2002 National Electrical Code Changes Developed and Presented by: The Codes and Standards Group of Schneider Electric Where We Started 1 Development Timeline Proposal Deadline November 5, 1999 Code-Making Panels Meet Jan 10-22, 2000 Written Ballots Due Feb 17 (or 24), 2000 Technical Correlating Committee Meeting May 8-12, 2000 NEC Report on Comments Available July 14, 2000 Public Comment Development Timeline Public Comments Due to NFPA October 27, 2000 Code-Making Panels meet Dec 4-16, 2000 Written Ballots Due Jan 5 (or 12), 2001 Technical Correlating Committee Meeting Feb 25 - Mar 1 NEC Report on Comments Available April 16, 2001 NFPA Annual Meeting May 13-17, 2001 Standards Council hears Appeals on July 11, 2001 2002 NEC Issued with Effective date of August 2, 2001 2 Use of the 2002 NEC l l l l 2002 is the Latest Edition of NFPA 70 Most jurisdictions specify what edition of the NEC they follow Adoption process must recognize the 2002 edition in order for it to be the “active” document in the locality Some jurisdictions have already completed process to utilize the 2002 edition on January 1, 2002 n e.g. North Carolina, Massachusetts l Other jurisdictions may not adopt the 2002 edition until some future date Numbering Format From Dash to Dot 3 Acronyms l l 2002 NEC will use standard acronyms Examples n RMC – Rigid Metal Conduit n RNMC – Rigid Nonmetallic Conduit n EMT – Electrical Metallic Tubing n LFMC – Liquidtight Flexible Metal Conduit n ENT – Electrical Nonmetallic Tubing n IMC – Intermediate Metal Conduit n NUCC – Nonmetallic Underground Conduit with Conductors n AC – Armored Cable n NM – Nonmetallic sheathed cable Article 80 (New) Administration and Enforcement l l Provides a set of model administrative rules to apply and enforce the NEC Covers n Inspection n Investigation of electrical fires n Review of construction plans, drawings and specifications n Design, alteration, modification, construction, maintenance and testing n Regulation and control of special events l Article 80 is informative only (not part of the Code) unless specifically adopted by the jurisdiction 4 90.1(D) - Purpose Relation to International Standards l l NEC addresses fundamental principles of protection for safety contained in IEC 60364-1, Section 131 Protection against: n Electrical shock n Thermal effects n Overcurrent n Fault-currents n Overvoltage 90.2(B)(5) – Scope Under exclusive control of a utility: Not Covered Service drops or laterals and associated metering Located in legally established easements, rights of way, etc and recognized by regulatory agencies On property owned or leased by the utility for purpose of communications, metering, generation, control, transformation, transmission, or distribution of electric energy. 5 90.3 Code Arrangement Chapter 1 - General Chapter 2 - Wiring and Protection Chapter 3 - Wiring Methods and Materials Chapter 4 - Equipment for General Use Supplements or modifies Chapters 1 through 4 Chapter 9 - Tables Annex A through Annex D Chapter 5 - Special Occupancies { Chapter 8 - Communications Systems } Applies generally to all electrical installations Chapter 6 - Special Equipment Chapter 7 - Special Conditions Chapter 8 is not subject to the requirements of Chapters 1 through 7 except as specifically referenced in Chapter 8 } } Applicable as referenced } Information only not mandatory 90.4 Enforcement l l l The authority having jurisdiction can waive specific requirements or permit alternative methods Only allowed where “equivalent safety” is assured Now requires “special permission” n Special permission as defined in Article 100 requires written consent of the authority having jurisdiction 6 90.7 Examination of Equipment for Safety Definition of “Listed” in Article 100 states that products must meet appropriate designated standards. 90.7 states that examination of equipment for safety under standard conditions provide a basis for approval. 90.7 FPN No. 3 notes that Annex A contains and informative product standards list Annex A – Product Safety Standards • Informative only • List of standards used for product listing What are the “appropriate” designated standards? • Makes the connection between the Code rules and properly evaluated products 90.9 – Units of Measurement Compliance l l NEC now has metric as the first dimension listed The conversions are not exact n e.g. 1m (3 ft) l l The installation can be made to either the SI (metric) or the “inch-pound” units Wire sizes did not change – still AWG and kcmil 7 Article 100 – Definitions Authority Having Jurisdiction l l l The organization, office, or, individual responsible for approving equipment, materials, an installation, or a procedure. This term is standardized through out the NFPA system Examples include n Public safety – electrical inspector, fire marshal, fire chief, building official, others having statutory authority n Insurance purposes – insurance inspection department, rating bureau n Others – property owner or designee n Government – commanding officer, departmental official Article 100 - Definitions Ground-Fault Circuit Interrupter Definition now makes it clear that a device intended to provide protection of personnel must be a Class A device. 8 Article 100 - Definitions Luminaire A complete lighting unit consisting of a lamp or lamps together with the parts designed to distribute the light, to position and protect the lamps and ballast (where applicable), and to connect the lamps to the power supply. Fixture Luminaire Lighting fixture Article 100 – Definitions Qualified Person One who has the skills and knowledge related to the construction and operation of the electrical equipment and installations and has received safety training on the hazards involved. 9 Article 100 – Definitions Structure l l l “That which is built or constructed” Not previously defined in the NEC Compatible with other building codes and standards 110.12(A) – Mechanical Execution of Work Unused Openings l l l l Combines the requirements in Article 110 with the requirements covering cabinets and cutout boxes Applies to boxes, raceways, auxiliary gutters, cabinets, cutout boxes, meter socket enclosures, equipment cases and housings Must be substantially equivalent to the wall of the equipment Metallic plugs in nonmetallic enclosures must be recessed at least 6 mm Box Close all unused openings 10 110.14(C) – Electrical Terminations Temperature Limitations Ampacity of the conductor (for ambient adjustment and derating) is permitted to be based on appropriate table (e.g. 310.17 for single conductors in free-air) Ampacities for conductors at equipment terminations must be based on Table 310.16 110.15 (new) High-leg Marking l l New section added to require the marking of the high- leg of a 4wire delta connect system with orange color or other effective means Identification required at each point on the system where a connection is made if the grounded conductor is also present 120V 120V 208V 11 110.16 (New) Flash Protection Switchboards, panelboards, industrial control panels, and motor control centers that are likely to be worked on while energized DANGER Arc -Flash Hazard Protective Equipment required in accordance with NFPA 70E Failure to use proper equipment can result in serious injury or death Field Marked with a label to warn of potential electric arc flash hazards Equipment in dwelling units is not included in the requirement 110.26(C)(2) – Entrance to Working Space Large Equipment Where the entrance to the space has a personnel door, it must open in the direction of egress and be equipped with panic bars, pressure plates, etc. Similar rule for over 600V equipment in 110.33 Equipment over 1200A and over 6 feet wide 12 110.26(F) – Spaces about Electrical Equipment Dedicated Equipment Space Piping Drip protection Space above the dedicated space up to the structural ceiling is permitted to have foreign systems, provided protection from leaks or breaks is provided Dedicated space extends 6 feet above the height of the equipment. Only electrical equipment allowed in this space. Space is the same width and depth as the equipment. 110.31 Enclosure for Electrical Installations l l l Fence shall not be less than 7ft in height Table 110.31 Minimum Distance from Fence to Live Parts Does not apply to enclosed equipment Minimum Distance to Live Parts Nominal Voltage 601 - 13,799 13,800 -230,000 Over 230,000 m 3.05 4.57 5.49 ft 10 15 18 13 110.58 – Tunnel Installations over 600V Disconnecting Means l A switch or circuit breaker shall be installed within sight of each transformer or motor location to serve as the disconnect. 200.6 Means of Identifying Grounded Conductors l l l The word “natural” has been deleted from “natural gray” Gray conductors are now permitted as grounded conductors Allows “gray” to be used for an ungrounded conductor to distinguish one system from the other n e.g. white for 120/240V and gray for 480Y/277V 14 210.6(E) – Voltage Limitations Over 600 Volts Between Conductors Over 600V circuits can supply utilization equipment in installations where conditions of maintenance and supervision ensure that qualified persons will service the installation. 4160V Compressor 210.7 Branch Circuit Receptacle Requirements New Article 406 covering Receptacles 1999 NEC 210-7 covered: • Requirements for grounding type receptacles • Methods of grounding receptacles Moved to • Replacement of receptacles 15 210.7(C) – Receptacle Requirements Multiple Branch Circuits Supplied by more than one branch circuit (can be multiple single circuits or a multi-wire circuit) More than one receptacle on a yoke Ø Ø N Must be provided with a means to simultaneously disconnect the ungrounded conductors at the panelboard where the circuits originate 210.8(A)(5) Exception No. 3 – Dwelling Units Unfinished Basements Omission of GFCI protection Fire and/or Burglar Alarm Control Panel Remove tab to limit to one receptacle Receptacle supplying only a permanently installed fire alarm or burglar-alarm 16 210.8(A)(8) – Dwelling Units Boathouses 15- and 20-ampere receptacles in boathouses on dwelling unit property are required to have GFCI protection. Article 555 now excludes private, noncommercial docking facilities for singlefamily dwellings 210.8(B)(3) – Other than Dwelling Units Kitchens GFCI protection now required for 15 and 20A receptacles in kitchens located in other than dwelling unit 17 210.12 Arc-Fault Circuit-Interrupter Protection Requirements: • All branch circuits supplying 15 or 20A outlets in the bedroom • NOTE: see definition of “outlet” in Article 100, this includes lighting outlets • AFCI must be listed to provide protection of the entire branch circuit 210.19(B) – Minimum Ampacity and Size Branch Circuits Over 600 Volts l l l Ampacity in accordance with Table 310.15 and 310.60 Size conductors at not less than 125% of the “designed potential load” of equipment to be operated simultaneously OR Sized by the engineer for supervised installations n Design and installation are under engineering supervision n Qualified persons with documented training and experience in over 600V systems provide maintenance, monitoring, and servicing of equipment 18 210.23 Permissible Loads l l No change to the code language Panel Statement is significant: n The 80% limitation on any single cord- and plug-connected appliance on a circuit with two or more receptacles applies to both continuous or intermittent loads 210.52 Dwelling Unit Receptacle Outlets Modified to indicate this section provides requirements for 125-volt, 15 and 20 ampere receptacle outlets. 19 210.52(C) Countertops Receptacle installed in appliance garage does not count as one of the required outlets. Must be not more than 24” to meet 210.52(C)(1) 210.52(C)(5) Exception - Countertops Receptacle Outlet Location Where a receptacle is mounted above the cabinets, it must be within 20” of the countertop to be counted as one of the required receptacles. Not more than 20” 20 210.52(D) Bathrooms l l l Receptacle now permitted to be installed on a partition or a wall Wall or partition must be “adjacent” to the basin or basin countertop The receptacle must be within 3 feet of the outside edge of the basin Wall Half-wall or partition 210.52(G) Basements GFCI Protected Unfinished portion GFCI Protected Finished Basement normal receptacle placement Unfinished portion A receptacle must be placed in each unfinished portion of the basement 21 210.63 Heating, AC, and Refrigeration Equipment Outlet Receptacle required within 25’ of all heating, AC or refrigeration equipment regardless of the type of installation 25’ max 210.70(A)(2)(c) – Dwelling Units Lighting Outlet Switch Locations Switch required at landing level if there is an entry at the landing. 22 215.2(B) – Minimum Rating and Size Feeders Over 600 Volts l l l l Ampacity in accordance with 310.15 and 310.60 Transformers – conductors supplying transformers shall not be less than the nameplate rating of the transformer Transformers and utilization equipment - Size conductors at not less than 125% of the “designed potential load” of equipment plus the nameplate ratings of the transformers OR Sized by the engineer for supervised installations n Design and installation are under engineering supervision n Qualified persons with documented training and experience in over 600V systems provide maintenance, monitoring, and servicing of equipment 225.26 Vegetation as Support Support of overhead conductor spans by vegetation is not permitted. The exception for temporary wiring has been deleted. 23 230.6 Conductors Considered Outside the Building Installed under not less than 2” of concrete beneath a building or structure Installed in conduit and under not less than 18” of earth beneath a building or structure Encased in not less than 2” of concrete or brick Installed in a vault that meets Article 450 Part III 230.40 Exception No. 1 – Service Entrance Conductors Number of Service Entrance Conductor Sets Occupancy #1 Occupancy #2 240V Service Occupancy #3 480V Service Permits a set of service entrance conductors run to each occupancy for each service of different characteristics as defined in 230.2(D) 24 230.70(A)(3) - Location Remote Control Shunt trip or “remote control” The service equipment must still be located at a readily accessible location where the conductors enter the building 230.82 Equipment Connected to the Supply Side of Service Equip l Additional Equipment Supply n Meter sockets n Meter disconnect switches rated 600 Volts max n Fuel Cell Systems l Surge Protective Devices removed from list of permitted devices n Surge Arresters are still included in the Meter disconnect switch 480Y/277V Typical permitted list of devices n Removed in order to clarify TVSS products are not permitted On to service equipment 25 230.212 Over 35,000 Volts l l Section previously applied when voltage exceeded 15,000 volts Where service conductors enter a building they must terminate in metal-enclosed switchgear compartment or a vault complying with Article 450 Part III 240.2 Definitions l Coordination n The proper localization of a fault condition to restrict outages to the equipment affected, accomplished by the choice of selective faultprotective devices l Current limiting overcurrent protective device n Moved from 240.11 l Supervised industrial installation n Moved from 240.91 l Tap conductors n Moved from 240.3(D) n Clarified to exclude service conductors 26 240.21(B)(5)(4)c – Feeder Taps Outside Taps of Unlimited Length Feeder Tap Conductors installed in accordance with 230.6 Equipment at a readily accessible location where the conductors enter 240.21(C)(6) – Transformer Secondary Conductors Secondary Conductors Not Over 25’ Long Primary conductors protected at their ampacity Conductors terminate in a single CB or set of fuses that limit load current to the ampacity of the secondary conductors 200A 480V 240V 25’ max 150A conductors Secondary conductors have an ampacity that is at least 1/3 the rating of the primary device when multiplied by the voltage ratio 150A 27 240.24(B) Exception No. 2 – Location In Premises Occupancy l l General rule requires that each occupant have ready access to overcurrent devices that supply that occupancy Exception recognizes that occupants of hotel/motel rooms do not need access if the building is under continuous building management supervision 240.83(D) - Marking Used as Switches l l Requires a breaker listed and marked as HID (high intensity discharge) to be used as a switch for HID lighting Florescent lighting can be switched with breakers marked SWD or HID 28 240.85 – Circuit Breakers Applications Clarifies that “slash” rated breakers should be applied only in solidly grounded circuits Slash Rated Breaker OK Article 240 Part VIII Supervised Industrial Installations At least one service more than 150V to ground and 300V phase-to-phase Conditions of maintenance and engineering supervision ensure that only qualified persons monitor and service the system System has at least 2500 kVA of load used in industrial process and/or manufacturing (calculated in accordance with Article 220) Does not apply to offices, garages, warehouses, etc. 29 240.92(B)(1)(1) – Transformer Secondary Conductors Short-Circuit and Ground-Fault Protection Primary overcurrent device not more than 150% of the secondary conductor ampacity multiplied by the secondary to primary voltage ratio Secondary conductor length changed from 50 feet to 100 feet See 240.92(B)(2) for overload protection requirements 240.92(B)(1)(2) – Transformer Secondary Conductors Short-Circuit and Ground-Fault Protection Differential Relay Conductor secondary is now permitted to be of any length See 240.92(B)(2) for overload protection requirements 30 240.92(B)(1)(3) – Transformer Secondary Conductors Short-Circuit and Ground-Fault Protection Secondary conductors considered protected if calculations made under engineering supervision determine that the system overcurrent devices will protect the conductors within the recognized time-current limits for ALL shortcircuit and ground-fault conditions. Secondary conductor length limitation removed 240.92(D) – Location in Circuit Protection by Primary Overcurrent Device l l l Secondary conductors are permitted to be protected by the primary overcurrent device Primary device time-current characteristics multiplied by the effective primary to secondary voltage ratio must effectively protect the secondary conductors Difficult to use with transformers that have greater than a 1:1 ratio of primary L-L voltage to secondary L-L voltage 31 250.4(B) – General Requirements for Grounding Ungrounded Systems l l l Material moved from 250.2 where it was mixed with grounding system requirements Ground all non-current carrying conductive materials of electrical equipment Bond together all noncurrent carrying conductive materials together to create a permanent, low- impedance path for ground-fault current 1st fault grounds the system 250.20 AC Circuits and Systems to Be Grounded l l l Specifies what systems are required to be grounded Notes that other systems are permitted to be grounded Now clarifies that if a system is grounded (either required or permitted) the grounding must comply with Article 250 32 250.30(A)(2)(b) and (3) – Sep Derived Systems Grounding Electrode Conductor l Allows a common grounding electrode for multiple separately derived systems l Must use exothermic weld, irreversible compression or connect to copper bus bars Keep main grounding electrode conductor without a splice or joint l Separately Derived Systems Size common grounding electrode conductor based on 250.66 using the total area of largest derived phase conductor from each system Size “tap” conductors based on 250.66 based on the derived phase conductor size Grounding Electrode (example shown is water pipe) 250.32(E) – Two or More Buildings/Structures Grounding Electrode Conductor Service Equip - Bldg #1 Bldg #2 Grounding electrode conductor sized by 250.66 based on largest ungrounded supply conductor. 33 Article 250 Part III – Grounding Electrode system l 250.52 establishes the electrodes PERMITTED for grounding n Metal underground water pipe n Metal frame of the building or structure n Concrete encased electrode n Ground ring n Rod and Pipe electrodes n Plate electrodes n Other local metal undergrounds systems or structures l 250.52(B) establishes electrodes NOT permitted for grounding n Metal underground gas piping n Aluminum electrodes Gas Pipe 250.53(C) – Grounding Electrode System Installation Bonding Jumper • Install – 260.64(A), (B) and (E) • Size - 250.66 • Connect – 250.70 34 250.102(E) – Equipment Bonding Jumper Installation Equipment bonding jumper permitted longer than 6’ permitted to bond isolated sections of metal raceways Rigid metal conduit Rigid nonmetallic conduit 250.104(A) – Bonding of Piping Systems Metal Water Piping Requires bonding of water pipe that is “installed in” or “attached to” a building or structure. “Attached to” “Installed in” 35 250.104(B) Bonding of Other Metal Piping l l l l Deleted old 250-104(c) that required bonding of all metal gas piping to the grounding electrode Gas piping now covered under 240.104(B) which requires bonding of piping that is “likely to become energized”. Bonding jumper sized based on the overcurrent device protecting the circuit that is likely to energize the piping. The equipment grounding conductor of the circuit is permitted to serve as the bonding means Gas Piping Branch Circuit 250.122(B) – Equipment Grounding Conductors Increase in Size Now requires proportional increase in equipment grounding conductor when phase conductors are increased for any reason. 36 250.146(A) Surface Mounted Box Box must be mounted “on” the surface Previous code allowed a box mounted “at” the surface to use metal to metal contact. Now a yoke must be listed to establish the grounding path for other than surface mounted boxes. Direct metal to metal contact acceptable for grounding the receptacle Article 285 Transient Voltage Surge Suppressors (TVSS) l l l Service. The TVSS shall be connected on the load side of a service disconnect overcurrent device Separately Derived System. The TVSS shall be connected on the load side of the first overcurrent device in a separately derived system. Short Circuit Current Rating. The TVSS shall not be installed at a point on the system where the available fault current exceeds the marking on the equipment. 37 285.1 - TVSS Article Scope l Covers n general requirements n installation requirements n connection requirements l Permanently installed only 285.3 - TVSS Uses Not Permitted l l l Circuits exceeding 600 volts. Ungrounded electrical systems as permitted in Section 250.21. Where the rating of the TVSS is less than the maximum continuous phaseto-ground power frequency voltage available at the point of application. 38 285.5 - TVSS Listing l l The TVSS shall be Listed. Most TVSS products will reference: n UL 1449 2nd Edition on the product. 285.6 - TVSS Short Circuit Current Rating l The TVSS shall be marked with a short circuit current rating... n DO NOT confuse the Short Circuit Current Rating (SCCR) with the Surge Current (Capacity) Rating !!! The Surge Current Rating is the maximum transient current level that can be suppressed by the TVSS. u The Short Circuit Current Rating is the available and sustainable power current level that can flow in the circuit, at the point of connection to the system, during a fault condition until the circuit is opened. u 39 Chapter 3 Reorganization Articles Moving to Different Chapters Moving to 305 527 380 404 384 408 Chapter 3 Reorganization Wiring Method Article Renumbering l l See new Annex F for cross-reference Articles 312-314 covers boxes and enclosures n Outlet boxes, cabinets, etc. l Articles 320-340 covers cables n MI, MC, AC, NM, UF, etc. l Articles 342-356 covers conduits n RMC, RNMC, FMC, etc. l Articles 358-362 covers tubing n EMT, ENT, FMT, etc. l Articles 366-390 covers other methods n Busway, cable bus, etc. l Articles 392-398 covers open wiring n Knob and tube, open wiring on insulators, etc. 40 Chapter 3 Reorganization Common Number Method for all articles .1 Scope .2 Definitions .6 Listing Requirements Part B Installation .10 Uses Permitted .12 Uses Not Permitted .16 Temperature Limits .30 Securing and Supporting .60 Grounding Part C - Construction Specifications .110 Corrosion Protection .120 Markings 300.1(C) Metric Designators and Trade Sizes Neither the metric designator nor the trade size relate to actual dimensions of the conduit or tubing. Metric Designator 12 16 21 27 35 Trade Size 3/8 ½ ¾ 1 1¼ 41 53 63 78 91 103 129 155 1½ 2 2½ 3 3½ 4 5 6 41 300.4(B)(1) – Protection Against Physical Damage NM Cable and EMT Through Metal Framing Members Metal Stud A listed bushing or grommet must cover all metal edges and be securely fastened to the opening 300.5(D)(3) – Underground Installations Service Conductors 18” or more 18” or more At least 12” Warning Ribbon Applies to all underground service conductors 42 300.5(K) – Protection Against Physical Damage Directional Boring Cables and raceways installed using directional boring equipment shall be “approved” for the purpose. 300.6(A) – Protection Against Corrosion General Where threads are cut in the field, the threads shall be coated with an approved, electrically conductive, corrosion resistant compound. Located in an area where corrosion protection is necessary 43 300.7(A) – Raceways Exposed to Different Temperatures Sealing Raceway Interior - 72°F Exterior - 25°F Fill raceway with approved material to prevent circulation of warm air to cold air region 300.11(C) – Securing and Supporting Cables Not Used as Means of Support Cable wiring method (e.g. MC cable) Other cable or raceway (e.g. Class 2 circuit) Cable wiring methods are not permitted to support other cables or raceways 44 300.22(B) – Wiring in Ducts, Plenums or Other Spaces Ducts or Plenums Used for Environmental Air Change specifically prohibits conduit with an overall nonmetallic coating Ducts or plenums in 300.22(B) are those specifically fabricated to transport environmental air. 300.22(C) – Other Spaces Used for Env Air Wiring Methods Return Air Space Suspended ceiling Rigid metal conduit with a nonmetallic coating now prohibited 45 310.15(B)(2) – Exception No. 5 Adjustment Factors – AC or MC Cable MC or AC cable No adjustment factor required where not more than 20 current carrying conductors are in the stack or bundle. • #12 AWG conductors • Not more than 3 current carrying conductors per cable • No overall outer jacket For more than 20 current carrying conductors, a 60% adjustment factor applies Table 312.6(B) Minimum Wire Bending Space at Terminals The table now recognizes smaller wire bending space for compact stranded AA-8000 aluminum conductors Using an example of a 400A circuit: 1999 NEC 2002 NEC Cu – 3/0 - 6 ½ inches Cu – 3/0 - 6 ½ inches Al – 250 kcmil – 8 ½ inches Al – 250 kcmil – 6 ½ inches 46 314.20 In Wall or Ceiling Surface of concrete, tile, gypsum, plaster or other noncombustible material Box not set back more than ¼” from the finished surface For surfaces of wood or other combustible material, the box must be flush with the finished surface 314.23(B)(1) – Structural Mounting Nails and Screws Where nails or screws are used to fasten a box, the nail or screw must pass thru a bracket outside of enclosure or must pass through the inside with ¼” of the back of the enclosure. 47 314.27(A) Exception Boxes at Luminaire Outlets Use #6 screws minimum Permits mounting of luminaire to a “standard” outlet box where the luminaire does not weigh more than 6 lb. Dimensional limitation on the fixture has been removed. 314.27(B) – Outlet Boxes Maximum Luminaire Weight Outlet box identified for luminaire (fixture) support Luminaire weighing not more than 50 lbs. Luminarie’s weighing over 50 lbs must be supported independently of the outlet box 48 330.10(13) – Uses Permitted Single-Conductor MC Installation of single-conductor MC must comply with NEC 300.20. Single-conductor MC is required to have a nonmagnetic sheath or armor (NEC 330.116) Where single conductor MC is used, the phase and neutral (if used) conductors shall be grouped together to minimize induced voltage 332.80 – Ampacity Single Type MI Conductors Grouped Together Not less than 2.15 times diameter of largest conductor in the group Open runs or on a messenger in a triangle or square configuration Permitted to use Table 310.17 ampacities for the MI cable. Temperature limitation of equipment terminations must be considered. Ampacity will be required to be reduced back to Table 310.16 levels before terminated within equipment. 49 334.6 – NM Cable Listed NM Cable is required to be listed 334.10(2) – NM Cable Uses Permitted Multifamily dwellings and other buildings that are of Type III, IV or V construction. New Appendix E will contain a table from NFPA 220 to explain the different building Types The building code in effect locally will also define the building types In general, this permits NM to be used in 4-story apartment buildings (typically R-2 buildings, Type III and IV) 50 Annex E Types of Construction l l l Type III – typically constructed of noncombustible, limited-combustible, or other approved combustible material Type IV – typically timber frame construction Type V – typical stick built construction Explanation of Headers – Example = 211 Construction 2 = 2 hr fire rating of exterior load bearing walls 1 = 1 hr fire rating of columns, beams, girders that support bearing walls or loads from more than one floor 1 = 1 hr fire rating of floor 334.12(A)(1) – Uses Not Permitted Types NM, NMC and NMS Space above suspended ceiling in other than one, two and multi-family locations NM cable not permitted in this space 51 338.10(B)(4) – Uses Permitted Installation Methods for Branch Circuits and Feeders l l l Applies installed as a branch circuit or feeder Must be installed in accordance with Article 334 (NM Cable) Parts I and II Specifically excludes 334.80 requirement that limits ampacity of NM cable to 60C 342.22 Number of Conductors IMC Conductor fill must comply with Table 1, Chapter 9 Cables are permitted to be installed where such use is permitted by the respective cable articles. 52 344.24 Bends – How Made l l One shot and Full shoe benders contained in one table Minimum radius is now measured to the centerline of the conduit 362.10(2) Exception – Installation Uses Permitted ENT 15 minute finish rating not required NFPA 13 sprinkler system throughout the building 53 400.8(5) Uses Not Permitted Flexible cord not permitted above a suspended or drop ceiling 404.6(C) Connection of Switches l l General rules says that blades must be de-energized when in the open position New text recognizes that a bottom fed bolted pressure switch can have energized blades if barriers are provided 54 404.8(B) – Accessibility and Grouping Voltage Between Adjacent Devices l l l Applies to switches grouped in an enclosure with other switches, receptacles or similar devices Voltage between adjacent devices must not exceed 300V A permanently installed barrier can be used to separate devices where the voltage does exceed 300V 404-14(E) Dimmer Switches Dimmer switches are permitted to supply only permanently installed incandescent luminaries, unless listed for the control of other loads. 55 404.15(B) – Marking Off Indication If a switch has a marked off position, it shall disconnect all ungrounded conductors Off On Auto 406.4(E) Receptacles in Countertops and Similar Work Surfaces in Dwelling Units Receptacles not permitted to be mounted face-up in any countertop or work surface in a dwelling unit 56 406.8(B)(1) 15- and 20-Ampere Outdoor Receptacles Requires the use of a “weatherproof” while in use cover in all outdoor wet locations. Applies to 15 and 20 ampere, 125 and 250-volt receptacles 406.8(B)(2) Other Receptacles Requires the use of a “weatherproof” while in use cover in all outdoor wet locations where the product intended to be plugged in is not attended while in use (e.g. sprinkler controllers, landscape lighting, holiday lighting, etc. For applications where the plugged in equipment will be attended while in use (e.g portable tools), a basic weatherproof cover can be used. Applies to receptacles other than 15 and 20 ampere, 125 and 250-volt 57 408.4 Circuit Directory l l l All circuits or circuit modifications shall be legibly identified as to their purpose Located on the panel face or inside the panel door Located at each switch on a switchboard Now applies to both switchboards and panelboards! 408.21 Grounded Conductor Terminations l Each grounded conductor must terminate in an individual terminal n Do not put two “neutrals” in one terminal n Do not put a neutral and an equipment ground in one terminal l Multiple equipment grounding conductors can still be terminated in a terminal if the panel is identified to allow the multiple connection 58 410.18(B) Exception – Exposed Luminaire Parts Made of Insulating Material Separate equipment grounding conductor installed in accordance with 250.130(C) Grounding means not available at the outlet Replacement luminaire. Permitted to have conductive parts. Grounding Electrode 430.32(C) – Continuous Duty Motors Selection of Overload Relays Sep Overload Device 115% to 125% Thermal Protector 140% to 170% One HP or less, automatically started 115% to 125% Approved for use with the motor 430-32(A) and (B) 130% to 140% NA NEC 430-32(A) Covers More than 1HP 430-32(B) 430-32(C) Clarifies that the sensing element or the setting of the overload relay can be increased if the values in 430.32(A) and (B) are not sufficient to start the motor. 59 430.52(C)(1) – Rating or Setting In Accordance with Table 430.52 Table moved from 430-152 to become Table 430.52 430.53(D) – Several Motors or Loads Single Motor Taps Group Installation: multiple motors installed on one branch circuit Not more than 10’ in length Branch shortcircuit/ground-fault device Conductors not less than 1/10 the rating of the branch SC/GF device Listed manual motor controllers additionally marked “suitable for tap conductor protection in group installations” Conductors sized by 430.22 60 430.62(A) Exception No. 2 – Rating or Setting Specific Load Feeder device must have a rating or setting that does not exceed the rating of the MCC main power bus (see 430.92) Feeder overcurrent device supplying a Motor-Control Center 430.102(B) – Disconnect Location Motor 430.102(B) requires a disconnect in sight of the motor 430.102(B) Exception allows omission of the disconnect in sight of the motor if one of the following applies: (a) the location is impracticable or introduces additional hazards 430.102(A) requires the disconnect in sight of the controller (b) Industrial installation with maintenance and supervision and written safety procedures 61 430.102(B) Exception Motor Disconnect l Where the exception is used to eliminate the disconnect at the motor the controller disconnect must be n Capable of being locked in the open position n Each disconnect must be individually lockable n The locking means must be permanently installed on or at the switch or circuit breaker 440.65 – Room Air Conditioners LCDI or AFCI Protection l l Single-phase cord- and plug-connected room air conditioners Must be provided with factory- installed n LCDI (Leakage Current Detection and Interruption) n or AFCI (Arc-Fault Circuit Interrupter) LCDI Must be integral with the attachment cap or located within 12” of the attachment cap 62 500.7(K) – Protection Techniques Combustible Gas Detection System Detection system restrictions: l In industrial establishments with restricted public access and l Where conditions of maintenance and supervision ensure only qualified persons service installation l System is listed for detection of specific gas or vapor Permitted equipment with detection system: l Inadequate Ventilation establishes Class I, Div. 1 location – Electrical equipment suitable for Class I, Div. 2 l l Interior of Building with opening into Class I, Div. 2 – Electrical equipment for unclassified locations Interior of Control Panel – Instrumentation measuring gas – Electrical equipment suitable for Class I, Div. 2 500.8(A)(1) – Suitable for Class and Properties Identified l Suitability of Identification by n Equipment listing or labeling n Evidence of equipment evaluation from a qualified testing lab or inspection agency n Evidence acceptable to the AHJ such as a manufacturer’s selfevaluation or owner’s engineering judgment 63 501.4(B)(3) – Class I Division 2 Nonincendive Field Wiring Unclassified Location Classified Location Nonincendive field wiring – not capable of igniting (through arcing or thermal effects) flammable gas or vapor under normal operating conditions. Cable or wiring method permitted for unclassified location Nonincendive field wiring apparatus • Install in accordance with the control drawings • Install in separate cables, cables where each conductor has a grounded metal shield or in multi-conductor cables where each conductor has a min of .25mm of insulation 504.80(B) – Intrinsically Safe Systems Identification of Wiring Intrinsic Safety Wiring l l l Labels located at least every 25 feet Visible after installation Must appear in every section separated by walls, partitions, etc. 64 511.1 – Commercial Garages Scope l l l Includes locations used for service and repair operations Self-propelled vehicles Flammable liquids or flammable gases used for propulsion 511.3(B)(2) – Classified Locations Within 18” of the Ceiling 18” Class I Division 2 unless provided with four air changes per hour CNG Vehicle 65 Articles 513 and 515 Zone Classification Article 513 Aircraft Hangers Zone 0 Div 1 Zone 1 Div 2 Zone 2 Article 515 Bulk Storage Plants Zone classification system now permitted 514.1 – Motor Fuel Dispensing Facilities Scope Scope and title changed from “Gasoline Dispensing” to “Motor Fuel Dispensing” Now includes: gasoline, LNG, CNG, etc. 66 517.2 – Definitions Health Care Facilities l l Definition correlates with NFPA 99 Buildings or portions of buildings that include: n n n n n n l Medical Dental Psychiatric Nursing Obstetrical Surgical Includes (but not limited to): n n n n n n Hospitals Nursing homes Limited care facilities Clinics Medical and dental offices Ambulatory care 517.18 – Tamper Resistant Receptacles Pediatric Locations l l l Applies to ALL receptacles in patient care areas of pediatric wards, rooms or areas Listed tamper resistant receptacle, or Listed tamper resistant cover 67 517.30(E) – Essential Electrical Systems Receptacle Identification in Hospitals Identification required for receptacles supplied from the emergency system. Identification shall be of the cover plate or the receptacle itself. Distinctive color or marking so as to be readily identifiable Similar requirement exists for emergency receptacles in nursing homes and limited care facilities [see 517.41(E)] 517.32(G) – Life Safety Branch Automatic Doors Connect to the life safety branch EXIT EXIT Automatically operated doors used for building egress 68 517.34 Exception Equipment System Connection to Alternate Power Source Requirement for time-lag interval for the equipment system is not required for essential systems of less than 150kVA Omission of the time-lag interval allows a single transfer switch to be used 520.1 – Theaters Scope Scope now includes performance areas and applies to both indoor and outdoor locations 69 Article 527 Temporary Installations Temporary Wiring has been renamed Temporary Installations The article covers more than just wiring methods allowed. GFCI’s, receptacle grounding, disconnecting means, etc. are also covered. 527.3(B) – Time Constraints 90 Days The new wording now reflects that the 90 day time limit applies to all holiday wiring, not just Christmas. 70 527.6(A) – Ground-Fault Protection for Personnel Receptacle Outlets l GFCI Protection Required for all 125- volt, 15, 20 and 30 ampere receptacle outlets n Used by personnel during construction, remodeling, maintenance, repair or demolition n GFCI in cords sets is acceptable l Exception for Industrial establishments where n Qualified personnel are involved n Assured Equipment Grounding Conductor Program is applied n Only permitted for receptacle outlets where having GFCI protection would be a greater hazard or equipment is not compatible with GFCI protection 527.6(B) – Ground-Fault Protection for Personnel Use of Other Outlets l l Applies to all receptacles other than 15, 20 and 30-ampere 125-volt Requires either n GFCI, or n Assured Equipment Grounding Conductor Program [527.6(B)(2)] 71 547.5(G) – Wiring Methods Receptacles l Requires GFCI protection on all 125-volt, 15 and 20-ampere general purpose receptacles installed in n Areas having an equipotential plane n Outdoors n Damp or wet locations 547.9 – Power Distribution Electrical Supply to Buildings/Structures from Distribution Point Site isolating device (may be a pole-top disconnect) Disconnects permitted to be located at distribution point – treat like a feeder (250.32 and Article 225) Alternatively, disconnects may be located at the buildings instead of the distribution point – 547.9(B)(1) 72 547.10 Equipotential Plans and Bonding of Equipotential Planes l Required where the following exist n Concrete floor of confinement area n Animals have access to metal equipment n The metal equipment is likely to become energized l Must be bonded to the electrical grounding system 550.25(B) – AFCI Protection Bedrooms of Mobile Homes and Manufactured Homes l l l Requires AFCI protection on branch circuits that supply 15 and 20 ampere, 125 volt outlets in bedrooms Parallel with 210.12 requirement HUD rules govern the construction of manufactured homes. HUD does not yet include the AFCI requirement. 73 Article 555 Marinas and Boatyards l l l Revised to be more consistent with NFPA 303 – Fire Protection for Marinas and Boatyards Specifically excludes private, noncommercial docking facilities associated with single-family dwellings Relates electrical requirements to the “electrical datum plane” n 2 ft above highest tide level for area under normal circumstances n 2 ft above highest water level under normal circumstances n 30” above water level at floating pier or landing stage and a minimum of 12” above the level of the deck 555.19 – Receptacles Shore Power and Other than Shore Power l Receptacles for shore power must be n Not less than 30 amps n single outlet type l l l Receptacles that are 30 to 50 amps must be of the locking and grounding type Receptacles 60 to 100 amperes must be of the pin and sleeve type GFCI protection required for receptacles other than shore power located n Outdoors n In boathouses n Buildings used for storage, maintenance or repair where electrical hand tools or diagnostic equipment are to be used. 74 600.21(F) – Ballasts, Transformers and… Suspended Ceilings Flexible cord not permitted Securely supported in place and not dependent on suspended ceiling grid for support Power supply for electric sign Support wires 604.6(E) – Construction Support New requirement clarifying that manufactured wiring systems shall be supported in accordance with the applicable cable or conduit article. 75 645.5(D)(5)(c) – Under Raised Floors ITC Cable l l l Type ITC Cable is now permitted under raised floors to supply IT equipment. Equipment grounding conductor may be either green insulation or green insulation with one or more yellow stripes Driven by more use of computer systems in instrumentation and control of industrial locations 645.5(D)(6) – Under Raised Floors Abandoned Cables Abandoned cables beneath a raise floor assembly shall be removed unless contained within a metal raceway. 76 Article 647 Sensitive Electronic Equipment l l l l New Article Material from Part G of Article 530 Covers the installation and wiring of separately derived systems operating at 120V line-to-line and 60V to ground for sensitive electronic equipment Expands the permitted use of this system outside television and motion picture venues. 60V 60V 120V Article 680 Swimming Pools, Fountains, and Similar Installations l l l l l l l Article completely revised Part I – General Part II – Permanently Installed Pools Part III – Storable Pools Part IV – Spas and Hot Tubs Part V – Fountains Part VI – Pools and Tubs for Therapeutic Use 77 680.6 Grounding “Pool” changed to “specified body of water” n Grounding requirements for all bodies of water covered under the scope of 680 now grouped in 680.6 680.12 Maintenance Disconnecting Means Maintenance disconnect within sight of the electrical equipment (not the pool or spa itself) 5ft minimum distance from pool moved to 680.22(C) 78 680.23(F)(1) Exception – Branch-Circuit Wiring Wiring Methods LFNC-B permitted to be used in lengths longer than 6ft where connecting a transformer to pool lights. X-fmr 680.26(B)(1) – Bonded Parts Metallic Structural Components l l l Basic rule requires bonding of steel structure of a pool (i.e. rebar) If rebar is insulated by encapsulation it is not be required to be bonded Provisions shall be made for an alternate means to eliminate voltage gradients n Example: installation of a #8 AWG bare copper conductor throughout the structure 79 680.26(B)(4) – Bonded Parts Electrical Equipment Double-insulated motor No. 8 copper l l l Basic rule requires bonding of all equipment associated with the circulating system Double insulated pumps are permitted Where a double insulated pump is installed, a #8 AWG bonding conductor is required at the pump location for use with a replacement motor. 680.27(B)(1) – Electrically Operated Pool Covers Motors and Controllers Controls for an electrically operated pool cover shall be located so that the operator has full view of the pool 80 680.44(B) – Spas/Hot Tubs – Protection Other Units GFCI protection required for outlets that supply a: • self-contained spa or hot tub • packaged spa or hot tub • field assembled spa or hot tub with a heater load of 50A or less Listed assemblies with integral GFCI protection for all electrical parts do not require additional GFCI at the outlet. A spa or hot tub rated greater than 250V or 3-phase shall not require GFCI protection. 680.57(C)(2) – Location Portable Signs 5 ft Portable electric signs shall not be placed within the pool or fountain, or within 5 ft (1.52 m ) measured horizontally from the inside walls of the pool or fountain 81 Article 692 Fuel Cells Includes requirements for: • Listing of the fuel cell • Identification of multiple power sources • Circuit requirements • Etc. 700.12(B)(6) – Generator Sets Outdoor Generator Sets l l Allows disconnect at a generator to also serve as the disconnect for a building or structure Comply with the following: n Generator disconnect must be readily accessible n Must be “within sight” of the building (visible and not more than 50 feet away) n Must still meet the requirements for a building disconnect in Article 225 (e.g. 225.36 requires that disconnect be suitable for use as service equipment) Similar language in 701.11(B)(5) for legally required systems 82 702.1 – Optional Standby Systems Scope l ... The systems covered by this article consist of those that are permanently installed in their entirety, including prime movers, and those that are arranged for a connection to a premises wiring system from a portable alternate power supply. 702.6 Transfer Equipment l Transfer equipment required for n permanently installed standby systems n and where an electric-utility supply is either the normal or standby source l l Must prevent the inadvertent interconnection of supplies Supplementary overcurrent protective devices shall be part of a listed transfer equipment. n Not a substitute for branch circuit or feeder overcurrent protection l Comply with Article 705 if system will be operated in parallel 83 725.3(A) – Locations and Other Articles Number and Size of Conductors in Raceway l l l References 300.17 for all of Article 725 This extends the raceway wire fill restrictions to Class 2 and 3 circuits Applies Chapter 9, Table 1 through references 725.6 Mechanical Execution of Work Class 1, 2 or 3 circuits Support wires l l l Installed in a neat and workmanlike manner Support to structural components Use proper straps, hangers or similar fittings 84 725.52(A) Exception No. 2 – Load Side of Class 2 or 3 Class 1 Wiring Methods and Materials l l l l Can reclassify Class 2 and Class 3 circuits as Class 1 circuits Must install as Class 1 Class 2 and Class 3 markings required in Section 725-42 are eliminated Entire circuit is installed using the wiring methods and materials in accordance the requirements for Class 1 circuits 800.48 – Communications Wiring within Buildings Communications Raceways New Exception 2: Conduit fill restrictions shall not apply. 85 Annexes l l l l l l l Annex A – Product Standards Annex B – Application of 310.10(A) formula Annex C – Conduit and Tubing Fill Tables Annex D – Examples Annex E – NFPA 220 Table for Building Types Annex F – Chapter 3 Cross Reference from 1999 to 2002 NEC The Annex material is for information only and is not part of the Code requirements Square D Company Codes and Standards l l l The Codes and Standards group can offer on-site custom training on the NEC and related topics Our staff has extensive involvement in codes and standards development, interpretation and application Excellent resource for resolution of field issues 86