Highline Public Schools

advertisement
School Facilities and Organization
HIGHLINE
INFORMATION AND CONDITION OF SCHOOLS
55.40% Poor
Detailed Condition Assessment by Building
Reporting Year 2015-2016
TYEE CAMPUS - 100 BUILDING
Building Details
PROFILE TYPE
Classroom Building - Slabs On Grade
NUMBER OF FLOORS
1
CHARACTERISTICS
Occupied
ANNUAL REVIEW COMPLETED BY
Building Inventory
AREA YEAR
BUILT
DISTRICT ASSIGNED
AREA
GROSS BUILDING
SQ FT
GROSS INSTRUCTIONAL SQ FT
SCAP RECOGNIZED
SQ FT
1962
100 Building
13,193
13,193
0
Building Totals
13,193
13,193
0
ORIGINAL OCCUPANCY
DATE
ORIGINAL BOARD
ACCEPTANCE DATE
Building Components
SUB-ASSEMBLY
COMPONENT
Foundations
Standard Foundation
A1010
90.00% Good
Slabs on Grade
Standard Slabs on Grade
A4010
90.00% Good
Water and Gas Mitigation
Building Subdrainage
A6010
90.00% Good
Superstructure
Roof Construction
B1020
62.00% Fair
Exterior Vertical Enclosures
School Facilities and Organization
COMPONENT
CODE
MAINTENANCE
PRIORITY
CONDITION
RATING
Deficiencies:
Other
Causes:
Other
Deficiency Comments:
Exposed roof structure (beam ends) are deteriorating
Exterior Walls
B2010
30.00% Poor
Deficiencies:
Other
Causes:
Not Seismically Compliant
Generated: Nov 03, 2015
Page 1 of 6
School Facilities and Organization
HIGHLINE
INFORMATION AND CONDITION OF SCHOOLS
55.40% Poor
Detailed Condition Assessment by Building
Reporting Year 2015-2016
TYEE CAMPUS - 100 BUILDING
Building Components
SUB-ASSEMBLY
COMPONENT
Exterior Vertical Enclosures
Exterior Windows
Exterior Horizontal Enclosures
Interior Construction
COMPONENT
CODE
B2020
School Facilities and Organization
CONDITION
RATING
30.00% Poor
Deficiencies:
Caulking/Weather Stripping, Material Condition, U-Value
Causes:
Deficient Hardware/Operating Parts, Excessive Heat Loss, Other
Deficiency Comments:
Single glazed widows with caulking and putty failing
Exterior Doors and Grilles
B2050
90.00% Good
Exterior Louvers and Vents
B2070
90.00% Good
Roofing
B3010
90.00% Good
Roof Appurtenances
B3020
90.00% Good
Overhead Exterior Enclosures
B3080
90.00% Good
Interior Partitions
C1010
62.00% Fair
Deficiencies:
Other
Causes:
Acoustical Transference, Cracks, Tears, Holes, Looseness, Damaged
or Missing Materials
Interior Doors
Interior Finishes
MAINTENANCE
PRIORITY
C1030
30.00% Poor
Deficiencies:
Other
Causes:
Not ADA Compliant
Deficiency Comments:
Non ADA compliant hardware
Suspended Ceiling Construction
C1070
90.00% Good
Wall Finishes
C2010
62.00% Fair
Deficiencies:
Surface Damage
Causes:
Cracking, Peeling, Flaking, Surface Appearance
Deficiency Comments:
Wall finishes are worn and ripped
Generated: Nov 03, 2015
Page 2 of 6
School Facilities and Organization
HIGHLINE
INFORMATION AND CONDITION OF SCHOOLS
55.40% Poor
Detailed Condition Assessment by Building
Reporting Year 2015-2016
TYEE CAMPUS - 100 BUILDING
Building Components
SUB-ASSEMBLY
COMPONENT
Interior Finishes
Interior Fabrications
COMPONENT
CODE
C2020
Other
Causes:
Other
Deficiency Comments:
Operable partitions are not functioning
C2030
62.00% Fair
Deficiencies:
Missing Material, Other
Causes:
Holes, Tears, Stains, Discoloration
Ceiling Finishes
C2050
90.00% Good
Domestic Water Distribution
D2010
30.00% Poor
Deficiencies:
Clogged Pipes, Other
Causes:
Discolored Fixtures, Mineral Build Up in Pipes, Other, Pressure Loss
Deficiency Comments:
System age is at end of useful life.
Sanitary Drainage
D2020
30.00% Poor
Deficiencies:
Other
Causes:
Clogged Drains, Other, Slow Draining
Deficiency Comments:
System age is at end of useful life.
Building Support Plumbing
Systems
School Facilities and Organization
CONDITION
RATING
62.00% Fair
Deficiencies:
Flooring
Plumbing
MAINTENANCE
PRIORITY
D2030
30.00% Poor
Deficiencies:
Other
Causes:
Other
Additional Comments:
insufficient qty of water closets
Deficiency Comments:
System age is at end of useful life.
Generated: Nov 03, 2015
Page 3 of 6
School Facilities and Organization
HIGHLINE
INFORMATION AND CONDITION OF SCHOOLS
55.40% Poor
Detailed Condition Assessment by Building
Reporting Year 2015-2016
TYEE CAMPUS - 100 BUILDING
Building Components
SUB-ASSEMBLY
COMPONENT
HVAC
Facility Fuel Systems
COMPONENT
CODE
Deficiencies:
Other
Causes:
Other
Heating Systems
D3010
62.00% Fair
D3020
30.00% Poor
Misadjusted Controls, Other
Causes:
Inoperable Devices, Other, System Inefficient
Deficiency Comments:
System age is at end of useful life. Newer boiler is in fair condition.
D3050
30.00% Poor
Deficiencies:
Dirty Ducts or Plenums, Equipment Obsolescence, Misadjusted Air
Balancing, Misadjusted Controls, Other
Causes:
Inoperable Devices, Other, System Inefficient
Deficiency Comments:
System age is at end of useful life.
Ventilation
D3060
30.00% Poor
Deficiencies:
Other
Causes:
Other, Stuffy Areas
Additional Comments:
System age is at end of useful life. Ventilation rates are assumed to
not meet current codes.
Fire Suppression
Deficiencies:
Other
Causes:
Other
Fire Protection Specialties
School Facilities and Organization
CONDITION
RATING
Deficiencies:
Facility HVAC Distribution
Systems
Fire Protection
MAINTENANCE
PRIORITY
Deficiencies:
Other
Causes:
Other
D4010
62.00% Fair
D4030
62.00% Fair
Generated: Nov 03, 2015
Page 4 of 6
School Facilities and Organization
HIGHLINE
INFORMATION AND CONDITION OF SCHOOLS
55.40% Poor
Detailed Condition Assessment by Building
Reporting Year 2015-2016
TYEE CAMPUS - 100 BUILDING
Building Components
SUB-ASSEMBLY
COMPONENT
COMPONENT
CODE
Electrical
Facility Power Generation
D5010
90.00% Good
Electrical Services and
Distribution
D5020
30.00% Poor
Electronic Safety and Security
School Facilities and Organization
CONDITION
RATING
Deficiencies:
Access Blocked
Causes:
Access Hazards
Deficiency Comments:
Main switchboard does not have visible AIC rating or ground fault
protection. Main electrical room does not have panic hardware and
open outwards in direction of egress.
General Purpose Electrical Power
Communications
MAINTENANCE
PRIORITY
D5030
62.00% Fair
Deficiencies:
Equipment Obsolescence
Causes:
Other
Deficiency Comments:
Noted two older vintage panels without AIC rating
Lighting
D5040
90.00% Good
Data Communications
D6010
62.00% Fair
Deficiencies:
Equipment Obsolescence
Causes:
Other
Deficiency Comments:
Category 5 system cabling
Voice Communications
D6020
90.00% Good
Distributed Communications and
Monitoring
D6060
90.00% Good
Access Control and Intrusion
Detection
D7010
62.00% Fair
Deficiencies:
Equipment Obsolescence
Causes:
Keypads Not Functioning
Additional Comments:
No access control noted
Generated: Nov 03, 2015
Page 5 of 6
School Facilities and Organization
HIGHLINE
INFORMATION AND CONDITION OF SCHOOLS
55.40% Poor
Detailed Condition Assessment by Building
Reporting Year 2015-2016
TYEE CAMPUS - 100 BUILDING
Building Components
SUB-ASSEMBLY
COMPONENT
Electronic Safety and Security
Electronic Surveillance
D7030
90.00% Good
Detection and Alarm
D7050
90.00% Good
Integrated Automation
Furnishings
MAINTENANCE
PRIORITY
CONDITION
RATING
Deficiencies:
Other
Causes:
Other
Deficiency Comments:
Where detection provided, is at top of beam and not installed per
code
Integrated Automation Facility
Controls
D8010
30.00% Poor
Deficiencies:
Equipment Obsolescence, Other
Causes:
Other, System Not working to Capacity
Deficiency Comments:
System age is at end of useful life.
Corrective Actions:
Replace pneumatic controls with BAS.
Fixed Furnishings
E2010
62.00% Fair
Deficiencies:
Other
Causes:
Other
Deficiency Comments:
Counters in the kitchen have cracks and delamination is occuring
Movable Furnishings
School Facilities and Organization
COMPONENT
CODE
E2050
90.00% Good
Generated: Nov 03, 2015
Page 6 of 6