nSP16 SECONDARY RELAY PACK 16 AMPS @ 120/277/347 VAC SPECIFICATIONS FEATURES Communicates w/ nLight Network Remotely Configurable/Upgradeable Push-Button Programmable Reversible Relay Logic Self-Contained Relay Switches Line Voltage Load Green LED Indicator Extended Chase Nipple PHYSICAL SPECS SIZE (not including ½” chase nipple) 3.38” H x 2.53” W x 1.83” D (8.59 cm x 6.43 cm x 4.65 cm) WEIGHT 6 oz MOUNTING ½” knockout COLOR White NETWORK CONNECTION 2 RJ-45 ports ELECTRICAL SPECS OPERATING VOLTAGE 120/277/3 47 VAC SWITCHING LOAD: 16 Amps @ 120/277/347 VAC MOTOR LOAD: 1 HP WIRES 16 AWG (2), 18 AWG (1) ENVIRONMENTAL SPECS OPERATING TEMP 14º to 160º F (-10º to 71º C) STORAGE TEMP -14º to 160º F (-26º to 71º C) RELATIVE HUMIDITY 20 to 90% non-condensing OTHER UL and CUL Listed Plenum Rated Title 24 Compliant 5 Year Warranty Assembled in the U.S.A. The nLight nSP16 Series Secondary Relay Pack switches lighting loads up to 16A. The Secondary Relay Pack’s two RJ-45 connectors make control wiring with standard CAT-5 cabling easy and clean. For simplifying installation, Secondary Packs have an elongated chase nipple that allows them to be attached either directly through a ½” knockout into a junction box, or inside an adjacent box for meeting specific local code requirements in ceiling plenums. OPTIONS SEMI-AUTOMATIC (SA2) • Unit’s Switch Tracking Channel set to 2 • Operational Mode set to Manual On LOW TEMP/HIGH HUMIDITY (LT) • Unit is corrosion resistant to moisture • Operates down to -40º F/C RELAY OPERATION The nSP16 is nLight-enabled, meaning it has the ability to communicate over an nLight network. Typically, an nSP16 is daisy-chain wired, using CAT-5 cabling, with other nLight-enabled power packs, sensors and/or WallPods in an nLight control zone. Left alone, the zone will assume default operation and can be programmed via its’ devices’ push-buttons. Once linked to a Gateway, directly or via a Bridge, the zone becomes capable of remote status monitoring and control via SensorView software. All switches and sensors can be configured to output on one of sixteen channels, referred to as broadcast channels. Devices with relays, such as the nSP16, can then be configured to follow any of these channels via the tracking channel settings. By default, the standard nSP16 is configured to follow all occupancy, photocell, and switch commands arriving on Channel 1. Using SensorView, however, channel tracking settings can be programmed for each device type individually. This is critical when an nSP16 is in a zone with a 2P or DZ sensor that sends information on two channels simultaneously. The nSP16 SA2 version is factory set to track switch commands on channel 2. Its default operating mode is also set to Manual On (Semi-Automatic). In this mode, the unit’s relay will not turn its connected lighting load on until someone manually presses an on switch in the zone. This allows a completely plug-and-play, out of the box solution for bi-level applications when connected in a zone to an nPP16 Power Pack, any occupancy sensor, and an nPOD 2P WallPod. ORDERING INFO nSP16 [DEFAULT OPERATION] [TEMP/HUMIDITY] OPTIONS TEMP/HUMIDITY SEMI-AUTOMATIC Blank = Automatic On (Default) SA2 = Semi-Automatic (Default) Blank = Standard LT = Low Temp Revised 03.06.12 © 2012 Sensor Switch, WIRING (DO NOT WIRE HOT) Device power is provided via the CAT-5 connection. CAT-5 cables should be wired using T568B pin/pair assignments. N CAT-5 nSP16 H N WHT BLU BLU LOAD OPERATIONAL SETTINGS Several operational settings for the nSP16 are available: Override (On/Off/Normal) Switch Tracking Channel (1-16) Occupancy Tracking (Enable/Disable) Button Mode (Enable/Disable) Photocell Tracking (Enable/Disable) Start to High (Enable/Disable) Switch Tracking (Enable/Disable) Invert Relay Logic (Enable/Disable) Occupancy Tracking Channel (1-16) LED (Override On/Override Off/Normal) Photocell Tracking Channel (1-16) Special Modes: Manual On to Auto Off (Semi-Auto), Auto to (Timed) Override On, Manual to (Timed) Override On, Manual On to Full Auto, Predictive Off INSTALLATION • Mount to any junction box through a ½” knockout (note: chase nipple is long enough to accomodate mounting inside an adjacent box if necessary for local code requirements) • Connect Class 1 wires to line voltage feed and load • Interconnect unit (via RJ-45 ports) with other nLight devices in lighting zone using CAT-5 cables • Once power is received via CAT-5 connection, all devices in zone will automatically begin functioning together according to each device’s defaults BUTTON RJ-45 PORTS LED WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material Authorization number and repair or replace returned product. LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances shall Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses. TN-603-03 900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com