Mechanical Inspection Asset Data Priority Condition Inspection

advertisement
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
M812
HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, MANHATTAN, NY, 10031
School:
InspectionId
Inspection Type
12000 MECHANICAL
Time In
Last Edited
2015-04-06 07:59AM
2015-04-16 04:46PM
Asset Data
Question
Answer
Have any Systems/Major Building Components been upgraded?
Systems:
Are there fuel tanks?
Total # of water main service entries to the asset
No
0
MERs/Fan Rooms Locations
MER C-10
Years:
Climate Control System; Science Labs; Science Prep
Rooms; Domestic Hot Water System for Science Labs
and Science Prep Rooms
2011
Priority Condition
Priority Condition
Exist Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s) Notified
No
Defective
Sprinkler/St
andpipe
System
Defective/M
issing CO
Detector
Painted
Sprinkler
Head (1)
Sprinkler Head
Computer Lab
C01
Kevin O'Rourke
Supervisor
No Photo Tak
N/A
Science Prep
Room
Science Prep
Rooms
Kevin O'Rourke
Supervisor
No Photo Tak
Yes
Person(s) Title
PhotoImage
Inspection
Question
Response
Mechanical
Inspected
AIR CONDITIONING
Chilled Water System
Does not exist
Condenser Water Piping
Does not exist
Condenser Water Pump
Does not exist
Cooling Coil in Ductwork
Does not exist
Cooling Tower
Does not exist
DX Split System
Inspected
Indoor Unit
Inspected
Condition
1- Good
Deficiency
No deficiencies recorded
Outdoor Unit
Inspected
Condition
1- Good
Deficiency
No deficiencies recorded
Packaged / Rooftop Unit
Does not exist
Packaged Terminal A/C
Does not exist
Refrigerant Piping
Inspected
1- Good
Condition
Deficiency
No deficiencies recorded
Return Fan
Inspected
Condition
1- Good
Deficiency
No deficiencies recorded
CENTRAL ACID WASTE NEUTRALIZING TANK
Does not exist
CLIMATE CONTROL SYSTEM
Inspected
BMS
Does not exist
Electric System
Does not exist
Hybrid System
Does not exist
Pneumatic System
Inspected
Instance
Instance Condition
Throughout
1- Good
Instance Quantity
1
Mobile Validity Version 2.0 (P)
Page 1 of 6
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
M812
Question
Response
CLIMATE CONTROL SYSTEM
Pneumatic System
Instance Quantity Uom
Building Area Covered by Operational System
EACH
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PNEUMATIC TUBING:DEFECTIVE/LEAKS AIR
Corridor near Room B17
10
L.F.
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
81-100%
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Deficiency
Deficiency Location/Instance
Deficiency Quantity
DEFECTIVE TEMPERATURE CONTROL THERMOSTAT
Room B08
1
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
COMPACTOR
Does not exist
CONVEYING
Does not exist
DOMESTIC WATER SYSTEM
Inspected
Domestic Cold Water System
Does not exist
Domestic Hot Water System
Inspected
Domestic Hot Water Remote Storage Tank
Does not exist
Domestic Water Heat Exchanger
Does not exist
Electric Domestic Water Heater
Inspected
Condition
1- Good
Deficiency
No deficiencies recorded
Gas Fired Domestic Water Heater
Does not exist
Oil Fired Domestic Water Heater
Does not exist
Inspected
Domestic Water Distribution Piping
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
DRAIN/WASTE/VENT AND STORM SYSTEM
Inspected
Interior Storm Piping
3- Fair
Condition
Deficiency
No deficiencies recorded
Sewage Ejector Pump
Does not exist
Sewage/Waste/Vent Piping
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Sump Pump
4- Between Fair and Poor
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
DEFECTIVE/DETERIORATED
MER C-10 (1 of 2)
1
EACH
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Does not exist
DUAL TEMPERATURE SYSTEM (CHILLED AND HOT WATER)
Enclosed IDF Room
Mobile Validity Version 2.0 (P)
Page 2 of 6
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
M812
Question
Response
Enclosed IDF Room
Instance on Room 28
Inspected
Dedicated A/C Equipment
Not required
Instance on Room 28
Inspected
FIXTURES
Staff And Other
Inspected
Janitor Sink
Inspected
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Lavatory/Sink
Condition
1- Good
Deficiency
No deficiencies recorded
Inspected
Toilet
Condition
1- Good
Deficiency
No deficiencies recorded
Does not exist
Urinal
Inspected
Student
Inspected
Drinking Fountain
Condition
1- Good
Deficiency
DEFECTIVE AUXILIARY (FAUCET, SHUT OFF
VALVE,ETC.)
Corridor near Toilet Room 110
1
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Deficiency Location/Instance
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
Lavatory/Sink
Condition
1- Good
Deficiency
DEFECTIVE AUXILIARY (FAUCET, SHUT OFF
VALVE,ETC.)
Girls Toilet Room 110
2
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Deficiency Location/Instance
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Locker Room Shower
Does not exist
Sink And Fountain Combo Unit
Does not exist
Toilet
Inspected
Condition
1- Good
Deficiency
No deficiencies recorded
Inspected
Urinal
Condition
1- Good
Deficiency
No deficiencies recorded
GAS FIRED FURNACE
Does not exist
GAS SERVICE
Does not exist
HEATING
Inspected
Heating Coil In Ductwork
Does not exist
Hydronic Heating
Inspected
Backflow Preventer
Does not exist
Hot Water Heat Exchanger
Does not exist
Hydronic Hot Water Distribution: Piping, Pumps and Auxiliaries
Inspected
Mobile Validity Version 2.0 (P)
Page 3 of 6
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
M812
Question
Response
HEATING
Hydronic Heating
Hydronic Hot Water Distribution: Piping, Pumps and Auxiliaries
Condition
3- Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PIPING:DEFECTIVE/LEAKS
Boys Toilet Room 112
10
L.F.
REPLACE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
Radiator/Convector/Fin Tube
3- Fair
Condition
Deficiency
No deficiencies recorded
Steam Heating
Does not exist
Steam supplied by External Sources
Does not exist
Unit Heater/Cabinet Heater
Inspected
1- Good
Condition
Deficiency
No deficiencies recorded
HEATING PLANT
Does not exist
KITCHEN
Does not exist
MDF Room
Inspected
Instance on Room B25
Dedicated A/C Equipment
Instance on Room B25
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Does not exist
SCIENCE DEMO ROOM
SCIENCE LAB
Instance on Rooms 107, 108
Inspected
Alternative Use
No
Acid Waste Neutralizing Tank
Instance on Rooms 107, 108
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
CO Detector
Instance on Rooms 107, 108
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Emergency Shower
Instance on Rooms 107, 108
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Eye Wash
Instance on Rooms 107, 108
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Fixed Laboratory Hood
Does not exist
Instance on Rooms 107, 108
Hood Exhaust Ductwork
Does not exist
Instance on Rooms 107, 108
Hood Exhaust Fan
Does not exist
Instance on Rooms 107, 108
Mobile Validity Version 2.0 (P)
Page 4 of 6
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
M812
Question
Response
SCIENCE LAB
Laboratory Sink
Instance on Rooms 107, 108
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Make-up Air Unit
Does not exist
Instance on Rooms 107, 108
Portable Laboratory Hood
Instance on Rooms 107, 108
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
SCIENCE PREP ROOM
Instance on Rooms 107A, 108A
Inspected
Alternative Use
No
Acid Waste Neutralizing Tank
Instance on Rooms 107A, 108A
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Emergency Shower
Does not exist
Instance on Rooms 107A, 108A
Eye Wash
Does not exist
Instance on Rooms 107A, 108A
Fixed Laboratory Hood
Instance on Rooms 107A, 108A
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Hood Exhaust Ductwork
Instance on Rooms 107A, 108A
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Hood Exhaust Fan
Instance on Rooms 107A, 108A
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Laboratory Sink
Instance on Rooms 107A, 108A
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Make-up Air Unit
Does not exist
Instance on Rooms 107A, 108A
Portable Laboratory Hood
Does not exist
Instance on Rooms 107A, 108A
Inspected
SPRINKLERS, STANDPIPE, FIRE SYSTEM
Dry Sprinkler Alarm Valve Assembly
Does not exist
Fire Booster Pump Assembly
Does not exist
Roof Tank
Does not exist
Siamese Connection
Does not exist
Sprinkler Head
Inspected
1- Good
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
DEFECTIVE/DETERIORATED
Computer Lab C01 (painted)
1
EACH
REPLACE
PRIORITY 5
Quantity Uom
Potential Action
Urgency of Action
Mobile Validity Version 2.0 (P)
Page 5 of 6
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
M812
Question
Response
SPRINKLERS, STANDPIPE, FIRE SYSTEM
Sprinkler Head
Purpose of Action
Violations
LEVEL 6
No violations recorded
Inspected
Sprinkler Piping
1- Good
Condition
Deficiency
No deficiencies recorded
Inspected
Standpipe System
Inspected
Hose Valve Assembly
Condition
1- Good
Deficiency
No deficiencies recorded
Inspected
Piping
Condition
1- Good
Deficiency
No deficiencies recorded
Water Gong
Does not exist
Wet Sprinkler Alarm Valve Assembly
Does not exist
SWIMMING POOL
Does not exist
VENTILATION
Inspected
Exhaust Fan
Inspected
1- Good
Condition
Approximate Total # of Fans
Deficiency
1-25
No deficiencies recorded
Heating And Ventilating Unit
Does not exist
Metal Ductwork
Inspected
1- Good
Condition
Deficiency
No deficiencies recorded
Supply Fan
Does not exist
Unit Ventilator
Does not exist
Mobile Validity Version 2.0 (P)
Page 6 of 6
Print Date: 6/18/2015