What is in the OBC SB-10 Update? Ontario Gets Serious about Energy Use in New Buildings 1 What is in the OBC SB-10 Update? Ontario Gets Serious about Energy Use in New Buildings Steve Kemp P.Eng., M.A.Sc., B.Sc., B.Eng. 2 Introduction OBC Introduced SB-10 in 2007 Prescribed minimum energy performance MNECB + ASHRAE 90.1-2004 Update published in July 2011, effective Jan 2012 Update is implementation of ASHRAE 90.1-2010 + ASHRAE 189.1-2009 envelope values Three methods of compliance Performance Prescriptive + envelope trade-off Prescriptive Today will focus on prescriptive path 3 Agenda What does the code say SB-10 Division 3 Enclosures requirements Common constructions that may no longer be compliant How to “fix” them Mechanical/Electrical requirements SB-10 Division 4: Part 9 Non-Residential Enclosure requirements Mechanical/Electrical requirements Compliance paths Closing remarks 4 Documents involved in the Code OBC 2006 Supplementary Standard SB-10, July 1, 2010 Update 5 http://www.mah.gov.on.ca/P age9528.aspx http://www.mah.gov.on.ca/A ssetFactory.aspx?did=9227 Documents involved in the Code ASHRAE 90.1-2010 (and User’s Manual) ASHRAE 189.1-2009 (and User’s Manual) 6 http://www.techstreet.com/ ashraegate.html Documents involved in the Code MNECB 1997 http://www.nrccnrc.gc.ca/eng/ibp/irc/codes /97-energy-codebuildings.html FYI: NECB-2011 is now published (not currently a part of OBC) 7 SB-10 July 2011 Division 1: General Energy Efficiency after December 31, 2011 Division 3: All buildings to conform to of SB-10 July 2011 update Except when within the scope of Division B Part 9 then, Division 4 of SB 10: if the building is within the scope of Part 9 Div B of the OBC and, does not contain a residential occupancy, and does not use electric space heating, and, is intended for occupancy on a continuing basis during the winter months i.e. most Non-Residential Part 9 buildings 8 i.e. all non Part 9 buildings SB-10 Division 3 1.1.2 Energy Efficiency Three paths to demonstrate performance Building shall use Exceptions 9 25% less energy than MNECB – Energy Modeling 5 % less energy than ASHRAE 90.1-2010 – Energy Modeling Not exceed ASHRAE 90.1-2010 and Chapter 2 (which replaces the 90.1enclosure performance values) – Energy Modeling or Prescriptive Heritage buildings Any building space which uses less than 12 W/m² peak energy Temporary structures Warehouses and storage rooms with design temperature under 10°C Primarily intended for manufacturing processing, commercial processing or industrial processing And other exceptions… SB-10 Div 3: Examples of Exemptions 10 OBC Compliance Paths Today’s Focus OBC Compliance 90.1 Prescriptive + Chapter 2 90.1-2010 + Chapter 2 90.1 + Chapter 2 Mandatories 25% Less than MNECB MNECB Mandatories Energy Modeling against MNECB prescriptive 90.1 Mandatories Energy modeling against 90.1 prescriptive 5% Less than 90.1 2010 11 Energy modeling against 90.1 + Chapter 2 prescriptive Today’s Presentation of Materials for Division 3 Largely will follow 90.12010 organization Will note SB-10 revisions (hint mostly in envelope) Today’s emphasis is on envelope Some attention paid to mechanical / electrical 12 ASHRAE 90.1-2010 / SB-10 Prescriptive Path Outlines minimum performance parameters for: Wall, Roofs, Windows elements etc. 13 Prescriptive and performance paths for insulation Weighted U-value allowed for some trade-offs within element type Envelope Trade-off calculations required for trade-offs across element types Maximum fenestration-to-wall ratio 40% Installed lighting power density Receptacle requirements Labeling (insulation, fenestration) HVAC plant minimum performance requirements (boilers, chillers) HVAC distribution performance requirements (fans, pumps) etc Division 3 Chapter 2 Enforces ASHRAE 90.1 2010 as minimum energy code for OBC Provides revisions to 90.1-2010 14 Section 1 “Purpose” Section 2 “Scope” Section 3 “Definitions” Section 4 “Administration and Enforcement” Section 5 “Building Envelope” Section 6 “HVAC” Section 7 “Service Hot Water” Section 10 “Other Equipment” (electric motors) 90.1-2010 Section 1 Purpose: To establish minimum energy efficiency requirements of buildings other than low-rise residential Note: ASHRAE is rebranding, not just HVAC&R anymore 15 90.1 Adoption as Building Code Most widely adopted building energy standard in North America British Columbia Vancouver 90.1-2004 90.1-2007 Ontario 16 90.1-2010 + 189.1-2009 envelope 90.1 History of Energy Improvements 17 Energy Use of All Buildings – By Age of Construction Zero energy buildings by year 3300 Total Energy Intensity (ekWh/m²) 500 400 300 200 100 0 Before 1920 1920-1959 1960-1969 1970-1979 1980-1989 Year building was contructed 1990-1999 2000-2004 Ref: Commercial and Institutional Building Energy Use, NRCAN 2005 18 90.1-2010 Section 2 Scope Establishes Energy Efficiency requirements for: New Buildings and their systems New portions of buildings and their systems New systems and equipment in existing buildings! New equipment or building systems specifically identified in the standard that are a part of industrial or manufacturing processes Establishes Criteria for identifying compliance! OBC largely silent regarding details of this, look to your local code official! – more on this in end of session discussion Does not apply to: Single family homes, multi family buildings under 3 stories, manufactures homes, or buildings that do not connect to utilities 19 SB-10 does not enforce any requirement for existing buildings Part 11 currently does not enforce any energy requirements for renovations Note: non-grid connected buildings have other reasons to greatly exceed this code! 90.1-2010 Section 3 Definitions, Abbreviations and Acronyms OK sounds boring… BUT How to interpret RATED R-VALUE How to interpret SPANDREL How to interpret METAL ROOF How to interpret ADOPTING AUTHORITY How to interpret BASELINE BUILDING DESIGN How to interpret ATTIC ROOF How to interpret SKYLIGHT How to interpret FENESTRATION AREA How to interpret F-FACTOR, U-FACTOR, C-FACTOR How to interpret CONTINUOUS INSULATION! AND LOTS OF OTHER STUFF! Read this section! (hint spandrel, U-factor, Continuous Insulation) 20 FYI: Spandrel sucks! 90.1-2010 Section 4 Administration and Enforcement 21 Interpretations, claims of exemption and rights of appear are specified by the authority having jurisdiction Conflict with other laws, codes etc, to be determined by authority having jurisdiction Normative Appendices are considered a part of the standard 90.1 Section 5 90.1 Requirements SB-10 Revisions 22 90.1 – Air Barriers / Vestibules 5.4.3.1 Continuous Air Barrier Clearly identified or otherwise noted on construction documents for each assembly The joints, interconnections and penetrations shall be detailed or otherwise noted 5.4.3.1.A. Air Barrier Materials, Assemblies and Systems 23 (1) The air barrier materials, assemblies and systems that are in conformance with Part 5 of Division B of the Building Code shall be deemed to be in compliance with Sentence 5.4.3.1.3 and Sentence 5.4.3.2. 5.4.3.4 Shall have vestibules, exceptions: Building entrances with revolving doors Doors not intended to be a building entrance Doors opening directly from a dwelling unit Building is less than 90 m² Doors separate from the building entrance that open unto a space under 280 m² Division 3 Chapter 2 Revision Mandatories insulation details introduced from MNECB 1997 24 Div 3 Ch 2 Revision to 90.1 – Slab Insulation 5.5.3.5.1 Slabs. Insulation continuity shall be maintained in the design of slab edge insulation systems. Continuity shall be maintained from the wall insulation through the slab/wall/footing intersection to the body of the slab edge insulation. Several representative configurations are illustrated in Figure 5-1 25 Div 3 Ch 2 Revision to 90.1 – Insulation Continuity 5.5.3.5.2 Where insulative continuity is impossible because of structural constraints, a minimum overlapping of insulation is acceptable. The insulation must overlap by a distance equal to (or greater than) four times the minimum insulation separation, as shown in Figure 5-2. 26 Div 3 Ch 2 Revision to 90.1 – Thermal Bridging 5.5.3.7 For the purposes of Section 5, the effects of thermal bridging are waived for: 27 intermediate structural connections of continuous steel shelf angles (or similar structural element) used to support the building facade provided there is a thermal break between the remaining contact surface of the supporting element and the building structure. This provision is intended to substantially reduce thermal bridging effects caused by the continuous bearing between structural elements supporting building facade and the building frame (ie. steel shelf angle attached to perimeter floor slab to support brick veneer), or structural connections of load bearing elements where a thermal break cannot be achieved Div 3 Ch 2 Revision to 90.1 – Thermal Bridging 5.5.3.8 In addition to the exceptions permitted above, the effects of thermal bridging are also waived for: a) 28 exposed structural projections of buildings where the total crosssectional area of the exposed element does not exceed 2% of the exterior building envelope area and the cross-sectional area of the exposed structural element is measured where it penetrates the insulation component of the building envelope. (For example, if the total cross-sectional area of cantilevered concrete balconies and other projections penetrating the insulation component of the building envelope does not exceed 2% of the exterior building envelope area, their thermal bridging effects need not be taken into account) Div 3 Ch 2 Revision to 90.1 – Thermal Bridging Cont’d 5.5.3.8 In addition to the exceptions permitted above, the effects of thermal bridging are also waived for: b) c) d) 29 ties in masonry construction, flashing, and top exposed portion of foundation walls provided the exposure does not exceed 200 mm measured from the top of the foundation wall to the top of exterior wall insulation which meets the minimum insulation RSI-Value for wall below grade stipulated in the appropriate Tables. (See Figure 5-3) 90.1 Section 5 Building Envelope Climate Definitions Many prescriptive requirements depend on climate ASHRAE Climate Zones: 1 thru 8 Modifier (HVAC): Ontario climates are: 30 A – Moist B – Dry C – Marine 5 thru 7 all A – moist 90.1 Section 5 Building Envelope Climate Definitions (SB-10 revision highlight) If space is electrically heated, then ALWAYS use Zone 7 31 90.1 Chapter 5 Building Envelope Climate Requirements (SB-10 revision highlight) Climate Zone 5: Brantford Mississauga Hamilton Sarnia Windsor Climate Zone 6: 32 Kitchener/Waterloo Toronto Kingston Ottawa Climate Zone 7: Cochrane North Bay Sudbury Thunder Bay Northern Ontario! 90.1 Chapter 5 Space Conditioning Categories 90.1 Section 5.5 Comply with Tables (SB5.5-5 thru -7) Minimum RATED R-values of insulation Maximum U-Factor, CFactor or F-Factor Appendix A tables Appendix A9 calculations 33 2-D calculations (e.g. Therm) 90.1 Chapter 5 How to Use Envelope Tables Determine envelope category Roof Mass Metal Building Steel-framed Wood-framed & other Etc. Determine space conditioning category Insulation above deck Metal Building Attic & other Walls above grade Determine Climate Zone 5, 6 or 7 Today’s examples will be: 34 Non-Residential Residential Semi-heated Climate Zone 6 Non-Residential 90.1 Chapter 5 – Roof Requirements (SB-10 revisions) Roofs: Metal Building: a roof that: 35 is constructed with a metal, structural, weathering surface has no ventilated cavity, and has the insulation entirely below “deck” 90.1 Chapter 5 – Roof Requirements (SB-10 revisions) ci (continuous insulation): Insulation that is continuous across all structural members without thermal bridges other than fasteners and service openings. It is installed on the interior or exterior or is integral to any opaque surface of the building envelope 36 ASHRAE Appendix A Assembly U-Factors for Roofs with Insulation Above Deck 37 ASHRAE Appendix A Assembly U-Factors for Metal Roofs 38 ASHRAE Appendix A Assembly U-Factors for Wood Joists, Single Rafter Roof 39 ASHRAE 90.1 Appendix A Roof Assembly U-Factors Available Tables: 40 A2.2 A2.3 A2.4 A2.4.2 A2.5 Roofs with Insulation Entirely Above Deck Metal Building Roofs Attic Roofs with Wood Joists Single Rafter Roofs Attic Roofs with Steel Joists 90.1 Section 5 – Above Grade Wall Requirements (SB-10 revisions) Steel Framed Wall: Includes curtain-wall / window-wall spandrel panel 41 42 ASHRAE Appendix A Above-Grade Concrete Walls & Masonry Walls No Listed Concrete or Masonry wall with continuous metal framing can meet code. 43 ASHRAE Appendix A Above-Grade Concrete Walls & Masonry Walls 44 ASHRAE Appendix A Above-Grade Concrete Walls & Masonry Walls 45 ASHRAE Appendix A Metal Building Walls 46 ASHRAE Appendix A Steel-Frame Walls 47 ASHRAE Appendix A Wall Assembly UFactors Available Tables: A3.1A 48 Above-Grade Concrete Walls and Masonry Walls A3.1B U-Factors, C-Factors, Ru, Rc and HC for Concrete A3.1C U-Factors, C-Factors, Ru, Rc and HC for Concrete Block Walls A3.1D Effective R-Values for Insulation/Framing Layers Added to Above/Below Grade Mass Wall A3.2 A3.3 A3.4 Metal Building Walls Steel-Frame Walls Wood-Frame Walls Metal Cladding with Z-Girts 49 13 mm drywall 102 mm steel stud @ 400 mm oc 13 mm exterior sheathing 102 mm z-girt @ 600 mm oc with semirigid Metal siding Metal Cladding with Z-Girts Nominal R-15 Actual R-8.6 50 OBC Requirement: U-0.055 BTU/hr-ft²-°F Assembly: U-0.116 BTU/hr-ft²-°F Metal Cladding with Orthogonal Z-Girts and Spray Foam 51 13 mm drywall 102 mm steel stud @ 400 mm oc 13 mm exterior sheathing 51 mm z-girt @ 600 mm oc with spray foam 51 mm z-girt @ 600 mm oc with spray foam Metal siding Metal Cladding with X Z-Girts and Spray Foam Nominal R-24 Actual R-21 52 OBC Requirement: U-0.055 BTU/hr-ft²-°F Assembly: U-0.048 BTU/hr-ft²-°F Spandrel ?? Nominal R-14 Actual R-4.0 53 OBC Requirement: U-0.055 BTU/hr-ft²-°F Assembly: U-0.250 BTU/hr-ft²-°F Spandrel will be challenging (condensation?) With 1” XPS interior insulation Nominal R-19 Actual R-9.1 OBC Requirement: U-0.055 BTU/hr-ft²-°F Assembly: U-0.11 BTU/hr-ft²-°F With 2” XPS interior insulation Nominal R-24 Actual R-14.2 OBC Requirement: U-0.055 BTU/hr-ft²-°F Assembly: U-0.070 BTU/hr-ft²-°F 54 Spandrel – 3D Results (ASHRAE RP-1365 by Morrison Hershfield) 55 Spandrel – 3D Results (ASHRAE RP-1365 by Morrison Hershfield) 56 90.1 Section 5 – Below Grade and Floor Requirements (SB-10 revisions) 57 ASHRAE Appendix A Slab on Grade Floors 58 90.1 Section 5 – Maximum Fenestration Area 5.5.4.2.1 Vertical Fenestration Area 59 The total vertical fenestration area shall be less than 40% of the gross wall area Perhaps this is the reason why? R3 R2 Modern R4 Old 60 Glass and the Walls they’re in… - John Straube 61 Windows in the Whole Building Daylighting Study by: Athanassios Tzempelikos (Concordia) 35% Fenestration to Wall ratio yields 90% of the daylight as 100% FWR Courtesy: Athanassios Tzempelikos 62 Windows in the Whole Building - Energy Curtainwall – Vancouver City Library 63 LBNL Building Design Advisor And that’s just the recent information! R. Sullivan, E.S. Lee, S. Selkowitz, LBNL 64 “A Method of Optimizing Solar Control and Daylighting Performance in Commercial Office Buildings” September 1992 Further back in history… Johnson C A. Besant R W., Schoenau G J., University of Saskatchewan 65 “Economic preferred window orientation and optimum fenestration design of a non-daylit and daylit large office building for different climatic conditions and different billing structures” - 1986 Best LCC (not energy) in Saskatoon… No Windows! No low-e or Argon back then Other locals 10-15% FWR 90.1 Section 5 – Fenestration Requirements (SB-10 revisions) 66 Window heat loss Flanking (and installation) Frame Edge of Glass Centre of Glass 67 Curtain Wall Plan View glazing system U-value 90.1 Section 5 – Determining Fenestration Performance 5.8.2 Vertical Fenestration U-Factors & SHGC shall be determined in accordance with: 68 Standard NRFC 100 or CSA-A440.2 or 90.1-2010 Table A8.2 – not recommended! 90.1 Section 5 – Determining Fenestration Performance 69 90.1 Section 5 – Determining Fenestration Performance FramePlus Online for project estimating Need supplier CSA/NFRC rating for code compliance http://tools.enermodal.com /webframeplus http://cmast.nfrc.org 70 FramePlus Online Curtain-Wall Performance Curtain Wall System U-values [BTU/ft²-hr-°F] 0.50 Fenestration System U-value 0.45 0.40 Climate Zone 5 & 6 0.35 0.30 Climate Zone 7 0.25 0.20 Dbl SB60 Argon 0.15 Tpl SB60 Argon 0.10 0.05 0.00 0 71 2 4 6 8 10 12 14 Curtain Wall Frame Thermal Break Size in mm 16 18 20 FramePlus Online Punched Alum Window Performance Punched Aluminum Window U-values [BTU/ft²-hr-°F] 0.50 Climate Zone 5 & 6 Fenestration System U-value 0.45 0.40 Climate Zone 7 0.35 0.30 0.25 0.20 Dbl SB60 Argon 0.15 Tpl SB60 Argon 0.10 0.05 0.00 0 2 4 6 8 10 12 14 Aluminum Frame Thermal Break Size in mm 72 16 18 20 FramePlus Online Casement/Awning Alum Window Performance Casement/Awning Aluminum Window U-values [BTU/ft²-hr-°F] Fenestration System U-value 0.60 0.50 Climate Zone 5 & 6 0.40 Climate Zone 7 0.30 Dbl SB60 Argon 0.20 Tpl SB60 Argon 0.10 0.00 0 1 2 3 4 5 6 7 Aluminum Frame Thermal Break Size in mm 73 8 9 10 90.1 Section 5 Limits of Prescriptive Compliance Prescriptive Compliance with 90.1-2010/SB-10 Prescriptive Building Envelope Option, provided that, 74 the vertical fenestration area is 40% or less of gross wall area for each space-conditioning category and the skylight fenestration area 5% or less of gross roof area for each space-conditioning category U/C/F-Factor area weighted trade-off 90.1 Section 5 Minimum Skylight Area 5.5.4.2.3 Minimum Skylight Fenestration Area for Climate Zone 5! 1% to 3% of roof area (read for details) For spaces with Exemptions for: 75 In building four stories or less roof height of 4.6 m or greater and Floor area of 465 m² or greater Of type: office, lobby, atrium, concourse, corridor, non-refrigerated warehouse or storage, gymnasium, convention center, automotive service, manufacturing, retail, distribution/sorting area, transportation or workshop General lighting power less than 5.4 W/m² Site conditions and/or architectural features would block skylight (read for details) Skylight area can be reduced to account for sidelight 90.1 Section 5 SHGC of Vertical Fenestration 5.5.4.4.1 SHGC of Vertical Fenestration Comply with Tables SB5.5-5 thru -7 (maximum SHGC) Modifier allowed for permanent architectural features that shade window Exceptions for street side fenestration (read for details): 76 provided street-level story 6 m high or less and has a continuous overhang 90.1 Section 5 Fenestration Orientation 5.5.4.5 Fenestration Orientation “South” Fenestration Area must greater or equal to “west” and “east” Exceptions for nearly any site restrictions 77 As ≥ Aw and As ≥ Ae Topography, adjacent structures within 6 meters Exceptions for 5.5.4.4.1 (street side fenestration) 90.1 Section 5 Labeling 5.8.2 Labeling of Fenestration and Doors All products shall have a permanent nameplate installed by the manufacturer OR Signed and Dated certification from manufacturer Or use Appendix A values for Door, Windows 78 U-factor, SHGC,VT, air leakage rate NRFC / CSA evaluation for performance values Remember vertical fenestration table! 90.1 Section 5 Envelope Trade-Offs within Prescriptive Path – Area Weighted Area weighted U / C / F factors within Class of construction and Space conditioning category Can trade off: Steel Framed / Non-Residential Walls with Attic / Non-Residential Roof with Attic / Non-Residential Roof Metal Framing Vertical Fenestration Residential with 79 Steel Framed / Non-Residential Walls Metal Framing Vertical Fenestration Residential Complying with Prescriptive Envelope: Area Weighted U-Factor Gross Walls W1 Spandrel W2 Steel Frame Window 15,020 4,735 4,735 5,550 U-Factor 31.5% 0.154 31.5% 0.055 37.0% Uavg 0.104 Ravg 9.576 Reff 6.5 18.2 Gross Walls W1 Spandrel W2 Steel Frame Window 15,020 4,735 4,735 5,550 U-Factor 0.154 31.5% 31.5% 0 37.0% Uavg 0.077 Ravg 13.000 Reff 6.5 Infinite! Gross Walls W1 Spandrel W2 Steel Frame Window 15,020 2,368 7,103 5,550 U-Factor 15.7% 0.154 47.3% 0.022 37.0% Uavg 0.055 Ravg 18.195 Reff 6.5 45.5 U-Factor Target for Steel Frames Walls: 0.055 80 Envelope Trade-Offs within Prescriptive Path – Building Envelope Trade-off 90.1 Section 5.6 comply with: 5.1General 5.4 Mandatories 5.7 Submittals 5.8 Product information and installation requirements the envelope performance factor is less than or equal to budget building Appendix C calculations Software Tool: ENVSTD 81 Do not try this at home! OBC version being developed ENVSTD Software (Version 4.0 Shown) OBC Version being developed Exceeding 50-60% fenestration will still be a challenge with only envelope trade-offs 82 Building Envelope Compliance Summary FWR Prescriptive Weighted U-Value / SHGC Envelope Trade-Off Whole Building Energy Model ≤40% ≤40% ≤40% in baseline ≤40% in baseline Compared to Tables SB5.5-5 thru -7 Compared to Tables SB5.5-5 thru -7 and HVAC / Electrical prescriptive targets Fenestration Tables SB5.5-5 thru -7 Walls Roof 84 and within same Tables SB5.5-5 thru -7 assembly type and conditioned space 90.1 Section 6: 90.1 Requirements SB-10 Revisions 85 Mostly just Canadian Standards HVAC Section 6 Heating/Cooling Peformance Mandatory 86 Minimum Equipment Efficiencies Tables 6.8.1 A-K Equipment not regulated by NAECA shall have permanent label stating compliance with 90.1 Equipment Air Conditioners Heat Pumps Minimum Efficiency COP 3.2 – 3.8 COPc >3.2 COPh > 2.2 Chillers Air Cooled COP IPLV > 3.6 Reciprocating COP IPLV > 5.6 Centrifugal COP IPLV > 5.9 Furnaces > 78% AFUE or > 80% thermal efficiency Boilers Heat Rejection under 88 kW / 300 MBH 80% Over 733 kW / 2500 MBH 82% Axial Fan Open-circuit >3.23 L/(s-kW) Centrifugal Fan Open-circuit >1.7 L/(s-kW) Axial Fan Closed-circuit >1.7 L/(s-kW) Centrifugal Fan Closed-circuit 0.59 L/(s-kW) 90.1 Section 6 HVAC Controls 6.4.3.1.2/6.4.3.3.2 Thermostats must be capable of 3°C dead band and setback (some exceptions) 6.4.3.9 Ventilation Controls for spaces with high occupancy Demand Control Ventilation required for (some exceptions): Spaces > 50 m² and Occupancy > 40 occ / 100m² 6.4.2.10 Single Zone Equipment Air handling and fan-coil units using chiller water with greater than 4 kW (5.4 hp) fan motors Air handing equipment and air-conditioner with DX cooling greater then 32 kW (9 tons) 87 Must have variable speed controls Must have 2-speed or variable speed fans 90.1 Section 6 – Free Cooling Economizers 6.5.1 Have either a air-side or water side economizer, unless 88 Less than 16 kW / 4.5 tons cooling or 40 kW / 11 tons in computer rooms Hospitals and ambulatory surgery center with humidification (note computer rooms humidification need not apply) System includes condenser heat recovery that meets minimum loads Residential systems where the space capacity is less than 3.2 kW / 0.9 ton Operates less than 20 hours per week Space is very leaky (infiltration) Use of outdoor air for cooling will affect supermarket open refrigerated casework Otherwise if humidifying (above 2°C dew point) and system uses hydronic cooling, use water side economizer 90.1 Section 6 Humidity Control 6.5.2.3 Dehumidification Controls shall prevent reheating, unless System is capable of reducing total supply air by 50% or to the minimum ventilation rate (i.e. most any VAV system) Systems serving areas with humidity controls to satisfy process needs (e.g. vivariums, museums, surgical suites, supermarkets) computer rooms excluded 6.5.2.4 Humidification 89 If humidification above 2°C dew point and system uses hydronic cooling, use water side economizer not an air side 90.1 Section 6 Fan Power – Option 1: Maximum Nameplate Fan Motor Power 45 60 40 Constant Volume 35 50 Variable Volume 30 40 25 30 20 15 20 10 10 5 0 0 2000 4000 6000 8000 10000 12000 14000 16000 18000 design maximum supply airflow rate to conditioned spaces serve by the system in litres per second 90 0 20000 the maximum combined motor nameplate hp the maximum combined motor namplate kW 50 90.1 Section 6 Fan Power – Option 2: Maximum Input Fan Motor Power 80 45 70 40 90.1-2010 Constant Volume with 70% ERV 35 60 90.1-2010 Variable Volume with 70% ERV 50 30 25 40 20 30 15 20 10 10 5 0 0 2000 4000 6000 8000 10000 12000 14000 16000 18000 design maximum supply airflow rate to conditioned spaces serve by the system in litres per second 91 0 20000 the maximum combined motor input at design conditions, hp the maximum combined motor inpout at design conidtions, kW 50 90.1 Section 6 – Variable Fan Control 6.5.3.2.1 All Fan motors > 7.4 kW / 10 hp shall have one of: Variable speed drive Variable pitch blades (axial fans) Other controls capable of achieving 30% energy consumption at 50% design flow 6.5.3.2.2 Static Pressure Sensor Location Shall be placed such that the controller setpoint is no greater than 1/3 of the design total fan static pressure If this results in the sensor being located downstream of major duct splits, multiple sensors shall be installed 6.5.3.3 VAV system with DDC Controls Shall reduce O/A rates in response to changes to system ventilation effectiveness, unless 92 Exhaust air heat recovery is installed Total design exhaust is more than 70% of total design outdoor air 90.1 Section 6 – Hydronic System 6.5.4.1 Systems having a total pump system power greater than 7.5 kW / 10 hp shall be variable speed Differential pressure transducer located where greatest pressure difference will occur 6.5.4.3 Hot or Cold Water systems that exceed 88 kW (300 MBH or 25 tons) shall have supply temperature reset, except 93 If required to have variable speed pumping Where reset causes improper operation 90.1 Section 6 – Exhaust Air Heat Recovery 50% energy recovery required for most multizone systems Exempt if 94 the largest single source of exhaust is less than 75% of O/A rate More than 60% of outdoor air heating from site solar or site recovered energy Operates less than 20 hr/week % Outdoor Air at Full Design Airflow Rate Design Supply Air Flow Rate ≥ 30% and < 40% > 2596 L/s > 5500 CFM ≥ 40% and < 50% > 2124 L/s > 4500 CFM ≥ 50% and < 60% > 1652 L/s > 3500 CFM ≥ 60% and < 70% > 944 L/s > 2000 CFM ≥ 70% and < 80% > 472 L/s > 1000 CFM >0 >0 > 80% 90.1 Section 6 Service Hot Water Heat Recovery 6.5.6.2 Condenser heat recovery for preheating/heating SHW shall be installed if all the following are true: Condenser heat recovery must either: Facility operates 24 hours / day Total installed heat rejection capacity of water cooled systems exceed 1800 kW (6150 MBH) ~ 600 tons The design SWH load exceeds 300 kW (1025 MBH) Hospitals and some large MURBs meet these requirements Supply 60% of peak SHW load Preheat peak service hot water draw to 29°C Exempt if: 95 Condenser heat recovery is already employed for space heating Facilities supply 60% of DHW heating from site-solar or other siterecovered heat recovery 90.1 Section 7 90.1 Requirements SB-10 Revisions Canadian Standards 7.4.5.2 Heated exterior public pools and public spas shall be equipped with a pool cover 96 Unless 60% of their annual heating from site-recovered or solar sources 90.1 Section 8 8.4.2 Automatic Receptacle Control For private offices, open office and computer classrooms 50% of receptacles shall have either 97 Occupancy sensors On a schedule to turn off during unoccupied hours Any other means to ensure power is turned off during unoccupied hours Exceptions where it can be shown that equipment needs to be on continuously 90.1 Section 9 Occupant sensor or timer switch shall be used in: Classrooms and lecture halls Conference, meeting and training rooms Employee lunch and break rooms Storage and supply rooms (15 to 305 m²) Rooms used for document copying and printing Office spaces up to 76 m² Restrooms Dressing, locker and fitting rooms Exception for space 98 With multi-scene control Shop and laboratory classrooms where automatic lights would endanger safety or security 24-hour operation spaces 90.1 Section 9 Lighting Power Density Table 9.5.1 LPD using Building Area Method Building Area Type Automotive facility Convention centre Courthouse Dining: bar lounge/leisure Dining: cafeteria/fast food Dining: family Dormitory Exercise centre Fire station Gymnasium Health-care clinic Hospital Hotel Library Manufacturing facility Motel 99 ASHRAE 90.1 2007 2010 W/m2 W/m2 10 8.8 13 11.6 13 11.3 14 10.7 15 9.7 17 9.6 11 6.6 11 9.5 N/A 7.6 12 10.8 11 9.4 13 13 11 10.8 14 12.7 14 11.9 11 9.5 Reduction 12% 11% 13% 24% 35% 44% 40% 14% N/A 10% 15% 0% 2% 9% 15% 14% Table 9.5.1 LPD using Building Area Method Building Area Type Motion picture theatre Multifamily Museum Office Parking garage Penitentiary Performing arts theatre Police/fire station Post office Religious builidng Retail School/university Sports arena Town hall Transportation Warehouse Workshop 100 ASHRAE 90.1 2007 W/m2 13 8 12 11 3 11 17 11 12 14 16 13 12 12 11 9 15 2010 Reduction W/m2 8.9 32% 6.5 19% 11.4 5% 9.7 12% 2.7 10% 10.4 5% 15 12% 10.3 6% 9.4 22% 11.3 19% 15.1 6% 10.7 18% 8.4 30% 9.9 18% 8.3 25% 7.1 21% 2.9 81% Average reduction in LPD 19% What about Division 4? Division 4 of SB 10: 101 if the building is within the scope of Part 9 Div B of the OBC and, does not contain a residential occupancy, and does not use electric space heating, and, is intended for occupancy on a continuing basis during the winter months i.e. most Non-Residential Part 9 buildings Division 4 Building Envelope Largely the same as the SB5-5 Tables of Division 3 Fewer climate zone, space categories, envelope types If Vertical fenestration gross area exceeds 40% or Skylights exceed 5% 102 Use Division 3 paths (including trade-offs and energy modeling) SB-10 Division 4 – Building Envelope Requirements 103 SB-10 Division 4 – HVAC Requirements Multi-zone systems Revert to Division 3 (90.1-2010 + SB10 Revisions) Single-zone systems Use Division 3 90.1-2010 equipment performance values Plus details on next slide…. (largely reminiscent of 90.1-2010) 104 SB-10 Division 4 Single Zone HVAC Details (4) An air-conditioning system with a cooling capacity of 40 kW or more shall have an economizer, (a) controlled by appropriate high limit shut-off control, and (b) equipped with either barometric or powered relief sized to prevent excess pressurization of the building. 105 (a) more than 1 400 L/s, and (b) more than 70% of the supply air quantity of the system. (7) Where a heat recovery ventilator is installed, the system shall have provisions to bypass or control the heat recovery ventilator to permit operation of the air economizer. (8) A heating, ventilating and air-conditioning system shall be controlled by a manual changeover or dual setpoint thermostat. (9) Except for a system requiring continuous operation, a heating, ventilating and airconditioning system that has a cooling or heating capacity greater than 4.4 kW and a supply fan motor rated for more than 0.5 kW shall be provided with a time clock that, (5) Outdoor air dampers for economizer use shall be provided with blade and jamb seals. (6) A heat recovery ventilator with a recovery effectiveness of 50% or more at the outside winter design temperature shall be provided where the quantity of the outdoor air supplied to the air duct distribution system is, (a) is capable of starting and stopping the system under different schedules for seven different daytypes per week, (b) is capable of retaining programming and time setting during a loss of power for a period of 10 hours or more, (c) includes an accessible manual override that allows temporary operation of the system for up to two hours, (d) is capable of temperature setback down to 13°C during off-hours, and (e) is capable of temperature setup to 32°C during off-hours. (10) Where separate heating and cooling equipment serves the same temperature zone, thermostats shall be interlocked to prevent simultaneous heating and cooling. (11) A heating, ventilating and air-conditioning system with a design supply air capacity greater than 5000 L/s shall have optimum start controls. SB-10 Division 4 – Lighting Requirements Largely taken from 90.1-2010 106 Compliance Paths Prescriptive Pure Prescriptive U-Value trade-off 107 Trade off better performing windows/walls/roof with lessor performing Envelope Trade-Off (for > 40% FWR) FWR 40% or less Meet all envelope, HVAC, lighting requirement Requires ENVSTD software, 50-60% FWR is likely limit PERFORMANCE PATHS Performance Path: 25% Less than MNECB Requires energy modeling Same baseline as LEED Canada 1.x Similar baseline as LEED Canada 2009 EE4-ecoEnergy LEED requires 23% energy cost savings OBC required 25% energy (GJ) savings Energy modeling software tool Automatically creates baseline building to MNECB rules Use energy modeling as part of design process 108 Otherwise potentially a surprise ending! Performance Path: 25% Less than MNECB Design must comply with MNECB mandatory requirements Reference complies with prescriptive requirements of MNECB Overall building energy consumption 109 proposed design vs. reference design regulated loads only Performance Path: 5% Less than 90.1-2010 Requires energy modeling Uses 90.1 Energy Cost Budget Method (ECBM) LEED Canada 1.0 requires 18% less than 90.1-1999 ECBM LEED Canada 2009 requires 10% less than 90.1-2004 using Appendix G Energy Modeling Software tools Meet the requirements of 90.1 section 11.2 Hourly tool, can model thermal mass, part load performance, etc. Tested against ASHRAE 140 standard EE4, eQuest, Trane-trace, HAP, IES, ESP-r Currently no tool creates 90.1-2010 reference case automatically!! Use energy modeling as part of design process 110 Otherwise potentially a surprise ending! Performance Path: 5% Less than 90.1-2010 Design must comply with ASHRAE mandatory requirements Reference complies with prescriptive requirements of ASHRAE 90.1-2010 Whole building energy consumption 111 proposed design vs. reference design regulated loads only Performance Path: No more than 90.1-2010 & Chapter 2 Design must comply with ASHRAE mandatory requirements Design must comply with Chapter 2 mandatory requirements Reference complies with prescriptive requirements of ASHRAE 90.1-2010 & Chapter 2 Whole building energy consumption 112 proposed design vs. reference design regulated loads only 90.1 Performance Paths Utilizes Chapter 11 of 90.1-2010 113 Energy Cost Budget Method Energy modeling rules are well defined Div 3 Ch 2 Revision to 90.1 – Feed-In Tariff 1.1.1.7. Energy Cost Method Sentence 11.2.3.A.(1) shall be added to Section 11.2. ”Simulation General Requirements” of ANSI/ASHRAE/IESNA Standard 90.1 114 11.2.3.A. Rates for Energy Supplied Back to the Grid System. Where energy generated by an on-site renewable energy source is supplied back to the grid system, for the purpose of Section 11, Energy Cost Budget Method, the rates for the energy supplied back to the grid system shall be assumed to be equal to the rates paid for the same type of purchased energy from the grid system. OBC SB-10 Enforcement? Remains to be seen But prior to Jan 1 in SB-10 envelope, window, lighting targets were set energy modeling was a compliance path building envelope trade-off was a compliance path Ministry has new checklists developed (ask me how I know that) Greater attention has been paid over the last 12 months 115 90.1-20XX Impact on the Market Product suppliers are paying attention 116 Closing Quotes Ludwig Wittgenstein (engineer, mathematician, philosopher) W.H. Auden (poet) “I don't know why we are here, but I'm pretty sure that it is not in order to enjoy ourselves.” “We are all here on earth to help others; what on earth the others are here for I don't know.” www.enermodal.com Kurt Vonnegut (writer) 117 "We are put on earth to fart around....don't let any one tell you any different." 118