What is the maximum distance allowed by Canadian Electrical Code between the disconnect and Air conditioning equipment? a. 1m b. 2m c. 3m d. 6m Feedback Rule 28-604-5 The correct answer is: 3m Question 2 Not answered Marked out of 1.00 Flag question Question text What is the maximum voltage drop allowed in a solar panel working on 48V supply? a. 0.48V b. 0.96V c. 1.44V d. 2.4V Feedback Your answer is incorrect. 5% is the maximum drop allowed. 5% of 48V= 2.4V 64-204(b) The correct answer is: 2.4V What is the correction factor that you will multiply the ampacity with to calculate final ampacity rating of a cable carrying 16 conductor? a. 1 b. 0.80 c. 0.70 d. 0.60 Feedback Rule 4-004 , Table 5C The correct answer is: 0.70 What is the minimum conductor size that can be installed in a class 2 circuit that has an Integral assembly of two or more conductor? a. 19 AWG b. 18 AWG c. 16 AWG d. 14 AWG Feedback Rule 16-210-4(c) The correct answer is: 19 AWG What is minimum size of copper conductor required in a class 1 circuit when laid in a raceway? a. 18 Awg b. 16 AWG c. 14 AWG d. 12 AWG Feedback Rule 16-110(2)(b) The correct answer is: 18 Awg Where the weight of a heating fixture does not exceed _________kg, the heating fixture shall be permitted to be supported by a ceiling outlet box attached directly to the building structure or by a ceiling outlet attached to a bar hanger a. 23 KG b. 13 KG c. 10KG d. 7 KG Feedback Rule 62-210(5) The correct answer is: 23 KG What is the minimum vertical distance required from the top of the cablebus to a heating duct? a. 1200mm b. 900mm c. 600mm d. 300mm Feedback Rule 12-2200(6)(b) The correct answer is: 300mm What type of weather proof receptacle will you install for Rooftop AC? a. 5-15R b. 5-20R c. 5-30R d. 5-50R Feedback Rule 26-710-c The correct answer is: 5-20R What is the maximum overcurrent device rating for protecting HID lighting in a commercial unit? a. 40A b. 30A c. 20A d. 15A Feedback Rule 30-104(b)(iii)(b) The correct answer is: 40A What is the FLA of a DC motor rated at 5HP, 240V? a. 1.5A b. 4.7A c. 12.5A d. 20A Feedback Table D2 The correct answer is: 20A What table will you refer to in order to find maximum length of wire allowed to be installed in a 240V circuit , considering 3% drop? a. Table D1 b. Table D2 c. Table D3 d. Table D4 Feedback Table D3 The correct answer is: Table D3 Which rule will you refer to in order to find info on number of receptacles required for electric vehicle supply equipment? a. Rule 36-000 b. Rule 78-050 c. Rule 86-306 d. Rule 86-404 Feedback Rule 86-306 The correct answer is: Rule 86-306 Conductors from the emergency power source to a fire pump shall have an ampacity not less than _________% of the full load current rating of the motor, where an individual motor is provided with the fire pump; a. 100% b. 115% c. 125% d. 150% Feedback Rule 32-300 The correct answer is: 125% Coil of a motor control circuit if over heating. What do you think is the problem? a. Broken shading coil b. Insufficient Tip pressure c. Dirt or rust on pole faces d. Sustained overload Feedback Table 1 of the Motor control module in ATTI electrical IP content The correct answer is: Dirt or rust on pole faces A 4-20mA signal transmitter is sitting at 85% of the range. What will the meter read in mA? a. 13.6 mA b. 17.6 mA c. 19.6 mA d. 21.6 mA Feedback In a 4 -20mA 85% (16/100*85)==> (13.6+4)==> 17.6 mA The correct answer is: 17.6 mA Two motors with FLA of 30Amps and 50 Amps are controlled by OCP of a time delay fuse. What is the fuse size? Both motors are SCIM a. 100Amps b. 110Amps c. 120Amps d. 150Amps Feedback 28-208(c) Table 13 The correct answer is: 110Amps Dielectric liquid-filled equipment in an indoor location must be installed in an electrical vault if dielectric is more than _________ of liquid in one tank. a. 23L b. 46L c. 69L d. None of the above Feedback Rule 26-010(1) The correct answer is: 23L For a power transformer rated at 1000V , each ungrounded conductor of the transformer will be provided with a fuse rated at not more than______________of the rated primary current of the transformer. a. 100% b. 110% c. 150% d. 300% Feedback Rule 26-250-1 The correct answer is: 150% Overload devices responsive to motor current are set to trip at not more than ___________of the full load current rating of a motor having a marked service factor of 1.15 or greater. a. 100% b. 125% c. 150% d. 250% Feedback Rule 28-306-1(a) The In fire Alarm circuits , stranded conductors with more than 7 strands shall be bunch-tinned or terminated in compression connectors a. True b. False Feedback Rule 32-100-3 The correct answer is: True correct answer is: 125% Cables included as part of photovoltaic modules shall be permitted for the interconnection of photovoltaic modules within an array, provided that the photovoltaic source and output circuits operate at a maximum system voltage of __________V or less. a. 6V b. 12V c. 24V d. 30V Feedback Rule 64-210(2) The correct answer is: 30V