nSP5-D-ER UL924 Relay Pack Cutsheet

advertisement
nSP5 D
SECONDARY RELAY PACK w/ DIMMING
5 AMPS @ 120/277/347 VAC
SPECIFICATIONS
The nLight nSP5 D Series secondary
OPTIONS
relay and dimming pack is designed to
LOW TEMP/HIGH HUMIDITY (LT)
both switch and dim a lighting fixture with
• Sensor is corrosion resistant to
0-10 VDC ballast(s). This combiniation of
moisture
• Operates down to -40º F/C
features makes it ideal for rooms where
multizone or individual control of lights
is required. Manual switching and adjustment of the dimming level is possible
via WallPods or through the SensorView software. The secondary relay pack’s
two RJ-45 connectors make control wiring with standard CAT-5 cabling easy and
clean. For simplifying installation, secondary packs have an elongated chase
nipple that allows them to be attached either directly through a ½” knockout into a
junction box or fixture.
FEATURES
Communicates w/ nLight Network
Remotely Configurable/Upgradeable
Push-Button Programmable
Configurable Relay Logic
Self-Contained Relay Switches
Line Voltage Load
Controls 0-10 VDC Dimmable Ballasts
Green LED Indicator
Extended Chase Nipple
PHYSICAL SPECS
SIZE (not including ½” chase nipple) 3.38” H x 2.53” W x 1.83” D
(8.59 cm x 6.43 cm x 4.65 cm)
WEIGHT 6 oz
MOUNTING ½” knockout COLOR White
NETWORK CONNECTION
2 RJ-45 ports
RELAY OPERATION
Power for the nSP5 D secondary pack is provided via the CAT-5 connection
and not taken off the line. Therefore the internal latching relay functions as a dry
contact for switching up to 5A loads.
NLIGHT OPERATION
The device is nLight-enabled, meaning it is powered and has the ability to
communicate over an nLight network. Typically, it is daisy-chain wired, using CAT5 cabling, with other nLight-enabled power packs, sensors and/or WallPods in an
nLight control zone. Left alone, the zone will assume default operation and can be
programmed via its’ devices’ push-buttons. Once linked to a Gateway, directly or
via a Bridge, the zone becomes capable of remote status monitoring and control
via SensorView software.
ELECTRICAL SPECS
SWITCHING LOAD:
5 Amps @ 120/277/347 VAC
MOTOR LOAD: 1/4 HP
DIMMING LOAD: Sinks < 20 mA;
~40 Ballasts @ .5 mA each
WIRES 18 AWG (2), 20 AWG (2)
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
STORAGE TEMP
-14º to 160º F (-26º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
All switches and sensors can be configured to output on one of sixteen channels,
referred to as broadcast channels. Devices with relays and/or dimming, such
as the nSP5 D, can then be configured to follow any of these channels via
the tracking channel settings. By default, an nSP5 D is configured to follow all
occupancy, photocell, and switch/dimmer commands arriving on Channel 1. Using
SensorView, however, channel tracking settings can be programmed for each
device type individually. This is critical when an nSP5 D is utilized in a room to
provide multizone dimming and personal control.
OTHER
UL and CUL Listed
Plenum Rated
Title 24 Compliant
5 Year Warranty
Made in the U.S.A.
ORDERING INFO
nSP5 D [TEMP/HUMIDITY]
OPTIONS
TEMP/HUMIDITY
Blank = Standard
LT = Low Temp
Revised 11.29.10 © 2010 Sensor Switch
WIRING (DO NOT WIRE HOT)
Device power is provided via the CAT-5 connection and not taken off the line. Therefore the internal latching relay functions
as a dry contact. T568B pin/pair assignment is recommended for all CAT-5 cables.
H
CAT-5
nSP5 D
N
BLU
BLU
VIO (+)
BALLAST
GRY (-)
OPERATIONAL SETTINGS
Several operational settings for the nSP5 D are available:
Override (On/Off/Normal)
Idle Time Until Dim
Occupancy Tracking (Enable/Disable)
Dimming Range High (0 - 100%)
Photocell Tracking (Enable/Disable)
Dimming Range Low (0 - 100%)
Switch Tracking (Enable/Disable)
Dimming Offset (-200% to +200%)
Occupancy Tracking Channel (1-16)
Start to High (Enable/Disable)
Photocell Tracking Channel (1-16)
LED (Override On/Override Off/Normal)
Switch Tracking Channel (1-16)
Follow Photocell Mode (Enabled +, Enabled +/-, Disabled
Button Mode (Enable/Disable)
Invert Relay Logic* (Enable/Disable)
*does not invert dimming operation
Special Modes:
Manual On to Auto Off (Semi-Auto), Auto to (Timed) Override On,
Manual to (Timed) Override On, Manual On to Full Auto, Predictive Off
INSTALLATION
• Mount to any junction box through a ½”
knockout (note: chase nipple is long enough to
accomodate mounting inside an adjacent box
if necessary for local code requirements)
• Connect Class 1 wires to line voltage feed and
load
• Connect Class 2 dimming output wires to
ballast dimming inputs
• Interconnect unit (via RJ-45 ports) with other
nLight devices in lighting zone using CAT-5
cables
• Once power is received via CAT-5 connection,
all devices in zone will automatically begin
functioning together according to each device’s
defaults
BUTTON
RJ-45 PORTS
LED
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a
period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material
Authorization number and repair or replace returned product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied
warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances shall
Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
TN-606-02
900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com
Download