School Facilities and Organization HIGHLINE INFORMATION AND CONDITION OF SCHOOLS 55.40% Poor Detailed Condition Assessment by Building Reporting Year 2015-2016 TYEE CAMPUS - 100 BUILDING Building Details PROFILE TYPE Classroom Building - Slabs On Grade NUMBER OF FLOORS 1 CHARACTERISTICS Occupied ANNUAL REVIEW COMPLETED BY Building Inventory AREA YEAR BUILT DISTRICT ASSIGNED AREA GROSS BUILDING SQ FT GROSS INSTRUCTIONAL SQ FT SCAP RECOGNIZED SQ FT 1962 100 Building 13,193 13,193 0 Building Totals 13,193 13,193 0 ORIGINAL OCCUPANCY DATE ORIGINAL BOARD ACCEPTANCE DATE Building Components SUB-ASSEMBLY COMPONENT Foundations Standard Foundation A1010 90.00% Good Slabs on Grade Standard Slabs on Grade A4010 90.00% Good Water and Gas Mitigation Building Subdrainage A6010 90.00% Good Superstructure Roof Construction B1020 62.00% Fair Exterior Vertical Enclosures School Facilities and Organization COMPONENT CODE MAINTENANCE PRIORITY CONDITION RATING Deficiencies: Other Causes: Other Deficiency Comments: Exposed roof structure (beam ends) are deteriorating Exterior Walls B2010 30.00% Poor Deficiencies: Other Causes: Not Seismically Compliant Generated: Nov 03, 2015 Page 1 of 6 School Facilities and Organization HIGHLINE INFORMATION AND CONDITION OF SCHOOLS 55.40% Poor Detailed Condition Assessment by Building Reporting Year 2015-2016 TYEE CAMPUS - 100 BUILDING Building Components SUB-ASSEMBLY COMPONENT Exterior Vertical Enclosures Exterior Windows Exterior Horizontal Enclosures Interior Construction COMPONENT CODE B2020 School Facilities and Organization CONDITION RATING 30.00% Poor Deficiencies: Caulking/Weather Stripping, Material Condition, U-Value Causes: Deficient Hardware/Operating Parts, Excessive Heat Loss, Other Deficiency Comments: Single glazed widows with caulking and putty failing Exterior Doors and Grilles B2050 90.00% Good Exterior Louvers and Vents B2070 90.00% Good Roofing B3010 90.00% Good Roof Appurtenances B3020 90.00% Good Overhead Exterior Enclosures B3080 90.00% Good Interior Partitions C1010 62.00% Fair Deficiencies: Other Causes: Acoustical Transference, Cracks, Tears, Holes, Looseness, Damaged or Missing Materials Interior Doors Interior Finishes MAINTENANCE PRIORITY C1030 30.00% Poor Deficiencies: Other Causes: Not ADA Compliant Deficiency Comments: Non ADA compliant hardware Suspended Ceiling Construction C1070 90.00% Good Wall Finishes C2010 62.00% Fair Deficiencies: Surface Damage Causes: Cracking, Peeling, Flaking, Surface Appearance Deficiency Comments: Wall finishes are worn and ripped Generated: Nov 03, 2015 Page 2 of 6 School Facilities and Organization HIGHLINE INFORMATION AND CONDITION OF SCHOOLS 55.40% Poor Detailed Condition Assessment by Building Reporting Year 2015-2016 TYEE CAMPUS - 100 BUILDING Building Components SUB-ASSEMBLY COMPONENT Interior Finishes Interior Fabrications COMPONENT CODE C2020 Other Causes: Other Deficiency Comments: Operable partitions are not functioning C2030 62.00% Fair Deficiencies: Missing Material, Other Causes: Holes, Tears, Stains, Discoloration Ceiling Finishes C2050 90.00% Good Domestic Water Distribution D2010 30.00% Poor Deficiencies: Clogged Pipes, Other Causes: Discolored Fixtures, Mineral Build Up in Pipes, Other, Pressure Loss Deficiency Comments: System age is at end of useful life. Sanitary Drainage D2020 30.00% Poor Deficiencies: Other Causes: Clogged Drains, Other, Slow Draining Deficiency Comments: System age is at end of useful life. Building Support Plumbing Systems School Facilities and Organization CONDITION RATING 62.00% Fair Deficiencies: Flooring Plumbing MAINTENANCE PRIORITY D2030 30.00% Poor Deficiencies: Other Causes: Other Additional Comments: insufficient qty of water closets Deficiency Comments: System age is at end of useful life. Generated: Nov 03, 2015 Page 3 of 6 School Facilities and Organization HIGHLINE INFORMATION AND CONDITION OF SCHOOLS 55.40% Poor Detailed Condition Assessment by Building Reporting Year 2015-2016 TYEE CAMPUS - 100 BUILDING Building Components SUB-ASSEMBLY COMPONENT HVAC Facility Fuel Systems COMPONENT CODE Deficiencies: Other Causes: Other Heating Systems D3010 62.00% Fair D3020 30.00% Poor Misadjusted Controls, Other Causes: Inoperable Devices, Other, System Inefficient Deficiency Comments: System age is at end of useful life. Newer boiler is in fair condition. D3050 30.00% Poor Deficiencies: Dirty Ducts or Plenums, Equipment Obsolescence, Misadjusted Air Balancing, Misadjusted Controls, Other Causes: Inoperable Devices, Other, System Inefficient Deficiency Comments: System age is at end of useful life. Ventilation D3060 30.00% Poor Deficiencies: Other Causes: Other, Stuffy Areas Additional Comments: System age is at end of useful life. Ventilation rates are assumed to not meet current codes. Fire Suppression Deficiencies: Other Causes: Other Fire Protection Specialties School Facilities and Organization CONDITION RATING Deficiencies: Facility HVAC Distribution Systems Fire Protection MAINTENANCE PRIORITY Deficiencies: Other Causes: Other D4010 62.00% Fair D4030 62.00% Fair Generated: Nov 03, 2015 Page 4 of 6 School Facilities and Organization HIGHLINE INFORMATION AND CONDITION OF SCHOOLS 55.40% Poor Detailed Condition Assessment by Building Reporting Year 2015-2016 TYEE CAMPUS - 100 BUILDING Building Components SUB-ASSEMBLY COMPONENT COMPONENT CODE Electrical Facility Power Generation D5010 90.00% Good Electrical Services and Distribution D5020 30.00% Poor Electronic Safety and Security School Facilities and Organization CONDITION RATING Deficiencies: Access Blocked Causes: Access Hazards Deficiency Comments: Main switchboard does not have visible AIC rating or ground fault protection. Main electrical room does not have panic hardware and open outwards in direction of egress. General Purpose Electrical Power Communications MAINTENANCE PRIORITY D5030 62.00% Fair Deficiencies: Equipment Obsolescence Causes: Other Deficiency Comments: Noted two older vintage panels without AIC rating Lighting D5040 90.00% Good Data Communications D6010 62.00% Fair Deficiencies: Equipment Obsolescence Causes: Other Deficiency Comments: Category 5 system cabling Voice Communications D6020 90.00% Good Distributed Communications and Monitoring D6060 90.00% Good Access Control and Intrusion Detection D7010 62.00% Fair Deficiencies: Equipment Obsolescence Causes: Keypads Not Functioning Additional Comments: No access control noted Generated: Nov 03, 2015 Page 5 of 6 School Facilities and Organization HIGHLINE INFORMATION AND CONDITION OF SCHOOLS 55.40% Poor Detailed Condition Assessment by Building Reporting Year 2015-2016 TYEE CAMPUS - 100 BUILDING Building Components SUB-ASSEMBLY COMPONENT Electronic Safety and Security Electronic Surveillance D7030 90.00% Good Detection and Alarm D7050 90.00% Good Integrated Automation Furnishings MAINTENANCE PRIORITY CONDITION RATING Deficiencies: Other Causes: Other Deficiency Comments: Where detection provided, is at top of beam and not installed per code Integrated Automation Facility Controls D8010 30.00% Poor Deficiencies: Equipment Obsolescence, Other Causes: Other, System Not working to Capacity Deficiency Comments: System age is at end of useful life. Corrective Actions: Replace pneumatic controls with BAS. Fixed Furnishings E2010 62.00% Fair Deficiencies: Other Causes: Other Deficiency Comments: Counters in the kitchen have cracks and delamination is occuring Movable Furnishings School Facilities and Organization COMPONENT CODE E2050 90.00% Good Generated: Nov 03, 2015 Page 6 of 6