PORTABLE CORD ► Type DLO ► Type RHH-RHW-2 ► EPR/XL-CPE ► 600V – 2kV PRODUCT CONSTRUCTION Conductor: 14 AWG through 1111.1 kcmil Class I, fully annealed, flexible, stranded, tin-coated copper per AAR 589. Insulation: Flame-retardant, cross-linked Ethylene Propylene (EP) with separator tape over the conductor to facilitate stripping. Jacket: Black, flame-retardant, sunlight-, ozone- and oil resistant, lead-free Cross-linked Chlorinated Polyethylene (XL-CPE). Other jacket colors available upon request. APPLICATIONS For use up to 2 kV as power cables in wind turbine generator applications per UL Subject 6140. Also for use in diesel electric locomotives, mining and earth-moving equipment, and general purpose use as flexible power leads in cable trays (sizes 1/0 AWG and larger). FEATURES Resists oil, heat, flame, gear lubricants, ozone and sunlight. Designed to withstand continuous flexing. 90ºC wet or dry temperature rating. Flexible tinned copper stranding. COMPLIANCES Industry: Type RHH/RHW-2 per UL 44, UL File #E90494. c(UL)US Type RW90 per CSA C.22.2-38, UL File #E90494. ICEA S-95-658/NEMA WC70. For CT Use on 1/0 AWG and larger in accordance with NEC®. Accepted for listing as flame resistant by MSHA. RoHS compliant. Flame Test: UL 2556 VW-1, IEEE 1202/CSA FT4 for sizes 1/0 AWG and larger. USAWC Part # USA14-01DLO USA12 01DLO USA12-01DLO USA10-01DLO USA8-01DLO USA6-01DLO USA4-01DLO USA2-01DLO USA1-01DLO USA1/0-01DLO USA2/0-01DLO USA3/0-01DLO USA4/0-01DLO USA262-01DLO USA313-01DLO USA373-01DLO USA444-01DLO USA535-01DLO USA646-01DLO USA777-01DLO USA929-01DLO USA1111-01DLO Size (AWG or kcmil) Cond. Strand 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 262.6 313.3 373.7 444.4 535.3 646.4 777.7 929.9 1111.1 19/0.0147 19/0 0185 19/0.0185 27/24 37/24 61/24 105/24 154/24 224/24 280/24 329/24 456/24 551/24 650/24 777/24 925/24 1110/24 1332/24 1609/24 1924/24 2318/24 2745/24 Nominal Insulation Thickness (Inches) 0.045 0 045 0.045 0.045 0.055 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.090 0.090 0.090 0.090 0.090 0.090 0.090 0.090 0.115 (mm) 1.1 11 1.1 1.1 1.4 1.5 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 Nominal O.D. (Inches) 0.20 0 22 0.22 0.25 0.33 0.38 0.46 0.51 0.64 0.70 0.73 0.80 0.84 0.94 1.00 1.06 1.11 1.20 1.29 1.38 1.56 1.77 (mm) 5.1 56 5.6 6.4 8.3 9.7 11.7 13.0 16.3 17.8 18.5 20.3 21.3 23.9 25.3 26.9 28.2 30.5 32.8 35.1 39.6 44.9 Current Amps (1) 25 30 40 55 75 95 130 150 170 195 225 260 296 326 362 400 445 493 546 602 635 (2) 35 40 55 80 105 140 190 220 260 300 350 405 467 522 591 652 728 815 904 1014 1115 Dimensions and weights are nominal and are subject to industry tolerances (1) Ampacities based on 90°C conductor and 30°C ambient temperature, based on the National Electrical Code® for not more than three current-carrying conductors in raceway, cable or earth. (2) Ampacities based on single-conductor in free air, 90°C conductor temperature and an ambient air temperature of 30°C, in accordance ® with the National Electrical Code . *Actual shipping weight may vary. Approx. Net Wt.* (lbs./1000 ft.) 30 39 56 87 131 202 285 417 494 587 718 845 1050 1185 1384 1634 1925 2307 2728 3570 4232