WSAT-XEE WSAN-XEE 82÷302 Water chiller WSAT-XEE: cooling only WSAN-XEE: reversible heat pump Air cooled Outdoor installation Capacity from 24,7 to 73 kW HYDRONIC ELFOEnergy Medium Liquid chillers and heat pumps of the ELFOEnergy Medium range, ideal for the small-scale commercial sector, are specifically designed for outdoor installation. energy efficiency, especially during operation at partial loads, High thanks to the use of two compressors of different capacity operating on a single cooling circuit for systems with radiant panels or hydronic terminal units Ideal Hydronic assembly supplied as standard, available with pumps with non-standard available head and/or with double pump tank not normally necessary, but available for applications Storage where the quantity of water in the system has values not fairs. Unit listed on www.eurovent-certification.com functions and features AIR Cooling only (WSAT-XEE) Heat pump (WSAN-XEE) FC R-410A Air cooled Outdoor installation R-410A Hermetic Scroll ELFOControl² Ice protection system FREE-COOLING dimensions and clearances C B1 A2 B B2 A A1 Size – WSAT-XEE A - Length B - Width C - Height A1 A2 B1 B2 Operating weight mm mm mm mm mm mm mm kg 82 1703 675 1209 700 700 700 700 298 102 1703 675 1209 700 700 700 700 303 122 1703 675 1209 700 700 700 700 323 162 1932 1100 1417 700 700 700 700 456 182 1932 1100 1417 700 700 700 700 469 222 1932 1100 1417 700 700 700 700 490 262 2332 1100 1417 700 700 700 700 547 302 2332 1100 1417 700 700 700 700 561 Size – WSAN-XEE A - Length B - Width C - Height A1 A2 B1 B2 Operating weight mm mm mm mm mm mm mm kg 82 1703 675 1209 700 700 700 700 315 102 1703 675 1209 700 700 700 700 320 122 1703 675 1209 700 700 700 700 370 162 1932 1100 1417 700 700 700 700 530 182 1932 1100 1417 700 700 700 700 550 222 1932 1100 1417 700 700 700 700 580 262 2332 1100 1417 700 700 700 700 675 302 2332 1100 1417 700 700 700 700 690 CAUTION!For trouble-free operation of the unit it is essential to maintain the safety The above mentioned data are referred to standard units for the constructive configurations indicated. For all the other configurations, refer to distances indicated by the green areas. the relative Technical Bulletin. versions and configurations FREE-COOLING (WSAT-XEE only): FREE-COOLING: not required (Standard) FCD Direct FREE-COOLING - Low temperature: Low temperature: not required (Standard) B Water low temperature - double set point: Double set point: not required (Standard) DSPB Double set point for water low temperature - External section fan consumption reduction (WSAT-XEE only): Device for fan consumption reduction of the external section: not required (Standard) CREFB Device for consumption reduction of the external section ECOBREEZE fans - Energy recovery: Energy recovery: not required (Standard) D Partial energy recovery - Operation (WSAN-XEE only): Operation in heat pump OHO Heating-only operation technical data Size – WSAT-XEE Terminal units A35/W7 capacity Cooling Total power input EER (EN 14511:2011) ESEER Water flow rate (Utility Side) Useful pump discharge head Standard power supply Sound Pressure Level (10m) Return air min. temperature Max water outlet temperature Size – WSAN-XEE Unit for radiant panels A7/W35 Heating capacity Total power input COP (EN 14511:2011) A35/W18 Cooling capacity Total power input EER (EN 14511:2011) Water flow rate (Utility Side) Useful pump discharge head Standard power supply Sound Pressure Level (10m) Min air inlet temperature (W.B.) Max water outlet temperature Terminal units A7/W45 Heating capacity Total power input COP (EN 14511:2011) A35/W7 Cooling capacity Total power input EER (EN 14511:2011) ESEER Water flow rate (Utility Side) Useful pump discharge head Standard power supply Sound Pressure Level (10m) Min air inlet temperature (W.B.) Max water outlet temperature (1) (1) (2) kW kW l/s kPa V dB(A) °C °C kW kW kW kW l/s (3) kPa V dB(A) (4)(5) °C (4) °C kW kW kW kW (1) l/s (1) kPa V dB(A) (4)(6) °C (4)(7) °C 82 102 122 162 182 222 262 302 24,7 9,25 2,67 3,95 1,20 132 400/3/50+N 44 -10 18 28,7 10,7 2,67 3,93 1,30 126 400/3/50+N 44 -10 18 34,2 12,8 2,68 3,88 1,60 120 400/3/50+N 44 -10 18 40,5 14,6 2,78 4,09 1,90 104 400/3/50+N 46 -10 18 46,4 17,1 2,72 3,99 2,20 88 400/3/50+N 47 -10 18 55,2 20,8 2,65 3,90 2,60 148 400/3/50+N 47 -10 18 65,0 24,0 2,70 3,97 3,10 139 400/3/50+N 49 -10 18 73,1 27,2 2,69 3,92 3,40 131 400/3/50+N 49 -10 18 82 102 122 162 182 222 262 302 28,8 7,49 3,84 33,2 8,37 3,96 37,5 9,50 3,95 46,5 11,6 3,99 53,7 13,8 3,89 62,5 16,3 3,84 73,1 18,8 3,88 84,5 21,7 3,89 31,9 10,4 3,08 1,50 92 400/3/50+N 44 -10 55 37,1 12,3 3,02 1,80 80 400/3/50+N 44 -10 55 44,2 14,8 3,00 2,10 73 400/3/50+N 44 -10 53 52,9 17,3 3,05 2,50 43 400/3/50+N 46 -10 55 60,4 19,6 3,08 2,90 17 400/3/50+N 47 -10 55 73,1 23,4 3,12 3,50 111 400/3/50+N 47 -10 55 83,9 27,3 3,08 4,00 102 400/3/50+N 49 -10 55 98,0 31,2 3,14 4,60 83 400/3/50+N 49 -10 55 28,4 9,42 3,01 32,5 10,7 3,04 37,0 12,1 3,06 45,1 14,5 3,11 52,6 17,0 3,10 61,1 19,7 3,10 71,5 22,8 3,13 82,8 26,2 3,16 24,0 9,75 2,46 3,77 1,10 136 400/3/50+N 44 -7,0 55 28,0 11,2 2,49 3,84 1,30 129 400/3/50+N 44 -7,0 55 33,2 13,4 2,48 3,85 1,60 125 400/3/50+N 44 -7,0 53 39,9 15,7 2,55 3,95 1,90 107 400/3/50+N 46 -7,0 55 46,1 18,2 2,54 4,01 2,20 89 400/3/50+N 47 -7,0 55 53,7 21,7 2,47 3,83 2,50 150 400/3/50+N 47 -7,0 55 63,9 25,6 2,49 3,86 3,00 141 400/3/50+N 49 -7,0 55 72,8 29,0 2,51 3,91 3,40 131 400/3/50+N 49 -7,0 55 Notes (1) Data referred to the following conditions : Internal exchanger water = 12/7°C; External exchanger air return 35°C (2) External exchanger air in quiet (3) Data referred to the following conditions : Internal exchanger water = 23/18°C; External exchanger air return 35°C (4) Internal exchanger water = 12/7°C (5) Exchanger water outlet 35°C (6) Outlet water internal exchanger 45°C (7) Room temperature = 7°C (RH = 85%) Performances according to EN 14511:2011 A7/W35 internal exchanger water 30/35°C; external air temperature 7°C D.B./ 6°C W.B. A7/W45 internal exchanger water 40/45°C; external air temperature 7°C D.B./ 6°C W.B. A35/W18 internal exchanger water 23/18°C; external air temperature 35°C A35/W7 internal exchanger water 12/7°C; external air temperature 35°C REF-DG13A001GB-00 OHP accessories CCCA CCCA1 1PUR 1PUM 2PUS 2PUR 2PUM ACC1 IFWX MHPX ■• AMRX ■• PGCEX ■• ■• Copper / aluminium condenser coil with acrylic lining Copper / aluminium condenser coil with Energy Guard DCC Aluminum Single-pump with reduced available head Single-pump with larger available head Standard double pump Double pump with reduced available head (sizes 222÷302) Double pump with larger available head Teflon steel storage device Water steel mesh strainer High and low pressure gauges Rubber antivibration mounts Coil protection grilles external air side HYDRONIC Key to symbols: ■• Accessories supplied separately. SFSTR4N Disposal for inrush current reduction, for unit 400/3/50+N Phase monitor ■• PMX Phase monitor ■• RCMRX Remote control via microprocessor control ■• CMMBX Serial communication module to supervisor (MODBUS) CMSC7 MODBUS/LON WORKS serial converter kit ■• PCDWX Daily and weekly programming clock ■• SCP3X Set point compensation according to the outside enthalpy CLSE Free contacts for alarm PFCP Power factor correction capacitors (cosfi > 0.9) WSAT-XEE only: ■• SPCX Set point compensation with outside temperature probe PM HYDRONIC Data contained in this document are not binding and may be changed by the Manufacturer without notice. www.clivet.it