6-461.1 September, 2009 WIRING DIAGRAMS gas-fired, power vented and separated combustion unit heaters for models HD/HDB, HDS/HDC, PTS/BTS, PTC WARNING 1. Fuel supply shall be shut-off and the electrical power disconnected before proceeding with the installation. Failure to do so could result in fire, explosion, electrical shock, or the unit starting suddenly resulting in injury. 2. All units must be wired strictly in accordance with wiring diagram furnished with the unit. Failure to wire this unit according to this wiring diagram could result in a hazard to persons and property. For deviations, contact the factory. 3. All wiring must be done with a wiring material having a temperature rating of at least 105°C. IMPORTANT 1. The use of this manual is specifically intended for a qualified installation and service agency. All installation and service of these kits must be performed by a qualified installation and service agency. 2. These instructions must also be used in conjunction with the Installation and Service manual originally shipped with the appliance being converted, in addition to any other accompanying component supplier literature which supersedes these instructions. Diagram Selection Diagrams are provided for both single and three-phase circuits, and are readily identified in the selection table on page 2. The selection table enables easy selection of the correct wiring diagram after the electrical components of the unit heater have been determined. Abbreviations and Symbols To facilitate interpretation and enable simplification the abbreviations and symbols have been selected as recommended by ANSI (American National Standards Institute) and NEMA (National Electrical Manufacturers Association) standards. XFMR or TR H1, H2, etc. X1, X2, etc. V Hz ø RC G H SW HI LO C “J” Box S/W O.L.C. SPDT DPDT VA L1, L2, L3 T1, T2, T3 Transformer Transformer Primary Terminals Transformer Secondary Terminals Volts Hertz Phase Relay Contactor Coil Ground Hot Switch High Low Common Junction Box Summer/Winter Switch Overload Contacts Single Pole Double Throw Switch Double Pole Double Throw Switch Volt-Ampere Load Terminals (Connect to Supply Voltage) Motor or Motor Starter Terminals Wire Color Coding BK Black BR Brown BL Blue R Red W White GY Gray Y Yellow NOTE: As indicated in every diagram, all wiring must comply with the National Electrical Code and all local codes. All components must agree with their respective power source. THIS MANUAL IS THE PROPERTY OF THE OWNER. PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB. Modine Manufacturing Company has a continuous product improvement program, and therefore reserves the right to change design and specifications without notice. WIRING DIAGRAM SELECTION Select the correct wiring diagram as follows: 1. 2. Determine the 12 digit unit heater model number. Example: PTS350SS0122 Breakdown the model number into the following parts (using the above example): a. Model: PTS b. Size : 350 c. Power Code: 01 d. Control Code: 22 Review the model number breakdown against Table 2.1 to select the correct wiring diagram. For the example in Step 2 above, the correct wiring diagram is located on page 6. Review Table 2.2 to determine if any additional wiring diagrams are necessary based on accessories included. 3. 4. Table 2.1 – Unit Heater Wiring Diagram Page Location Index Propeller Type Model Size Power Code Supply Voltage HD/HDS 30-125 01 c 115V/1ph 150-350 PTC HDB/HDC Blower 01 c 115V/1ph PTS Control Code 11 or 21 Single Stage Wiring Diagram 5H079963B1 12 or 22 Two Stage 5H079963B2 4 11 or 21 Single Stage 5H079963B1 3 Gas Controls Page 3 12 or 22 Two Stage 5H079963B2 4 11 or 21 Single Stage 5H079963B3 5 400 01 c 115V/1ph 12 or 22 Two Stage 5H079963B4 6 135-215 01 c 115V/1ph 11 or 21 Single Stage 5H080716B1 11 260-310 01 c 115V/1ph 11 or 21 Single Stage 5H080716B2 12 11 or 21 Single Stage 5H079963B1 3 12 or 22 Two Stage 5H079963B2 4 11 or 21 Single Stage 5H079963B1 3 12 or 22 Two Stage 5H079963B2 4 11 or 21 Single Stage 5H080273B1 7 12 or 22 Two Stage 5H080273B2 60-125 150 BTS 01 d 115V/1ph 01 d 115V/1ph 02, 13, 24,35 d 115/230V/1ph 8 08, 11, 19, 22, 30, 33, 38, 11 or 21 Single Stage 5H080274B1 9 41, 42, 44, 49, 53, 55, 60, 208/230/460/575V/3ph 12 or 22 Two Stage 5H080274B2 10 64, 66, 71, 75, 77 d c All propeller models (HD/HDS/PTS/PTC) are Power Code 01 for 115V/60Hz/1ph supply voltage only. To operate the unit on a supply voltage other than 115V/1ph, an accessory step down transformer is required. Refer to the latest revision of Literature #6-567 for instructions on properly wiring the unit heater and transformer. 150-400 d All blower models (HDB/HDC/BTS) that are operated with a supply voltage other than 115V/1ph, an accessory step down transformer is required. Refer to the latest revision of Literature #6-567 for instructions on properly wiring the unit heater and transformer. Table 2.2 – Accessory Wiring Diagram Page Location Index Model 2 Accessory Page All Thermostat with Fan On/Auto Subbase Switching 13 All Thermostat without Fan On/Auto Subbase Switching and Summer/Winter Switch 13 All Wiring Multiple Single Stage Unit Heaters to a Single Thermostat 14 PTC Terminal Board Jumper Removal for Accessory Wiring 14 6-461.1 6-461.1 C R W G Y R WH FLAME ROLLOUTS (SEE NOTE 6) 1 4 7 2 5 8 3 6 9 BL R SEC COM COM N E U T R A L N E U T R A L 24VAC L1 L1 L1 IND EAC EAC/BLO IND PARK XFMR PARK M1 UT LABEL COOL HONEYWELL LABEL L2, (WH) R Y L1, (BK) BK WH SWITCH CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. ATTACH WIRES NOT USED TO "PARK" TERMINALS P1-8 P1-3 P1-6 P1-5 P1-4 NTRL P1-9 NTRL P1-2 MV C NTRL R P1-7 24V COM SEC 115V L1 NTRL 6. TWO SWITCHES: 30-75, ONE SWITCH: 100-125 NOT USED ON 150-400 UNITS. WIRING DIAGRAM, SINGLE STAGE W * INTEGRATED CONTROL EAC SPARK IGNITOR 7. OPTIONAL UNIT DISCONNECT SWITCH. 5H079963B1 REV L XFMR IND BLOWER MOTOR GND 115V Unit Power 5H079963B1 COM FAN MOTOR L1 INDUCER MOTOR REFER NOTE 7 *SHOWN WITH UNITED TECHNOLOGIES LABEL, SEE CHART FOR OTHER LABELS 5. USED ON PROPELLER MODELS 100 AND LARGER. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. WH-NEUTRAL BK-HI BL-MED RED-LO 24 120 PE MOTOR REFER NOTE 7 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. NOTES TO INSTALLER: SINGLE STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT LIMIT CONTROL (SEE NOTE 5) Y PIN 6 PIN 5 Y FOR BLOWER MOTORS, LIMIT CONTROL PRESSURE SWITCH LOW VOLTAGE THERMOSTAT (BY OTHERS) O IGNITION CONTROL SPARK IGNITOR 115V/60HZ/1Ø POWER CIRCUIT BREAKER (BY OTHERS) CALL FOR HEAT L2, (WH) L1, (BK) THERMOSTAT GR, (G) ROLLOUT GND HIGH LIMIT FLAME SENSOR ROLLOUT GAS VALVE BK 115V/60HZ/1Ø L1 L2 CIRCUIT BREAKER (BY OTHERS) PRESSURE INDICATES TERMINAL BOARD CONNECTION HIGH LIMIT 24V GAS VALVE LINE FUSE WIRING LEGEND FLAME SENSOR FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODELS HD/HDB, HDS/HDC, PTS/BTS 3 6-461.1 LIMIT CONTROL (SEE NOTE 5) R FLAME ROLLOUTS (SEE NOTE 6) CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. UNITS ARE FACTORY WIRED FOR HIGH SPEED OPERATION. ATTACH WIRES NOT USED TO "PARK" TERMINALS WH-NEUTRAL BK-HI BL-MED RED-LO R COM 24V FS IND L1 C R HEAT W2 UT LABEL PARK O PARK 1 4 7 2 5 8 3 6 9 BL IGNITION CONTROL SPARK IGNITOR FLAME SENSOR G WH HI L2, (WH) BK Y BK WH SWITCH 7. OPTIONAL UNIT DISCONNECT SWITCH. 6. TWO SWITCHES: 30-75, ONE SWITCH: 100-125 NOT USED ON 150-400 UNITS. 5. USED ON PROPELLER MODELS 100 AND LARGER. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. 24 120 PE MOTOR REFER NOTE 7 COM XFMR FAN MOTOR GND 115V/60HZ/1Ø POWER L2, (WH) CIRCUIT BREAKER (BY OTHERS) L1, (BK) 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. NOTES TO INSTALLER: L1, (BK) R TWO STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT Y LO COM W1 Y HONEYWELL GAS VALVE MOTOR LEAD COLOR FOR DIRECT DRIVE BLOWER MOTORS ONLY. LIMIT CONTROL PRESSURE SWITCH PIN 8 Y HI LOW VOLTAGE THERMOSTAT (BY OTHERS) CALL FOR FAN 1ST STAGE 2ND STAGE M COM COM WHITE ROGERS GAS VALVE P6 P9 R INDUCER MOTOR G IND L1 L2 W2 HEAT T-STAT W1 24V 115V BLOWER MOTOR P2 GND P4 P7 HI M COM LO HONEYWELL GAS VALVE FS WIRING DIAGRAM, TWO STAGE HI WHITE ROGERS GAS VALVE COM P8 PRESSURE SWITCH P3 * INTEGRATED CONTROL COM SPARK IGNITOR 115V Unit Power 5H079963B2 24V L1 HI IND REFER NOTE 7 ROLL OUT ROLL OUT 115V Unit Power HIGH LIMIT 115V/60HZ/1Ø CIRCUIT BREAKER (BY OTHERS) W2 INDICATES TERMINAL BOARD CONNECTION W1 24V CALL FOR HEAT HIGH LIMIT LO FIRE LINE HI FIRE WIRING LEGEND FLAME SENSOR 4 FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODELS HD/HDB, HDS/HDC, PTS/BTS 6-461.1 C R W 1 4 7 2 5 8 3 6 9 R SEC COM COM N E U T R A L 24VAC L1 IND N E U T R A L L1 L1 IND EAC XFMR PARK COOL PARK UT LABEL EAC/BLO M1 HONEYWELL LABEL SWITCH REFER NOTE 6 L2, (WH) L1, (BK) R Y BK WH PE MOTOR L2, (WH) COM 0 6. OPTIONAL UNIT DISCONNECT SWITCH. 5. USED ON PROPELLER MODELS 100 AND LARGER. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. NOTES TO INSTALLER: 24 120 1 XFMR FAN MOTOR 3 4 2 7 86 115V/60HZ/1Ø UNIT POWER CIRCUIT BREAKER (BY OTHERS) SINGLE STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT R WH CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. ATTACH WIRES NOT USED TO "PARK" TERMINALS WH-NEUTRAL BK-HI BL-MED RED-LO Y G LIMIT CONTROL Y PIN 6 PIN 5 Y FOR BLOWER MOTORS, LIMIT PRESSURE SWITCH LOW VOLTAGE THERMOSTAT (BY OTHERS) BL O IGNITION CONTROL SPARK IGNITOR FLAME SENSOR BK L1, (BK) See note #6 for motor connections 8 6 FAN MOTOR 4 2 7 3 1 0 EAC P1-8 P1-3 P1-6 P1-5 * INTEGRATED CONTROL IND P1-4 MV NTRL P1-9 NTRL P1-2 C NTRL R FUSE P1-7 24V COM SEC 115V SPARK IGNITOR 115V/60HZ/1Ø UNIT CIRCUIT CIRCUIT BREAKER (BY OTHERS) L1 NTRL GND L2 L1 WIRING DIAGRAM, SINGLE STAGE, RELAY 5H079963B3 W L1 PE MOTOR REFER NOTE 7 115V Unit Power THERMOSTAT GND HIGH LIMIT 115V Unit Power CALL FOR HEAT INDICATES TERMINAL BOARD CONNECTION HIGH LIMIT GAS VALVE 24V PRESSURE LINE GAS VALVE WIRING LEGEND FLAME SENSOR FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODELS HD/HDB, HDS/HDC, PTS/BTS 5 6-461.1 Y R COM 24V FS REFER NOTE 6 SWITCH L2, (WH) L1, (BK) R Y BK WH PE MOTOR 24 120 6. OPTIONAL UNIT DISCONNECT SWITCH. 5. USED ON PROPELLER MODELS 100 AND LARGER. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. 0 COM 1 XFMR FAN MOTOR 3 4 2 7 86 115V/60HZ/1Ø UNIT POWER CIRCUIT BREAKER (BY OTHERS) 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. NOTES TO INSTALLER: GND L1, (BK) L2, (WH) TWO STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT LIMIT CONTROL (SEE NOTE 5) R L1 C IND HEAT R PARK UT LABEL PARK O G 1 4 7 2 5 8 3 6 9 BL W1 WH IGNITION CONTROL SPARK IGNITOR FLAME SENSOR W2 Y HI COM 115V Unit Power CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. LIMIT CONTROL PRESSURE SWITCH PIN 8 Y HI LOW VOLTAGE THERMOSTAT (BY OTHERS) CALL FOR FAN 1ST STAGE 2ND STAGE M COM COM LO BK HONEYWELL GAS VALVE GND GND L1 L2 REFER NOTE 7 115V/60HZ/1Ø UNIT POWER CIRCUIT BREAKER (BY OTHERS) GND 24V P6 L1 P9 IND R G W2 T-STAT W1 P2 * INTEGRATED CONTROL P4 P7 HEAT HI HI M LO HONEYWELL GAS VALVE COM P8 PRESSURE SWITCH P3 WHITE ROGERS GAS VALVE COM FS COM SPARK IGNITOR 0 1 4 3 GND 2 6 See note #6 for motor connections FAN MOTOR 8 7 WIRING DIAGRAM, TWO STAGE, RELAY 5H079963B4 24V 115V PE MOTOR 115V Unit Power HIGH LIMIT WHITE ROGERS GAS VALVE W2 INDICATES TERMINAL BOARD CONNECTION W1 24V CALL FOR HEAT HIGH LIMIT LO FIRE LINE HI FIRE WIRING LEGEND FLAME SENSOR 6 FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODELS HD/HDB, HDS/HDC, PTS/BTS C R W LIMIT CONTROL (SEE NOTE 5) Y PIN 6 PIN 5 Y Y G R WH LIMIT CONTROL PRESSURE SWITCH LOW VOLTAGE THERMOSTAT (BY OTHERS) GAS VALVE C R W LIMIT CONTROL (SEE NOTE 5) Y PIN 6 PIN 5 Y Y G R WH O R IND N E U T R A L IND N E U T R A L SEC L1 COM L1 COM EAC L1 XFMR 24VAC PARK COOL PARK UT LABEL EAC/BLO M1 HONEYWELL LABEL REFER NOTE 7 SWITCH L1, (BK) 1 4 7 2 5 8 3 6 9 BL O R SEC COM COM N E U T R A L N E U T R A L 24VAC L1 L1 IND L1 IND EAC XFMR PARK COOL PARK UT LABEL EAC/BLO M1 HONEYWELL LABEL IGNITION CONTROL SPARK IGNITOR FLAME SENSOR L2, (WH) Y 230V/60HZ/1Ø FAN CIRCUIT POWER CIRCUIT BREAKERS (BY OTHERS) CONTROL CIRCUIT MUST BE 115V POWER 230V Fan/Blower Power Only 1 4 7 2 5 8 3 6 9 >Disconnect relay power leads (#2 & #6) from 115V supply and connect 230V as shown. >All other unit power must be 115V as shown. >See note #6 for motor connections. LIMIT CONTROL PRESSURE SWITCH LOW VOLTAGE THERMOSTAT (BY OTHERS) BL IGNITION CONTROL SPARK IGNITOR FLAME SENSOR R 24 120 BK WH PE MOTOR COM 0 XFMR See note #6 for motor connections FAN MOTOR 3 4 2 7 8 6 XFMR See note #6 for motor connections FAN MOTOR 3 4 2 7 86 CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. 24 120 1 0 COM 115V/60HZ/1Ø CONTROL CIRCUIT POWER FROM STEP DOWN TRANSFORMER (BY OTHERS) GND L2, (BL) L1, (BK) Y R BK WH PE MOTOR 1 FAN MOTOR 8 6 FAN MOTOR 4 2 See note #6 for motor connections 7 3 7 3 1 0 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. W L1 P1-8 P1-3 P1-6 P1-5 * INTEGRATED CONTROL IND PE MOTOR P1-4 MV NTRL P1-9 NTRL P1-2 C NTRL EAC W L1 7. OPTIONAL UNIT DISCONNECT SWITCH USED ON 115V UNITS ONLY. 6. UNIT IS SHIPPED WIRED FOR 115V. WHEN WIRING FOR 230V FOLLOW THIS DIAGRAM AND MOTOR WIRE LABELS FOR 230V. P1-8 P1-3 P1-6 P1-5 * INTEGRATED CONTROL IND PE MOTOR P1-4 MV NTRL P1-9 NTRL P1-2 C NTRL R P1-7 24V SEC COM SPARK IGNITOR 115V L1 NTRL P1-7 24V L2 L1 230V/60HZ/1Ø FAN CIRCUIT POWER CIRCUIT BREAKER (BY OTHERS) 115V/60HZ/1Ø UNIT CIRCUIT CIRCUIT BREAKER (BY OTHERS) *SHOWN WITH UNITED TECHNOLOGIES LABEL, SEE CHART FOR OTHER LABELS GND L1 L2 GND WIRING DIAGRAM, SINGLE STAGE, RELAY 5H080273B1 SEC 115V L1 SPARK IGNITOR COM NTRL 115V/60HZ/1Ø CONTROL CIRCUIT POWER FROM STEP DOWN TRANSFORMER (BY OTHERS) R CONTROL CIRCUIT MUST BE 115V POWER 5. USED ON PROPELLER MODELS 100 AND LARGER. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. EAC 230V Fan/Blower Power Only 1 0 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. NOTES TO INSTALLER: 8 4 See note #6 for motor connections 6 2 REFER NOTE 7 Factory 115V Unit Power THERMOSTAT GAS VALVE THERMOSTAT 115V/60HZ/1Ø UNIT POWER CIRCUIT BREAKER (BY OTHERS) HIGH LIMIT GR, (G) L1, (BK) L2, (WH) HIGH LIMIT HIGH LIMIT GND BK PRESSURE Factory 115V Unit Power CALL FOR HEAT BK L1, (BK) GAS VALVE SINGLE STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT GAS VALVE INDICATES TERMINAL BOARD CONNECTION L2, (WH) FUSE 24V 5H080273B1 REV _ CALL FOR HEAT HIGH LIMIT FLAME SENSOR LINE FUSE WIRING LEGEND PRESSURE 6-461.1 FLAME SENSOR FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODELS HD/HDB, HDS/HDC, PTS/BTS 7 Y HI LIMIT CONTROL PRESSURE SWITCH Y PIN 8 Y HI LOW VOLTAGE THERMOSTAT (BY OTHERS) CALL FOR FAN 1ST STAGE 2ND STAGE M COM COM WHITE ROGERS GAS VALVE R L1 C LIMIT CONTROL (SEE NOTE 5) R HEAT LIMIT CONTROL (SEE NOTE 5) R R L1 C COM 24V FS IND HEAT R PARK UT LABEL W1 O W2 1 4 7 2 5 8 3 6 9 BL IGNITION CONTROL SPARK IGNITOR PARK WH HI COM LO FLAME SENSOR BK WH PE MOTOR R Y 24 120 BK WH PE MOTOR COM 0 XFMR GND See note #6 for motor connections FAN MOTOR 3 4 2 7 8 6 XFMR GND See note #6 for motor connections FAN MOTOR 3 4 2 CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. 24 120 1 115V/60HZ/1Ø CONTROL CIRCUIT POWER FROM STEP DOWN TRANSFORMER (BY OTHERS) GND 0 COM 1 7 8 6 115V/60HZ/1Ø UNIT POWER CIRCUIT BREAKER (BY OTHERS) L2, (BL) L1, (BK) GR, (G) L1, (BK) L2, (WH) 230V/60HZ/1Ø FAN CIRCUIT POWER CIRCUIT BREAKERS (BY OTHERS) CONTROL CIRCUIT MUST BE 115V POWER G Y HONEYWELL GAS VALVE R Y 230V Fan/Blower Power Only COM 24V FS IND PARK R PARK UT LABEL G O IGNITION CONTROL W1 1 4 7 2 5 8 3 6 9 BL SWITCH NOTE 7 SPARK IGNITOR REFER FLAME SENSOR W2 Y LO COM WH HONEYWELL GAS VALVE >Disconnect relay power leads (#2 & #6) from 115V supply and connect 230V as shown. >All other unit power must be 115V as shown. >See note #6 for motor connections. LIMIT CONTROL PRESSURE SWITCH PIN 8 Y HI LOW VOLTAGE THERMOSTAT (BY OTHERS) CALL FOR FAN 1ST STAGE 2ND STAGE M COM COM WHITE ROGERS GAS VALVE GND Factory 115V Unit Power 5H080273B2 REV _ GND 115V/60HZ/1Ø CONTROL CIRCUIT POWER FROM STEP DOWN TRANSFORMER (BY OTHERS) 24V 115V 24V 115V 7. OPTIONAL UNIT DISCONNECT SWITCH USED ON 115V UNITS ONLY. 6. UNIT IS SHIPPED WIRED FOR 115V. WHEN WIRING FOR 230V FOLLOW THIS DIAGRAM AND MOTOR WIRE LABELS FOR 230V. P6 L1 P9 IND PE MOTOR R G W2 T-STAT W1 P2 * INTEGRATED CONTROL P4 P7 HEAT HI M HI LO HONEYWELL GAS VALVE COM WHITE ROGERS GAS VALVE COM P8 PRESSURE SWITCH P3 FS COM GND 24V P6 L1 P9 IND PE MOTOR R G W2 T-STAT W1 P2 * INTEGRATED CONTROL P4 P7 HEAT HI M HI LO FS COM SPARK IGNITOR 0 1 7 8 FAN MOTOR 4 GND 2 6 8 FAN MOTOR 4 GND 2 6 See note #6 for motor connections 3 7 See note #6 for motor connections 3 *SHOWN WITH UNITED TECHNOLOGIES LABEL, SEE CHART FOR OTHER LABELS SPARK IGNITOR 0 1 WIRING DIAGRAM, TWO STAGE, RELAY 5H080273B2 HONEYWELL GAS VALVE COM WHITE ROGERS GAS VALVE COM P8 PRESSURE SW ITCH P3 CONTROL CIRCUIT MUST BE 115V POWER 230V Fan/Blower Power Only GND 24V 5. USED ON PROPELLER MODELS 100 AND LARGER. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. NOTES TO INSTALLER: GND L1 L2 230V/60HZ/1Ø FAN CIRCUIT POWER CIRCUIT BREAKER (BY OTHERS) L1 L2 115V/60HZ/1Ø UNIT POWER CIRCUIT BREAKER (BY OTHERS) Factory 115V Unit Power TWO STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT HIGH LIMIT HIGH LIMIT INDICATES TERMINAL BOARD CONNECTION HIGH LIMIT CALL FOR HEAT HIGH LIMIT 24V CALL FOR HEAT LINE FLAME SENSOR WIRING LEGEND W2 W2 BK BK W1 W1 L1, (BK) L1, (BK) LO FIRE LO FIRE L2, (WH) L2, (WH) HI FIRE HI FIRE 6-461.1 FLAME SENSOR 8 FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODELS HD/HDB, HDS/HDC, PTS/BTS 6-461.1 Y PIN 6 PIN 5 Y R 1 4 7 2 5 8 3 6 9 BL R SEC COM COM N E U T R A L N E U T R A L 24VAC L1 L1 L1 IND EAC EAC/BLO IND PARK COOL XFMR PARK UT LABEL M1 HONEYWELL LABEL REFER NOTE 7 SWITCH L1, (BK) R Y BK WH PE MOTOR 7. OPTIONAL UNIT DISCONNECT SWITCH. 6. NA 5. MAKE MOTOR CONNECTIONS PER THE MOTOR WIRE DIAGRAM. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. NOTES TO INSTALLER: 24 120 COM See note #5 for motor connections 3Ø Starter (By Others) 115V/60HZ/1Ø CONTROL CIRCUIT POWER FROM STEP DOWN TRANSFORMER (BY OTHERS) SINGLE STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT C R W G Y WH CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. LIMIT CONTROL PRESSURE SWITCH LOW VOLTAGE THERMOSTAT (BY OTHERS) O IGNITION CONTROL SPARK IGNITOR BK FLAME SENSOR L2, (WH) L3 L2 L1 L2 T3 L3 FAN MOTOR T2 C XFMR T1 L1 5H080274B1 REV. ~ GND T1 L1 L3 T3 FAN MOTOR T2 C L2 L1 L2 L3 EAC W L1 L1 P1-8 P1-3 P1-6 P1-5 * INTEGRATED CONTROL IND PE MOTOR 115V/60HZ/1Ø CONTROL CIRCUIT POWER FROM STEP DOWN TRANSFORMER (BY OTHERS) 3Ø/60HZ FAN POWER CIRCUIT CIRCUIT BREAKERS (BY OTHERS) P1-4 P1-9 NTRL C NTRL R P1-7 24V COM SEC 115V L1 NTRL SPARK IGNITOR WIRING DIAGRAM, SINGLE STAGE, 3 Ø MV P1-2 NTRL L2 *SHOWN WITH UNITED TECHNOLOGIES LABEL, SEE CHART FOR OTHER LABELS 5H080274B1 See note #5 for motor connections 3Ø Starter (By Others) GND CALL FOR HEAT 3Ø/60HZ FAN CIRCUIT POWER CIRCUIT BREAKERS (BY OTHERS) THERMOSTAT INDICATES TERMINAL BOARD CONNECTION HIGH LIMIT 24V PRESSURE GAS VALVE 3 Phase GAS VALVE 115V FUSE WIRING LEGEND FLAME SENSOR FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODELS HD/HDB, HDS/HDC, PTS/BTS 9 6-461.1 Y LO R COM 24V FS L2, (WH) L1, (BK) BK R Y BK WH PE MOTOR 5. MAKE MOTOR CONNECTIONS PER THE MOTOR WIRE DIAGRAM. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. 24 120 COM See note #5 for motor connections 3Ø Starter (By Others) 115V/60HZ/1Ø CONTROL CIRCUIT POWER FROM STEP DOWN TRANSFORMER (BY OTHERS) 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. NOTES TO INSTALLER: TWO STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT R L1 C IND HEAT R PARK UT LABEL PARK O W1 1 4 7 2 5 8 3 6 9 BL IGNITION CONTROL SPARK IGNITOR FLAME SENSOR W2 WH HI COM G Y HONEYWELL GAS VALVE CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. LIMIT CONTROL PRESSURE SWITCH PIN 8 Y HI LOW VOLTAGE THERMOSTAT (BY OTHERS) CALL FOR FAN 1ST STAGE 2ND STAGE M COM COM WHITE ROGERS GAS VALVE L3 L2 L1 L2 T3 L3 FAN MOTOR T2 C XFMR T1 L1 5H080274B2 REV. ~ GND 24V 115V L2 P6 P9 IND PE MOTOR R G W2 T-STAT W1 P2 P4 L2 P7 HI M LO HONEYWELL GAS VALVE COM P8 FS COM SPARK IGNITOR FAN MOTOR See note #5 for motor connections WIRING DIAGRAM, TWO STAGE, 3 Ø HI T3 L3 PRESSURE SWITCH P3 WHITE ROGERS GAS VALVE COM T2 C 3Ø/60HZ FAN POWER CIRCU CIRCUIT BREAKERS (BY OTHERS) * INTEGRATED CONTROL HEAT T1 L1 GND L1 L2 L3 3Ø Starter (By Others) 5H080274B2 GND 24V L1 L1 115V/60HZ/1Ø CONTROL CIRCUIT POWER FROM STEP DOWN TRANSFORMER (BY OTHERS) HIGH LIMIT 3Ø/60HZ FAN CIRCUIT POWER CIRCUIT BREAKERS (BY OTHERS) W2 INDICATES TERMINAL BOARD CONNECTION CALL FOR HEAT 24V W1 3 Phase LO FIRE 115V HI FIRE WIRING LEGEND FLAME SENSOR 10 FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODELS HD/HDB, HDS/HDC, PTS/BTS W 6-461.1 BL GY R 1 4 7 2 5 8 3 6 9 R UNIT LIMIT CONTROL AUTO RESET C R W G Y BK O R Y N E U T R A L N E U T R A L W W NOTES TO INSTALLER: 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. BK LOW VOLTAGE THERMOSTAT (BY OTHERS) T2 F G T1 C V SEC IND IND COM L1 COM L1 L1 XFMR 24VAC EAC PARK PARK UT LABEL EAC/BLO COOL M1 HONEYWELL LABEL CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. FAN MOTOR Y PIN 6 PRESSURE SWITCH PIN 5 Y GAS VALVE BL BLU GAS VALVE OPEN AMB R CALL FOR HEAT POWER GRN R R Y Y W BK W BK W GND L1, (BK) COM 5H080716B1 REV C 115V/60HZ/1Ø POWER CIRCUIT BREAKER (BY OTHERS) L2, (WH) L1, (BK) GR, (G) XFMR 24 120 PE LIMIT CONTROL MANUAL RESET PE MOTOR SINGLE STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT W BR SPARK IGNITOR 115V Unit Power L2, (W) IGNITION CONTROL L1 W IND INDUCER MOTOR DISCONNECT SWITCH P1-8 P1-3 T2 NTRL T1 C F V R P1-7 GREEN POWER TO UNIT 24V COM AMBER CALL FOR HEAT BLUE GAS VALVE OPEN SEC 115V L1 NTRL SPARK IGNITOR WIRING DIAGRAM, PTC 5H080716B1 THERMOSTAT MV C NTRL NTRL PE LIMIT CONTROL MANUAL RESET GND 115V Unit Power *SHOWN WITH UNITED TECHNOLOGIES LABEL, SEE CHART FOR OTHER LABELS P1-6 P1-5 P1-4 P1-2 P1-9 * INTEGRATED CONTROL EAC GROUND L1 L2 BLOWER MOTOR GROUND CALL FOR HEAT FLAME SENSOR 115V/60HZ/1Ø CIRCUIT BREAKER (BY OTHERS) HIGH LIMIT AUTO RESET INDICATES TERMINAL BOARD CONNECTION PRESSURE 24V GAS VALVE LINE FUSE WIRING LEGEND FLAME SENSOR 11 FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODEL PTC W BL 6-461.1 BK 0 3 4 2 1 7 8 6 R W O BL BK RELAY 1 4 7 2 5 8 3 6 9 UNIT LIMIT R CONTROL AUTO RESET C R W G Y R Y N E U T R A L N E U T R A L W GY NOTES TO INSTALLER: 1. ALL WIRING MUST COMPLY WITH NATIONAL ELECTRIC CODE AND ALL LOCAL CODES. 2. ALL COMPONENTS MUST AGREE WITH THEIR RESPECTIVE POWER SOURCE. 3. VERIFY THE POWER SOURCE AND THE UNIT POLARITY. 4. USE TYPE 105°C REPLACEMENT WIRE 300V OR GREATER. BK LOW VOLTAGE THERMOSTAT (BY OTHERS) T2 F G T1 C V COM IND IND COM L1 XFMR SEC L1 24VAC EAC L1 PARK PARK UT LABEL EAC/BLO COOL M1 HONEYWELL LABEL IGNITION CONTROL CAUTION: FAILURE TO WIRE THIS UNIT ACCORDING TO THIS WIRING DIAGRAM MAY RESULT IN INJURY TO THE INSTALLER OR USER. FOR DEVIATIONS CONTACT THE FACTORY. FAN MOTOR Y PIN 6 PRESSURE SWITCH PIN 5 Y GAS VALVE FLAME SENSOR BLU GAS VALVE OPEN AMB R CALL FOR HEAT POWER GRN R W R Y Y BK W W BL GND L1, (BK) COM 5H080716B2 REV C 115V/60HZ/1Ø POWER CIRCUIT BREAKER (BY OTHERS) L2, (W) L1, (BK) GR, (G) XFMR 24 120 PE LIMIT CONTROL MANUAL RESET PE MOTOR SINGLE STAGE, DIRECT SPARK IGNITION, 100% SHUT-OFF, MULTIPLE RETRY W/ AUTO RESET FROM LOCKOUT W BR SPARK IGNITOR FAN MOTOR DISCONNECT SWITCH 2 6 L1 4 8 W 3 7 0 T2 GROUND NTRL PE LIMIT CONTROL MANUAL RESET T1 C F V R P1-7 GREEN POWER TO UNIT 24V COM AMBER CALL FOR HEAT BLUE GAS VALVE OPEN SEC 115V L1 NTRL WIRING DIAGRAM, PTC, RELAY 5H080716B2 THERMOSTAT MV C NTRL NTRL SPARK IGNITOR 115V Unit Power GND *SHOWN WITH UNITED TECHNOLOGIES LABEL, SEE CHART FOR OTHER LABELS P1-6 P1-5 P1-4 P1-2 P1-9 * INTEGRATED CONTROL IND PE MOTOR L1 L2 P1-8 P1-3 EAC 1 CALL FOR HEAT 115V Unit Power L2, (W) 115V/60HZ/1Ø CIRCUIT BREAKER (BY OTHERS) HIGH LIMIT AUTO RESET INDICATES TERMINAL BOARD CONNECTION PRESSURE 24V GAS VALVE LINE FUSE WIRING LEGEND FLAME SENSOR 12 FACTORY WIRING INTERNAL COMPONENT WIRING FIELD WIRING WIRE NUT WIRING DIAGRAMS – MODEL PTC WIRING DIAGRAMS – THERMOSTAT & SUMMER/WINTER SWITCH Single Stage Thermostat & Summer/Winter Switch Wiring SUMMER/WINTER SWITCH & 1-STAGE ROOM STAT WITHOUT SUB-BASE FAN SWITCH 1-STAGE ROOM STAT WITH SUB-BASE FAN SWITCH MODELS HD/HDB, HDS/HDC, AND PTS/BTS 1-STAGE LOW VOLTAGE ROOM STAT WITH SUB-BASE SWITCHING (BY OTHERS) R C W MODEL PTC FAN OPERATION (BASED ON FAN SUB-BASE SWITCH): SWITCH = ON - CONTINUOUS SWITCH = AUTO - INTERMITTENT ON A CALL FOR HEAT 1-STAGE LOW VOLTAGE ROOM STAT WITH SUB-BASE SWITCHING (BY OTHERS) G R 2-STAGE ROOM STAT WITH SUB-BASE FAN SWITCH G G T2 F G T1 C V TERMINAL BOARD ON UNIT HEATER W R C 1-STAGE LOW VOLTAGE ROOM STAT WITH NO SWITCHING (BY OTHERS) R C FAN OPERATION: SUMMER - CONTINUOUS FAN WINTER - INTERMITTENT FAN ON A CALL FOR HEAT 1-STAGE LOW VOLTAGE ROOM STAT WITH NO SWITCHING (BY OTHERS) W R C SUMMER/WINTER SWITCH (BY OTHERS) FAN OPERATION: SUMMER - CONTINUOUS FAN WINTER - INTERMITTENT FAN ON A CALL FOR HEAT W SUMMER/WINTER SWITCH (BY OTHERS) WINTER TERMINAL STRIP ON UNIT HEATER TERMINAL BOARD ON UNIT HEATER WINTER Y SUMMER G SUMMER W T2 F G T1 C V R C MODELS HD/HDB, HDS/HDC, AND PTS/BTS SUMMER/WINTER SWITCH & 2-STAGE ROOM STAT WITHOUT SUB-BASE FAN SWITCH W TERMINAL STRIP ON UNIT HEATER Y Two Stage Thermostat & Summer/Winter Switch Wiring 2-STAGE LOW VOLTAGE ROOM STAT WITH SUB-BASE SWITCHING (BY OTHERS) R W1 W2 C FAN OPERATION (BASED ON FAN SUB-BASE SWITCH): SWITCH = ON - CONTINUOUS SWITCH = AUTO - INTERMITTENT ON A CALL FOR HEAT Notes on Thermostat and Summer/Winter Switch Wiring: Units are equipped as standard with a controller that activates the unit fan in either of the following ways: • On a call for heat (thermostat closure between R & W terminals (W1 for 2-stage units) on the unit heater terminal strip (T1 & T2 on the external terminal board for model PTC units). The control automatically recognizes a call for heat as requiring fan operation. • With switch closure between R & G terminals on the unit heater terminal strip (T1 & G on the external terminal board for model PTC units). The control recognizes this as an override to the fan control based on a call for heat and starts the fan. G TERMINAL STRIP ON UNIT HEATER G W1 W2 C R 2-STAGE LOW VOLTAGE ROOM STAT WITH NO SWITCHING (BY OTHERS) R C FAN OPERATION: SUMMER - CONTINUOUS FAN WINTER - INTERMITTENT FAN ON A CALL FOR HEAT W1 W2 SUMMER/WINTER SWITCH (BY OTHERS) TERMINAL STRIP ON UNIT HEATER The diagrams on this page are arranged as follows: 1. Single stage thermostat with a Fan On/Auto switch for fan control. 2. Single stage thermostat without a Fan On/Auto switch and a Summer/Winter switch for fan control. 3. Two stage thermostat with a Fan On/Auto switch for fan control. 4. Two stage thermostat without a Fan On/Auto switch and a Summer/Winter switch for fan control. WINTER G SUMMER W1 W2 C R NOTE: GENERIC ROOM STAT TERMINALS SHOWN. ACTUAL STAT MAY USE DIFFERENT TERMINALS AND/OR WIRING. PLEASE CONSULT WIRING INSTRUCTIONS FOR STAT FOR PROPER WIRING. 13 C FAN OPERATION (BASED ON FAN SUB-BASE SWITCH): SWITCH = ON - CONTINUOUS SWITCH = AUTO - INTERMITTENT ON A CALL FOR HEAT 6-461.1 Note: A Summer/Winter switch used on these models does NOT require a control relay as was required on previous models. WIRING DIAGRAMS – ACCESSORIES Wiring Multiple Single Stage Units to a Single Thermostat MODELS HD/HDB, HDS/HDC, AND PTS/BTS 1-STAGE LOW VOLTAGE ROOM STAT (NO SWITCHING) (BY OTHERS) R MODEL PTC TERMINAL STRIP ON UNIT HEATER #1 1-STAGE LOW VOLTAGE ROOM STAT (NO SWITCHING) (BY OTHERS) W R TERMINAL BOARD ON UNIT HEATER #1 W Y G T2 F G T1 C V W R C 0 2 4 3 2 4 3 6 8 7 6 8 7 0 DPDT CONTROL RELAY (BY OTHERS) 2 4 3 2 4 3 6 8 7 6 8 7 1 DPDT CONTROL RELAY (BY OTHERS) 1 Y G W T2 F G T1 C V R C 0 2 4 3 2 4 3 6 8 7 6 8 7 DPDT CONTROL RELAY (BY OTHERS) 0 1 2 4 3 6 8 7 6 8 7 1 TERMINAL STRIP ON UNIT HEATER #2 TO ADDITIONAL UNIT/RELAY PAIRINGS (IF APPLICABLE) 2 4 3 DPDT CONTROL RELAY (BY OTHERS) TERMINAL BOARD ON UNIT HEATER #2 TO ADDITIONAL UNIT/RELAY PAIRINGS (IF APPLICABLE) Notes on Wiring Multiple Single Stage Units to a Single Thermostat When two or more unit heaters are controlled by one thermostat, it is necessary to electrically isolate each unit by using relays. If relays are not used, feedback in the low voltage circuits can occur. This feedback may cause operational problems, damage the electrical components in the low voltage circuit, or cause burnout of the low voltage transformers. The figure above shows that the thermostat, powered from the terminal strip of unit heater #1 (UH-1), energizes the relay coil of the first relay (RE-1). When the RE-1 coil is energized, the first set of normally open (NO) contacts of that DPDT relay close and activate the gas controls of UH-1. The second set of normally open (NO) contacts on RE-1 are used to energize the relay coil of the second relay RE-2, powered through the terminal strip of UH-2. The first set of NO contacts on RE-2 close and activate the gas controls of UH-2. If a third unit is to be controlled from the same thermostat, a third relay RE-3 coil is wired to the second set of contacts on RE-2. This procedure is repeated for each additional unit which is to be controlled by the thermostat. Generally, there should be a quantity of DPDT relays that is one less than the quantity of heaters to be controlled. Accessory Wiring for Model PTC Units T2 F G T1 C V TERMINAL BOARD ON UNIT HEATER SEE NOTE BELOW FOR REMOVAL OF JUMPER BARS ACCESSORY ACCESSORY NOTE: FOR FIELD WIRED CONDENSATE PUMP AUX SWITCH AND/OR CONDENSATE DRAIN LINE SAFETY OVERFLOW SWITCH, REMOVE TERMINAL BOARD JUMPERS AS FOLLOWS: -FOR ONE ACCESSORY, REMOVE "T1" TO "C" JUMPER -FOR TWO ACCESSORIES, REMOVE "T1" TO "C" & "C" TO "V" JUMPERS FOR FURTHER INSTRUCTIONS, REFER TO THE LATEST REVISION OF INSTALLATION INSTRUCTIONS 6-585 FOR THE CONDENSATE PUMP AND/OR 6-586 FOR THE CONDENSATE DRAIN LINE SAFETY OVERFLOW SWITCH. 14 6-461.1 THIS PAGE INTENTIONALLY LEFT BLANK 6-461.1 15 Commercial Products Group • Modine Manufacturing Company • 1500 DeKoven Avenue • Racine, Wisconsin, USA 53403-2552 Phone: 1.800.828.4328 (HEAT) • www.modine.com © Modine Manufacturing Company 2009 6-461.1 09/09 Litho in USA