ELECTRICAL CODE CLARIFICATION 700 N. TRYON STREET CHARLOTTE, NC 28202 (704) 336-2831 SUBJECT: Unfused Service Conductors CODE REFERENCE: 230.70 (A) 1 & 230.91 SUBMITTED BY: Electrical Department EFFECTIVE DATE: Immediately PROBLEM: The length of unfused conductors permitted to run inside a service trough inside a commercial / industrial building SOLUTION: For all commercial / industrial projects the length of unfused conductors permitted to be run inside to a service trough shall not exceed 16 feet from the point of entry into the building to the point of termination to its overcurrent protection, where located in an electrical equipment room. APPROVED BY: GERALD HARVELL ELECTRICAL CPM