1 Grounding and Overvoltage Requirements for Distributed Generation (Wind and Solar) Reigh Walling Walling Energy Systems Consulting, LLC 2 Scope of Presentation We will cover: – Temporary and transient overvoltages on distribution feeders – Related to interconnection of distributed wind and solar plants – Ways to avoid or mitigate these overvoltages 3 Overvoltage Definitions • Transient overvoltage – impulses and supersynchronous oscillations lasting less than a couple of cycles – Examples: lightning, switching, etc. • Temporary overvoltage – oscillatory overvoltage persisting for many cycles to seconds – Examples: load rejection, single-phase faults, ferroresonance, etc. 4 Impacts of Temporary Overvoltage • Utility equipment – surge arresters 5 Surge Arresters • Surge arresters are designed to limit transient overvoltages, not intended to limit TOV • Surge arresters are the likely victims of TOV • Failure modes of surge arresters – MOV material fails to a low resistance – Physical integrity of arrester housing uncertain – Ground lead disconnects blow off 6 Impacts of TOV on Customers • TOV withstands of consumer equipment are poorly documented • Not defined by any formal standards 1.2 p.u. for 3 ms !! • ITIC (formerly CBEMA) curve is often cited • Experience suggests ITIC curve is excessively conservative • TOV can result in large claims against utility 7 Loss of Ground Scenario • Focus of utility concern regarding DG plants – – – – Ground fault on feeder Feeder breaker trips; losing normal ground source DG doesn’t trip immediately, continues to energize If there is no ground source, high TOV may result C B N 1 p.u. 1 p.u. Phase A faulted to ground 1.73 p.u. A 8 Effectively Grounded Systems • Definition of effectively grounded system is where the COG < 0.8 (COG = TOV/VL-L) – TOV < 1.39 p.u. in effectively grounded systems • C62.91 states X0/X1<3 and R0/X1<1 generally results in COG<0.8, but is not the definition • Multi-grounded feeders are designed to be effectively grounded – Coordinates with arrester TOV capabilities – Experience indicates customers are ok 9 Ground Sources – Desired and Unintended Ground sources are the zero-sequence admittances of the circuit • Primary substation transformer – breaker open • Cable charging and grounded cap banks • Grounded-wye loads • Grounded-wye delta and zig-zag transformers – May be added to feeder to mitigate loss-of-ground – Subject to overload from feeder imbalance 10 Classic TOV Analysis Sym. component network for single-phase fault x Z1 V1 x I0 x Z2 V2 x x Z0 V0 x • Generators conventionally assumed to be voltage sources behind impedance • Loads and shunt capacitance usually ignored 11 Wind and Solar Sources • Solar (PV) inverters – grid interactive – Controlled current sources, not voltage source – Three-phase inverters are ungrounded source – Three-phase inverters may not pass I2 • Wind generation – Legacy induction generators (Types 1 and 2) approximately a voltage source until flux collapses – Full conversion (Type 4) are inverters just like PV – Doubly-fed (Type 3) are current sources until they crowbar, then they are like an induction generator 12 Conventional X0/X1 only applies to: • Solar (PV) inverters – grid interactive – Controlled current sources, not voltage source – Three-phase inverters are ungrounded source – Three-phase inverters may not pass I2 • Wind generation – Legacy induction generators (Types 1 and 2) approximately a voltage source until flux collapses – Full conversion (Type 4) are inverters just like PV – Doubly-fed (Type 3) are current sources until they crowbar, then they are like an induction generator 13 Loading Impact on Type 1 and Type 3(crowbarred) WTG TOV • These are the only wind and solar DG that can be assumed to behave as a voltage source 14 Inverter-Interfaced DG • The following behave as current sources: – PV – Type 4 wind turbines – Type 3 (wind turbines when not crowbarred) • Conventional X0/X1 criteria do not apply 15 Other DG Overvoltage Issues • Abrupt isolation of inverter into light load – Known as “load rejection overvoltage” – Tests and field events have shown voltage > 2 p.u. – Inverter should trip immediately • Reclose out of phase of a compensated feeder 16 Other DG Overvoltage Issues • Self-excitation of induction generator – Light load – Sufficient capacitive compensation 17 Overvoltage Mitigation • Provision of ground source where needed – Grounded-wye delta or zig-zag grounding banks – Grounded-wye delta interconnection transformer – Grounded wye-wye does not make a ground source • Adequate load relative to DG – Load to DG capacity ratio depends on type • Coordinated transfer trip – DG disconnected before feeder opens • Coordinated grounding switch (crowbar) 18 Overvoltage Mitigation (cont’d) • Fast DG overvoltage tripping – DG may not see TOV on primary side – Coordination with VRT will be needed in future • Fast islanding detection – Increased challenge with evolving ride-through requirements • Sacrificial arresters – Difficult to coordinate with utility arresters – Coordination with load withstand is uncertain 19 Conclusions • Overvoltages, particularly TOV, can be a major issue for wind and solar plants interconnected to distribution • Conventional X0/X1 criteria are irrelevant for most wind and solar • Overvoltage and grounding solutions exist, but must be appropriately analyzed and applied