling area just west of the staircase and in the higher ceiling area in the northwest corner of the building footcandle measurements were registered between 8.9 - 38.7 footcandles. Vertical footcandles were measured on August 19. These results showed footcandles ranging from 1.4-3.1 footcandles at 12 inches above the floor in the low ceiling area to 9.3-10.2 footcandles near the top of the stack. In the higher ceiling area vertical footcandle measurements registered between 3.2-5.4 footcandles at 12 inches above the floor and 16.8-18.4 footcandles near the top of the stack. The current lighting layout does not meet the suggested recommendations for lighting in a library stack environment (see below). Recommendations Lighting standards for library stack areas suggest vertical lighting levels no less than 6 footcandles at 12” above the floor plane and a maximum of 35 vertical footcandles at any point along the stack face for a 6 to 1 maximum to minimum ratio across the stack face. Option 1: Provide lighting between the stacks and provide a direct/indirect lighting approach allowing light to wash the ceiling and allow a direct component (1015%) of light down between the stacks. In the low ceiling area, lighting should hang between 12-18 inches below the ceiling. Option 2: Provide lighting between the stacks and mount light fixtures directly to each stack, making the lighting integral to the stacks. Provide lighting capable of direct/indirect lighting with 10-15% down lighting component. Appendix B: Electrical Assessment Brown County Library Central Branch – Building Assessment Exterior Lighting Description During a site visit on the evening of July 15, 2009 lighting measurements were taken around the facility to determine lighting levels for safety and for normal walking about the site. Along the south side of the building, lighting was measured at between .2 - .4 footcandles, .1 - .4 footcandles was measured along the walkway on the west side, .2 – 5.3 footcandles were measured along the north side with levels of 1.1 – 3.4 footcandles measured in the parking area and drive up area. Additionally, exterior lighting was measured at 3.4 – 5.1 footcandles along the northeast corner of the building, 0.0 footcandles were measured from middle of the east side of the building to the southeast corner of the property. The Illuminating Engineering Society of North America (IESNA) provides a recommendation of between .6 and 1.0 footcandles along a walkway for commercial and intermediate areas. The IESNA recommends lighting in the range of .6 to .9 footcandles for a general parking area. The parking lot lighting is adequate except for the southeastern corner of the building. Additional lighting should be provided in this area. Also, during the walkthrough, it was noticed that two fixtures had lamps that were not on (exit door in northwest corner and a newer metal halide fixture under the canopy along the north walk way). Recommendations Lighting levels should be increased around the perimeter of the building for both security and safety. Additional light poles should be added near the south entrance to the parking lot. The addition of two poles along the entrance drive will add sufficient lighting to the area per IES recommendations. Option 1: Trim some of the foliage in the immediate area. There are several trees that are blocking lighting from being able to illuminate the area. Option 2: Replace the lighting technology from Mercury Vapor lamps and ballasts to a different technology such as induction lighting or LED lighting. Both of these style lamps have a lamp life that may approach 100,000 hours and could provide more illumination to the walk ways.