Lightning and Surge Protection IsoPro Kompact BC IPK BC TNC 350 (/FM) IPK BC TNS 350 (/FM) Combined 3-pole – (TNC net) resp. 4-pole (TNS net) lightning current and surge arrester meeting the requirements of SPD type 1+2 (BC); IEC: SPD class I+II, acc. to IEC 62305 part 1 For equipotential bonding lightning protection in TNC- or TNS-Power Net Systems IPK BC TNC 350 • • • • • • • • • IPK BC TNS 350 Leakage current free lightning current and surge protective device (SPD) Based on hermetically sealed inert gas filled ceramic GDT-spark-gaps No blow-out type, no safety distances necessary for installation Voltage Protection level ≤ 2,5 kV at Iimp Highly TOV resistant Lightning impulse current of 100 kA High insulation resistance Risol > 10 GΩ Function monitoring by potential-free remote signal contact (/FM..optional) Visual monitoring by 2-stage LED indication Product description IPK BC TNC 350 (/FM) is a 3-pole lightning current surge arrester for the protection of unstable TNC-Power Net Systems and IPK BC TNS 350 (/FM) is a 4-pole lightning current surge arrester for the protection of unstable TNC-Power Net Systems with high TOV risk. These combined devices with a 2-stage protection of class I and class II SPD. It contains in the class I stage a hermetical sealed heavy-duty isolating spark-gap, filled with inert gas. The class II stage contains a high performance MOV + GDT in serial connection.It has a selective function and is a redundant execution. This makes dangerous blow-out vents unnecessary. This also saves you from keeping the safety distance to adjoining electrical components usually necessary to avoid unwanted electric arcs. There is no risk of leakage current which could corrode grounding system! The protective circuit is installed in an easy-to-handle compact housing of only 88mm (5 DIN modules, each 17,5 – 18mm) with fixable snap-on clips for mounting on 35 mm form C DIN rail. Large size screw terminals for wire connections up to 50mm² for optimal ground connection. There is optional available a built in potential-free thermal sensor with NC remote signal contact (FM). Application The IPK devices for TT net are usually installed in main-distribution panels, at the boundary LPZ 0B-1 or higher, according to the lightning zones concept of IEC EN 62305:2006-10 part 1-4 (DIN EN 62305:10.2006,Teil 1-4; VDE 0185-305:2006-10, Teil 1-4) Protects People and Valuables Technical Data: Type Order / Part. No.: Application IPK BC TNC 350 IPK BC TNC 350 /FM 38 54 80 38 54 90 for three phases (L1, L2, L3 –PE) with potential-free remote signal contact IPK BC TNS 350 IPK BC TNS 350/FM 38 55 00 38 55 10 for three phases and neutral (L1, L2, L3, N – PE) with potential-free remote signal contact SPD class I+II SPD Type T1 + T2 (BC) IEC 61643-1 EN 61643-11 E DIN VDE 0675-6 11/98-A1 Nominal power supply voltage 50/60 Hz Rated voltage (max. continuous operating voltage) 50/60 Hz Voltage protection level at 100 % lightning impulse spark over voltage (1,2/50 µs) Voltage protection level at Iimp (8/80µs) / at 5kA 8/20µs Insulation resistance Response time Lightning impulse current Iimp (10x 8/80 µs) Un [V] 230 / 400 Uc [V] 350 UP [kV] ≤ 1,5 UP [kV] ≤ 2,5 / ≤ 2 Risol [GΩ] > 10 tA [ns] Ipeak Q W/R [kA] [As] [kJ/Ω] < 50 TNC TNS 75kA (15kA 10/350 µs) 10 5x 10 100kA (20kA 10/350 µs) 10 5x 10 [A] 160 A gL/gG [°C] -40 … +85 Max. cross-sectional area [mm²] stranded 50 / flexible 35 Recommended cross sectional area [mm²] 25 Recommended connection torque [Nm] 4,5 Max. cross-sectional area for remote signal contact terminal [mm²] 1,5 Max. permissible line resp. backup fuse F2 Operating temperature range T 250V / 0,5A Max. switching capacity of remote signal contact Keripol / yellow-grey Noril SE100 Material of housing / colour IP 20 Ambient protection category (IEC/EN 60529) 35mm DIN rail form C (DIN/EN 50 022) Mounting on Dimensions in mm / Diagram IPK BC TNS 350 /FM IPK BC TNC 350 /FM Dimension acc. DIN 43880: 5 DIN modules (á 17,50) = 88mm IPK BC TNC-TNS 350 09.03.2009 .pdf © 2009 by LEUTRON GmbH Subject to technical modifications and delivery possible LEUTRON GmbH Lightning and Surge Protection Humboldtstraße 30-32 D-70771 Leinfelden-Echterdingen GERMANY Phone Fax Email: +49 711 / 9 47 71-0 +49 711 / 9 47 71-70 info@leutron.de www.leutron.de