Outline principle SMO 40 with multiple air/water heat pumps, additional heat and accessory (liquid condensation) Application Buildings with water-borne heating systems. Alternative Heat pump Quantity ☑ 2x (Slave 2) ☐ 3x (Slave 3) ☐ 4x (Slave 4) ☐ 5x (Slave 5) ☐ 6x (Slave 6) ☐ 7x (Slave 7) ☐ 8x (Slave 8) ☐ Hot water charging 1 x ☐ VPA 2 x ☐ VPA 3 x ☐ VPA 4 x ☐ VPA ☐ VPB ☐ VPB ☐ VPB ☐ VPB Select location of reversing valve that charges hot water: -AA25-BT25 -RM21 ☐ Slave 1 ☐ Slave 2 ☐ Slave 4 -AA25-GP10 -AA25-BT71 ☐ Additional water heater ☐ Hot water comfort with core water heater ☐ Hot water comfort with extra hot water and additional core water heater ☐ Solar coil in VPA 1 (VPAS) / VPB1 (VPBS) ☐ Extra additional heat ☐ Electric boiler (step controlled) ☐ Combustion boiler (shunt controlled) ☐ District heating (shunt controlled) ☐ Extra climate system ☐ Extra climate system 1 ☐ Extra climate system 2 ☐ Extra climate system 3 -AA25 ☐ UKV ☐ 2 pipe, Low tempered unbalanced low flow ☐ 2 pipe, High tempered low flow -AA25-EB102 -EB102 ☐ POOL ☐ Pool system 1 -FL10 -BT3 Select location of reversing valve that charges pool: ☐ Slave 1 ☐ Slave 2 -BT12 ☐ Slave 4 ☐ Pool system 2 -QM31 -QM32 -GP12 -RM11 -HQ1 -QM43 -QM1 -AA25-EB101 -EB101 -BT12 -FL10 -BT3 -QM31 -QM32 -GP12 -RM11 -AA25 -BT1 -HQ1 -QM43 -FL2 -QM1 -CM1 Start again NOTE! This is an outline diagram. Actual installation must be engineered according to current standards. See the appropriate "installer manual" for more information. Designations according to standard IEC 81346-1 and 81346-2. NIBE AB - Energy Systems Box 14, 285 21 Markaryd Tel 0433 - 73 000 Fax 0433 - 73 190 www.nibe.se ODM GB 1412-1 M11624 PAGE 1 (4) Function SMO 40 with multiple air/water heat pumps, additional heat and accessory (liquid condensation) Operate modes • Activating temporary lux (extra hot water) Pool • External adjustment of the flow temperature This function requires accessory POOL 40. A reversing valve • Switch for "SG ready" and a circulation pump can be connected to control all of Heat production All control signals should occur with potential-free relays. the charge flow from the heat pump(s) to a pool exchanger. The heating control system on the SMO 40 is controlled SMO 40 can control 2 pools; 2 x accessoriesPOOL 40 are by the outside temperature. This means that the supply AUX outputs then required. of heat to the house is regulated in accordance with the It is possible to have an external connection through the During pool heating the heating medium is circulated chosen setting of the regulating curve (curve slope and offset). After adjustment, the correct amount of heat for relay function via a potential free variable relay (max 2 A) between the heat pump(s) and the pool exchanger using circulation pump GP12. the outside temperature is supplied. The supply tempera- on the input card (AA3), terminal block X7. ture of SMO 40 will hover around the required value. For • Optional functions for external connection: subnormal temperatures the control system calculates a • Indication of buzzer alarm signal (preselected at the External additional heat heating deficit in the form of "degree-minutes",・which factory). means that heating production is accelerated. The larger This function requires accessory AXC30. This accessory the subnormal temperature, the greater the heat produc- • Control of circulation pump for hot water circulamakes external additional heat possible in three different tion. tion. The internal immersion heater is connected autoways, the selection is made in the controls. matically when the energy requirement exceeds the heat • External circulation pump (for heating medium). pumps' capacity. • External alarm (NO/NC). Gas/oil fired boiler • Blocking heating. A circulation pump is activated when the temperature Hot water production If any of the above is installed to terminal block X7 it of the boiler sensor has exceeded the temperature set in must be selected in the control system. During hot water demand, SMO40 prioritises the heat SMO 40. The heat is shunted to the requested temperapumps that are selected for hot water production for this. The accessory card is required if two or more of the ture using the internal shunt. above functions are to be connected to terminal block X5 Maximum time for hot water charging can be adjusted in the menu system. Hot water charging starts when the at the same time. Electric heater hot water sensor has fallen to the set start temperature. Hot water charging stops when the hot water temperaWhen the degree minute deficit is below the set value, a ture on the hot water sensor (BT6) has been reached. For Room control circulation pump is activated and the electric heater steps occasional higher demand for hot water, the "temporary SMO 40 can be supplemented with a room sensor in as needed. (BT50). lux"・function can be used to raise the temperature for 3 – 12 hours (selected in the menu system). Periodic hot The room temperature sensor has up to three functions: water increase is factory set to every 14 days. Hot water comfort • Show current room temperature in the heat pump's This function requires accessory AXC 30, which allows display. temporary lux, mixing valve and hot water circulation. • Option of changing the room temperature in °C. Functions/accessories • Makes it possible to change/stabilise the room temperature. Install the sensor in a neutral position where the set temHeat pumps perature is required. A suitable place is on a free inner Heat pumps with on/off compressor. wall in a hall approx. 1.5 m above the floor. It is imporThe entire compressor output is routed to heating, hot tant that the sensor is not prevented from measuring the water or any pool heating. Compressors step in if needcorrect room temperature by being located, for example, ed. If the output of all available compressors is not suffiin a recess, between shelves, behind a curtain, above or cient, additional heat engages automatically. close to a heat source, in a draft from an external door Heat pumps with inverter compressor. The compres- or in direct sunlight. Closed radiator thermostats can also sor output is adjusted according to the demand and rout- cause problems. ed to heating, hot water or any pool heating or cooling. The heat pump operates without the sensor, but if you Compressors step in if needed. If the output of all availawant to read off the accommodation's indoor temperable compressors is not sufficient, additional heat engages ture in the SMO 40 display, the sensor must be installed. automatically AUX inputs SMO 40 has software controlled inputs for connecting the switch function or sensor. This means that when an external switch function or sensor is connected to one of six AUX connections, the correct function must be selected for the correct connection. For further information see the Installer's manual. The following functions can be controlled: • Blocking of additional heat and/or compressor • Tariff blocking Extra climate system This function requires accessory ECS 40/ECS 41. A shunt valve, supply and return sensor and a circulation pump are connected to a second heating circuit with a lower temperature demand (e.g. underfloor heating system). The temperature in the extra climate system is controlled by the heat pump and the shunt valve by offsetting the heat curve (each climate system has its own heat curve), room sensor or room unit. Up to 3 extra climate systems can be connected to SMO 40. Temporary lux (extra hot water) If an immersion heater is installed in the tank it can be used to raise the temperature of the hot water, to a temperature that exceeds the operating range of the heat pump. In addition, it can be permitted to produce hot water, at the same time as the heat pump prioritises heating. Mixer valve A temperature sensor reads the temperature of the outgoing hot water to the domestic hot water and adjusts the mixing valve from the water heater until the set temperature has been reached. Hot water circulation (VVC) One pump can be controlled for the circulation of the hot water during selectable periods. Sun This function requires accessory Solar 40/42 as well as a pump station. The solar panel can be used to heat the hot water. NIBE AB - Energy Systems Box 14, 285 21 Markaryd Tel 0433 - 73 000 Fax 0433 - 73 190 www.nibe.se ODM GB 1412-1 M11624 PAGE 2 (4) List of Components SMO 40 with multiple air/water heat pumps, additional heat and accessory (liquid condensation) Pos Name Product name Supplier Part no. AA25 BT1 BT6 BT7 BT25 BT50 BT63 Control module Outdoor sensor Temperature sensor, hot water charging Temperature sensor, hot water top Temperature sensor, external supply Room sensor Temperature sensor, external supply line after "additional heating before QN10" Temperature sensor, external return line Circulation pump, heating medium Reversing valve, hot water/heating medium Pool system 1 Unit box Temperature sensor, pool Heat exchanger, pool Circulation pump, pool Particle filter Reversing valve, pool Trim valve Additional heat Electric heater Auxiliary relay/Contactor Immersion heater Immersion heater SMO 40 NIBE NIBE NIBE NIBE NIBE NIBE NIBE 067 225 Auxiliary relay/Contactor Heat pump system Temperature sensor, return line Temperature sensor, condenser supply line Heat pump Charge pump BT71 GP10 QN10 CL11 AA25 BT51 EP5 GP9 HQ4 QN19 RN10 EB1 EB1 KA1 EB20 EB20 KA1 EB101 BT3 BT12 EB101 GP12 HQ1 QM1 QM31 to 32, QM43 RN10 EM1 AA25 BT52 CM1 EM1 FL2 KA1 QN11 EP21 AA25 BT2 BT3 GP20 QN25 Included Included Included Included Included Included NIBE VST 05/VST 11/VST 20 POOL 40 POOL 40 NIBE – NIBE NIBE in in in in in in SMO SMO SMO SMO SMO SMO 40 40 40 40 40 40 Included in SMO 40 089 982 /089 152 / 089 388 067 062 067 062 Tel.: 08 - 59 41 10 50 Tel.: 08 - 59 41 10 50 Tel.: 08 - 59 41 10 50 POOL 40 NIBE – 067 062 ELK 15/ELK 26/ELK 42 HR 10 NIBE NIBE 069 022/ 067 074/ 067 075 067 309 IU (immersion heater) + K11 (terminal block) NIBE HR 10 NIBE IU 3kW: 218 009 IU 6kW: 218 011 IU 9kW: 218 003 K11: 188 93 067 309 F2025/F2026//F2030/F2040/F2300 CPD 11 NIBE NIBE NIBE NIBE Particle filter Drain valve, heating medium Shut-off valve Trim valve External addition Unit box Temperature sensor, boiler Expansion vessel, closed Oil, gas, pellets or wood boiler Safety valve Auxiliary relay/Contactor Shunt valve Extra climate system Unit box Temperature sensor, heating medium supply Temperature sensor, heating medium return Circulation pump Shunt valve Remarks Included in F2025/F2026//F2030/F2040/F2300 Included in F2025/F2026//F2030/F2040/F2300 F2025/F2026/F2300: The software must be 55 or later. (CPD 11-25/65: 067 321 CPD 11-25/75: 067 320 NIBE Included in F2025/F2026//F2030/F2040/F2300 Certain boilers have their own circulation pumps, if not they must be equipped with a flow guard. AXC 30 AXC 30 NIBE NIBE 067 304 067 304 HR 10 NIBE 067 309 NIBE NIBE NIBE NIBE NIBE 067 067 067 067 067 ECS ECS ECS ECS ECS 40/ECS 40/ECS 40/ECS 40/ECS 40/ECS 41 41 41 41 41 287/067 287/067 287/067 287/067 287/067 288 288 288 288 288 NIBE AB - Energy Systems Box 14, 285 21 Markaryd Tel 0433 - 73 000 Fax 0433 - 73 190 www.nibe.se ODM GB 1412-1 M11624 PAGE 3 (4) Pos Name QZ1 Hot water circulation Circulation pump GP11 Other information CM1 CP5 Product name Expansion vessel, closed Buffer vessel, UKV UKV UKV UKV UKV CP10 Accumulator tank with hot water heating EB10 FL2 Additional water heater Safety valve, Heating medium Control module Air/water heat pump Accumulator with hot water heater SMO 40 with multiple air/water heat pumps, additional heat and accessory (liquid condensation) Part no. Remarks Supplier 100 200 300 500 VPA 300/200 VPA 450/300 VPAS 300/450 VPB 500 VPB 750-2 VPB 1000 Circ. pump NIBE NIBE NIBE NIBE NIBE NIBE Water heater HW Control Addition 088 080 080 080 207 321 330 302 088 088 087 083 083 083 710 660 720 220 231 240 Note that the tank must be able to receive the heat pump charge effect. See the last page for a table of possible combinations of NIBE's range. Volume vessel F2030 – 7 kW F2030 – 9 kW F2040 – 8 kW VPA 300/200 VPA 450/300 SMO 40 F2040 – 12 kW VPAS 300/450 F2040 – 16 kW VPB 500 VPB 750-2 VPB 1000 F2300 – 14 kW F2300 – 20 kW CPD 11-25/65 CPD 11-25/75 VPB 200 VPB 300 VPBS 300 VPB 500 VPB 750-2 VPA 450/300 VPAS 300/450 VPB 750-2 VPB 1000 VST 11 ELK 15 ELK 26 ELK 42 VST 20 UKV 100 UKV 200 UKV 300 UKV 500 VST 11 VST 20 VST 20 NIBE AB - Energy Systems Box 14, 285 21 Markaryd Tel 0433 - 73 000 Fax 0433 - 73 190 www.nibe.se ODM GB 1412-1 M11624 PAGE 4 (4)