EPR-CPE 2kV DLO, UL RHH-RHW Locomotive Cable

advertisement
PORTABLE CORD
► Type DLO
► Type RHH-RHW-2
► EPR/XL-CPE
► 600V – 2kV
PRODUCT CONSTRUCTION
Conductor: 14 AWG through 1111.1 kcmil Class I, fully annealed, flexible, stranded, tin-coated copper per AAR 589.
Insulation: Flame-retardant, cross-linked Ethylene Propylene (EP) with separator tape over the conductor to facilitate stripping.
Jacket: Black, flame-retardant, sunlight-, ozone- and oil resistant, lead-free Cross-linked Chlorinated Polyethylene (XL-CPE). Other jacket
colors available upon request.
APPLICATIONS
For use up to 2 kV as power cables in wind turbine generator applications per UL Subject 6140. Also for use in diesel electric locomotives,
mining and earth-moving equipment, and general purpose use as flexible power leads in cable trays (sizes 1/0 AWG and larger).
FEATURES
Resists oil, heat, flame, gear lubricants, ozone and sunlight. Designed to withstand continuous flexing. 90ºC wet or dry temperature rating.
Flexible tinned copper stranding.
COMPLIANCES
Industry: Type RHH/RHW-2 per UL 44, UL File #E90494. c(UL)US Type RW90 per CSA C.22.2-38, UL File #E90494. ICEA S-95-658/NEMA
WC70. For CT Use on 1/0 AWG and larger in accordance with NEC®. Accepted for listing as flame resistant by MSHA. RoHS compliant.
Flame Test: UL 2556 VW-1, IEEE 1202/CSA FT4 for sizes 1/0 AWG and larger.
USAWC
Part #
USA14-01DLO
USA12 01DLO
USA12-01DLO
USA10-01DLO
USA8-01DLO
USA6-01DLO
USA4-01DLO
USA2-01DLO
USA1-01DLO
USA1/0-01DLO
USA2/0-01DLO
USA3/0-01DLO
USA4/0-01DLO
USA262-01DLO
USA313-01DLO
USA373-01DLO
USA444-01DLO
USA535-01DLO
USA646-01DLO
USA777-01DLO
USA929-01DLO
USA1111-01DLO
Size
(AWG
or kcmil)
Cond.
Strand
14
12
10
8
6
4
2
1
1/0
2/0
3/0
4/0
262.6
313.3
373.7
444.4
535.3
646.4
777.7
929.9
1111.1
19/0.0147
19/0 0185
19/0.0185
27/24
37/24
61/24
105/24
154/24
224/24
280/24
329/24
456/24
551/24
650/24
777/24
925/24
1110/24
1332/24
1609/24
1924/24
2318/24
2745/24
Nominal Insulation Thickness
(Inches)
0.045
0 045
0.045
0.045
0.055
0.060
0.060
0.060
0.080
0.080
0.080
0.080
0.080
0.090
0.090
0.090
0.090
0.090
0.090
0.090
0.090
0.115
(mm)
1.1
11
1.1
1.1
1.4
1.5
1.5
1.5
2.0
2.0
2.0
2.0
2.0
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.9
Nominal O.D.
(Inches)
0.20
0 22
0.22
0.25
0.33
0.38
0.46
0.51
0.64
0.70
0.73
0.80
0.84
0.94
1.00
1.06
1.11
1.20
1.29
1.38
1.56
1.77
(mm)
5.1
56
5.6
6.4
8.3
9.7
11.7
13.0
16.3
17.8
18.5
20.3
21.3
23.9
25.3
26.9
28.2
30.5
32.8
35.1
39.6
44.9
Current Amps
(1)
25
30
40
55
75
95
130
150
170
195
225
260
296
326
362
400
445
493
546
602
635
(2)
35
40
55
80
105
140
190
220
260
300
350
405
467
522
591
652
728
815
904
1014
1115
Dimensions and weights are nominal and are subject to industry tolerances
(1) Ampacities based on 90°C conductor and 30°C ambient temperature, based on the National Electrical Code® for not more than three
current-carrying conductors in raceway, cable or earth.
(2) Ampacities based on single-conductor in free air, 90°C conductor temperature and an ambient air temperature of 30°C, in accordance
®
with the National Electrical Code .
*Actual shipping weight may vary.
Approx.
Net Wt.*
(lbs./1000 ft.)
30
39
56
87
131
202
285
417
494
587
718
845
1050
1185
1384
1634
1925
2307
2728
3570
4232
Download