34-7045-2684-6 5/11/98 1:23 PM Page 1

Volition

Reference Cables

Testing Instructions

VOL-REF-ST

VOL-REF-SC

34-7045-2684-6

34-7045-2684-6 5/11/98 1:23 PM Page 2

Volition Patch Cords

Volition Reference Cable

Volition White Light Source

The Volition

Reference Cable Set can be used with any standard LED Source

or Power Meter including the 3M

VOL-23XT-VT Test Set.

Volition Reference Cable Set

Bill of Materials

D e s c r i p t i o n

Volition ™ Patch Cords

(Hybrid ST* or SC to Volition Plug)

Volition ™ Reference Cable

(ST or SC to Volition™ Socket)

Documentation worksheet

Loss measurements

Q u a n t i t y

2

1

1

Optional Accessories Quantity

LED Source 1

Standard Power Meter 1

Visible White Light Source 1

Establishing the Reference:

1.

Connect the beige boot connector of one of the Volition patch cords to the LED source.

2.

Connect the Volition reference cable to the optical power meter with the beige boot connector.

3.

Connect the patch cord from the LED source to the reference cable connected to the optical power meter.

4.

Turn on the source and the optical power meter.

5.

Record the reference power level on the meter per the manufacturer’s instructions.

6.

Remove the reference cable from the optical power meter and replace it with the second patch cord. Be sure to connect the gray boot connector of the patch cord to the optical power meter.

34-7045-2684-6 5/11/98 1:23 PM Page 3

Taking End-to-End Measurements:

1.

For taking measurements in the “A-to-

Z” direction, proceed with the LED source to the patch panel. Connect the

Volition patch cord to the first data line to be tested.

2.

Proceed to the appropriate wall outlet with the optical power meter and connect it to the wall outlet.

3.

Record the loss value displayed on the meter per the manufacturer’s instructions.

4.

Connect the source to the next data line in the patch panel, and proceed with the optical power meter to the appropriate wall outlet and connect the meter to it.

5.

Repeat steps 3 and 4 until all data lines have been tested.

Note: There are two fibers in each data line.

At this point, you have only tested one fiber in each line. For single-direction measurements, proceed to the “Re-

Referencing” section. For bi-directional measurements, (see diagram 1), proceed as follows:

6.

For bi-directional measurements, move the optical power meter to the patch panel and connect it to the first data line. Take the LED source and connect it to the appropriate wall outlet. You will now be measuring the second fiber in each line from the “Z-to-A” direction.

7.

Record the loss value displayed on the meter per the manufacturer’s instructions.

8.

Move the optical power meter to the next location in the patch panel, and proceed with the LED source to the appropriate wall outlet. Repeat steps 7 and 8 until all lines have been tested.

Note: In order to measure loss in the second direction for each fiber, you must switch the launch connectors on the Volition ™ Patch Cords and rereference the LED source and optical power meter.

Re-Referencing the LED Source and Optical Power Meter:

1.

Connect the gray boot connector of one of the Volition patch cords to the LED source.

2.

Connect the Volition ™ Reference Cable to the optical power meter using the gray boot connector on the cable.

3.

Connect the patch cord from the LED source to the reference cable that is connected to the optical power meter.

4.

Turn both the LED source and optical power meter on.

5.

Record the reference power level on the meter per the manufacturer's instructions.

6.

Remove the Volition reference cable from the optical power meter and replace it with the second Volition patch cord. Be sure to connect the beige boot connector of the patch cord to the optical power meter.

7.

Proceed with steps 1 through 5 in the

“End-to-End Measurements” section for single direction measurements. For bidirectional measurements, proceed with steps 1 through 8 in the same section.

34-7045-2684-6 5/11/98 1:23 PM Page 4

Diagram 1

"A" to "Z" measurements

Patch Panel Wall Outlet

Source Meter

Meter Source

Patch Panel Wall Outlet

"Z" to "A" measurements

Sample Data Sheet

DATE:

JOB LOCATION:

TECHNICIAN:

4

4

3

3

5

5

Reference 1300nm

Reference 850nm

LINE # FIBER

2

2

1

1

A

B

A

B

A

B

A

B

A

B

WAVELENGTH

1300 nm

850 nm

1300 nm

850 nm

1300 nm

850 nm

1300 nm

850 nm

1300 nm

850 nm

A TO Z Z TO A AVERAGE

Important Notice

All statements, technical information, and recommendations related to Seller’s products are based on information believed to be reliable, but the accuracy or completeness thereof is not guaranteed. Before utilizing the product, the user should determine the suitability of the product for its intended use. The user assumes all risks and liability whatsoever in connection with such use.

Any statements or recommendations of the Seller which are not contained in the Seller’s current publications shall have no force or effect unless contained in an agreement signed by an authorized officer of Seller. The statements contained herein are made in lieu of all warranties, expressed or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose which warranties are hereby expressly disclaimed.

SELLER SHALL NOT BE LIABLE TO THE USER OR ANY OTHER PERSON UNDER ANY LEGAL THEORY, INCLUDING BUT NOT LIMITED

TO NEGLIGENCE OR STRICT LIABILITY, FOR ANY INJURY OR FOR ANY DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL

DAMAGES SUSTAINED OR INCURRED BY REASON OF THE USE OF ANY OF THE SELLER’S PRODUCTS.

Telecom Systems Division

6801 River Place Blvd.

Austin, TX 78726-9000

800/695-0447

FAX 512/990-7962 http://www.3M.com/volition

Volition, and the “dot wave” symbol are trademarks of 3M.

ST* is a trademark of Lucent Technologies.

40% Pre-consumer waste paper

10% Post-consumer waste paper

34-7045-2684-6

Download