61F-GP-N_ Datasheet - Omron United States

advertisement
Floatless Level Switch (Compact, Plug-in Type)
61F-GP-N@
Cat. No. N42I-E-01
Space-saving Design Ideal for Control Panel
Downsizing. Easy Maintenance.
• Compact: 49.4 × 38 × 84 mm (H×W×D).
• Easy identification of operating status with LED operation
indicator.
• Independent DPDT contacts on 11-Pin Models.
• CE marking and UL/CSA compliance.
Refer to Safety Precautions for Floatless Level
Controllers.
■ Model Number Legend
1. No. of Pins
61F-GP-@@
N: 11 pins
N8: 8 pins
1 2
Position of LED indicator
2. Type
Blank:
L 2KM:
L 4KM:
H:
D:
R:
T:
General-purpose
Long-distance (for 2 km)
Long-distance (for 4 km)
High-sensitivity
Low-sensitivity
Two-wire
High-temperature
■ Ordering Information
Type
11-pin
Type
11-pin
Type
General-purpose
Long-distance (for 2 km)
Model
Model
61F-GP-N
61F-GP-NL 2KM
High-sensitivity
Low-sensitivity
Model
Model
61F-GP-NH
61F-GP-ND
Tropical environments
Type
8-pin
Type
8-pin
61F-GP-N-TDL
Model
Model
61F-GP-NT
Long-distance (for 2 km)
Model
Model
61F-GP-N8L 2KM
High-sensitivity
Low-sensitivity
Model
Model
61F-GP-N8H
Two-wire
61F-GP-NR
General-purpose
61F-GP-N8
Model
61F-GP-NL 4KM
High-temperature
Model
8-pin
Long-distance (for 4 km)
61F-GP-N8D
Long-distance (for 4 km)
Model
61F-GP-N8L 4KM
Two-wire
Model
61F-GP-N8R
61F-GP-N8HY
Note: When ordering, specify the desired operating voltage at the end of the model number.
Example: 61F-GP-N [220 VAC]
Desired supply voltage
1
61F-GP-N@
■ Compact Plug-in Models (11-pin Type)
Specifications
Item
General-purpose
Controller
Hightemperature
Controller
61F-GP-N
61F-GP-NT
Long-distance
Controllers
High-sensitivity
Controller
Low-sensitivity
Controller
Two-wire
Controller
61F-GP-NL 2KM
(for 2 km)
61F-GP-NL 4KM
(for 4 km)
61F-GP-NH
(see note 4)
61F-GP-ND
61F-GP-NR
For control of ordinary purified water
in cases where the
distance between
sewage pumps
and water tanks or
between receiver
tanks and supply
tanks is long or
where remote control is required.
For control of liquids with high specific resistance
such as distilled
water
For control of liquids with low specific resistance
such as salt water,
sewage water,
acid chemicals, alkali chemicals
For control of ordinary purified water
or sewage water
used in combination with Two-wire
Electrode Holder
(incorporating a
resistor of 6.8 kΩ)
Approx. 0.12 mA
AC max.
Approx. 1 mA AC max.
Controlling materials
and operating conditions
For control of ordi- For control of ordinary purified water nary purified water
or sewage water or sewage where
operating ambient
temperature is
high.
Supply voltage
24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz
Operating voltage
range
85% to 110% of rated voltage
Interelectrode voltage 8 VAC
Interelectrode current Approx. 1 mA AC max.
Power consumption
Approx. 3.5 VA max.
Interelectrode operate 0 to approx. 4 kΩ
resistance
0 to approx. 4 kΩ
0 to approx. 1.3 kΩ Approx. 10 kΩ to
approx. 40 kΩ
(for 2 km)
0 to approx. 0.5 kΩ (see note 3)
(for 4 km)
0 to approx.
1.3 kΩ
Interelectrode release Approx. 15 k to
resistance
∞Ω
Approx. 15 k to
∞Ω
4 k to ∞ Ω (for 2
Approx. 100 k to
km)
∞Ω
2.5 k to ∞ Ω (for 4
km)
Approx. 4 k to ∞ Ω Approx. 15 k to
∞Ω
2 km max.
4 km max.
1 km max.
Response time
Operate:80 ms max.
Release:160 ms max.
Cable length
(see note 1)
1 km max.
Control output
1 A, 250 VAC (Inductive load: cosφ = 0.4)
3 A, 250 VAC (Resistive load)
Ambient temperature
Operating:–10 to 55°C (–10 to 70°C for high-temperature controller)
Ambient humidity
Operating:45% to 85% RH
Insulation resistance
(see note 2)
100 MΩ min. (at 500 VDC)
Dielectric strength
(see note 2)
2000 VAC, 50/60 Hz for 1 min.
Life expectancy
Electrical: 100,000 operations min.
Mechanical: 5,000,000 operations min.
Weight
Approx. 155 g
Accessories
Hold-down clip PFC-N8
600 m max.
50 m max.
0 to
approx. 2 kΩ
800 m max.
Note: 1. The length when using completely insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as
the cable diameter or number of conductors becomes larger. For details, refer to Safety Precautions for Floatless Level Controllers.
2. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals. For details, refer to Safety Precautions for
Floatless Level Controllers.
3. Possible to use with 15 kΩ or less, however, this may cause reset failure.
4. 61F-GP-NH High-sensitivity Controller uses advanced operation.
When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the internal relay will not operate.
When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal
relay will operate.
If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation.
2
61F-GP-N@
Internal Circuit Diagrams
61F-GP-N/-NT/-NL/-ND
61F-GP-NH
Power supply
61F-GP-NR
Power supply
Power supply
24 V Control circuit
24 V Control circuit
24 V Control circuit
8V
8V
8V
(See note.)
U
3
9
4
5
11
S0
S1
E3
E1
Ta1 Tc1
10
(See note.)
U
U
1
7
Tb1
Ta2 Tc2
6
8
3
9
4
5
11
Tb2
S0
S1
E3
E1
Ta1 Tc1
10
U
U
1
7
Tb1
Ta2 Tc2
6
U
8
3
9
4
5
11
10
1
Tb2
S0
S1
E3
E1
Ta1
Tc1
Tb1
Note: When applying a self-holding circuit, short between terminals 5 and 6 and use terminal 7 as E2.
3
61F-GP-N@
■ Connections
Automatic Water Supply and
Drainage Control
Compact, Plug-in Type
61F-GP-N
Dimensions:
page 14
Automatic Water Supply Control
Automatic Drainage Control
Connections
Connections
61F-GP-N
Commercial Voltage
R S T
61F-GP-N
Commercial Voltage
R S T
8
7
6
5
U
MCCB
0V
4
24 V
Control
circuit
8
6
0V
U
Contactor
Control
circuit
U
8V
U
11
4
24 V
Power
supply
U
3
10
5
U
MCCB
8V
Power
supply
7
1
9
3
2
10
Contactor
(See note.)
9
11
1
2
(See note.)
PS-3S
Stop
Motor
protection
relay
Water supply
source
M
Water
tank
E1
E3
E2
Start
Motor
protection
relay
M
P
PS-3S
Wastewater
tank
P
Start
E1
E3
E2
Stop
Reservoir
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
PF113A (Front-connecting)
PL11 (Rear-connecting)
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
PF113A (Front-connecting)
PL11 (Rear-connecting)
Connect terminal 1 to the contactor’s coil terminal.
Connect terminal 1 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of the
model.
Note: The power supply depends on the specifications of the
model.
Principles of Operation
Principles of Operation
Water
supply
P
Pump OFF
E1
Pump ON
E2
(Indicator ON)
(Indicator OFF)
E3
Pump ON
E1
Pump OFF
E2
E3
(Indicator ON)
(Indicator OFF)
P
Water drainage
The pump stops when the water level reaches E1 (indicator ON)
and starts when the water level drops below E2 (indicator OFF).
The pump starts when the water level reaches E1 (indicator ON)
and stops when the water level drops below E2 (indicator OFF).
4
61F-GP-N@
Liquid Level Indication
(Connection Example)
Compact, Plug-in Type
61F-GP-N
Dimensions:
page 14
Liquid Level Indication
Connections
Lower limit
Commercial Voltage
R S T
Intermediate
61F-GP-N
8
61F-GP-N
6
7
U
0V
MCCB
5
4
U
1
61F-GP-N
9
2
6
7
U
0V
3
10
5
4
8
0V
11
1
9
2
3
10
Control
circuit U
24 V
Power
supply
8V
U
5
4
6
7
U
Control U
circuit
24 V
Power
supply
8V
11
8
Control U
circuit
24 V
Power
supply
3
10
Upper limit
8V
U
9
2
1
11
(See note.)
PS-4S
E1
Water supply
source
M
Water
tank
P
E2
E4
E3
Upper limit
Intermediate
Lower limit
Note: The power supply phases (terminals 3 to 9) can be matched to use the same ground for the
common Electrode (the longest Electrode, terminal 4).
Principles of Operation
• Terminals 6 and 7, and terminals 10 and 11 on the lower -limit 61F-GP-N are shorted when the water level reaches E3 (indicator ON).
• Terminals 6 and 7, and terminals 10 and 11 on the intermediate 61F-GP-N are shorted when the water level reaches E2 (indicator ON).
• Terminals 6 and 7, and terminals 10 and 11 on the upper-limit 61F-GP-N are shorted when the water level reaches E1 (indicator ON).
5
61F-GP-N@
Replacing 61F-G3N Functions (Automatic Water
Supply Control with Abnormal Water Increase and
Water Shortage Alarms)
Compact, Plug-in Type
61F-GP-N
Dimensions:
page 14
Replacing 61F-G3N Functions
Connections
Water shortage
Commercial Voltage
R S T
Pump control
61F-GP-N
8
61F-GP-N
6
7
5
4
U3
0V
MCCB
PL
Control
circuit
24 V
Lower limit
Contactor
7
1
9
2
B
Alarm
6
U2
0V
U3
3
10
5
4
Control
circuit
24 V
8
U2
11
1
0V
U2
5
4
6
9
2
3
10
PL
Control
circuit
24 V
U1
8V
Power
supply
U1
11
9
2
1
Upper limit
(See note.)
PS-5S
Motor protection
relay
E1
Water
tank
Water supply
source
M
7
U1
8V
Power
supply
U3
11
61F-GP-N
8
8V
Power
supply
3
10
Full tank
E2
E3
E5
P
E4
Full tank
Stop
Start
Water shortage
Note: The power supply phases (terminals 3 to 9) can be matched to use the same ground for the common Electrode
(the longest Electrode, terminal 4).
Principles of Operation
• The pump stops when the water level
reaches E2 (U2 indicator ON) and starts
when the water level drops below E3 (U2
indicator OFF).
• If the water level rises to E1 for any reason,
the upper-limit indicator turns ON and the
alarm sounds (U1 indicator ON).
If the water level drops below E4 for any
reason, the lower-limit indicator turns ON
and the alarm sounds (U3 indicator OFF).
Water supply
Upper
limit
P
E1
Pump OFF
Pump ON
(U1 indicator ON)
(U2 indicator OFF)
E3
E5
B
(U2 indicator ON)
E2
E4
LH
Lower
limit
(U3 indicator OFF)
LL
B
6
61F-GP-N@
Two-Wire Connections
Automatic Water Supply and Drainage Control
Compact, Plug-in Type
61F-GP-NR
Dimensions:
page 14
Automatic Water Supply Control
Automatic Drainage Control
Connections
Connections
Commercial Voltage
R S T
Commercial Voltage
R S T
61F-GP-NR
5
MCCB
61F-GP-NR
5
MCCB
4
4
0V
Power
supply
24 V
Control
circuit
24 V Control
circuit
0V
U
Power
supply
8V
8V
U
U
3
10
Contactor
11
1
9
3
2
10
(See note.)
PS-3SR
R
Motor
protection
relay
M
Stop
Water
tank
Water supply
source
U
E3
E2
E1
11
1
2
Contactor
(See note.)
Motor
protection
relay
Wastewater
tank
Start
M
P
9
P
R
E3 E2
PS-3SR
E1
Reservoir
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
PF113 (Front-connecting)
PL11 (Rear-connecting)
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
PF113 (Front-connecting)
PL11 (Rear-connecting)
• Connect terminal 1 to the contactor’s coil terminal.
• Connect terminal 11 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of the
model.
• With 2-wire connections, only two wires are required between
the 61F-GP-NR and Electrode Holder, but three wires are
required for the Electrodes.
• The Electrode Holder must be specified for 2-wire connections.
(Resistance R is built into Electrode Holders for 2-Wire
Connections.)
Note: The power supply depends on the specifications of the
model.
• With 2-wire connections, only two wires are required between
the 61F-GP-NR and Electrode Holder, but three wires are
required for the Electrodes.
• The Electrode Holder must be specified for 2-wire connections.
(Resistance R is built into Electrode Holders for 2-Wire
Connections.)
Principles of Operation
Principles of Operation
Water
supply
P
Pump OFF
Pump ON
(Indicator ON)
E1
(Indicator OFF)
E2
Pump ON
(Indicator ON)
E1
Pump OFF
(Indicator OFF)
E2
P
E3
E3
Water drainage
The pump stops when the water level reaches E1 (indicator ON)
and starts when the water level drops below E2 (indicator OFF).
The pump starts when the water level reaches E1 (indicator ON)
and stops when the water level drops below E2 (indicator OFF).
7
61F-GP-N@
■ Connection with Three-phase Four-line Circuit
When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams.
Line voltage (R-S, S-T, or R-T):
380 or 415 VAC
Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC
61F-GP-N@ 220 or 240 VAC
61F-GP-N
8
7
6
4
U
Power source
380 or 415 VAC
R S T N *
0V
5
Control circuit
24 V
U
8V
220 or
240 V
Source voltage:
between 3 and 9
U
3
10
9
1
11
A
2
(See note 1)
Electromagnetic switch
Water
tank
Water supply source
M
Stop
Start
E1
E2
* (See note 2.)
E3
P
Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal 1 to terminal 11.
2. Be sure to ground terminal 4.
8
61F-GP-N@
■ Compact Plug-in Models (8-pin Type)
Specifications
Item
General-purpose
Controller
Long-distance
Controllers
High-sensitivity
Controllers
Low-sensitivity
Controller
Two-wire
Controller
61F-GP-N8
61F-GP-N8Y
(see note 4)
61F-GP-N8L 2KM
(for 2 km)
61F-GP-N8L 4KM
(for 4 km)
61F-GP-N8H
61F-GP-N8HY
(see note 4)
61F-GP-N8D
61F-GP-N8R
For control of liquids with high specific resistance
such as distilled
water
For control of liquids with low specific resistance
such as salt water,
sewage water, acid
chemicals, alkali
chemicals
Controlling mate- For control of ordi- For control of ordirials and operat- nary purified water nary purified water
ing conditions
or sewage water
in cases where the
distance between
sewage pumps and
water tanks or between receiver
tanks and supply
tanks is long or
where remote control is required.
Supply voltage
Variable
Sensitivity
Controller
61F-GP-N8-V50
For control of ordinary purified water
or sewage water
used in combination with Two-wire
Electrode Holder
(incorporating a resistor of 6.8 kΩ)
24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz
For control of cases
where variable sensitivity control is required such as
detection of froth on
the surface of a liquid, control of soil
moisture content,
or detection of degree of water pollution
24, 110, 220 or
240 VAC; 50/60 Hz
Operating voltage 85% to 110% of rated voltage
range
Interelectrode
voltage
8 VAC
24 VAC
8 VAC
24 VAC
Interelectrode
current
Approx. 1 mA AC max.
Approx.
0.4 mA AC max.
Approx. 1 mA AC max.
Approx. 3 mA AC
max.
Power consumption
Approx. 3.5 VA max.
Approx. 15 kΩ to
approx. 70 kΩ
(see note 3)
0 to approx. 1.3 kΩ 0 to approx. 2 kΩ
0 to 50 kΩ (Variable)
Approx. 300 k to
∞Ω
Approx. 4 k to ∞ Ω Approx. 15 k to ∞ Ω Operating resistance +50 kΩ max.
50 m max.
1 km max.
Interelectrode op- 0 to approx. 4 kΩ
erate resistance
0 to 1.3 kΩ (for
2 km)
0 to 0.5 kΩ (for
4 km)
Interelectrode re- Approx. 15 k to ∞ Ω 4 k to ∞ Ω
lease resistance
(for 2 km)
2.5 k to ∞ Ω
(for 4 km)
Response time
Operate: 80 ms max.
Release: 160 ms max.
Cable length
(see note 1)
1 km max.
Control output
1 A, 250 VAC (Inductive load: cosφ = 0.4)
3 A, 250 VAC (Resistive load)
2 km max.
4 km max.
800 m max.
50 m max.
Ambient tempera- Operating: –10 to 55°C
ture
Ambient humidity Operating: 45% to 85% RH
Insulation resistance
(see note 2)
100 MΩ min. (at 500 VDC)
Dielectric
strength
(see note 2)
2000 VAC, 50/60 Hz for 1 min.
Life expectancy
Electrical: 100,000 operations min.
Mechanical: 5,000,000 operations min.
Weight
Approx. 155 g
Accessories
Hold-down clip PFC-N8
Note: 1. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as
the cable diameter or number of conductors becomes larger.
2. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power terminals and contact terminals, and between Electrode terminals and contact terminals.
3. Possible to use with 15 kΩ or less, however, this may cause reset failure.
4. 61F-GP-N8H/-N8Y High-sensitivity Controllers use advanced operation.
When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the internal relay will not operate.
When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal
relay will operate.
If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation.
9
61F-GP-N@
Internal Circuit Diagrams
61F-GP-N8/-N8L/-N8D/-N8HY
Power supply
61F-GP-N8R
61F-GP-N8H
Power supply
Power supply
24 V
Control circuit
8 V (see note)
24 V
24 V Control circuit
Control circuit
8V
24 V
2
Note: 24 V for the 61F-GP-N8HY.
61F-GP-N8Y
61F-GP-N8-V50
Power supply
Power supply
24 V Control circuit
8V
24 V
Control circuit
24 V
3
4
2
10
61F-GP-N@
Automatic Water Supply and Drainage Control
Compact, Plug-in Type
61F-GP-N8
Dimensions:
page 14
Automatic Water Supply Control
Automatic Drainage Control
Connections
Connections
61F-GP-N8
Commercial Voltage
R S T
2
61F-GP-N8
Commercial Voltage
R S T
1
8
MCCB
7
2
0V
24 V
Control
circuit
U
Contactor
8V
24 V Control circuit U
Power
supply
U
3
7
U
8V
Power
supply
8
MCCB
U
0V
1
U
4
5
6
3
Contactor
(See note.)
4
5
6
(See
note.)
PS-3S
Stop
Motor
protection
relay
Water supply
source
Water
tank
E1
E3
M
E2
Start
Motor
protection
relay
PS-3S
Wastewater
tank
M
P
Start
E1
E3 E2
P
Stop
Reservoir
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
PF083A (Front-connecting)
PL08 (Rear-connecting)
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
PF083A (Front-connecting)
PL08 (Rear-connecting)
• Connect terminal 2 to the contactor’s coil terminal.
• Connect terminal 3 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of the
model.
Note: The power supply depends on the specifications of the
model.
Principles of Operation
Principles of Operation
Water
supply
P
Pump OFF
E1
Pump ON
E2
(Indicator ON)
Pump ON
(Indicator OFF)
Pump OFF
E3
E1
E2
E3
(Indicator ON)
(Indicator OFF)
P
Water drainage
The pump stops when the water level reaches E1 (indicator ON)
and starts when the water level drops below E2 (indicator OFF).
The pump starts when the water level reaches E1 (indicator ON)
and stops when the water level drops below E2 (indicator OFF).
11
61F-GP-N@
Two-Wire Connections
Automatic Water Supply and Drainage Control
Compact, Plug-in Type
61F-GP-N8R
Dimensions:
page 14
Water Supply
Automatic Drainage
Connections
Connections
Commercial Voltage
R S T
Commercial Voltage
R S T
61F-GP-N8R
2
MCCB
61F-GP-N8R
1
8
7
2
MCCB
1
8
U
U
8V
0V
Control
circuit
24 V
Control
circuit
24 V
Power
supply
U
U
3
A
8V
0V
Power
supply
7
4
5
3
6
4
5
6
A
(See note.)
Contactor
PS-3SR
(See
note.)
Contactor
R
Motor
protection
relay
Stop
Water
tank
Water supply
source
E3
M
E2
E1
Motor
protection
relay
Wastewater
tank
Start
E1
M
P
PS-3SR
R
P
E3
E2
Start
Stop
Reservoir
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
• Connect terminal 2 to the contactor’s coil terminal.
• Connect terminal 3 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of the
model.
• With 2-wire connections, only two wires are required between
the 61F-GP-N8R and Electrode Holder, but three wires are
required for the Electrodes.
• The Electrode Holder must be specified for 2-wire connections.
(Resistance R is built into Electrode Holders for 2-Wire
Connections.)
Note: The power supply depends on the specifications of the
model.
• With 2-wire connections, only two wires are required between
the 61F-GP-N8R and Electrode Holder, but three wires are
required for the Electrodes.
• The Electrode Holder must be specified for 2-wire connections.
(Resistance R is built into Electrode Holders for 2-Wire
Connections.)
Principles of Operation
Principles of Operation
Water
supply
P
Pump OFF
E1
Pump ON
E2
(Indicator ON)
(Indicator OFF)
E3
Pump ON
E1
Pump OFF
E2
E3
(Indicator ON)
(Indicator OFF)
P
Water drainage
The pump stops when the water level reaches E1 (indicator ON)
and starts when the water level drops below E2 (indicator OFF).
The pump starts when the water level reaches E1 (indicator ON)
and stops when the water level drops below E2 (indicator OFF).
12
61F-GP-N@
■ Connection with Three-phase Four-line Circuit
When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams.
Line voltage (R-S, S-T, or R-T):
380 or 415 VAC
Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC
61F-GP-N8@, 220 or 240 VAC
Power source
380 to 415 VAC
R S T N *
5
6
Control
circuit
U
3
24 V
8V
U
7
4
Transformer
1
8
2
A
*
Electromagnetic switch
Stop
Start
E1
Water tank
E2
Water supply source
M
E3
P
Note: Be sure to ground terminal 1.
13
61F-GP-N@
Dimensions
Note: All units are in millimeters unless otherwise indicated.
When mounting a Display Unit to a PF113A
Surface-mounting Socket, secure the PF113A with
the groove facing toward the bottom and then
connect the 61F-GP-N the PFC-N8 accessory.
61F-GP-N, -NT, -NL, -NH, -ND, -NR, -N -TDL, -N14, -N15, -NH3
PFC-N8
4
61F-GP-N
49.4
101
38
Approx.
80
70
84
83
PF113A
4.5
6
t = 0.3
Note: PFC-N8 Mounting Bracket (provided with
the Level Controller)
61F-GP-N8, -N8L, -N8H, -N8HY, -N8D, -N8R
Use a PFC-N8 Mounting Bracket to mount the
Level Controller to a PF083A Rail-mounted
Socket.
PFC-N8
4
49.4
61F-GP-N8
38
91
Approx.
80
70
84
83
PF083A
4.5
6
t=0.3
Note: PFC-N8 Mounting Bracket (provided with
the Level Controller)
■ Safety Precautions
Refer to Safety Precautions for All Level Controllers.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
14
Terms and Conditions of Sale
1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed
part of all quotes, agreements, purchase orders, acknowledgments, price lists,
catalogs, manuals, brochures and other documents, whether electronic or in
writing, relating to the sale of products or services (collectively, the "Products")
by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron
objects to any terms or conditions proposed in Buyer’s purchase order or other
documents which are inconsistent with, or in addition to, these Terms.
2. Prices; Payment Terms. All prices stated are current, subject to change without notice by Omron. Omron reserves the right to increase or decrease prices
on any unshipped portions of outstanding orders. Payments for Products are
due net 30 days unless otherwise stated in the invoice.
3. Discounts. Cash discounts, if any, will apply only on the net amount of invoices
sent to Buyer after deducting transportation charges, taxes and duties, and will
be allowed only if (i) the invoice is paid according to Omron’s payment terms
and (ii) Buyer has no past due amounts.
4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or
the maximum legal rate, whichever is less, on any balance not paid within the
stated terms.
5. Orders. Omron will accept no order less than $200 net billing.
6. Governmental Approvals. Buyer shall be responsible for, and shall bear all
costs involved in, obtaining any government approvals required for the importation or sale of the Products.
7. Taxes. All taxes, duties and other governmental charges (other than general
real property and income taxes), including any interest or penalties thereon,
imposed directly or indirectly on Omron or required to be collected directly or
indirectly by Omron for the manufacture, production, sale, delivery, importation, consumption or use of the Products sold hereunder (including customs
duties and sales, excise, use, turnover and license taxes) shall be charged to
and remitted by Buyer to Omron.
8. Financial. If the financial position of Buyer at any time becomes unsatisfactory
to Omron, Omron reserves the right to stop shipments or require satisfactory
security or payment in advance. If Buyer fails to make payment or otherwise
comply with these Terms or any related agreement, Omron may (without liability and in addition to other remedies) cancel any unshipped portion of Products sold hereunder and stop any Products in transit until Buyer pays all
amounts, including amounts payable hereunder, whether or not then due,
which are owing to it by Buyer. Buyer shall in any event remain liable for all
unpaid accounts.
9. Cancellation; Etc. Orders are not subject to rescheduling or cancellation
unless Buyer indemnifies Omron against all related costs or expenses.
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery
resulting from causes beyond its control, including earthquakes, fires, floods,
strikes or other labor disputes, shortage of labor or materials, accidents to
machinery, acts of sabotage, riots, delay in or lack of transportation or the
requirements of any government authority.
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:
a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship
except in “break down” situations.
b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall
constitute delivery to Buyer;
c. All sales and shipments of Products shall be FOB shipping point (unless otherwise stated in writing by Omron), at which point title and risk of loss shall
pass from Omron to Buyer; provided that Omron shall retain a security interest in the Products until the full purchase price is paid;
d. Delivery and shipping dates are estimates only; and
e. Omron will package Products as it deems proper for protection against normal handling and extra charges apply to special conditions.
12. Claims. Any claim by Buyer against Omron for shortage or damage to the
Products occurring before delivery to the carrier must be presented in writing
to Omron within 30 days of receipt of shipment and include the original transportation bill signed by the carrier noting that the carrier received the Products
from Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the
Products will be free from defects in materials and workmanship for a period of
twelve months from the date of sale by Omron (or such other period expressed
in writing by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
14.
15.
16.
17.
18.
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. Omron further disclaims all warranties and responsibility of
any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form
originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying
Product, or (iii) repay or credit Buyer an amount equal to the purchase price of
the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding
the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the
use of Products in combination with any electrical or electronic components,
circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing,
are not to be construed as an amendment or addition to the above warranty.
See http://www.omron247.com or contact your Omron representative for published information.
Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual
price of the Product on which liability is asserted.
Indemnities. Buyer shall indemnify and hold harmless Omron Companies and
their employees from and against all liabilities, losses, claims, costs and
expenses (including attorney's fees and expenses) related to any claim, investigation, litigation or proceeding (whether or not Omron is a party) which arises
or is alleged to arise from Buyer's acts or omissions under these Terms or in
any way with respect to the Products. Without limiting the foregoing, Buyer (at
its own expense) shall indemnify and hold harmless Omron and defend or settle any action brought against such Companies to the extent based on a claim
that any Product made to Buyer specifications infringed intellectual property
rights of another party.
Property; Confidentiality. Any intellectual property in the Products is the exclusive property of Omron Companies and Buyer shall not attempt to duplicate it
in any way without the written permission of Omron. Notwithstanding any
charges to Buyer for engineering or tooling, all engineering and tooling shall
remain the exclusive property of Omron. All information and materials supplied
by Omron to Buyer relating to the Products are confidential and proprietary,
and Buyer shall limit distribution thereof to its trusted employees and strictly
prevent disclosure to any third party.
Export Controls. Buyer shall comply with all applicable laws, regulations and
licenses regarding (i) export of products or information; (iii) sale of products to
“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of
regulated technology or information.
Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right
and no course of dealing between Buyer and Omron shall operate as a waiver
of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder
without Omron's written consent. (c) Law. These Terms are governed by the
law of the jurisdiction of the home office of the Omron company from which
Buyer is purchasing the Products (without regard to conflict of law principles). (d) Amendment. These Terms constitute the entire agreement between
Buyer and Omron relating to the Products, and no provision may be changed
or waived unless in writing signed by the parties. (e) Severability. If any provision hereof is rendered ineffective or invalid, such provision shall not invalidate
any other provision. (f) Setoff. Buyer shall have no right to set off any amounts
against the amount owing in respect of this invoice. (g) Definitions. As used
herein, “including” means “including without limitation”; and “Omron Companies” (or similar words) mean Omron Corporation and any direct or indirect
subsidiary or affiliate thereof.
Certain Precautions on Specifications and Use
1. Suitability of Use. Omron Companies shall not be responsible for conformity
with any standards, codes or regulations which apply to the combination of the
Product in the Buyer’s application or use of the Product. At Buyer’s request,
Omron will provide applicable third party certification documents identifying
ratings and limitations of use which apply to the Product. This information by
itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application
or use. Buyer shall be solely responsible for determining appropriateness of
the particular Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases but the following is a
non-exhaustive list of applications for which particular attention must be given:
(i) Outdoor use, uses involving potential chemical contamination or electrical
interference, or conditions or uses not described in this document.
(ii) Use in consumer products or any use in significant quantities.
(iii) Energy control systems, combustion systems, railroad systems, aviation
systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
(iv) Systems, machines and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to this Product.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
2.
3.
4.
5.
ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products. Omron Companies shall not be responsible for the
user’s programming of a programmable Product, or any consequence thereof.
Performance Data. Data presented in Omron Company websites, catalogs
and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s
test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations
of Liability.
Change in Specifications. Product specifications and accessories may be
changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed,
or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for
your application. Please consult with your Omron’s representative at any time
to confirm actual specifications of purchased Product.
Errors and Omissions. Information presented by Omron Companies has been
checked and is believed to be accurate; however, no responsibility is assumed
for clerical, typographical or proofreading errors or omissions.
OMRON AUTOMATION AND SAFETY • THE AMERICAS HEADQUARTERS • Hoffman Estates, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com
OMRON CANADA, INC. • HEAD OFFICE
Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron247.com
OMRON ARGENTINA • SALES OFFICE
Cono Sur • 54.11.4783.5300
OMRON ELECTRONICS DE MEXICO • HEAD OFFICE
México DF • 52.55.59.01.43.00 • 01-800-226-6766 • mela@omron.com
OMRON CHILE • SALES OFFICE
Santiago • 56.9.9917.3920
OMRON ELECTRONICS DE MEXICO • SALES OFFICE
Apodaca, N.L. • 52.81.11.56.99.20 • 01-800-226-6766 • mela@omron.com
OTHER OMRON LATIN AMERICA SALES
54.11.4783.5300
OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE
São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br
OMRON EUROPE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • +31 (0) 23 568 13 00 • www.industrial.omron.eu
Authorized Distributor:
Automation Control Systems
• Machine Automation Controllers (MAC) • Programmable Controllers (PLC)
• Operator interfaces (HMI) • Distributed I/O • Software
Drives & Motion Controls
• Servo & AC Drives • Motion Controllers & Encoders
Temperature & Process Controllers
• Single and Multi-loop Controllers
Sensors & Vision
• Proximity Sensors • Photoelectric Sensors • Fiber-Optic Sensors
• Amplified Photomicrosensors • Measurement Sensors
• Ultrasonic Sensors • Vision Sensors
Industrial Components
• RFID/Code Readers • Relays • Pushbuttons & Indicators
• Limit and Basic Switches • Timers • Counters • Metering Devices
• Power Supplies
Safety
• Laser Scanners • Safety Mats • Edges and Bumpers • Programmable Safety
Controllers • Light Curtains • Safety Relays • Safety Interlock Switches
Cat. No. N42I-E-01
Note: Specifications are subject to change.
Printed on recycled paper.
© 2014 Omron Electronics LLC