wire diagrams for 1-lamp emergency operation

advertisement
Catalog Number
UPC Number
Description
72902
60198672902
Emergency Lighting Ballast
650 Lumen
CFL Double ) Triple Twin Tube
4 Pin
Features
For both normal and emergency Flourescent lighting.
In the event of a Power Failure, the Ballast Switches to the Emergency Mode
and operates one or two of the existing lamps for a minimum of 90 minutes.
Contains a Ni-Cad Battery, Charger, and Inverter Circuit in a single package.
Can be mounted in the wireway or on top of the fixture.
90 minute minimum emergency power, 24 hour recharge time
o
o
Temperature Range: 20 C to 50 C
120/277 Volt
60 Hz
UL listed for factory installation or retrofit applications
UL Listed Damp Location
Standard Ballasts
Standard Emergency ballasts are Rated for use with lamp types:
4-Pin Compact lamps.
standard energy saving & dimming AC ballasts
General
Housing:
Finish:
Lamp Type:
Battery :
Emergency Power:
Galvanized Steel
Powder Coat
4 Pin CFL 2 0r 3 Twin Tube
Ni-Cad
90 minutes
Dimension Information
Length:
Height:
Depth:
9.4"
1.5"
2.4"
Specifications
Temperature Rating
Voltage Rating
Frequency:
Flammability Rating
Input Wattage:
Wattage Rating
Battery:
0oC to 50oC
120/277 V
60 Hz
N/A
3.5
13-39 Watt
Ni-Cad 3.6V, 14.4 Wh, 280 mA
Packaging
Box Qty
1
Certifications
UL
cUL
RoHS
UL 924
Yes
Yes
www.morrisproducts.com
Morris Products 53 Carey Road, Queensbury, NY 12804
AC
LINE IN
AC
LINE IN
3
3
CONNECT
TO LAMP
FIXTURE
CONNECT
TO LAMP
FIXTURE
CONDUIT
CONNECT
2
EMERGENCY
BALLAST
CONDUIT
CONNECT
2
4
JUNCTION
BOX
CONDUIT
CONNECT
CONDUIT
CONNECT
4
A
JUNCTION
BOX
1
1
1
CONDUIT
CONNECT
CEILING
CEILING
Emergency ballast
Shading - Equipment supplied by others
EMERGENCY
BALLAST
WALL OR
CEILING
CONDUIT
CONNECT
WALL OR
CEILING
TEST/MONITOR
PLATE
TEST/MONITOR
PLATE
1
NOTE: The test/monitor plate can be remotely installed up to 50 feet from the emergency
ballast. The emergency ballast may be remotely mounted up to half the distance
recommended by the AC ballast manufacturer. If no AC ballast is used,
the emergency ballast can be remotely mounted up to 50 feet away.
1
Flexible conduit (supplied) to connect ballast wire.
2
Existing conduit to run existing wire to lamp holder (AC ballast on junction box). If AC ballast is on reflector, run yellow, yellow/black,
blue/ white and blue wires from emergency ballast through this conduit.
AC line in.
3
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT
COMMON
BLACK 120V
UNSWITCHED HOT
(CAP UNUSED LEAD)
WALL
SWITCH
WHT/BLK
WHITE
BLUE
BLUE
BLACK
BLUE
BLU/WHT
YELLOW
RED
YELLOW
RED
LAMP 1
LAMP 2
WHITE
WHITE
OR
ORANGE 277V
RED
YEL/BLK
YELLOW
B
B
A
A
BLK
TEST
SWITCH
BLK
VIOLET+
BROWN-
INDICATOR
LIGHT
RED
WHITE
INVERTER
CONNECTOR
WIRE DIAGRAMS FOR 1-LAMP EMERGENCY OPERATION
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
B. TWO (2) LAMP RAPID START BALLAST
WHITE
COMMON
UNSWITCHED HOT
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
WALL
SWITCH
WHT/BLK
BLUE
WHITE
BLACK
YELLOW
YELLOW
2 LAMP
RAPID START
BALLAST
BLUE
WHITE
B
BLUE
BLU/WHT
YELL/BLK
B
A
RED
TEST
SWITCH
BLK
VIOLET+
INDICATOR
LIGHT
BROWN-
EMERGENCY
BALLAST
YELLOW
RED
RED
A
BLK
RED
INVERTER
CONNECTOR
WHITE
LAMP 1
LAMP 2
WHITE
COMMON
UNSWITCHED HOT
B
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
BLUE
WHITE
B
A
A
TEST
SWITCH
BLK
VIOLET+
INDICATOR
LIGHT
BROWN-
EMERGENCY
BALLAST
RED
INVERTER
CONNECTOR
WHITE
WHITE
B
BLK
A
A
BLK
TEST
SWITCH
BLK
VIOLET+
INDICATOR
LIGHT
BROWN-
RED
INVERTER
CONNECTOR
WHITE
WHITE
COMMON
UNSWITCHED HOT
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
WALL
SWITCH
WHT/BLK
WHITE
BLACK
1 LAMP
RAPID START
BALLAST
BLUE
BLUE
BLUE
BLU/WHT
YELL/BLK
RED
YELLOW
RED
RED
B
A
WHITE
TEST
SWITCH
BLK
VIOLET+
BROWN-
INDICATOR
LIGHT
RED
WHITE
LAMP
BLK
INVERTER
CONNECTOR
WHITE
COMMON
B
BLACK 120V
OR
ORANGE 277V
UNSWITCHED HOT
(CAP UNUSED LEAD)
WALL
SWITCH
WHT/BLK
WHITE
2 LAMP
CIRCLINE
BALLAST
BLACK
YELLOW
YELLOW
BLUE
BLUE
BLUE
BLU/WHT
YELL/BLK
RED
YELLOW
RED
RED
WHITE
B
A
A
EMERGENCY
BALLAST
BLK
TEST
SWITCH
BLK
VIOLET+
INDICATOR
LIGHT
BROWN-
RED
INVERTER
CONNECTOR
WHITE
LAMP 1
LAMP 2
UNSWITCHED HOT
B
WHITE
COMMON
BLACK 120V
OR
ORANGE 277V
WALL
SWITCH
(CAP UNUSED LEAD)
WHT/BLK
RED
1 LAMP
RAPID START
BALLAST
BLACK
WHITE
RED
BLUE
BLUE
BLU/WHT
YELL/BLK
YELLOW
RED
B
A
A
WHITE
BLK
TEST
SWITCH
BLK
VIOLET+
INDICATOR
LIGHT
BROWN-
RED
INVERTER
CONNECTOR
WHITE
LAMP
WHITE
COMMON
BLACK 120V
OR
ORANGE 277V
UNSWITCHED HOT
(CAP UNUSED LEAD)
WALL
SWITCH
WHT/BLK
WHITE
BLACK
BLUE
RED
RED
2 LAMP
CIRCLINE
BALLAST
WHITE
RED
RED
BLUE
WHITE
B
BLUE
BLU/WHT
RED
WHITE
B
A
A
BLK
TEST
SWITCH
BLK
VIOLET+
INDICATOR
LIGHT
BROWN-
RED
YELL/BLK
INVERTER
CONNECTOR
YELLOW
WHITE
32 WATT
LAMP
22 WATT
LAMP
WHITE
COMMON
BLACK 120V
OR
ORANGE 277V
UNSWITCHED HOT
WHITE
WALL
SWITCH
BLACK
(CAP UNUSED LEAD)
WHT/BLK
BLUE
BLUE
BLU/WHT
1 LAMP
RAPID START
BALLAST
BLUE
RED
RED
RED
YELL/BLK
B
WHITE
B
A
A
TEST
SWITCH
BLK
VIOLET+
BROWN-
INDICATOR
LIGHT
RED
YELLOW
WHITE
LAMP
BLK
INVERTER
CONNECTOR
WHITE
A
BLK
TEST
SWITCH
BLK
VIOLET+
INDICATOR
LIGHT
BROWN-
RED
INVERTER
CONNECTOR
WHITE
WHITE
WHITE
COMMON
UNSWITCHED HOT
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
CAP
CAP
CAP
WHT/BLK
B
BLUE
B
A
A
YELL/BLK
YELLOW
RED
TEST
SWITCH
BLK
VIOLET+
INDICATOR
LIGHT
BROWN-
EMERGENCY
BALLAST
BLU/WHT
BLK
RED
INVERTER
CONNECTOR
WHITE
LAMP
WHITE
COMMON
UNSWITCHED HOT
BLACK 120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
CAP
CAP
CAP
LAMP
WHT/BLK
BLUE
B
WHITE
B
A
A
BLK
TEST
SWITCH
BLK
VIOLET+
BLU/WHT
YELL/BLK
BROWN-
YELLOW
RED
RED
WHITE
INDICATOR
LIGHT
INVERTER
CONNECTOR
Download