fuji 1/16 din super timers

advertisement
Fuji 1/16 DIN Super Timers Overview
FUJI 1/16 DIN SUPER TIMERS
Overview
The MS4S series super timers are a 1/16
DIN style timing relay designed for
process control, machine tool control,
safety control and many other types of
applications. The timers are plug-in 8pin or 11-pin surface/DIN rail mountable with up to four selectable modes of
operation and four selectable timing
ranges.
Features
MS4SA
MS4SM
1 - 80 0 - 633 - 0405
• Timing range from 0.05 seconds to 60
hours
• Timer scale with selectable ranges of
0-6, 0-12, 0-30 and 0-60
• Timing units in selectable ranges of
0.1s, sec, min and hrs
• LED indicators. Power on (green)
flickers during timing operation UP
(red) on when N.O. contact is closed
• Multi-mode timer with mode indication. On-delay (PO), flicker (FL),
one-shot (OS), or signal off-delay (SF)
• 11-pin plug-in with start, reset and gate
(interrupt) input signals and a DPDT
contact output.
• On-delay timer
• 8-pin plug-in with a DPDT contact
output
• Timing range from 0.05 seconds to 60
hours
• Timer scale with selectable ranges of
0-6, 0-12, 0-30 and 0-60
• Timing units in selectable ranges of
0.1s, sec, min and hrs
• LED indicators — power on (green)
flickers during timing operation. UP
(red) on when N.O. contact is closed
MS4SC
• On-delay timer
• 8-pin plug-in with a SPDT timed
contact output and a SPDT instantaneous contact output
• Timing range from 0.05 seconds to 60
hours
• Timer scale with selectable ranges of
0-6, 0-12, 0-30 and 0-60
• Timing units in selectable ranges of
0.1s, sec, min and hrs
• LED indicators — power on (green)
flickers during timing operation. UP
(red) on when N.O. contact is closed
Product Selection Guide
Part Number
Description
MS4SM-AP-ADC
Multi-mode timer with selectable timing range from 0.05s to 60 hours. Input power is 100 - 240 VAC. DPDT relay
output. 11-pin connection. UL, CSA , TÜV approved
Voltage
MS4SA-AP-ADC
On-delay timer with selectable timing range from 0.05s to 60 hours. Input power is 100 - 240 VAC. DPDT relay
output. 8-pin connection. UL, CSA, TÜV approved
MS4SC-AP-ADC
On-delay timer with selectable timing range from 0.05s to 60 hours. Input power is 100 - 240 VAC. SPDT timed
relay output and SPDT instantaneous relay output. 8-pin connection. UL, CSA, TÜV approved
0.05 seconds to 60 hours
MS4SM-CE-ADC
Multi-mode timer with selectable timing range from 0.05s to 60 hours. Input power is 24 VDC/ VAC DPDT relay
output. 11-pin connection. UL, CSA , TÜV approved
0.05 seconds to 60 hours
MS4SA-CE-ADC
On-delay timer with selectable timing range from 0.05s to 60 hours. Input power is 24 VDC/ VAC. DPDT relay out24 VDC/VAC
put. 8-pin connection. UL, CSA, TÜV approved
0.05 seconds to 60 hours
MS4SC-CE-ADC
On-delay timer with selectable timing range from 0.05s to 60 hours. Input power is 24 VDC/ VAC. SPDT timed
relay output and SPDT instantaneous relay output. 8-pin connection. UL, CSA, TÜV approved
0.05 seconds to 60 hours
TP411X
Surface mount socket for MS4SM series timers. UL, CSA, TÜV approved
TP411SBA
Flush mount socket for MS4SM series timers. UL, CSA, TÜV approved
TP48X
Surface mount socket for MS4SA and MS4SC series timers. UL, CSA, TÜV approved
TP48SBA
Flush mount Socket for MS4SA and MS4SC series timers. UL, CSA, TÜV approved
SPDT
N.C.
C
DPDT
N.O.
0.05 seconds to 60 hours
100-240VAC
N/A
C
Time Range
0.05 seconds to 60 hours
N/A
N.O.
N.C.
C
N.C .
N.O
N.C.
A single pole, double throw relay switches one
common line between two stationary contacts,
one normally open and one normally closed.
1090
Process Control
A double pole, double throw relay simultaneously
switches two independent commons with two independent normally open/normally closed contacts.
Fuji 1/16 DIN Super Timers Specifications
FUJI 1/16 DIN SUPER TIMERS
P ROCESS
MS4SM-AP-ADC
MS4SM-CE-ADC
MS4SC-AP-ADC
MS4SC-CE-ADC
TP48SBA
TP48X
TP411X
TP411SBA
Specifications
Approvals
Repeat Accuracy
Reset Time
UL file no.: E44592, CSA file no.: LR20479, TÜV license no: R9551800
±0.3% at maximum setting time
0.1 second or less
85-264VAC
20.4-26.4VDC/VAC
Operating Voltage Range
MS4SM-AP-ADC
MS4SA-AP-ADC
MS4SC-AP-ADC
MS4SM-CE-ADC
MS4SA-CE-ADC
MS4SC-CE-ADC
Operating Temperature Range
Humidity
Contact Ratings
Power Consumption
Insulation Resistance
-10 to +55°C (14 to 131°F) (no icing)
Dielectric Strength
Vibration
35 to 85% (no condensation)
5A at 30VDC resistive load, 1A @ 30VDC inductive load, 5A @ 250VAC resistive load, 2.5A @ 120VAC inductive load
Approx. 10VA at120/240VAC; 1W at 24VDC
100M⏲ at 500 VDC insulation tested
2000VAC 1 min. between current carrying part and non-current carrying part
2000VAC 1 min. between output contact and control circuit
1000VAC 1 min. between open contacts
Malfunction durability: 10 to 55Hz, 0.5mm double amplitude
Mechanical durability: 10 to 55Hz, 0.75mm double amplitude
Life Expectancy
Malfunction durability: 100m/s2
Mechanical durability: 500m/s2
Mechanical: 20 million operations
Electrical: 100,000 operations at 250VAC 5A resistive load
Weight
Approx. 100g (3.527 oz.)
Shock
w w w. a u to m at i o n d i re c t . c o m / t i m e rs
MS4SA-AP-ADC
MS4SA-CE-ADC
Process Control
1091
Fuji 1/16 DIN Super Timers Specifications
FUJI 1/16 DIN TIMERS TIMING AND WIRING DIAGRAMS
Timing and wiring diagrams
6
5
MS4SM
7
4
Reset
signal
1. On-delay PO
Start
signal
Gate
signal
8
3
9
2
Signal start
(- )
Power on start
T
T
1
10
11 (+)
Power
T
Power 2-10
쐌 With power off turn the mode selector until PO is displayed.
쐌 When power is on, applying the start signal turns the
timed N.O. normally open) contact on after the set time
has elapsed.
쐌 When using a power-on start, pins 2 and 6 (start signal) must
be jumpered together
Start signal 2-6
Reset signal 2-7
Timed NC 1-4
11-8
Timed NO 1-3
11-9
Indicator POWER
Indicator OUTPUT
2. Flicker FL
T-a
T
T
T
T
쐌 With power off, turn the mode selector until FL is displayed.
쐌 When power is on, applying the start signal turns the
timed contact on and off repeatedly at the set time
intervals.
Power 2-10
Start signal 2-6
Reset signal 2-7
1 - 80 0 - 633 - 0405
Timed NC 1-4
11-8
Timed NO 1-3
11-9
Indicator POWER
Indicator OUTPUT
3. One-shot OS
T
T-a
T
쐌 With power off, turn the mode selector until OS is displayed.
쐌 When power is on, applying the start signal instantly
turns the timed N.O. contact on and turns it off after the set
time has elapsed.
T-a
Power 2-10
Start signal 2-6
Reset signal 2-7
Timed NC 1-4
11-8
Timed NO 1-3
11-9
Indicator POWER
Indicator OUTPUT
4. Signal off-delay SF
T-a
T-a
쐌 With power off, turn the mode selector until SF is displayed.
쐌 When power is on, applying the start signal instantly
turns the timed N.O. contact on. Removing the start signal
turns the contact off after the set time has elapsed.
T-a
T
Power 2-10
Start signal 2-6
Reset signal 2-7
Timed NC 1-4
11-8
Timed NO 1-3
11-9
Notes:
1. T= set time. t = time period within set time.
2. The gate signal is used to interrupt the timing operation.
Indicator POWER
Indicator OUTPUT
MS4SA
On-delay
Power
2-7
Timed NO
1-3
8-6
Timed NC
1-4
8-5
NC
NO
T
6
3
(Ð) 2
COM
NC
5
4
1
8
NO
7 (+)
COM
쐌 When power is applied, the timed N.O. contacts make after
the set time has elapsed.
쐌 When power is removed, the contacts reset.
Power
MS4SC
On-delay
Power
NC
2-7
T
Timed NO
8-6
Timed NC
8-5
Inst. NO
1-3
Inst. NC
1-4
N
1092
Process Control
NO
4
6
3
(Ð) 2
COM
NC
5
1
8
Power
NO
7 (+)
COM
쐌 Timed contact
When power is applied, the N.O. contact makes after the
set time has elapsed. When power is removed, the
contacts reset.
쐌 Instantaneous contact
When power is applied, the N.O. contact makes instantly.
When power is removed, the contacts reset.
Fuji 1/16 DIN Super Timers Specifications
FUJI 1/16 DIN SUPER TIMERS DIMENSIONS
Side View
Side View
MS4SA and
MS4SA
andMS4SC
MS4SC
MS4SM
MS4SM
48
15
48
66.5
52.3
14.2
44.5
39
48
P ROCESS
48
6
Wt : Approx. 100g (3.53oz)
Sockets for MS4SA, MS4SC (8-pin)
Socket
for for
MS4SA,
MS4SC
(8-pin) (8-pin)
Socket
MS4SA,
MS4SC
TP48SBA
TP48X
Terminal
M3.5x8
38.4
18.8
4
3
Terminal M3.5x7
3 4 5 6
40 0.2
45
5
All dimensions in mm
5.5
70
6
Dia. 27
14
35.4
TP48X
2-Diam 4.5
2 1 8 7
7
8
1
Mounting hole 2- Diam. 4.5
45
4
7.8
2
5
7
17
50
Mass : Approx. 40g
20.3 or less
Wt: Approx. 50g (1.76oz)
Selection of operation mode/MS4SM
24.5
2-Diam 4.5
Dia. 27
5.5
Terminal M3.5x7
9
10 11
3
1 2
50
0.2
Mounting hole 2 - Diam. 4.5
5
4.5 17.5 5
45
Connection of p
7
Mass : Approx. 45g
31.2 or less
Wt: Approx. 70g (2.47oz)
2 1 11 7 6
4 3 8 9 10
4
7.8
40
45
6 5
4
7
70
8
Terminal
M3.5x8
26.8
38.4
18.8
35.4
TP411X
TP411X
Selection of tim
Sockets for MS4SM (11-pin)
Sockets for MS4SM (11-pin)
TP411SBA
Socket
MS4SM
(11-pin)
Socketforfor
MS4SM
(11-pin)
w w w. a u to m at i o n d i re c t . c o m / t i m e rs
Dimensions in mm
Using the super timer
Operation mode indication window
Power ON indicator (Green)
Operation mode
selector
Timing range
selector
Output indicator (Red)
Time unit selector
Process Control
1093
Download