WSAN_WSAT-XEE (24kW

advertisement

WSAT-XEE WSAN-XEE

Water chiller

4

WSAT-XEE: cooling only

4

WSAN-XEE: heat pump

Air cooled

Outdoor installation

Capacity from 24,3 to 72,2 kW

On Line Monitoring Service available

A

Eurovent Energy

Efficiency Class

ELFO

ENERGY MEDIUM

82÷302

Liquid chillers and heat pumps of the ELFOEnergy WSAT-XEE and WSAN-XEE series are units designed for outdoor installation and best energy efficiency in relation to their reduced size.

The ELFOEnergy series has been the turning point in the evolution of chillers.

Every unit has been conceived and made by applying state-of the art technology, emphasising the qualities of EFFICIENCY , SELF-ADAPTATION and EASY

INSTALLATION that distinguish this product

Thanks to its constructional and electronic peculiarities, ELFOEnergy permits:

4 high energy efficiency, in particular during partial-load operation, thanks to the use of two compressors with different capacities that work on a single refrigerant circuit;

4 Eurovent energy efficiency classification class "A" in heating operation, also in full load condition;

4 adaptability of operating parameters to the load conditions of the connected system, thereby optimising consumption, efficiency and working life of the parts;

4 easy, quick installation thanks to the standard hydronic group and the factory test carried out prior to dispatch;

4 installation of hydronic group with non-standard working head pumps or with double pump .

functions and features

AIR R-410A

Cooling only

(WSAT-XEE)

Heating-Cooling

(WSAN-XEE)

Air cooled Outdoor inst.

Refrig. R-410A

available configurations

WSAT-XEE

(1)

S 82

(2)

400TN

(3)

1PUS

(4)

-

(1) LOW TEMPERATURE:

4 S

4 B

Standard

Low water temperature

This version allows unit operation within the water and glycol mixing temperature range between +4°C and -8°C inclusive.

4 DSPB Double set-point for water low temperature (Brine)

(2) SUPPLY VOLTAGE:

4

400TN 400/3/50+N

(3) HYDRONIC GROUP USER SIDE:

4

1PUS Standard pump

4

1PUR Single pump with reduced discharge head

4 1PUM Single pump with larger discharge head

4 2PUS Standard double pump

4

2PUR Double pump with reduced discharge head

4

2PUM Double pump with larger discharge head

4 Not required

(4) ENERGY RECOVERY:

4

-

4 D

Not required (Standard)

Partial recovery

Carried out using braze-welded plate-type exchangers suited for recovering the desuperheating heat up to a maximum of

25% of the total unit heat.

Herm. Scroll ELFOControl Ice protection system (WSAN-XEE only)

(5)

OHP

(6)

-

(7)

-

(8)

-

(9)

-

(10)

-

(5) OPERATION (WSAN-XEE only):

4 OHP Operation in heat pump

Cooling and heating unit (Standard)

4

OHO Operation in heating-only

Heating only unit

(6) CONDENSER COIL:

4

CCS Standard condenser coil

4

CCCA Condenser coil in copper/aluminium with acrylic coating

4 CCCA1 Condenser coil in copper/aluminium with Fin Guard (Silver) treatment

4

CCCC Condenser coil in copper/copper

(7) SOFT STARTER:

4 Not required (Standard)

4

SFSTR4N Device for inrush current reduction, for 400/3/50+N units

(8) FREE CONTACTS HEATING EXTERNAL SIGNAL:

4 -

4

CLS

Not required (Standard)

Free Contacts External Signal

(9) SHUNT CAPACITORS (POWER FACTOR > 0,9):

4 -

4

PFCP

Not required (Standard)

Shunt capacitors (power factor > 0,9)

(10) STORAGE TANK:

4 Not required (Standard)

4

ACC1 Teflon steel storage tank

accessories

4

4

4

4

4

4

4

Rubber antivibration mounts

Serial communication module (MODBUS)

Steel mesh filter on water side (when unit is in “without hydronic group” configuration)

High and low pressure gauges

Daily and weekly programming clock

Finned coil protection grilles

Phase monitor to check the presence and correct sequence of the power supply phases

4

Control keypad for remote installation that repeats all the functions already present on the onboard microprocessor control

4

Humidity probe for summer set point compensation according to the outside enthalpy and defrosting optimization in winter operation

Key to symbols:

Accessories supplied separately.

technical data

Sizes

Application with terminal units

Cooling capacity WSAT-XEE

Total input WSAT-XEE

EER - WSAT-XEE

ESEER - WSAT-XEE

Heating capacity

Total input

COP

Pump working head WSAT-XEE

Number of refrigerant circuits

Number and type of compressors

Sound pressure level

Power supply

(1)

(1)(2)

(1)

(3)

(2)(3)

(3)

(1)

(4)

Application with radiant panels (WSAN-XEE only)

(5)

Total input

EER

Heating capacity

Total input

COP

Pump working head

Number of refrigerant circuits

Number and type of compressors

Sound pressure level

Power supply

(2)(5)

(5)

(6)

(2)(6)

(6)

(5)

(4) kW kW

kPa

-

kW kW

-

dB(A)

V/Ph/Hz

kW

kPa kW kW

kW

dB(A)

V/Ph/Hz

60

60

Data referred to the following conditions:

(1) Internal exchanger water = 12/7°C; air entering external exchanger = 35°C

(2) Total input is obtained from the compressor input + fan input + auxiliary circuit input.

(3) Ambient temperature = 7°C (R.H. = 85%); internal exchanger water outlet temperature 45°C

dimensions and clearances

31,5

9,95

3,16

29,2

7,07

4,13

92

82

24,3

8,90

2,73

4,32

28,8

9,00

3,20

132 leave free

B1

B

B2

A1

C

A

A2

122

33,7

12,5

2,71

4,18

37,5

11,7

3,20

120

60

43,8

14,4

3,0

38,0

9,1

4,2

73

60

102

28,2

10,4

2,72

4,48

32,9

10,3

3,20

126

60

36,7

11,86

3,09

33,6

7,97

4,21

80

60

162 182

40,0

14,2

2,81

4,20

45,6

45,9

16,7

2,74

4,34

53,0

14,1

3,23

104

16,5

3,21

88

1

2 SCROLL

61 62

400/3/50+N

52,6

16,8

3,1

46,9

60,2

18,9

3,2

54,1

11,2

4,2

43

13,3

4,1

17

1

2 SCROLL

61 62

400/3/50+N

302

72,2

26,6

2,71

4,06

83,7

25,6

3,27

131

64

97,2

30,5

3,2

85,4

21,1

4,1

83

64

262

64,1

23,4

2,74

4,19

72,4

22,2

3,27

139

64

83,1

26,6

3,1

74,0

18,2

4,1

102

64

222

54,4

20,1

2,71

4,47

61,9

19,0

3,26

148

62

72,3

22,7

3,2

63,3

15,6

4,1

111

62

(4) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions.

(5) Internal exchanger water = 23/18°C; air entering external exchanger = 35°C

(6) Fresh air temperature = 7°C D.B. / 6°C W.B.; internal exchanger water temperature 30/35°C

Sizes

Length (A)

Width (B)

Height (C)

4 (A1)

(A2)

(B1)

(B2)

WSAT-XEE

Weight in oper.

WSAN-XEE

Weight in oper.

mm mm mm mm mm mm mm

Kg

Kg

700

700

700

700

82

1703

675

1209

305

315

The above data refer to standard units.

700

700

700

700

102

1703

675

1209

310

320

700

700

700

700

122

1703

675

1209

360

370

700

700

700

700

162

1932

1100

1417

520

530

700

700

700

700

182

1932

1100

1417

540

550

222

1932

1100

1417

700

700

700

700

570

580

700

700

700

700

262

2332

1100

1417

665

675

700

700

700

700

302

2332

1100

1417

680

690

CAUTION!

For trouble-free operation of the unit it is essential to maintain the safety distances indicated by the green areas.

Data contained in this document are not binding and may be changed by the Manufacturer without notice. No part of this publication may be reproduced.

www.clivet.com