2015 May Consistency Questions/Topics 1) Do I need an electrical permit to wire the control wires to an HVAC system? It will consist of a cable from the air handler to the thermostat and a cable to the condenser unit. No, if done by the mechanical contractor it is covered in their costs and the mechanical regs. state it will comply with NFPA70. - Rains 2) If I am replacing the cabinets in my kitchen, do I have to bring the kitchen counter outlets and the appliances up to current code? Assuming it met the code as the time of installation and if the layout is unchanged no. If the layout is changed we would now need to meet current code with any added/reconfigured items. Our Electrical Code Team will be changing the policy book (13.7) in the near future. When all policies are reviewed and updated we will run through them for our consistency meetings. - Barnes 3) I am installing a receptacle on the ceiling of my screen porch for a flat screen TV. What type of cover is required for this installation? Also, are there any special requirements for the TV or should I just wait until it passes inspection and put the TV up afterwards? The receptacle cover and TV need to be rated for the environment. Typically this will be a wet or damp location. Out interpretation has been that anything within a 45 degree angle from the roof line will be a wet location and the rest of the area would be a damp location. See NEC 406.9 - Dellinger 4) I have a receptacle mounted on an exterior wall at a set of steps leading up to an outdoor stage. Would it be necessary to install an extra heavy duty cover since it could be damaged by foot traffic? If allowed by building code (can’t protrude more than 4” max & can’t be in the required clearance) the cover needs to comply with 406.9 B 1. - King 5) Where premises wiring includes both AC and DC systems, are the DC conductors required to be identified in any special way? In PV (690.4) systems you can’t mix and they require marking, but you can mix conductors of AC and DC circuits if it meets the requirements of NEC 300.3(C)(1) with no mention of special identification except 210.5. - West 6) I was turned down for not meeting the requirements of 682.11, not having a shutdown on a service feeding a floating dock. I have wired several in the past without this kind of disconnect. What’s changed? Article 555 covers Marinas and Boatyards. Section 555.1 gives the scope of the Article however the last sentence in the scope reads; “Private, Noncommercial docking facilities constructed or occupied for use of the owner or residents of the associated single-family dwelling are not covered by this article.” Therefore a dock at a single-family residence built on Lake Norman would not have to meet the requirements of Article 555. Please explain. You may be confusing the floating dock with a land dock which does not have to meet the requirements as do floating docks. There has been a disconnect requirement since 2005 for the floating docks and submersible equipment. We must comply with 682.11. Locally we will accept a feeder shut down if the service is remote and out of the datum plane requirements. We also need to be sure and consider 682.3 which enacts 555.13 B. Installation when appropriate. – Rains 7) I have had several inspectors pass my ceiling roughs when using caddy devices to ceiling support wires. Now I have one who is turning me down. Why the inconsistency? 300.11 says we can’t unless ceiling manufacturer rates the installation for that purpose for non fire rated ceilings and not at all in fire rated ceilings. Our policy has been we can use them for limited use of fixture whips and switch legs in non fire rated assemblies since they are already supporting the fixtures. - Simpson 8) I have a 3000 amp switch gear and we are changing out a 1200 amp OCP device. The problem is the existing wire size is parallel 600 kcmil and will not fit under the breaker. If I use an approved terminal block to tie in with 4 - 350 kcmil to lugs to make final termination will I pass inspection? As long as we have sufficient space and all phases are treated the same we are good. See 310.2 H King 9) How do you properly size grounding conductors for increased ungrounded conductors in 250.122(B)? Voltage Drop Example: Single phase 120/240 volts, Circuit load of 153 amps, length of 655 feet, OCD 200 amps Standard circuit would call for 3/0 cu with #6 cu grounding conductor K=Copper resistance per cm per foot =12.9 ohms/ aluminum resistance per cm per foot=21.2ohms Single Phase Vd= 2K x Length x amperes = CM 2 x 12.9 x 655 x 153 = 2585547 =15.41volts =6.45% 167800 167800 (3/0 per table 8) 240 volts Voltage drop per industry standards should be limited to 3% or less 2585547= 7.39 =3.07350000% 350000 The 3/0 copper must be increased to 350kcmil to limit the Vd, the grounding conductor must be increased the same ratio per 250.122B 350000 =2.08 or 208% 167800 ( #6 per table 8) 26240 x 208% =54579=#2 cu - RAINS 10) I have low voltage under cabinet lighting under 12 volts, my wire passes through the sheetrock and edge of the back of the cabinet into the light fixture unprotected .The inspector turned me down for not having a sleeve on ½” of exposed low voltage wire, is he correct? We only have the concern to protect the cable from physical damage. How was this cable subject to damage? Perhaps the inspector was mistaken. See 300.4 - Barnes 11) I have a residence that has a CT on the outside with 2 - 200 amp main panels in the house. The electrician has installed a transfer switch beside the CT and re fed one main panel for optional standby power. The transfer has a line side disconnect and the genset has a load side disconnect. Will this work per the NEC? If so, how? No. The grouping of the normal service mains cannot be separated for this purpose. See 230.72 12) Can I use a gas light instead of a switch controlled light, at the front door, as required by 210.70(A)(2)(b)? No. The lighting outlet has to be there per the code reference above. -West 13) I am a low voltage contractor and I was turned down on a new house because the inspector said I needed to terminate or blank-off a set of speaker wires that we left rolled up outside over the deck. Is this a violation? Yes, if not tagged future. See 640.6. Additionally we requested clarity about speaker listing and labeling from DOI and Ron Chilton at NCDOI tells us if it is a non powered speaker we may accept it without listing. On all of these type systems we only need to be sure the powered units are listed. Further code concerns in differing projects are; 640.25 Loudspeaker Installation in Fire ResistanceRated Partitions, Walls, and Ceilings Loudspeakers installed in a fire resistance-rated partition, wall, or ceiling shall be listed for that purpose or installed in an enclosure or recess that maintains the fire resistance rating. 640.3 Locations and Other Articles Circuits and equipment shall comply with 640.3(A) through (M), as applicable. (E) Assembly Occupancies. Equipment used in assembly occupancies shall comply with Article 518. (J) Combination Systems. Where the authority having jurisdiction permits audio systems for paging or music, or both, to be combined with fire alarm systems, the wiring shall comply with Article 760. 690.4(C) Output Wiring and Listing of Amplifiers. Amplifiers with output circuits carrying audio program signals shall be permitted to employ Class 1, Class 2, or Class 3 wiring where the amplifier is listed and marked for use with the specific class of wiring method. UL does provide listing for speakers. If the referenced cable is non powered we could be safe in not addressing it on new systems. - Simpson 14) Can I bond a CATV Smart Box to the ground in the circuit feeding the receptacle in the box, or does it need to be terminated on the grounding electrode system per 800.100? Yes, we accept the circuit equipment ground and no we do not have authority over the provider system by legislation. The point of demarcation is the key. In this case the system bond would be ahead of the box. - Dellinger 15) Can I install a floor box for a device on a screened in porch or a porch that’s covered by a roof? Maybe, but only if it is listed/rated for the application. 314.27. - King 16) I'm a contractor "out of town". Does Mecklenburg County have any requirements for the license holder to be on site during inspection/construction? Are there any requirements of how many men can work under the qualified person on site? Per the licensing rules of NC we have no requirements for on site management or ratio numbers. We have no local ordinances addressing this issue either. If we have repetitive issues we will request the qualified individual to meet us for resolution. - Mullis 17) I installed a metal 3 foot long 8x8 wireway under two panels to adjust for the rough in locations. The inspector said I would have to derate the conductors to 40%. Why? This makes no sense since there is plenty of separation between conductors. First the wireway cannot be over 20% filled. If it has over 30 conductors in a given cross section the derating is required per 376.22. -Barnes 18) Do swimming pool pump motors of 240 volt, greater than 20 amps and not located within 10 feet of pool require GFCI protection? See 680.21. C. The motor is not required to have GFCI protection. – Dellinger 19) The building shell has power. Do the upfit projects, whether it is metered or not, need to use the temporary utilities process? Per the code and statutes no project may be energized until the appropriate inspection has occurred. Therefore they would be as any “new project” with regards to being energized. - West 10.7 Service Utilities 10.7.1 Connection of Service Utilities – No person shall make connections from a utility, source of energy, fuel or power to any building or system which is regulated by the technical codes until approved by the Inspection Department and a Certificate of Compliance is issued (General Statute 143-143.2)