630 kVA, 12 kV, Ecodesign, A0Bk max.

advertisement

Cast Resin Distribution Transformers - type aTSE

50 - 630 kVA, 12 kV, Ecodesign, A

0

B

k

max.

Member of International BEZ Group

Technical data

Standard IEC 60076 - 11, EN 50541 - 1

Ecodesign regulation EU no. 548/2014

Indoor use

Continuous loading

Cooling system

Ambient temperature

Thermal class

Climatic class

Environmental class

Fire behaviour class

Partial discharges

Degree of protection

AN , ANAF - rated power + 40 % with fans

≤ 40°C *, altitude ≤ 1000 m *

155 (F) - Temperature rise 100 K

C2 Thermal shock - 60°C

E2

F1

≤ 10 pC

IP 00 - without enclosure

IP 21 *, IP 31 * - with metal enclosure metal parts hot - dip galvanized Corrosion protection

Rated power

- pressure (1m)

- power

Total weight kVA

Type aTSE

No-load losses A o max.

P o

(W)

No-load current I o

(%)

Load-losses B k max.

P k 75°C

(W)

P k 120°C

(W)

Sound level

L pA dB(A)

L

WA dB(A)

[ kg ]

50

667/10

200

0,5

1450

1700

35

49

400

100

697/10

280

0,4

1750

2050

37

51

610

160

717/10

400

0,35

2500

2900

39

54

865

Electrical characteristics

Rated power

High voltage (HV)

Tapping range HV

Low voltage (LV)

Frequency

Insulation level

50 kVA - 630 kVA*

10, 6 kV *

± 2 x 2,5 % * off- circuit

400/231 V, 420/242 V *

50 Hz *

Um 12 kV LI/AC 75/28

Um 7,2 kV LI/AC 60/20

Impedance voltage

Vector group

Um 1,1 kV LI/AC - /3

6% *

Dyn *

HV windings - Aluminium wire, strip, casted in resin

LV windings - Aluminium wire, tape, impregnated

250

737/10

520

0,3

3300

3800

42

57

1335

400

757/10

750

0,3

4750

5500

44

60

1600

For any alternative requirements (*) please contact manufacturer.

BEZ TRANSFORMÁTORY, a. s., Rybni č ná 40, 835 54 Bratislava, Slovak Republic, tel.: +421 2 4961 1200, e-mail: bez.or@bez.sk, www.bez.sk

630

777/10

1100

0,3

6600

7600

46

62

2280

133.A_02.02.2016

LV Terminal

Standard fittings

▪ 4 bi - directional flat rollers

▪ 4 lifting holes

▪ 4 haulage holes on the underbase

▪ 2 earthing points

▪ 1 rating plate (on HV site)

Optional fittings

▪ Temperature senzors in the LV windings - 2 PTC thermistors or PT 100/phase

▪ Temperature monitoring device with alarm and tripping contacts and cooling fans control

▪ Dial thermometer

▪ AF cooling system (+ 40 %) with the fans

▪ Antivibrations pads

▪ Placement of the LV/HV terminals

HV Terminal

Dimensions

[kVA]

aTSE

A

B

C

D

E

F

G

H

50

667/10

950

650

1000

100

430

430

40

310

100

697/10

1090

710

1060

100

430

430

40

365

160

717/10

1120

730

1225

100

520

520

40

370

250

737/10

1340

750

1305

100

570

570

40

445

400

757/10

1390

820

1370

125

670

670

40

465

630

777/10

1480

835

1660

125

670

670

40

495

Company reserves the right to modify data without notice.

Shown values serve as guidance only i.e. definitive dimensions and weights are subject to modification according to concrete purchase order.

BEZ TRANSFORMÁTORY, a. s., Rybni č ná 40, 835 54 Bratislava, Slovak Republic, tel.: +421 2 4961 1200, e-mail: bez.or@bez.sk, www.bez.sk