1 TOV Issues in Renewable Plant Collectors and Application of Grounding Transformers Reigh Walling Walling Energy Systems Consulting, LLC 2 Overvoltage Definitions • Transient overvoltage – impulses and supersynchronous oscillations lasting less than a couple of cycles – Examples: lightning, switching, etc. • Temporary overvoltage – oscillatory overvoltage persisting for several cycles to seconds – Examples: load rejection, single-phase faults, ferroresonance, etc. 3 Impacts of Temporary Overvoltage • Primary impact is on surge arresters • MV arresters are inexpensive • Arrester failures are not! 4 Surge Arresters • Should be applied at open ends of collector feeders for impulse and switching surge protection • Surge arresters are designed to limit transient overvoltages, not intended to limit TOV • Surge arresters are the likely victims of TOV 5 Grounding • Two different uses of the term grounding in the power industry – Equipment or safety grounding – Bonding to provide a low impedance path between casing or other non-energized parts and local ground • System grounding provides a reference point for the voltages on the three electrical phases with respect C B to ground – I.e., provide a defined zero-sequence admittance – Defines severity of unfaulted-phase voltage rise during ground faults N 1 p.u. 1 p.u. A 1.73 p.u. 6 Loss of Ground Scenario • Focus of utility concern regarding DG plants – – – – Ground fault on feeder Feeder breaker trips; losing normal ground source DG doesn’t trip immediately, continues to energize If there is no ground source, high TOV may result C B N 1 p.u. 1 p.u. Phase A faulted to ground 1.73 p.u. A 7 Effectively Grounded Systems • Definition of effectively grounded system is where the COG < 0.8 (COG = TOV/VL-L) – TOV < 1.39 p.u. in effectively grounded systems • C62.91 states X0/X1<3 and R0/X1<1 generally results in COG<0.8 – but is not the definition of effective grounding • Arresters required to protect 150 kV BIL equipment on 34.5 kV feeders generally require effective grounding 8 Loss of Grounding Scenario WTGs are not typically grounded, Y-Y unit transformer does NOT provide a ground source! Substation transformer is normal ground source Ground fault on collector cable WTGs do not see fault after collector breaker trips, may run-on Breaker trip, isolates collector feeder 9 Feeder Isolation TOV • Magnitude and character of TOV is highly dependent on the details of the “generators” • Type 1 and 2 WTGs can be reasonably approximated as voltage sources behind impedance – Classical symmetrical component analysis applies • Type 4 WTG and PV inverters behave more like current sources – Classical analysis and X0/X1 criteria do not apply • Type 3 act like Type 1 & 2 if crowbarred, like Type 4 if not 10 Classic TOV Analysis Sym. component network for single-phase fault x Z1 V1 x I0 x Z2 V2 x x Z0 V0 x Unfaulted phase-to-ground voltage (p.u.) 3 2.8 2.6 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0 5,000 10,000 15,000 20,000 Feet of 500 kcmil 34.5 kV cable per MVA of WTG • Generators conventionally assumed to be voltage sources behind impedance • Feeder cable capacitance can increase TOV > 3 11 Limitations of Conventional Analysis • Voltage source representation only reasonable for Types 1 and 2 WTGs • Inverters (Type 4 WTG and PV) designed to behave like positive-sequence current sources – Negative sequence may appear as a large impedance or as nonlinear impedance – Will not be able to drive ordered current into the high capacitive impedance of feeder – Modulation index is liked to be maxed out – Unstable control behavior may occur, generating complex non-sinusoidal waveforms 12 Type 3 (DFG) WTG Behavior • Normal operating mode is similar to inverter – Constant power regulation • If solidly crowbarred (rotor protectively shorted out), will behave like Type 1 & 2 – Initial feeder fault is likely to initiate crowbar • Controls designed for fault ride-through may attempt to recover from crowbar – Complex behavior may result 13 Analysis and Modeling of TOV and Grounding for Inverters and Type 3 WTG • No analytical approach is even close • EMT simulation is the only means to obtain adequate accuracy • Detailed OEM-supplied model is essential: – – – – Outer loop controls (i.e., power, ac voltage regulation) Inner loop current regulators Protective sequences Protective tripping 14 TOV Mitigation • Grounding transformers • Grounding breakers • Direct (fast) transfer trip 15 Grounding Transformers GT GT GT • Grounding transformer on each collector feeder – Typically at the substation end • Zig-zag or grounded-wye delta configuration 16 Grounding Transformer Application • Zig-zag or Yg-delta – no functional difference – Zig-zag theoretically uses less copper and iron – Grounded-wye delta can be a commodity distribution xfmr • Impedance – chosen to achieve acceptable TOV – Based on simulations, not calculations! • Current ratings – Continuous – very little in a wind or solar plant – Temporary • Ground fault with feeder breaker closed • Sustained energization from WTGs/inverters after breaker opens • Impact on feeder protection 17 Conclusions • TOV mitigation is a critical element of wind and solar plant collector system design • Grounding transformers are a popular solution to wind plant TOV issues – And what about large-scale PV plants? • Detailed simulation is the only suitable approach to selection of grounding transformers for modern renewable plants