Features:
Lightning performance improvement of transmission lines
Reduction of double and multicircuit outages
Switching overvoltage control
Overvoltage control in the vicinity of high voltage substations
Prevention of risk to people and animals
Open breaker protection
Line design without shield wire: Loss reduction
Compact line design
Line voltage uprating
US 138 kV line
Advantages of the polymer housed surge arresters:
Sediver has more than 30 years experience in composite insulator technology in direct injection molding of the polymer
housing under high pressure and high temperature. This technology is applied to our surge arresters out of which we
obtain:
Increased life time of the ZnO blocks which are protected from moisture ingress
thanks to our impenetrable design
Excellent mechanical characteristics due to the fiber glass reinforced polymer tube
Excellent pollution performance of the silicone housing
Excellent protection performance due to very stringent selection of extra high
quality, high energy duty metal oxide blocks
Increased safety of surrounding crew and equipment thanks to the explosion proof
design (air-free)
Easy to install and transport due to the low weight
Reduced space requirements thanks to its compact design
Norway 300 kV line
Selection:
Through expertise conducted using simulation software tools, our experts are able to determine optimal arresters types
& location to protect the key points of the system, thus providing effective protection at the lowest cost.
Contact Sediver representative
Installation:
• Directly on the insulator string
• On transmission towers
• Suspended under phase conductor
• Customized installation configuration according to your specific requirements is also possible
Sediver composite gapless line surge arresters
Sediver surge arresters offer unique features for enhanced performance of your High Voltage system.
technical file 2008
Sediver composite
gapless line surge arresters
Product range (*)
System voltage
SLA.1
44-170
(kV)
Arrester class [IEC 60099.4]
SLA.2
44-245
1
SLA.3
44-400
2
3
Nominal discharge current
(kA)
10
10
10
High amplitude current withstand [4/10 ms]
(kA)
100
100
100
Maximum long duration current impulse
(A)
250
500
800
Maximum short circuit rating
(kA)
40
63
63
Maximum permissible bending moment
(Nm)
700
1350
2500
SLA.1 - Class 1 surge arresters (**)
8/20 μs residual voltage (kV crest)
Ur
MCOV
TOV (1s)
SSPL
SIPL
kV rms
kV rms
kV
kV crest
kV crest
5 kA crest
10 kA crest
20 kA crest
60
48
70
138
185
161
176
194
72
58
84
166
222
194
211
233
96
77
112
221
296
258
281
310
108
86
126
249
333
290
316
349
120
96
140
276
370
323
351
388
144
115
168
332
444
387
422
465
SLA.2 - Class 2 surge arresters (**)
Ur
MCOV
TOV (1s)
SSPL
SIPL
8/20 μs residual voltage (kV crest)
kV rms
kV rms
kV
kV crest
kV crest
5 kA crest
10 kA crest
20 kA crest
60
48
70
128
171
150
162
178
72
58
84
154
205
180
194
214
96
77
112
205
273
240
259
285
108
86
126
231
307
270
291
321
120
96
140
257
341
300
324
356
144
115
168
308
409
360
388
427
192
154
224
411
546
480
518
570
SLA.3 - Class 3 surge arresters (**)
Ur:
MCOV:
SSPL:
SIPL:
Ur
MCOV
TOV (1s)
SSPL
SIPL
8/20 μs residual voltage (kV crest)
kV rms
kV rms
kV
kV crest
kV crest
5 kA crest
10 kA crest
20 kA crest
72
58
84
148
190
168
180
199
96
77
112
198
253
223
240
265
108
86
126
222
285
252
270
298
120
96
140
247
316
280
300
331
144
115
168
296
379
336
360
397
192
154
224
395
506
447
480
530
228
182
266
469
601
531
570
629
252
202
294
518
664
587
630
696
336
269
392
691
885
783
840
927
360
288
420
741
949
839
900
994
Rated voltages
Maximum Continuous Operating Voltage
Switching Surge Protective Level (30/60 μs wave; 250 Acrest for Class 1; 500 Acrest for Class 2; 1000 Acrest for Class 3)
Steep Impulse Protective Level (1/20 μs wave; 10 kA crest)
Seves Canada Inc.
Seves USA Inc.
172 Merizzi,
Ville St-Laurent, Quebec, Canada H4T 1S4
T +1 514 739 3385 - F +1.514.739.3669
info@seves.ca - www.sevespower.com
6605 Cypresswood Drive, suite #450,
Houston, Texas 77379
T +1 281 257 8222 - F +1 281 257 8225
info@sevesusa.com - www.sevespower.com
(*) Subject to change without prior notice < Continuous product improvement
(**) Frequently used arresters - all rated voltages according to IEC 60099 and ANSI/IEEE C62.11 available
Sediver © Doc.S.D.L/S.S/C.L/P.S -C04-V2011_US
Sediver composite gapless line surge arresters
Protective characteristics (*)
Download