2: 5: SYS19: BASE2 PDFINFO 50: 95: 98: 100: JOB: CRMAIN06-0438-2 Name: 5C-438 5C DATE: JAN 19 2006 Time: 5:25:15 PM Operator: RB COLOR: CMYK TCP: 15001 Typedriver Name: TS name csm no.: 100 Cl. I, Div. 1 & 2, Groups B*,C,D Cl. II, Div. 1, Groups E,F,G Cl. II, Div. 2, Groups F,G Cl. III NEMA 3,7B*CD,9EFG EFS Factory Sealed Selector Switches Maintained Contact, 600VAC Heavy Duty, Dimensions Pg. 430 Explosionproof Dust-Ignitionproof Raintight Wet Locations Furnished with pushbuttons, cam actuated by a maintained contact selector mechanism to operate in the sequences shown in the diagrams below. Specify indicating plate markings. See table below listings. EFS11271 EFS11273 Single Gang Enclosure With Switch Replacement Contact Blocks† Hub Size Dead End Cat. # Through Feed Cat. # TwoPosition, TwoCircuit ED11 1⁄2 3⁄4 EFS11271 EFS21271 EFS31271 EFSC11271 EFSC21271 EFSC31271 TwoPosition, FourCircuit ED12 EFS11272 EFS21272 EFS31272 EFSC11272 EFSC21272 EFSC31272 EFS11273 EFS21273 EFS31273 EFSC11273 EFSC21273 EFSC31273 EFS11274 EFS21274 EFS31274 EFSC11274 EFSC21274 EFSC31274 EFS11275 EFS21275 EFS31275 EFSC11275 EFSC21275 EFSC31275 Style Position 1 Position 2 Position 3 1 1⁄2 3⁄4 1 ThreePosition, TwoCircuit ED11 1⁄2 3⁄4 1 ThreePosition, FourCircuit ED12 ED12 1⁄2 3⁄4 1 1⁄2 3⁄4 1 Standard indicating plate markings available are as follows: Two-Position RUN, JOG FAST, SLOW IN, OUT HAND, AUTOMATIC OPEN, CLOSE RAISE, LOWER FORWARD, REVERSE UP, DOWN START, STOP ON, OFF Three-Position RUN, OFF, JOG 1, OFF, 2 HAND, OFF, AUTOMATIC OPEN, OFF, CLOSE FORWARD, OFF, REVERSE UP, OFF, DOWN FAST, OFF, SLOW * Class I, Group B: All enclosures listed above are suitable for Class I, Group B, Div. 1 usage. Seals only have to be installed on 1 inch conduit within 5 ft. in Division 1. † For replacement contact blocks see page 400. 438 STIBOINFO((CRH:66008com:5C:438)) CH0 5 C- 1 3 US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2006 Cooper Crouse-Hinds Zoom: 100 2: 5: SYS19: BASE2 PDFINFO 50: 95: 98: JOB: CRMAIN06-0428-6 Name: 5C-428 5C 100: DATE: JAN 19 2006 Time: 5:25:03 PM Operator: GK COLOR: CMYK Dimensions Pg. 430 Factory sealed enclosures are installed in a rigid metallic conduit system for surface mounting adjacent to or remote from equipment being controlled and are used: ɀ to prevent arcing of enclosed device from causing ignition of a specific hazardous atmosphere or atmospheres external to the enclosure ɀ in industrial areas such as chemical plants, oil and gas refineries, paint and varnish manufacturing plants, gasoline bulk loading terminals, grain elevators, grain processing industries, coal processing or handling areas, or metal handling or finishing areas where atmosphere may contain hazardous gases and/or dust ɀ in non-hazardous areas where sturdy, durable enclosures are required ɀ in conjunction with magnetic starters or contactors for remote control of motors Manual motor starting switch enclosures are used: ɀ for manual starting of small ac or dc motors ɀ to provide manual starting and stopping and, in the case of units with heaters, motor running protection Features: Factory sealed devices have many distinct advantages: ɀ reduce installation problems ɀ eliminate external seals ɀ lower installation costs ɀ improve safety ɀ are used with general purpose snap and pushbutton type switches ɀ standard neoprene covers for front operated pushbuttons. Prevents accumulation of dirt and entrance of water around operating shafts ɀ mounting lugs and taper tapped hubs with integral bushings ɀ large machine screws for fastening covers to bodies ɀ lockout provisions on front operated push button (marked ‘‘STOP’’ and ‘‘OFF’’) and selector switch covers ɀ lockout hole for padlock having 1⁄4⍯ hasp is provided when used with covers for front lever and side rocker type operation ɀ close tolerances in machining of wide, mating flanges and journalled shafts and bearings for front button operation, produces flametightness of enclosure joints ɀ on enclosures with front lever and side rocker type operating handles, threaded type shafts and bushings are used to ensure flametightness ɀ dead end (EFS or EDS) or through feed (EFSC or EDSC) hubs – 1⁄2⍯ to 1⍯ sizes ɀ Shafts – stainless steel ɀ Shaft bushings – stainless steel ɀ Rocker handle and pushbutton guards – type 6/6 nylon ɀ Sealing enclosures – copper-free aluminum Standard Finishes: Feraloy iron alloy – electrogalvanized and aluminum acrylic paint ɀ Copper-free aluminum – natural ɀ Type 6/6 nylon – black ɀ Stainless steel – natural ɀ NEC/CEC: Class I, Division 1 & 2, Groups B*,C,D Class II, Division 1, Groups E,F,G Class II, Division 2, Groups F,G Class III ɀ NEMA/EEMAC: 3,7B*CD,9EFG ɀ UL Standard: 894, 698 ɀ CSA Standard: C22.2 No. 30 Options: The following special options are available from the factory by adding suffix to Cat. No. Suffix to be Added to Cat. # Description Emergency ‘‘Stop’’ button (momentary) – front operated red mushroom button . . . . . . . . . . S111 Lockout provision on front operated pushbutton cover (standard on buttons marked ‘‘OFF’’ and ‘‘STOP’’) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S153 For 24 VDC operation on pilot lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S300 Three-position selector switches with modified operation: Momentary contact clockwise operation, spring return to center, maintained contact counter-clockwise operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S634 Momentary contact counter-clockwise operation, spring return to center, maintained contact clockwise operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S635 Bodies and covers (single and two gang units) – copper-free aluminum. . . . . . . . . . . . . . . . . . . SA Where indicated in the catalog listings, EDS units suitable for Class I, Division 1, Group B usage can be supplied, add suffix - GB, EFS units are suitable for Class I, Division 1, Group B as standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GB Maintained contact mushroom head with lockout and guard. Maximum one per cover and cannot be used with a pilot light with a transformer or another standard pushbutton.. . S769 EDS bodies and factory sealed cover and device sub-assemblies are available for field assembly (see pages 394 to 396). ɀ Bodies – Feraloy® iron alloy; copper-free aluminum. ɀ Front operated pushbutton and pilot light covers – Feraloy iron alloy ɀ Side operated type pushbutton covers – copper-free aluminum STIBOINFO((CRH:66008com:5C:428)) CH0 0 5 C- 0 Explosionproof Dust-Ignitionproof Raintight Wet Locations Certifications and Compliances: Suffix S769 Standard Materials: 428 Typedriver Name: TS name csm no.: 100 Cl. I, Div. 1 & 2, Groups B*,C,D Cl. II, Div. 1, Groups E,F,G Cl. II, Div. 2, Groups F,G Cl. III NEMA 3,7B*CD,9EFG EFS and EDS Factory Sealed Control Devices and Manual Motor Starting Switches Application: TCP: 15001 US: 1-866-764-5454 * See Options: suffix GB CAN: 1-800-265-0502 Copyright© 2006 Cooper Crouse-Hinds Zoom: 100