IPK BC TNC 350 (/FM)

advertisement
Lightning and Surge Protection
IsoPro Kompact BC
IPK BC TNC 350 (/FM)
IPK BC TNS 350 (/FM)
Combined 3-pole – (TNC net) resp. 4-pole (TNS net) lightning current and surge arrester
meeting the requirements of SPD type 1+2 (BC); IEC: SPD class I+II, acc. to IEC 62305 part 1
For equipotential bonding lightning protection in TNC- or TNS-Power Net Systems
IPK BC TNC 350
•
•
•
•
•
•
•
•
•
IPK BC TNS 350
Leakage current free lightning current and surge protective device (SPD)
Based on hermetically sealed inert gas filled ceramic GDT-spark-gaps
No blow-out type, no safety distances necessary for installation
Voltage Protection level ≤ 2,5 kV at Iimp
Highly TOV resistant
Lightning impulse current of 100 kA
High insulation resistance Risol > 10 GΩ
Function monitoring by potential-free remote signal contact (/FM..optional)
Visual monitoring by 2-stage LED indication
Product description
IPK BC TNC 350 (/FM) is a 3-pole lightning current surge arrester for the protection of unstable TNC-Power
Net Systems and IPK BC TNS 350 (/FM) is a 4-pole lightning current surge arrester for the protection of
unstable TNC-Power Net Systems with high TOV risk.
These combined devices with a 2-stage protection of class I and class II SPD. It contains in the class I stage a
hermetical sealed heavy-duty isolating spark-gap, filled with inert gas. The class II stage contains a high
performance MOV + GDT in serial connection.It has a selective function and is a redundant execution.
This makes dangerous blow-out vents unnecessary. This also saves you from keeping the safety distance to
adjoining electrical components usually necessary to avoid unwanted electric arcs. There is no risk of leakage
current which could corrode grounding system!
The protective circuit is installed in an easy-to-handle compact housing of only 88mm (5 DIN modules, each
17,5 – 18mm) with fixable snap-on clips for mounting on 35 mm form C DIN rail. Large size screw terminals for
wire connections up to 50mm² for optimal ground connection.
There is optional available a built in potential-free thermal sensor with NC remote signal contact (FM).
Application
The IPK devices for TT net are usually installed in main-distribution panels, at the boundary LPZ 0B-1 or higher,
according to the lightning zones concept of IEC EN 62305:2006-10 part 1-4 (DIN EN 62305:10.2006,Teil 1-4;
VDE 0185-305:2006-10, Teil 1-4)
Protects People and Valuables
Technical Data:
Type
Order / Part. No.:
Application
IPK BC TNC 350
IPK BC TNC 350 /FM
38 54 80
38 54 90
for three phases (L1, L2, L3 –PE)
with potential-free remote signal contact
IPK BC TNS 350
IPK BC TNS 350/FM
38 55 00
38 55 10
for three phases and neutral (L1, L2, L3, N – PE)
with potential-free remote signal contact
SPD class I+II
SPD Type T1 + T2
(BC)
IEC 61643-1
EN 61643-11
E DIN VDE 0675-6 11/98-A1
Nominal power supply voltage 50/60 Hz
Rated voltage
(max. continuous operating voltage) 50/60 Hz
Voltage protection level at 100 % lightning impulse spark
over voltage (1,2/50 µs)
Voltage protection level at Iimp (8/80µs) / at 5kA 8/20µs
Insulation resistance
Response time
Lightning impulse current Iimp (10x 8/80 µs)
Un
[V]
230 / 400
Uc
[V]
350
UP
[kV]
≤ 1,5
UP
[kV]
≤ 2,5 / ≤ 2
Risol
[GΩ]
> 10
tA
[ns]
Ipeak
Q
W/R
[kA]
[As]
[kJ/Ω]
< 50
TNC
TNS
75kA (15kA 10/350 µs)
10
5x 10
100kA (20kA 10/350 µs)
10
5x 10
[A]
160 A gL/gG
[°C]
-40 … +85
Max. cross-sectional area
[mm²]
stranded 50 / flexible 35
Recommended cross sectional area
[mm²]
25
Recommended connection torque
[Nm]
4,5
Max. cross-sectional area for
remote signal contact terminal
[mm²]
1,5
Max. permissible line resp. backup fuse F2
Operating temperature range
T
250V / 0,5A
Max. switching capacity of remote signal contact
Keripol / yellow-grey Noril SE100
Material of housing / colour
IP 20
Ambient protection category (IEC/EN 60529)
35mm DIN rail form C (DIN/EN 50 022)
Mounting on
Dimensions in mm / Diagram
IPK BC TNS 350 /FM
IPK BC TNC 350 /FM
Dimension acc. DIN 43880:
5 DIN modules (á 17,50) =
88mm
IPK BC TNC-TNS 350
09.03.2009 .pdf
© 2009 by LEUTRON GmbH
Subject to technical modifications and delivery
possible
LEUTRON GmbH
Lightning and Surge Protection
Humboldtstraße 30-32
D-70771 Leinfelden-Echterdingen
GERMANY
Phone
Fax
Email:
+49 711 / 9 47 71-0
+49 711 / 9 47 71-70
info@leutron.de
www.leutron.de